HVAC Coil Design & Operating Data

The document provides specifications for a coil-fin heat exchanger, including tube dimensions, fin properties, and operating data. The heat exchanger is designed to provide a total cooling load of 60 kW at full load, with 20 kW devoted to latent cooling. Air enters at 26°C dry bulb and 19°C wet bulb temperatures, with a face velocity of 2.8 m/s. Chilled water enters at 6°C and exits at 11°C, with a mass flow rate of 2.9 kg/s. Psychrometric data is also provided for the inlet air conditions.

Uploaded by

Ranu Januar
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
378 views4 pages

HVAC Coil Design & Operating Data

The document provides specifications for a coil-fin heat exchanger, including tube dimensions, fin properties, and operating data. The heat exchanger is designed to provide a total cooling load of 60 kW at full load, with 20 kW devoted to latent cooling. Air enters at 26°C dry bulb and 19°C wet bulb temperatures, with a face velocity of 2.8 m/s. Chilled water enters at 6°C and exits at 11°C, with a mass flow rate of 2.9 kg/s. Psychrometric data is also provided for the inlet air conditions.

Uploaded by

Ranu Januar
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
You are on page 1/ 4

1 Coil construction parameters

Outside tube diameter do 13.41 mm


Inside tube diameter di 12.09 mm
Longitudinal tube spacing SL 26.16 mm
Transverse tube spacing ST 31.75 mm
No. of fins/m Nf 554
Aluminum fin thickness tf 0.15 mm
Exchanger compactness β 1060 m2/m3
Outside area/inside area (Ao/Ai) 23
Aflow/Aface on the air-side σ 0.529
Finned-surface weighted efficiency ηS 0.85
Number of tube-passes per water loop Np 6

2 Design operating Data


Moist air
Total cooling load at full load Qc 60 kW
Latent Load at full load QL 20 kW
Inlet air conditions t Dry tdry 26 oC
Inlet air conditions t Wet twet 19 oC
Air face velocity Vface 2.8 m/s
Air heat transfer coefficient hc 60 W/(m2oC)
Air mean specific heat cpm 1.001 kJ/(kg.K)

3 Chiller Water
Inlet Water Temperature TWin 6 oC
Water mass flowrate mW 2.9 kg/s
Water inlet velocity VW 1.25 m/s
Heat Transfer coefficient on water side hi 4000 W/(m2oC)
Number off tube passes per water loop Ntp 6
Exit water temperature TWout 11 oC
Water specific heat CPW 4.14 kJ/(kg.K)

4 Psychorometric Chart Air In


Inlet air conditions t Dry tdry 26 oC
Inlet air conditions t Wet twet 19 oC
RH 50 %
Entalphi hain 54 kJ/kg
Moisture Content Wain 0.011 kgv/kga
Dew Point dpt 15.5 oC
CSHF 0.75
Moisture Air In Φ 95 %

5 Psychorometric Chart Air In


Inlet air conditions t Dry tdry 26 oC
Inlet air conditions t Wet twet 19 oC
RH 50 %
Entalphi hain 54 kJ/kg
Moisture Content Wain 0.011 kgv/kga
Dew Point dpt 15.5 oC
CSHF
Moisture Air In Φ 95 %
Design operating Data
Moist air
Total cooling load at full load Qc 60 kW
Latent Load at full load QL 20 kW
Inlet air conditions t Dry tdry 26 oC
Inlet air conditions t Wet twet 19 oC
Air face velocity Vface 2.8 m/s
Air heat transfer coefficient hc 60 W/(m2oC)
Air mean specific heat cpm 1.001 kJ/(kg.K)