TRF Oil
TRF Oil
NAGARAJA.M.C
Executive Engineer (E), R.T South Division, KPTCL,
Rajajinagar, K.P.T.C.L, Bangalore :560010
Transformer oil or insulating oil is a highly refined mineral oil that is
stable at high temperatures and has excellent electrical insulating
properties.Mineral insulation oil, refined from crude oil.
Resistivity: Resistivity of oil reduces considerably due to presence of moisture, acidity and polar
contaminants. Unsatisfactory results indicate a greater extent of contamination and it may not be
possible to restore the oil to a satisfactory level by reconditioning. This will affect the total
insulation and consequently lower the Insulation Resistance values which is not good for the
operation of the the transformer. Even small traces of contaminating material will give a marked
lowering of the oil resistivity value. Low resistivity indicates the presence of moisture and
conductivity contaminants.
3
SIGNIFICANCE OF VARIOUS TEST PARAMETERS
Dissipation Factor: It is an established method used for the detection of gross defect in the
insulation. Dissipation factor represents the overall loss in the bulk of the insulation. Tan delta
characteristics provide useful information regarding the state of the insulation. Higher Tan delta
value indicates the presence of dirt, conducting particle and other extraneous contaminants in
the insulation. At some point in the system the insulation would have failed allowing current to
flow along paths where it is not desired. The subsequent damage to the equipment may involve
burnt conductors, ruined magnetic core materials and destructive fires. The high dielectric loss
can trigger a thermal break down
Neutralisation Number: Neutralisation number or the acid content of the insulating oil is
defined as the number of milligrams of KOH required to neutralize completely the acids present
in one gram of the oil. The presence of acids, besides corroding the various part of the
equipment i.e. transformer, it also lowers the di-electric strength of the oil and often polymerize
to form insoluble sludge which can clog the cooling system.
Water Content: Water may originate from the atmosphere or be produced by the deterioration
of insulating materials. High water content accelerates the chemical deterioration of insulating
paper and is indicative of undesirable operating conditions.
Break down Voltage: The breakdown voltage is of importance as a measure of the suitability
of oil to withstand electric stress. Dry and clean oil exhibits an inherently high breakdown
voltage. Free water and solid particles, the latter particularly in combination with high levels of
dissolved water, tend to migrate to regions of high electric stress and reduce breakdown voltage
dramatically. The measurement of breakdown voltage, therefore serves primarily to indicate the
presence of the contaminants such as water or conducting particles.
4
Highest equipment voltage, KV
Sl. No. Property
<72.5 72.5 to 170 >170
1 Appearance Clear, free from sediment and suspended matter
2 Density at 29.5°C (gms/cm3), 0.89 0.89 0.89
max
7
ACIDITY OR NEUTRALISATION NUMBER(NN)
Test Method: ASTM D974
Acids in the oil originate from oil decomposition/oxidation products. Acids
can also come from external sources such as atmospheric contamination.
These organic acids are detrimental to the insulation system and can induce
corrosion inside the transformer when water is present.
• The Interfacial Tension (IFT) measures the tension at the interface between
two liquid (oil and water) which do not mix and is expressed in dyne/cm.
• The test is sensitive to the presence of oil decay products and soluble polar
contaminants from solid insulating materials.
• Good oil will have an interfacial tension of between 40 and 50 dynes/cm. Oil
oxidation products lower the interfacial tension and have an affinity for both
water (hydrophilic) and oil. This affinity for both substances lowers the IFT.
The greater the concentration of contaminants, the lower the IFT, with a badly
deteriorated oil having an IFT of 18 dynes/cm or less.
9
IFT-NN RELATIONSHIP
Studies have shown that a definite relationship exists between acid number(NN) and
Interfacial Tension(IFT). An increase in NN should normally be followed by a drop in
IFT. The IFT test is a powerful tool for determining how an insulating oil has
performed and how much life is left in the oil before maintenance is required to
prevent sludge.
