TABLE OF CONTENTS
1. INTRODUCTION
2, CONTROL SYSTEM OVERVIEW.
2.1 Panet Equipment...
2.2 Environmental Consraints
23 Power Supply...
2.4 DC Contrel inputs.
2.5 DC Contol Outputs
26 DC Sender Inputs.
2.7 AC Voltage Inputs
2.8.AC Current Inputs
2.8 Communication Interface
3. CONTROL,
4. OPERATING INSTRUCTIONS.
4.4 Automatic Mode Of Operation...
4.2 Manual Mode of Operation ...onesennn
4.3 Display Menus. .
5. FAULT CONDITIONS ....-
5.1 Internal Fault Conditions ..
5.2 External Fault Condtions
6. CONFIGURATION...
6.1 System Menu...
6.2 Setpoints Men...
6.6 Calibrate Menu
7. CONTROL SYSTEM OPTIONS AND UPGRADES.
7.4 Battery Trickle Charger
7.2 Heaters. an
7.3 Electric Fuel Transfer Pumps.
7-4 Remote Annunciator Interface,
7.5 Remote Control and Monitoring,
8. CONTROL SYSTEM FAULT FINDING/TROUBLE SHOOTING GUIDE.
8, SPECIFICATION.
‘© Copyright 1999 FG. Wison (Engineering) Limited. All ightsrese
Document: MAN-AGOOO
Issue: 2
Dato: 0509
Part No.276-0494.
INTRODUCTION
‘The ACCESS 4000 mioraprocessor based generator conirol panel is
an auto-start system providing a comprehensive array of operational
features, Utilising the latest advances in embedded microprocessor
technology, surface mount printed circuit board assembly and software
development techniques, the design provides for a powerful, easy to
se system together with high accuracy for all metering and protection
functions.
(Once activated the ACCESS 4000 module carries aut all the start and
slop procedures for the engine, indicates the operational status and
‘auk conditions; and automatically shuts down the generator set in the
‘event of critical condition arising.
‘A ange of optional features alfow other functions such as an open
protocol communication interface, for communicating with Supervisory
Control And Data Acquistion (SCADA) systems, or remote monitoring
Via. a vo ree relay interface module.
‘The module is housed in a robust plastic case for front panel mounting
within a control panel. Connection tothe unit is via locking plugs and
sockets.
‘The ACCESS 4000 provides the following advanced features:
‘© Microprocessor based circuitry
‘¢ NFPA 110 Level 1 compliance
+ NEMA 1 enclosure
‘+ Large format alpha-numeric Liquid Crystal Display
‘* Open protocot communication interface
‘© Digital sor 1 phase voltage and current metering
‘+ Digital engine parameter metering
© Upto 16 faull circuits utilising analogue and digital inputs
‘= 20event faut log memory
‘+ Password protected operator levels.
‘¢ Site programmable using the integral Keypad or
Laptop PC.
‘+ Configuration stored in non-volatile memory
‘CONTROL SYSTEM OVERVIEW
‘The following installation guidelines are provided for general
information only. For specifc site installation information, consult your
local desler as required.
‘CAUTION:
1 Altinstalation andlor service work performed must be done by
‘quslfed personnel only. Fallue te do so may cause personal
injury or death
24 Panel Equipment
‘The ACCESS 4000 control panel consists of three main parts;
‘an ACCESS 4000 control module, external control equipment
and a panel enclosure. Figuie 2.1 shows a fully optionised
diagram of an ACCESS 4000 control panel.
Note:
© The addition of non-standard optional equipment may ada
items not shown here. The following descriptions explain the
function of each item on the panel, a more detailed
description of the control module folows in section 3.
Figure 2.4 - Diagram of a Typical ACCESS 4000 Control Panel
1. ACCESS 4900 Control Module
2, Panal Enclosure - housing the module and
associated external controls.
