CHAPTER 11
BUSBAR PROTECTION
Chapter 11
Page 1
Busbar Protection
BUS PROTECTION
Bus Protection Methodologies
Overcurrent Protection
Full Differential
Partial Summation
High Impedance Bus Differential Relaying
Basic Concept
Relay Operation Analysis
Setting the Relay
Low to Moderate Impedance Restrained Differential Relaying
Basic Concept
Multi-restraint Design
Slope
Comparison between High impedance and Low Impedance Busbar
Differential Schemes
Busbar Protection Schemes for Various Bus Designs
Chapter 11
Page 2
Busbar Protection
PROTECTION OF SUBSTATION BUSBARS INTRODUCTION
The busbars in a substation are possibly one of the most critical elements in a power
system. If a fault is not cleared or isolated quickly, not only could substantial damage
to the busbars and primary plant result, but also a substantial loss of supply to all
consumers who depend upon the substation for their electricity. It is therefore
essential that the protection associated with them provide reliable, fast and
discriminative operation.
As with any power system the continuity of supply is of the utmost importance,
however, faults that occur on substation busbars are rarely transient but more
usually of a permanent nature. Circuit breakers should, therefore, be tripped and not
subject to any auto-reclosure.
The busbar protection must also remain stable for faults that occur outside of the
protected zone as these faults will usually be cleared by external protection devices.
In the case of a circuit breaker failure, it may be necessary to open all of the adjacent
circuit breakers. Tthis can be achieved by issuing a backtrip to the busbar protection.
Security and stability are key requirements of a busbar protection scheme. Should
the busbar protection mal-operate under such conditions, substantial loss of supply
could result unnecessarily.
Many different busbar configurations exist. A typical arrangement is a double busbar
substation with a transfer bar. The positioning of the primary plant can also vary and
also needs to be considered which in turn introduces endless variations, all of which
have to be able to be accommodated within the busbar protection scheme.
Backup protection is also an important feature of any protection scheme. In the event
of equipment failure, such as signalling equipment or switchgear for example it is
necessary to provide alternative forms of fault clearance. It is desirable to provide
backup protection, which can operate with minimum time delay and yet discriminate
with other protection elsewhere on the system.
Chapter 11
Page 3
Busbar Protection
BUS PROTECTION METHODOLOGIES
Bus protection systems are more straightforward than transformer protection
systems because of the many different variables that are involved with transformer
protection (for example, a 30 phase shift and different ratio CTs).
Bus protection has been the most difficult protection to achieve because of the
severity of an incorrect bus fault relay operation that results in loss of the entire plant
industrial power system. This section will briefly describe the following types of relay
bus protection: overcurrent, full differential, and partial differential.
OVERCURRENT PROTECTION
If the system design does not require fast bus fault clearance, overcurrent relays
(ANSI Device Nos. 51 and 51G) are used to provide bus protection. Referring to
Figure 11-1 and assuming that the bus is fed from a transformer, both devices are
coordinated with the feeder protective devices (ANSI Device Nos. 50/51 and
50G/51N).
Figure 11-1.
Achieving Busbar Differential Protection through the Use of Overcurrent Relays
Chapter 11
Page 4
Busbar Protection
FULL DIFFERENTIAL
Many design standards specify full differential bus protection on all switchgear buses
that are rated 13.8 kV and higher. The basic principle behind full differential
protection is that the phasor sum of all currents that enter and that leave the bus
protection zone be zero, unless there is a fault within the protection zone. Although
differential protection is the most sensitive and reliable method of protecting station
buses, problems can result from the large number of circuits that are involved and
the different energization levels that are encountered in these circuits for external
faults. For example, if there is an external fault on one circuit of a six-circuit bus, five
of the current transformers may supply varying amounts of fault current, but the sixth
and faulted circuit must balance out the total of all the others. Consequently, this sixcircuit bus is energized at a much higher level at or near saturation, and it could
result in possible high false differential currents.
Figure 11-2 illustrates a typical scheme for full differential bus fault protection. A fault
anywhere on the bus will energize either ANSI Device Nos. 87B1 or 87B2 that will
result in a trip of the main, bus, and feeder breakers on the same side of the bus as
the fault location. A fault below the feeder breakers is outside the bus zone of
protection, and consequently, it should only result in tripping of ANSI Device Nos.
