RESULTS AND CALCULATIONS
i) Major Components In The Plant
Figure 1 : P&I Diagram of the system
a) T90 Air Tank
b) FE91 Orifice meter
c) FT91 Differential Pressure Transmitter, with a square root function
d) PT91 Absolute Pressure Transmitter
e) TE91 RTD Temperature Sensor
f) TIT911 Temperature Transmitter
g) FIC90 ON/OFF controller
h) FIC91 Flow Controller (PID)
i) FCV90 Pneumatic ON/OFF control valve with solenoid valve, TSV90
j) FCV91 Control valve with FCY91 current-to-air (I/P) converter and pneumatic
positioner, PP
k) FPTR91 Recorder
ii) AIR FLOW MEASUREMENT
Instrument I II III
Controller
Reading MV=-6.3% MV=50% MV=70%
At the panel FIC91, I/O Data
FT91,√ℎ X1-% of 0-100mm 82.8 48.9 29.6
TIT911, T X2-% of 0-120℃ 24.5 21.8 24.9
PT911, P X3-% of 0-60psia 69.9 96.8 109.9
Fm FIC91, Main Face plate
PV, kg/hr 53.1 37.5 24.4
Fv FIC91, Main Face plate
PO1, m3 /hr 21.2 12.5 7.5
Recorder FPTR91
Channel 1 (Red) Fm, kg/hr 50 37.5 23.8
Channel 2 Fvb, m3 /hr 21.2 12.5 7.4
(Green)
By Calculation Fvb, Nm3 /hr 189.65 131.00 84.32
Fm, kg/hr 245.17 169.36 109.01
At the plant
FI911, Nm3 /hr 48 46 54
PG900, psig 31.5 30 16
Table 1: Result for Air Flow Measurement