Northern
Doors (UK) Ltd
Controlled Fire and Smoke Containment Systems
DATA SHEET NUMBER TYPICAL FIRE & SMOKE CURTAIN INSTALLATION
2 4
5
6
FIRE CURTAIN DESCENDING
1 Window Fire Curtains, preventing the spread of fire to
higher floors and any nearby building structures. A more cost
effective way of fire resistance in lieu of expensive Fire Glass.
2 Multiple Fire Curtains, covers openings of up to
54 metres wide. No need for fire rated walls allowing freedom
and space with the building design.
3 Vertical Fire/Smoke Curtain, controls the spread of
fire & contains the leakage of smoke.
4 Shop Front Fire Curtain, offering fire resistance
replacing fire doors, fire glass & alternative to roller shutters.
5 Reservoir & Channelling Smoke Curtain, guides
SMOKE CURTAIN DESCENDING the smoke in a determined area direction so gases direct
upwards, maintaining the smoke temperature enabling the smoke to
rise rapidly. Reservoir smoke curtains descend to a pre determined
height so that the smoke accumulates within the reservoir & then
exhausted by the building extraction system.
Channelling smoke curtains are used to channel the smoke &
prevent the smoke from moving laterally around the atrium.
The smoke is channelled into the ceiling area where it is safely
exhausted by the building extraction system.
6 Void Edge Curtains, stops smoke from low level from
spreading and contains the smoke in the immediate area.
Northern
We reserve the right to make appropriate technical modifications without prior notice.
Doors (UK) Ltd
DATA SHEET NUMBER TYPICAL FIRE CURTAIN FIXING DETAILS
GUIDE FIXING ARRANGEMENTS - FACE FIXED GUIDE OPTION
‘B’ Type Guide Option ‘A’ Type Guide Option
75mm 170mm
M8 EXPANSION BOLT
FACE FIXING THROUGH
STEEL ANGLE
50mm 50mm
GUIDE FIXING ARRANGEMENTS - BETWEEN FIXED OPTIONS
‘C’ Type Side Fixed Option ‘C’ Type Side Fixed (FLUSH FITTING)
FIRE FIXINGS
THROUGH THE
BACK OF THE GUIDE
90mm
TYPICAL ARRANGEMENT
(OF ‘C’ TYPE FLUSH FITTING)
DECORATIVE CLADDING
BY OTHERS
ATRIUM
LINE OF CURTAIN
Northern
We reserve the right to make appropriate technical modifications without prior notice.
Doors (UK) Ltd
DATA SHEET NUMBER TYPICAL FIRE CURTAIN FIXING DETAILS
HEADBOX OPTIONS
BEAM 02 RSC FACE FIXED SOFFIT FIXED UNISTRUT AND DROP RODS
DROP ROD
OPTION 3 UNISTRUT
OPTION 1 OPTION 2
OPTION 4
CONCEALED CURTAINS
SUSPENDED CEILING WITH SUSPENDED CEILING WITH
FLUSH FIT RECESSED GAP REMOVABLE ACCESS
APP 1 APP 2 APP 3
REMOVABLE ACCESS
PANEL BY NDL
REMOVABLE ACCESS
PANEL IN SUSPENDED
CEILING BY OTHERS
HEADBOX SIZES
Max Width = 5000mm Max Width = 5000mm Max Width = 5000mm Max Width = 54000mm
Max Drop = 4000mm Max Drop = 6000mm Max Drop = 8000mm Max Drop = 4000mm
Northern
We reserve the right to make appropriate technical modifications without prior notice.
Doors (UK) Ltd
DATA SHEET NUMBER TYPICAL FIRE CURTAIN ARRANGEMENTS
CURTAIN ARRANGEMENTS
Fire curtains detailed are using the Unistrut and Drop Rod Method of fixing.
SINGLE CURTAIN DOUBLE CURTAIN
1
600 Overlap
H
H
W
Max Width = 5000mm
W Max Height = 4000mm
Max Width = 5000mm 1 On larger openings where curtains are overlapped & the
Max Height = 6000mm roller assemblies are one above each other to prevent the
curtain from gaping and losing its fire integrity.
MULTIPLE CURTAIN
Unistrut Drop Rods
1
600 Overlap
Curtain Overlap
600 Overlap
CONTINOUS DOUBLE
ANGLED BOTTOM RAIL
Max Width = 54000mm
Max Height = 4000mm
Northern
We reserve the right to make appropriate technical modifications without prior notice.
Doors (UK) Ltd
DATA SHEET NUMBER FIRE CURTAIN FABRIC
MAGNIFIED VIEW
Fire Resistance To BS 476: Part 22: 1987. 4 hours fire resistance
(tested by the Loss Prevention Council). LPCP Approved and certified.
Wire reinforced glass cloth. Style 7600 PUI 22,
710grms square metre.