3. Audible Alarm -a buzzer that sounds on sensing
a fault condition, [option]
4. Emergency Stop push-button - 2 red lock-dewn
button Is used fo intiate an emergency stop
signal to the generator set. This wil cause the
‘engine to immediately stop and be prohibited
{form operation until the button is released.
5. Voltage Adjust Control - a potentiometer
providing manual control ofthe generator output
voltage (AVR excitation). [option]
8. Thormostart Control-a momentary action button
is used to pre-heat the engine prior to cranking.
{option}
7. Control Switch -a three position switch
ccontrolkng the mode of operation. Refer to the
‘operating instructions for detailed information.
© pw
In this positon, the engine wil start and operate
continuously providing ne shutdown faut
ondiions ae active. Al protective functions wil
‘be operative inthis mode. There wil be no start,
dolay or slop (cooldown) delay inthis mode.
© or
Manually initiates a stop signal tothe generator
‘and prohisits automatic startngiunning. The
control switch must be retumed to this position
following @ shutdown fault condition before any
further generator set operation wil occur.
© suro
In this position, starting and stopping of the
‘engine will be controlled by the REMOTE
START contact. With the contact closed, the
‘generator set wil start and run, With the contact
removed, the generator set wil stop and return
to standby,8, Fue! Transfer System Run - a momentary action button used
to inate the operation ofthe fuel transfer system. [option]
8. Fue! Transfer System Stop -a lock-down button used to
cancel the operation of the uel transfer system. [option}
10. Battery Charger Boost - a two position switch controling the
engine starter battery charging voltage. [option]
11. Speed Adjust Control - a potentiometer providing manval,
Control of the generator output frequency (engine speed).
{Option}
2.2 Environmental Constraints
‘The module when mounted correctly within a panel will conform
to IEC 528 IP-56 and NEMA 1. The panel should be vibration
isolated from the engine and altemator and protected against
excessive temperature swings,
23 Power Supply
‘The ACCESS 4000 control system is designed to operate on any
direct current (DC) battery supply io the range 9 to 32 volts. The
battery negative must be grounded to the engine block, usually
via the starter motor negative terminal. An intemal batiery is not
provided and is not necessary.
conta age
” 0298 400
K—
vec
eee
Figure 22 - Typical DC Control Input Wiring
24 DE Control Inputs
‘All DC control inputs to the ACCESS 4000 are optically isolated
for protection ftom noise and transient spikes. All inputs are
designed to switch law ie. to the battery negative including the
emote start contact. The use of POWERED CONTACTS may
damage the control module.
28 OC Control Outputs
‘All de control outputs from the ACCESS 4000 are vol-ree relay
‘contacts. The contacts are rated for 2 Amps at 30Vde and are
isolated Form C type. The use of interposing relays between the
ACCESS 4000 and the extemal device is necessary to prevent
potential internal damage due to excessive current. For loads
‘generating switching spikes, the application of kansient
Suppress is alo recommenced.
Now:
© Onpower toss ALL oupus wil sth othe de-energised
ste
oo tos oy eae
scene 109
[rr O
° cag
Figure 2.3 - Typical DC Control Cutput Wiring
2.6 DG Sender Inputs
Both engine sender inputs {oil pressure and engine
‘coolant temperature) are designed to operate with
vatlable resistive typo senders.
kay
Figure 2.4 - Typical DC Sender Input Wiring
27 AC Voltage Inputs
‘The ACCESS 4000 is designed using a multtapped
potential transformer forall AC voage input in the
range 60 - 300Vac, using one of four tappings on the
high accuracy potential transformers fied external
to the ACCESS 4000 (Agure 25), Standard singe or
three phase systems can be accommodated using
‘one af five alternator winding configurations 3s.
‘shown in figure 2.6. High voltage systems may be
interfaced using additional specialised transformers.
WARNING
! The incorrect connection of the AC Voltage
Inputs will damage the controlier. Ensure that
correct primary voltage tapping connections
are made.
320v oO
250, |
130V 25vims
ev
N
0
Figure 2.5 - Mult-tap Transformer