Although a low IFT with a low NN is an unusual situation , it does occur because
of contamination such as solid insulation materials, compounds from leaky pot heads
or bushings, or from a source outside the transformer.
10
CONTAMINATION BY GASES
11
• QUALITY INDEX SYSTEM
• Dividing the Interfacial Tension(IFT) by the Neutralisation Number(NN) provides a
numerical value that is an excellent means of evaluating oil condition. This value is
known as the Oil Quality Index(OQIN) or Myers Index Number(MIN). A new oil , for
example has a OQIN of 1500.
OQIN = IFT 1500=45.0(typical new oil)
NN 0.03(typical new oil)
TRANSFORMER OIL CLASSIFICATIONS *
1. Good Oils
NN 0.00 - 0.10
IFT 30.0 - 45.0
Colour Pale Yellow
OQIN 300-1500
2. Proposition A Oils
NN 0.05 - 0.10
IFT 27.1 - 29.9
Colour Yellow
OQIN 271 - 600
3. Marginal Oils
NN 0.11 - 0.15
IFT 24.0 - 27.0
Colour Bright Yellow
OQIN 160 - 318 12
4. Bad Oils
NN 0.16 - 0.40
IFT 18.0 - 23.9
Colour Amber
OQIN 45 - 159
14
TRANSFORMER OIL RESULTS ANALYSIS
Oil Color Acid (NN) IFT Oil Status Transformer Condition
Water White 0.03-0.10 30-45 Excellent Good
Yellow Tint 0.05-0.10 27-30 Good Sludge dissolved in oil
Yellow Solution 0.11-0.15 24-27 Marginal Acid coating insulation, sludge ready to
deposit in transformer
Orange 0.16-0.40 18-24 Bad Sludge in radiators, core & coil
Reddish-Brown 0.41-0.65 14-18 Very Bad Sludge hardening & layering,
insulation is shrinking & weakening
Brown 0.66-1.5 9-14 Extremely Bad Radiators blocked with bad sludge,
increased operating temperature
Black Over 1.5 Below 9 High Risk Transformer failure is likely
15
The IEEE Guide for reclamation of Insulating Oil and Criteria for Its Use (IEE Std 637-
1985) has four group classifications for oil evaluation.
Group I: Oils that are in satisfactory condition for continued use.
Group II: Group III: Oils that required only reconditioning for further service.
Oil in poor condition. Such oil should be reclaimed or disposed of depending upon
Group IV: economic considerations
Oil in such poor condition that it is technically advisable to dispose of it.
Test Suggested Limits for In-Service Oils Group I by Voltage Class
Neutralization Number,
mg KOH/g (max)
For oil that does not meet the recommended thresholds above, there are two
options. One, the oil can be utilized in a lower voltage application, assuming it
was utilized above a 69KV application. Two, the oil can be reconditioned or
reclaimed to meet the Group I classification. Listed below are the thresholds for
oil treatment
16
Suggested Limits for in-Service oils Group II & Group III
17
18
19
20
21
22
23
24
25
26
27
GAS ANALYSIS
• Dissolved gas analysis (DGA) and the information it can provide are
particularly important in analysing the health of the transformer and determining
whether oil treatment is necessary. The rate of insulation decomposition will
increase significantly in the presence of faults. By drawing a sample and having
the gas composition analyzed, it's possible to distinguish between different fault
types.
28
29
• TRANSFORMER OIL GAS ANALYSIS
• Test Method IEC 567
Transformers are vital components in both the transmission and distribution of
electrical power. The early detection of incipient faults in transformers is extremely
cost effective by reducing unplanned outages. The most sensitive and reliable
technique used for evaluating the health of oil filled electrical equipment is dissolved
gas analysis (DGA). .
Insulating oils under abnormal electrical or thermal stresses break down to liberate
small quantities of gases.The qualitative composition of the breakdown gases is
dependent upon the type of fault. By means of dissolved gas analysis (DGA), it is
possible to distinguish faults such as partial discharge (corona), overheating (pyrolysis)
and arcing in a great variety of oil-filled equipment.