Case Construction :- 16 ends per cm
:- 15 picks per cm
Yarn Count : 205 TEX Ward W4A, 500 Text Weft V4A
Weave Type : 8 End Satin
Fabric Weight per metre square : 650grms
Fabric Thickness : 0.70gms
Coating / Treatment Details.
Cloth is coated on both sides with 30 GRMS per metre square of PU
Rubber. Colour Silver Grey incorporating aluminium pigment V4A is
stainless steel wire used as reinforcement in each thread.
Northern
We reserve the right to make appropriate technical modifications without prior notice.
Doors (UK) Ltd
DATA SHEET NUMBER CONTROLS SPECIFICATION
OPERATION
Under normal conditions the curtain is retracted in the head box and is held in position by the electronics contained within a remote enclosure
mounted on the motor end of the box. The bottom bar will be resting against the under side of the box or below the box if a stopping bar is installed,
the stopping will then rest against the box.
In the event of a fire condition or operation of the test key switch the group control panel removes the power to the curtain motors. The curtain de-
scends in a controlled manner under the power of gravity and stops in the lower position when all the fabric is unwound from the roller. When the
signal is reset the group control panel re connects the power to the motors which will retract the curtains to the up position.
FEATURES
• Gravity fail safe operation
• Current limiting device incorporated, motor limit switches are not required
• Synchronized motor control circuitry, variable speed control is not required
• Back EMF controlled speed of descent, separate brake units are not required
• 24 v operation
• Control panels can control up to 6 curtain rollers
• Battery low voltage cut off facility, the curtains descend in a controlled manner.
GROUP CONTROL
SINGLE CURTAIN DOUBLE CURTAIN MULTIPLE CURTAIN
TWO STAGE DECENT FACILITY
The above panels include two timers which when set
allow the smoke/fire curtain to be halted during
descent. The curtain will descend for the preset
run time and will then be stopped by the operation of
the integral brake unit on the roller mechanism.
When the chosen delay time has elapsed the brake
unit will be de-energized and the curtain will AUDIBLE/VISUAL
continue on its descent. STAGE 1 WARNING (OPTION) STAGE 2
PART CLOSE FULLY CLOSED
Both timers commence operation simultaneously,
(TIME DELAY)
either upon receipt of a fire signal or if the GCP is
placed in test mode. The run timer should be set to
the time required for the curtain to descend to its
delay position. The delay timer should be set to the
required period of delay plus the run time. E.g. The
curtain is to descend for a time of 10
seconds and then hold at this position for
15 seconds.
1) Set Run Timer to 10 seconds
2) Set Delay Timer to 10 secs + 15 secs = 25 secs
The curtain will retract as normal.
Northern
We reserve the right to make appropriate technical modifications without prior notice.
Doors (UK) Ltd
DATA SHEET NUMBER COMPACT SERVERY FIRE CURTAIN
Compact Fire Resistant Vertical Rolling Curtain to prevent the spread of fire & hot glass on applications
such as kitchens, kiosks etc.
4 5
SECTION THROUGH
150mm
160mm
1
3
OPENING HEIGHT (H)
OPENING WIDTH (W)
ELEVATION 2
GUIDE FIXING OPTIONS SPECIFICATION
1 4Hour Rated Glass Cloth Fabric with
‘A’ Type Guide Option ‘B’ Type Guide Option a Polymer coating to both sides.
(See data sheet number FC05)
170mm 75m 2 30x30x3m Twin Inverted Mild Steel
Angled Bottom Rail.
M8 EXPANSION
3 90x32mm Galvanised Steel Guide
with integral fabric retaining system.
50mm
FACE FIXING
50mm
4 Roller Assembly enclosed with a 1.2mm
Galvanised Steel Hood Cover.
Min Opening Width (W) 1000 1500 2000 2500 3000 5 76x4mm thick diameter tube gives support
to the Curtain and Bottom Rail.
Min Opening Height (H) 1000 1000 1000 1000 1000
6 3mm Mild Steel Endplates.
OPERATION
- Power Supply : 230V AC, 50HZ Supply via 13 amp un-switched fused spur. - Test Facility : Keyswitch
- Alarm Signal : Normally Open Volt - Free Contacts Open upon activation. - Motor : 24V DC Gravity fall safe
- Fire Curtain : Fire Curtain shall drive up and down via day to day - Option : Audio Visual Warning Panel.
operation upon the receipt of an alarm signal. If curtain is in the open
position the Fire Curtain will delay for 30 seconds then automatically
close through fall safe gravity control.
Northern
We reserve the right to make appropriate technical modifications without prior notice.
Doors (UK) Ltd
OTHER FIRE RESISTANT PRODUCTS
NORFYDOR FIRE RESISTANT SHUTTER ESCALATOR FIRE RESISTANT SHUTTER
WAYFINDER FIRE RESISTANT SHUTTER STRAIGHT SLIDING FIRE DOOR
SLIDING FOLDING FIRE RESISTANT DOUBLE STEEL HINGED
SINGLE STEEL HINGED LEAF AND HALF STEEL HINGED