50/51 or 50/51G
Figure 11-2. Full Busbar Differential Scheme
Chapter 11
Page 5
Busbar Protection
PARTIAL DIFFERENTIAL
Many design standards also specify the use of partial bus differential schemes on
those buses that are rated over 600 V with normally closed (N.C.) bus tie breakers
and where a full bus differential scheme is not required. Figure 11-3 illustrates a
typical scheme for partial differential bus fault protection. For external faults,
negligible current flows in the ANSI Device No. 51 relays. On the other hand, total
fault current is available for bus faults and for faults out on the feeder cables.
Figure 11-3. Partial Summation Schemes
Chapter 11
Page 6
Busbar Protection
HIGH IMPEDANCE BUS DIFFERENTIAL ELAYING
BASIC CONCEPT
High impedance bus differential relaying is the leading means of bus protection on
high voltage buses and critical medium voltage buses. It also becomes more
predominant on high fault duty switchgear where the enclosed space of the bus
allows little room for dissipation of arc energy.
RELAY OPERATION ANALYSIS
An AC connection diagram of a high impedance bus differential system is shown in
Figure 11-4. In large substation yards the summation point for the CTs is frequently
made in one or more sub-panels in the yard.
Figure 11-4. Basic Scheme for High Impedance Busbar Differential Protection
Chapter 11
Page 7
Busbar Protection
CT RATIOS
For CT currents to balance, all CTs must have the same turns ratio. This need for all
CTs to have the same ratio can be a major difficulty of this type of bus protection.
OPERATION FOR EXTERNAL FAULTS
There are two settings to be made on the relay: the voltage pickup setting and the
current pickup setting, selected to prevent operation for external faults.
RELAY VOLTAGE
The worst case condition for which the relay must not operate is the complete
saturation of a CT during an external fault (typically the CT nearest the fault). The
relay voltage setting is based on this condition.
Since each manufacturer has different calibration and safety margins built into its
design, the following settings discussion attempts to remain somewhat generic.
In general, the process begins by assuming that an external fault occurs and the
current is flowing at maximum bus fault levels toward the fault. Next, one assumes
complete saturation of the CT nearest the fault. When the CT saturates, it is
assumed that no other CT saturates. The CT saturation is assumed total, as if the
core can accept no additional flux.
Hence, the CT acts as a negligible reactance air core reactor. Thus, the CT
impedance is reduced to the secondary winding resistance in series with the line
resistance. The relay voltage setting is chosen to ensure that the voltage developed
across the relay under this condition will not exceed the tripping voltage of the relay.
At each CT, the maximum fault level just outside the zone of protection, adjacent to
each CT, is calculated. Using the fault current and CT ratio, the current that flows in
the CT leads is calculated as if the CT had not saturated. However, the current is
considered driven into the saturated CT by other good-performing CTs rather than by
the CT's own internal current transformation effect. This causes a voltage rise at the
CT summation point, conceptually shown in Figure 11-5.
Chapter 11
Page 8
Busbar Protection
Figure 11-5. Concept Voltage Profile, Non-saturated and Saturated CT
The voltage impressed upon the relay connected across the summation point can be
calculated using anticipated current and lead impedance. This must be evaluated for
both phase and ground faults, noting the differing primary currents, lead lengths, and
neutral wire currents in each case, taking into account that current may not return all
the way back to the control house if yard summation cabinets are used. This must be
evaluated for a fault on any line. The worst case is typically associated with a phaseto-ground fault on the weakest in-feed line.
Chapter 11
Page 9
Busbar Protection
Equations used are:
CTR
The voltage unit is set at a level corresponding to the voltage calculated above, but
offset from this voltage by some margin factor guidelines given by the
manufacturers. The assumption of total saturation also includes a safety factor
because in actual practice total saturation likely does not occur.
