Clearances required for substation up to 800 kV
( According to CBIP )
                                                    Minimum clearance $           safety
                                                                               clearances
Highest        Lightning      Switching
                                                                                  (mm)
system         impulse        impulse voltage
Voltage ( kV ) voltage ( kVp ) ( kVp )                        Phase -to-
                                                  Phase -to- Phase
                                                 earth ( mm )   ( mm )
      36             170               -             320          320              2800
     72.5            325               -             630            630            3100
     123             450               -            900            900             3400
                     550               -            1100           1100            3700
     145             550               -            1100           1100            3700
                     650               -            1300           1300            3800
     245            950                -            1900           1900            4300
                    1050               -            2100           2100            4600
     420            1425       1050 (Ph- E)         3400 *          -              6400
                               1575 (Ph-Ph)           -           4200 **
     800            2100       1550 (Ph-E)          6400 *        9400 **         10300
                               2550 (Ph-Ph)
* Based on Rod - structure air gap
** Based on Rod - conductor air gap
$ This value of air clearances are the minimum values dictated by electrical consideration and do not include
any addition for construction tolerances, effect of short circuits, wind effects and safety of personnel, etc.
             Minimum Electrical clearance for outdoor switchgear
                     According to IS : 10118 ( part III )
Voltage rating                                 Minimum
                  Impulse
(Highest                         Min clearance clearance     Sectional
                  Withstand
System                           to Earth      between       clearance
                  Level
Voltage)                                       phases
kV (rms)          kV (peak)      mm            mm            mm
      12               60             90             90            2600
                       75             120           120            2600
      36              145              -            270            2750
                      170             320           320            3000
      72.5            325             630           630            3500
      123             450             900           900            3500
                      550             1100          1100           4000
      145             450             900           900            3500
                      550             1100          1100           4000
                      650             1300          1300           4000
      245             650             1300          1300           4000
                      750             1500          1500             -
                      850             1600          1700           4500
                      950             1900          1900           4500
                      1050            2400          2100           5000
                              CORRELATIONS BETWEEN INSULATION LEVELS AND
                        Minimum clearances in air- Voltage range I ( 1kV < Um ≤ 245 kV )
                                         ( Table 1 of IEC 61936-1 )
                                         Rated short
           Nominal        Highest        duration power- Rated lightning
                                                                           Minimum phase-to-earth and phase-
           voltage of     voltage for    frequency       impulse withstand
                                                                           to-phase clearance,N c
           system         equipment      withstand       voltage a
                                         voltage
 Voltage
  range
           Un             Um                               1.2/50 μs           Indoor            Outdoor
                                         r.m.s
           r.m.s          r.m.s                            ( peak value )      installations     installations
                   kV             kV             kV                 kV                  mm                   mm
                                                                    20                  60                   120
                   3              3.6            10
                                                                    40                  60                   120
                                                                    40                  60                   120
                  6              7.2              20
                                                                    60                  90                   120
                                                                    60                  90                   150
                  10             12               28                75                  120                  150
                                                                    95                  160                  160
                                                                    75                  120                  160
                  15            17.5              38
                                                                    95                  160                  160
                                                                    95                           160
                  20             24               50               125                           220
                                                                   145                           270
                                                                   145                           270
                  30             36               70
                                                                   170                           320
     I            45             52               95               250                           480
                  66            72.5              140              325                           630
                                                 185 b             450                           900
                 110            123
                                                  230              550                          1100
                                                 185 b            450 b                          900
                 132            145               230              550                          1100
                                                  275              650                          1300
                                                 230 b            550 b                         1100
                 150            170               275              650                          1300
                                                  325              750                          1500
                                                 275 b            650 b                         1300
                                                 325 b            750 b                         1500
                 220            245               360              850                          1700
                                                  395              950                          1900
                                                  460             1050                          2100
a. The rated lightning impulse is applicable to phase- to-phase and phase- to earth.
b. If values are considered insufficient to prove that the required phase-to-phase withstand voltages are met,
additional phase-to-phase withstand tests are needed.
c. For rod-structure.
