100% found this document useful (2 votes)
617 views8 pages

Thermal Inspection Summary

The thermal image report summarizes inspections of the main switchboard and three distribution boards at a student housing location. Thermal images found no issues requiring immediate action, with all boards rated priority 4 meaning a problem was not found and reinspection is recommended in 12 months.

Uploaded by

rupesh kumar
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
100% found this document useful (2 votes)
617 views8 pages

Thermal Inspection Summary

The thermal image report summarizes inspections of the main switchboard and three distribution boards at a student housing location. Thermal images found no issues requiring immediate action, with all boards rated priority 4 meaning a problem was not found and reinspection is recommended in 12 months.

Uploaded by

rupesh kumar
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 8

Techforce Electrical

1/14 Blackly Row


Cockburn Central WA 6164
P – 0425 830 447
E – info@techforceelectrical.com.au

Sample Client

Thermal Image Report


Prepared for:

Sample Client
Address
Address
Address

July 2013
Table of Contents
Introduction & Summary 3

Technical Information 5

Main Switchboard 6

Distribution Board 1 8

Distribution Board 2 12

Distribution Board 3 16

Distribution Board 4 20

2
INTRODUCTION

A summary of all the switchboards and/or plant equipment scanned during this inspection is detailed in this
report.

REQUIRMENTS DURING TESTING

In order to perform the thermal inspection properly it is required that any panel doors and escutcheon panel’s
plastic or glass be removed during testing. This is necessary because infrared radiation testing does not pass
through the above objects.

Covers have only been removed if safety and integrity of the plants operation is not compromised. Any plant
not operating at the time of the Thermal Inspection will be inspected as part of the whole plant but no thermal
observations will be made due to non-operation of that plant.

ACTIONS & RISK ANALYSIS

The following report contains a series of thermograms of the switchboards/plant inspected during the Thermal
Inspection which may highlight possible faults with equipment categorised as per the repair priority schedule.

Techforce Electrical recommend that you conduct your own Risk Assessment of each observation and report in
this document as we only observe & report the seriousness of faults. You will need to determine the possible
impact the observed fault may have on the operation of your plant and prepare your own repair schedule based
on your assessment.

FOLLOW UP

We recommend regular Thermal inspections at (12) twelve monthly intervals. This may reduce unscheduled
downtime and failures. Will also assist with an effective maintenance program.

3
Summary
Based on these test results there are no immediate actions to be taken.

Switchboard Recommended Action


Main Switchboard Nothing to Report
Reinspect in 12 Months
Distribution Board 1 Nothing to Report
Reinspect in 12 Months
Distribution Board 2 Nothing to Report
Reinspect in 12 Months
Distribution Board 3 Nothing to Report
Reinspect in 12 Months
Distribution Board 4 Nothing to Report
Reinspect in 12 Months

4
Technical Information

The temperature observations that are detailed in this report can be referenced to the Australian standards
“Limiting Temperatures” information, which may assist you in your risk analysis of each observation, further
information can be found in the Australian standards AS/NZS 3000, section 3; 3.4.2 and AS/NZS 3008.

In summary, the Australian Standards state that;


1. In all boards the temperature rises shall be related to the ambient temperature. Accessible
boards, i.e. touchable, the rise is not to exceed 30°C and non-accessible boards 40°C.
2. The temperature of the various components are related to the adjacent cable insulation maximum
temperatures, these ideally should not be exceeded. Maximum temperatures: Thermoplastics V-
75 Cables etc. – 75°C; High temp. V-105 – 105°C: Cross linked elastomers e.g. R-EP-90 and
XLPE-90 – 90°C; R-HF-110 – 110°C; 150 – 150°C etc.

The priorities as specified in the repair priority schedule below are based on the above mentioned standards.
The temperature difference as stated below is the difference in temperature between the operating & maximum
fault temperature recorded. The above temperature difference can exist in an electrical installation between
phases, across switches, contactors and other components. Other factors that can effect a temperature
difference are the loading and application of an electrical circuit.