Ideally, the voltage set point would be no higher than the Vknee point of the CT excitation
curve but this is not critical, and manufacturers have guidelines by which the relay
will work successfully with settings above the CT knee points. However, for secure
and reliable performance during an internal fault:
where
VHighest is the highest summing point voltage calculated for an external fault during the
saturation of one CT, as previously described K refers to the manufacturers
setting margin guidelines
Vrelay
refers to the relay voltage setting
Vct,rated refers the CT voltage rating, e.g., the ANSI knee point voltage
Chapter 11
Page 10
Busbar Protection
RELAY CURRENT
The overcurrent element and voltage element trip contacts are in parallel. The
overcurrent element monitors the current through the non-linear impedance. The
setting is intended to add dependability. A typical current setting is equivalent to the
current passing through the non-linear impedance when the voltage at the relay is
equal to the relays voltage setting. Consult the manufacturers' manuals for more
information.
Figure 11-6. Typical MOV Connection
Chapter 11
Page 11
Busbar Protection
Example of High Impedance Bus
DifferentialProtection
GE MIB RELAY
The MIB, a member of the M family of protection relays, is a microprocessor based
relay that provides three phase high impedance differential protection for Substation
busbars of any voltage level. Additionally, it can also be used to protect electrical
machines like transformers, generators or motors against restricted earth faults.
Basic protection functions features include a high impedance differential protection
unit. Stability against external faults is guaranteed thanks to the use of a stabilizing
resistor.
Additionally, the unit includes a set of MOVs (Metal Oxide Varistors) in order to
clamp the secondary peak voltage below 2kV during fault conditions.
Chapter 11
Page 12
Busbar Protection
PROTECTION
Applications
High impedance differential protection
Restricted Ground Fault protection with
One/two elements
Lockout logic
Monitoring and Metering
24 Event record per M Family Unit
Analog/digital oscillography
Per phase current metering
Description
The relay provides three phase high impedance differential protection for Substation
busbars of any voltage level. Additionally, it can also be used to protect electrical
machines like transformers, generators or motors against restricted earth faults.
Differential Unit (87H)
This unit detects internal faults within the busbars. It is based on a very sensitive
overcurrent differential unit that can be adjusted between 10mA and 400mA. The
relay includes a 2000 Ohm set of stabilizing resistors to make sure that the unit
remains stable for pass-through faults.
In order to protect the unit, a set of MOVs clamps the secondary voltage under faults
to less than 2 kV. Please note that all the CTs must have the same ratio.
Alarm Unit (87L)
The alarm unit detects any current unbalance condition, like the ones produced
when one of the CTs has a phase open. Once the condition is detected a timer starts
that finally blocks the operation of the relay.
Settings go between 10mA and 400mA. Timer is up to 600 sec in steps of 10 ms.
Chapter 11
Page 13
Busbar Protection
Restricted Earth Fault
Restricted Earth Fault (REF) protection is intended to provide sensitive ground fault
detection for low magnitude fault currents. This protection is often applied to
machines and transformers having impedance grounded wye windings. It is intended
to provide sensitive ground fault detection for low magnitude fault currents which
would not be detected by other protection functions.
Configurable Logic
Up to a maximum of 4 configurable logic schemes can be implemented into each
MIB relay by means of using a set of 4 preconfigured logic gates and timer cells. A
graphical user interface is provided for configuration of the logic. The outputs of the
configurable logic can be used to configure digital outputs and LEDs.
Multiple Setting Groups
Two separate settings groups are stored in non-volatile memory, with only one group
active at a given time. Switching between setting groups 1 and 2 can be done by
means of a setting, a communication command or digital input activation.
Inputs and Outputs
Two configurable inputs and six contact outputs (four of them configurable) are
provided for each relay.
Metering
The relay provides metering values for phase differential current.
Chapter 11
Page 14
Busbar Protection
FUNCTIONAL BLOCK DIAGRAMS
Figure 11-7
Chapter 11
Page 15
Busbar Protection
SETTING THE RELAY: DIFFERENTIAL UNITS
The relay provides 2 Differential Units, 87 1 and 87 2. Each one can be
enabled/disabled and set independently.
This element consists of overcurrent detectors that measure the current flowing in
the High-impedance differential circuits. The pick up value can be set between 5 mA
and 400 mA, and the time delay from 0 to 600 seconds.