                                                 Minimum clearances in air- Voltage range II ( Um> 245 kV )
                                                               ( Table 2 of IEC 61936-1 )
                                                                                                                       Rated
                                         Rated lightning
           Nominal        Highest                          Rated switching                                             switching
                                         impulse                                                                                      Minimum phase-to-phase
           Voltage of     Voltage for                      impulse withstand Minimum phase-to-earth clearence          impulse
                                         withstand                                                                                    clearence
           System         equipment c                      voltage                                                     withstand
                                         voltage a
                                                                                                                       voltage
 Voltage
  range                                                                                                                               Conducto Rod
                                                                                                             Rod       Phase-to-
                                                           Phase-to-earth         Conductor                                           r         -
           Un             Um             1.2/50 μs                                                     -               phase
                                                           250/2500 μs (peak           -                                              -         conductor
           r.m.s          r.m.s          (peak value)                                                      structure   250/2500 μs
                                                           value)                  structure                                          conductor
                                                                                                               N       (peak value)
                                                                                                                                      parallel
                   kV             kV             kV                kV                           mm                          kV                 mm
                                                                                       1600
                                             850/950               750                                       1900          1125         2300        2600
                275               300                                                  1700 b
                                                                                        1800
                                             950/1050              850                                       2400          1275         2600        3100
                                                                                       1900 b
                                                                                        1800
                                             950/1050              850                                       2400          1275         2600        3100
                330               362                                                  1900 b
                                            1050/1175              950                  2200                 2900          1425         3100        3600
                                                                                        1900
                                            1050/1175              850                                       2400          1360         2900        3400
                                                                                       2200 b
    II
                380               420                                                   2200
                                            1175/1300              950                                       2900          1425         3100        3600
                                                                                       2400 b
                                            1300/1425             1050                  2600                 3400          1575         3600        4200
                                                                                        2200
                                  525       1175/1300              950                                       2900          1615         3700        4300
                                                                                       2400 b
                480
                             (550) c          1300/1425           1050                  2600            3400               1680         3900        4600
                                              1425/1550           1175                  3100            4100               1763         4200        5000
                                              1675/1800           1300                  3600            4800               2210         6100        7400
                                765
                 700                          1800/1950           1425                  4200            5600               2423         7200        9000
                              (800) c
                                              1950/2100           1550                  4900            6400               2480         7600        9400
a. The rated lightning impulse is applicable phase- to-phase and phase- to earth.
b. Minimum clearance required for upper value of rated lightning impulse withstand voltage.
c. The introduction of Um = 550 kV (instead of 525 kV): 800 kV(Instead of 765 kV): 1200 kV, of a value between 765 kV
and 1200kV, and of the associated rated withstand voltages, is under consideration.
                                            Clearences practice used within UK
                                                Section 5 of BS 7354 : 1990
                                                        Safety working
                   Basic Electrical Safety Working                            Insulation Height
Nominal system                                          clearence                                      Phase- to-phase
                   clearence        clearence                                 (pedestrian access)
voltage/BIL/SIL                                         (horizontal)                                   clearence
                   (phase-to-earth) (Vertical)                                (see note 2)
                                                        (see note 1)
kV                 m                m                   m                     m                        m
6.6/75             0.5 2)           2.9                 2.3                   2.1                      0.25
11/95              0.5 2)           2.9                 2.3                   2.1                      0.25
33/170             0.5 2)           2.9                 2.3                   2.1                      0.43
66/325             0.7              3.1                 2.5                   2.1                      0.78
132/550/650        1.1              3.5                 2.9                   2.1                      1.4
275/1050/850       2.1              4.8                 3.9                   2.4                      2.4
400/1425/1050      2.8              5.5                 4.6                   2.4                      3.6
Note: 1. The safety working clearences(horizontal) in column 4 are regarded as minimum clearences.
For systems where the predominant volatges are higher (275 kV and 400 kV) it is practice in the UK that the
horizontal and vertical clearences are equal, conforming to the minimum figures in column 3.
Note: 2. The insulation height(pedestrain access)figures in column 5 are shown in respect of the appropriate system
voltage as follows:
(a) for systems predominantly involving distribution voltages,i.e. upto and including 132 kV,2.1 m is the recommended
minimum requirement:
(b) for systems where the predominant voltages are higher,i.e. 275 kV and 400kV, 2.4 m is the recommended
minimum requirement.
The above figures are regarded as minimum clearences. Users and operators may wish to allow further clearence greater
than that shown for the voltage level in column 5, particularly for equipment at the higher distribution voltages situated in
a single compound with higher voltage equipment present in a compound subject to a greater clearence. In these
circumstances, it might be convenient to design and operate to the clearence for the highest voltage equipment.
                   Clearances required for different voltage levels as per TCE standard
   Highest          Basic          Switching           Minimum clearance                  Sectional         Ground
   system      insulation level insulation level                                      clearance         clearance    (
Voltage ( kV )     ( kVp )          ( kVp )                                                ( mm )           mm ) *
                                                     Phase -    Phase -Phase
                                                   Earth ( mm )    ( mm )
            36             170          -                   320           320                    2800           3700
          72.5             325          -                    630               630               3000           4000
           123             450          -                     900               900              3500           4600
                           550          -                    1100              1100              4000           4600
           145             550          -                    1100              1100              4000           4600
                           650          -                    1300              1300              4000           4600
           245             950          -                    1900              1900              4500           5500
                          1050          -                    2100              2100              5000           5500
           420            1425 1050 (Ph- E)        3400 **                 -                     6500           8000
                               1575 (Ph-Ph)              -          4200 ***
* This is defined by IE rules
** Based on Rod - structure air gap
*** Based on Rod - conductor air gap
                   As per IE rules ( Rule 64)
Highest system voltage (kV)       Safety working clearance (m)
            12                                   2.6
            36                                   2.8
           72.5                                  3.1
           145                                   3.7
           245                                   4.3
           420                                   6.4
           800                                  10.3