Repair
Average Temp Fault Temp Suggested Action
Priority
1 >30oC >100oC Serious Problem identified, should be corrected
as soon as possible, could fail at any time,
check adjacent components for damage.

2 20oC - 30oC 100oC - 75oC Not serious problem should be corrected within
weeks it could fail at any time resulting to
breakdown, check adjacent components for
damage.

3 20oC - 10oC 75oC - 60oC Minor problem, should be checked and


repaired when convenient or during routine
maintenance should be reinspected during next
inspection to determine trends.

4 <10oC <60oC No problem found. Reinspect in 12 months.

The following general assumptions can be made:

1. Where fuses/circuit breakers are hot at one end it can be assumed that a problem exists with the
contacts and/or connections.
2. Where fuses/circuit breakers are hot overall check the fuse size and load should be checked for
correct rating.
3. A high temperature on both sides of a component suggests faulty contacts/connections and/or out of
balance load. Testing will confirm/eliminate the balance as a problem.
4. Where contactor terminals are hot and the screws are tight, the problem may exist internally with in the
contactor.
5. Generally overloads run cooler than the contactor coil. If the overload is hotter the loads and sizing
should be checked.

5
Inspection Date: 6/25/2013 10:17:45 AM Location Student Housing
Equipment Switchboard Equipment Name: Main Switchboard
Potential Problem: Nil Repair Priority: 4
Emissivity: 0.76 Reflected Temperature: 13.3 °C
Camera Manufacturer Fluke Thermography Camera: 09060417
Hot Image Marker: 34.1°C Cold Image Marker 17.0°C

IR001271.IS2

Inspection Date: 6/25/2013 10:20:12 AM Location Student Housing


Equipment Switchboard Equipment Name: Main Switchboard
Potential Problem: Nil Repair Priority: 4
Emissivity: 0.27 Reflected Temperature: 26.0 °C
Camera Manufacturer Fluke Thermography Camera: 09060417
Hot Image Marker: 26.6°C Cold Image Marker 17.9°C

IR001273.IS2

6
Inspection Date: 6/25/2013 10:23:23 AM Location Student Housing
Equipment Switchboard Equipment Name: Main Switchboard
Potential Problem: Nil Repair Priority: 4
Emissivity: 0.27 Reflected Temperature: 26.0 °C
Camera Manufacturer Fluke Thermography Camera: 09060417
Hot Image Marker: 20.5°C Cold Image Marker 17.3°C

IR001274.IS2

Inspection Date: 6/25/2013 10:31:24 AM Location Student Housing


Equipment Switchboard Equipment Name: Main Switchboard
Potential Problem: Nil Repair Priority: 4
Emissivity: 0.27 Reflected Temperature: 26.0 °C
Camera Manufacturer Fluke Thermography Camera: 09060417
Hot Image Marker: 36.5°C Cold Image Marker 18.3°C

IR001275.IS2

7
Inspection Date: 6/25/2013 10:39:53 AM Location Student Housing
Equipment Switchboard Equipment Name: Distribution Board 1
Potential Problem: Nil Repair Priority: 4
Emissivity: 0.27 Reflected Temperature: 26.0 °C
Camera Manufacturer Fluke Thermography Camera: 09060417
Hot Image Marker: 19.3°C Cold Image Marker 16.8°C

IR001277.IS2

Inspection Date: 6/25/2013 10:40:13 AM Location Student Housing


Equipment Switchboard Equipment Name: Distribution Board 1
Potential Problem: Nil Repair Priority: 4
Emissivity: 0.27 Reflected Temperature: 26.0 °C
Camera Manufacturer Fluke Thermography Camera: 09060417
Hot Image Marker: 24.5°C Cold Image Marker 17.0°C

IR001278.IS2

You might also like