For a Bus-bar differential application, this element will receive the differential
currents corresponding to phase A, B and C. The element will measure the three
differential currents, and operate if any of them surpass the pickup setting during the
specified time delay.
Calculation of Settings
The formulas and procedures described in the following paragraphs for determining
relay settings assume that the relay is connected to the full winding of the
differentially connected CTs. It is further assumed that the secondary winding of
each CT has negligible leakage reactance and that all the CTs have the same ratio.
It is assumed that an external fault causes complete saturation of the CT in the
faulted circuit. The current forced through this secondary by the CTs in the in feeding
circuits will be impeded only by the resistance of the windings and leads. The
resulting IR drop will be the maximum possible voltage that can appear across the
MIB relay for an external fault. The setting of the high impedance differential unit is
expressed as follows:
Chapter 11
Page 16
Busbar Protection
IF (RS + P * RL)
VS =
IR
1.6 K
VS
RE
Where:
IR
= Pickup setting of the 87 unit
RS
= DC resistance of fault CT secondary windings and leads to housing terminal
RL
= Single conductor DC resistance of CT cable for one way run from CT housing
terminal to junction point (at highest expected operating temperature.
= 1 for three phase faults; 2 for single phase to ground faults
IF
= External fault current primary RMS value
= CT ratio
1.6 = Margin Factor
K
= CT Performance Factor (see Figure 11-10)
RE= stabilizing resistance (2000)
The calculations need only be made with the maximum value of IF for single phase
and three phase faults. If the relay is applicable for these conditions, it will perform
satisfactorily for all faults.
The pessimistic value of voltage determined by the equation, for any of the methods
outlined, is never realized in practice. The CT in the faulted circuit will not saturate to
the point where it produces no assisting voltage.
Furthermore, the condition that caused the fault CT core to saturate also tends to
saturate the cores of the CTs in the in-feeding circuits, which results in a further
decrease in voltage across the MIB. These effects are not readily calculated.
The value of the 87 setting established by the equation is the minimum safe setting.
Higher settings will provide more safety margin, but will result in somewhat reduced
sensitivity.
Chapter 11
Page 17
Busbar Protection
The method of utilizing the above equation is outlined below:
a) Determine the maximum three phase and single phase to ground fault
currents for faults just beyond each of the breakers.
b) The value of RL is the one-way cable DC resistance from the junction point to
the fault CT being considered.
c) For each breaker in turn calculate IR separately utilizing the associated
maximum external three phase fault current with P=1 and the maximum
external single phase to ground fault current with P=2.
d) Use the highest of the values of IR so obtained in c) above.
It is desirable for the pickup current of the 87 unit multiplied by 2000 ohm. to plot
below the knee of the excitation curve (i.e. point on the excitation curve where the
slope is 45) of all the CTs in use.
Chapter 11
Page 18
Busbar Protection
Minimum Fault To Trip 87
After the pickup setting of 87 has been established for an application, a check should
be made to determine the minimum internal fault current that just causeS the unit to
operate. If this value is less than the minimum internal fault current expected, the
pickup setting is suitable for the application. The following expression can be used to
determine the minimum internal fault current required for the particular 87 pickup
setting.use.
n
IMIN=
[ IX + IR + IM ] * N
1
Where:
IMIN = Minimum internal fault current to trip 87
n=
Number of breakers connected to the bus (i.e. number of CTs per phase)
IX=
Secondary excitation current of individual CT at a voltage equal to pickup
level of 87
IR =
Pickup level in 87 unit
IM =
Current in the MOV unit at 87 pickup level
N=
CT ratio.
The values of I1, I2, .. etc are obtained from the secondary excitation characteristics
of the respective CTs. The first term in the equation reduces to N*Ix if it is assumed
that all CTs have the same excitation characteristics. The current drawn by the MOV
unit can be obtained from that curve in Figure 11-12 that applies to the relay being
used.