Information from the analysis of gasses dissolved in insulating oils is valuable in a
preventative maintenance program. A number of samples must be taken over a period
of time for developing trends. Data from DGA can provide
Advance warning of developing faults.
A means for conveniently scheduling repairs.
Monitor the rate of fault development
NOTE : A sudden large release of gas will not dissolve in the oil and this will cause the
Bucholtz relay to activate.
30
31
• ORIGIN OF GASES IN TRANSFORMER OIL
Fault gases are caused by corona (partial discharge), thermal heating (pyrolysis) and arcing.
PARTIAL DISCHARGE is a fault of low level energy which usually occurs in gas-filled voids
surrounded by oil impregnated material. The main cause of decomposition in partial discharges
is ionic bombardment of the oil molecules.
The major gas produced is Hydrogen. The minor gas produced is Methane.
THERMAL FAULTS
A small amount of decomposition occurs at normal operating temperatures. As the fault
temperature rises, the formation of the degradation gases change from Methane (CH4) to
Ethane (C2H6) to Ethylene (C2H4).
A thermal fault at low temperature (<300deg/C) produces mainly Methane and Ethane and
some Ethylene. A thermal fault at higher temperatures (>300deg/C) produces Ethylene. The
higher the temperature becomes the greater the production of Ethylene.
ARCING is a fault caused by high energy discharge.
The major gas produced during arcing is acetylene. Power arcing can cause temperatures of over
3000deg/C to be developed.
NOTE : If the cellulose material (insulating paper etc.) is involved , carbon monoxide and
carbon dioxide are generated.
A normally aging conservator type transformer having a CO2/CO ratio above 11 or below 3
should be regarded as perhaps indicating a fault involving cellulose, provided the other gas
analysis results also indicate excessive oil degradation.
32
GAS NORMAL ABNORMAL INTERPRETATION
H2
< 150 ppm > 1000 ppm Arcing corona
CH4
< 25 ppm > 80 ppm Sparking
C2H6
< 10 ppm > 35 ppm Local Overheating
C2H4
< 20 ppm > 100 ppm Severe Overheating
C2H2
< 15 ppm > 70 ppm Arcing
CO
< 500 ppm > 1000 ppm Severe Overloading
CO2
< 10 000 ppm > 15 000ppm Severe Overloading
N2
1-10 % NA -
O2
0.03 % > 0.5 % Combustibles 33
The gases generated inside the transformers
are hydrogen and hydrocarbon gases.
34
35
36
37
38
PERMISSIBLE LIMITS
Permissible concentrations of dissolved gases in the oil of a healthy
transformer (Transformer Union AG)
Less than four
Gas 4 – 10 years > 10yrs
year in service
Ethylene 100 / 150 ppm 150 / 200 ppm 200 / 400 ppm
Carbon
200 / 300 ppm 400 / 500 ppm 600 / 700 ppm
Monoxide
40
Periodic DGA reveals increase of gas concentration of
key gas Ethylene even when load was reduced, indicating
severe thermal fault - overhead joint.
41
DGA indicates P.D. of high energy discharges in gas
filled cavities resulting from incomplete impregnation or
super-saturation or cavitation or high humidity leading
to tracking or perforation of insulation.
42
Implementing your own preventive maintenance programme
(Overseas Example)
43
The Typical Faults That May Occur During Routine
Tests Are:
44
GREATEST ADVANTAGE OF DGA TECHNIQUE
45
GREATEST ADVANTAGE OF DGA TECHNIQUE
• Avoidance of unplanned outage as transformer defects are
detected at incipient stages itself so that timely remedial measures
can be undertaken to prevent damage or total loss of equipment
• Status of health check for transformer periodically
• Is a quality test for new transformer / repaired transformer
before dispatch, installation & commissioning
• Cleaning transformer without internal faults, when they have
tripped due to other reasons
• Several gases where transformers have been saved from total
destruction, the confidence in DGA technique is so high that the
transformers are sent to repairs by no other evidence other than
that of DGA
46