Chapter 11
Page 19
Busbar Protection
MIB TECHNICAL SPECIFICATIONS
DIFFERENTIAL UNIT (87)
Pickup Level:
10mA to 400mA
Definite Time:
Up to 600 sec (10 msec steps)
Accuracy:
Level: 3% in the complete range
Time: Greater of 3% or 25 ms
ALARM UNIT (87AL)
Pickup Level:
10mA to 400mA
Definite Time:
Up to 600 sec (10 msec steps)
Accuracy:
Level: 3% in the complete range
Time: Greater of 3% or 25 ms
RESISTOR
Value: 2000 Ohm
Max. Operating Cont. Voltage 300 V
MOVs
V Peak: 1900 V
Max. Withstand Energy: 5400 J
Chapter 11
Page 20
Busbar Protection
WORKED EXAMPLE
Set an MIB relay to provide busbar protection for the shown system, based on
the above:
System has 30 breakers
All CT ratios are 1200/5
Maximum available 3 phase fault at the bus is 45,000 A Asymmetric
30 breakers
Figure 11-8. Single Line Diagram for Worked Example
Chapter 11
Page 21
Busbar Protection
Figure 1 1 - 9 . 1 2 0 0 / 5 A CT saturation curve
Calculating R S
The characteristics for the CT are shown in Figure 11-9. The value of RS from
this figure is:
Rs = 0.0029 240 + 0.113 = 0.809 ohm s
Calculating R L
The cable resistance for the longest CT run is given at 25 0 C. If higher
operating temperatures are expected, this must be taken into account to
determine the maximum expected resistance. Resistance values of wire at
25 0 C, or at any temperature t1 , may be corrected to any other temperature t2
as follows:
R ( at t2 ) = ( 1 + P1 ( t2 t1 ) )R ( at t1 )
where:
R (at t1 ) = resistance in ohms at t1
R (at t2) = resistance in ms at t2
P1 = temperature coefficient of resistance at t1
For standard annealed copper, P1 = 0.00385 at t1 = 25 C, the value of RL at
50 0 C is RL = 0.548 ohms.
Chapter 11
Page 22
Busbar Protection
Calculating K
The CT performance factor must be determined next. First, calculate the
following:
Using P = 2 and the knee point ES = 300 V from Figure 11-9, we have:
From Figure 11-10 below, we have K = 0.7 at 1.06.
Figure 11-10. CT Performance Factor
The equation for calculating the I pickup setting, taking CT p e r f o r m a n c e and
margin into account, is as follows:
Chapter 11
Page 23
Busbar Protection
Given our values for K, RS , P, RL , and N, we have
V across CT 177.5 * 2000 355 Volts (still OK even though the knee of the
CT occurs at 300 volts)
Since the maximum internal fault current is 45,000 Asymmetric (primary
amperes) (equivalent to 188 secondary amperes), the curve of Figure 11-11(at
300 V and 188 A) shows that the application is appropriate for either PVD
and M I B relays.
Figure 11-11. Safe limits of application
The next step is to determine the sensitivity of the relay to internal faults. This
may be done using the following equation:
Chapter 11
Page 24
Busbar Protection
IMIN=
[ IX + IR + IM ] * N
1
where:
IMIN
is the minimum internal fault current to trip
is the numbers of breakers connected to the bus (i.e. CTs per phase)
(n=30)
IX
is the secondary excitation current of individual CTs at a voltage equal
to the 87L pickup
(from CT excitation curve at V = 355 volts)
IR
is the current through the MIB unit to pickup the relay,
(IR = 177.5 milli-amps)
IM
is the current in the MOV (thyrite) at pickup voltage (pickup current x
2000); (refer to Figure 11-12)
is the CT ratio (N = 240)
Chapter 11
Page 25
Busbar Protection
Figure 11-12. MOV Voltage and Current Characteristics
Therefore, for 30 breakers, the minimum fault current is:
IMIN=
[ IX + IR + IM ] * N
1
= [30(0.07 A) + 0.177.5 A + 0.004 A] * 200
= 548 primary amps
Chapter 11
Page 26
Busbar Protection
CONCLUSIONS
As we can see, the main limiting factor in regards to the number of feeders an
MIB can support is dictated by the minimum fault current available. In theory, if
we have enough short circuit current and a correct CT dimensioning, there is no
limitation in the number of feeders.
The other limitation is thermal in nature, driven by the presence of any
considerable level of short circuit generated during an internal fault.
The stabilizing resistor and MOV (thyrite) have been designed, on a base case,
to support 50,000 primary amperes for internal faults with CTs of 1250/5 A, and
total operating time of 40 ms (this time is calculated through the sum of the relay,
MOV short circuit latching relay, resistor, and MIB current input).
Finally, to apply the MIB, the following information must be obtained:
Minimum short circuit current during internal faults
Maximum short circuit current during internal faults
Maximum through current during external faults
CT ratio of all the CTs
Saturation curve of all CTs
Secondary CT resistance for all CTs
Maximum CT secondary loop impedance (resistance of the lead that
connect the CT with the relay)
Number of feeders in the substation
Chapter 11
Page 27
Busbar Protection
LOW TO MODERATE IMPEDANCE RESTRAINED
DIFFERENTIAL RELAYING
BASIC CONCEPT
The low impedance restrained bus differential scheme is similar in concept to the
familiar transformer restrained differential relay, and some companies have used a
transformer differential relay for this application. There are through current restraint
quantities and differential operate quantities. The restraint and operate windings
interact so that the higher the through current level, the higher the required operate
current. But in the bus relay the restraint and operate circuit may be simpler, the
restraint slope may be fixed, the CT tap adjustment system may not exist, and the
harmonic restraint may not exist.
The operate circuit may contain some impedance. This adds some security against
operation during the poor performance of a CT.
MULTI-RESTRAINT DESIGN
The most involved version of this concept has all CT signals brought into the relay
individually into separate restraint windings before being summed together for the
operate circuit as shown below. Individual tap adjusts may or may not exist on each
input.
Figure 11-13.
Multi-restraint Design of Low Impedance Relay
Chapter 11
Page 28
Busbar Protection
Figure 1114
Transformer differential relays are sometimes used for this type of bus protection.
Sometimes questions arise about how to set a transformer differential relay when
used for bus protection.
Transformer differential type relays have little means to differentiate between an
internal fault and the absolute and complete saturation of a CT during an external
fault. The assumed worst case complete saturation of a CT during an external fault
looks identical, to the relay, to an internal fault where the breaker was not supplying
any current (e.g., breaker was open). For these relays to be secure against operation
for an external fault, there must be some assumption of CT performance for an
external fault. There are three approaches: either slow down the relay operation so
that transient DC saturation can be ridden through, use CTs robust enough to only
slightly go into DC induced saturation, and combined with these, the third approach
of setting the relay to not operate for some lower level of CT saturation.
Chapter 11
Page 29
Busbar Protection
TYPICAL BUSBAR DIFFERENTIAL RELAYS
Chapter 11
ABB REB500
Page 30
Busbar Protection
Overview of the functionalities REB500 / REB500sys
Table 11-1 Overview of the functionalities REB500 / REB500sys
Chapter 11
Page 31
Busbar Protection
Chapter 11
Page 32
Busbar Protection
Chapter 11
Page 33
Busbar Protection
Chapter 11
Page 34
Busbar Protection
Functionality of REB500 System
Chapter 11
Page 35
Busbar Protection
Chapter 11
Page 36
Busbar Protection
Chapter 11
Page 37
Busbar Protection
COMPARISON BETWEEN HIGH IMPEDANCE AND LOW
IMPEDANCE BUSBAR DIFFERENTIAL SCHEMES
High Impedance Schemes
Established technology
Low Impedance Schemes
Flexible in case you have multiple
system configurations
Well proven principle
CT's can be of different CT ratios and
accuracy classes
Simple relay
Can add interposing CT's
Simple busbar protection scheme
Establishing a relay setting is relatively
easy
Establishing a relay setting is relatively
easy
Can use same set of CT's for
overcurrent and differential protection
All CT's (main and feeder) have to be
the same ratio, accuracy, burden, .. etc
Does not usually work unless you have
numerical relays
Need separate set of CT's for bus
differential relay . Can not use CT's
used for overcurrent relays
All leads from the CT to the relay have
to be of the same impedance
Not practical if you have several
system schemes (scheme not easily
configurable
Relay can only be used as a differential
relay. Can not use the relay to perform
breaker failure schemes
Table 11-2. Comparison between High-Impedance and Low-Impedance Busbar
Protection Schemes
Chapter 11
Page 38
Busbar Protection