Faculty of electrical and computer engineering
POWER SYSTEM I
EEng-3132
Characteristics and Performance of Transmission
Lines
Compiled by: Biniyam Z.
1 4/9/2019
Chapter Five
Characteristic and performance of power transmission
lines
Outline
Introduction
ABCD constants
Representation of transmission lines
Short transmission line
medium transmission line and
Long transmission line
2 4/9/2019
INTRODUCTION
This chapter deals with the representation and performance of transmission
lines under normal operating conditions
Transmission lines are represented by an equivalent model with appropriate
circuit parameters on a per-phase basis
The terminal voltages are expressed from one line to neutral, the current
for one phase and, thus, the three-phase system is reduced to an equivalent
single phase system
This model used to calculate voltages, currents, and power flows depends
on the length of the line
3 4/9/2019
ABCD Constants
It is convenient to represent a transmission line by the two port
network, where in the sending-end voltage Vs and current Is are related
to the receiving-end voltage VR and IR through A, B, C and D
parameters (ABCD constants) as
VS = AVR + BI R Volts
IS = CVR + DI R Amp
or, in matrix form
Figure: Two-port representation ofTx lines
VS A B VR
I = C D I R
(5.1)
S
A, B, C and D are the parameters that depend on the transmission line
constants R, L, C and G
4 4/9/2019
The ABCD parameters are, in general complex numbers
A and D are dimensionless
B has units of Ohms and
C has units of Siemens
Also the following identity holds for ABCD constants
AD BC 1 (5.2)
5 4/9/2019
SHORT TRANSMISSION LINES
Capacitors may be ignored without much error if the lines are less than
80 km long or if the voltage is not over 66 kV
The short line model is obtained by multiplying the series impedance
per unit length by line length
Z r j L l
R jX (5.3)
where: r - per phase resistance per unit length
L - per phase inducatnce per unit length
l - the line length
The short line model on per-phase basis is shown in figure 5.2 below
Figure 5.2 Short line model
6 4/9/2019
If a three phase load with apparent power S R (3 ) is connected at the end
of the transmission line, the receiving end current is obtained by:
S R* (3 )
IR *
(5.4)
3V R
The phase voltage at the sending end is
VS VR ZI R (5.5)
since the shunt capacitance is neglected, the sending end and the receiving end
currents are equal
IS IR (5.6)
The relationship between sending-end, receiving-end voltages and
currents can be written as in the form of equation 5.1
A 1, B Z , C 0 and D 1
VS 1 Z VR
I 0 1 I (5.7)
S R
7 4/9/2019
The phasor diagram for the short line is shown in figure 5.3
Figure 5.3 Phasor diagram for short transmission line
Voltage Regulation and Efficiency
Voltage regulation of the transmission line may be defined as the
percentage change in voltage at the receiving end of the line ( expressed
as percent of full load voltage) in going from no-load to full-load
8 4/9/2019
VR ( NL ) VR ( FL )
Percent VR x100 (5.8)
VR ( FL )
At no load, I R 0, and from eqn. (5.1)
VS
VR ( NL ) (5.9)
A
For a short line, A 1 ( VR ( NL ) VS ) and VR ( FL ) VR
VS VR
Percent voltage regulation x100 (5.10)
VR
Voltage regulation is a measure of line voltage drop and depends on the
load power factor
Voltage regulation will be poorer at low lagging power factor loads.
With capacitive loads (leading P.f.) regulation may become negative
9 4/9/2019
Once the sending end voltage is calculated the sending end power is
obtained by
S S (3 ) 3VS I S* (5.11)
The total line loss is then given by
S L (3 ) S S (3 ) S R (3 ) (5.12)
and the transmission line efficiency is given by
PR (3 )
(5.13)
PS (3 )
where PR (3 ) and PS (3 ) are the total real power at the receiving end and sending end
of the line, respectively
10 4/9/2019
Example
A 220 kV, three phase transmission line is 40 km long. The resistance
per phase is 0.15 Ω per km and the inductance per phase is 1.3263
mH per km. The shunt capacitance is negligible. Use the short line
model to find the voltage and power at the sending end and the
voltage regulation and efficiency when the line is supplying a three
phase load of
a). 381 MVA at 0.8 power factor lagging at 220 kV
b). 381 MVA at 0.8 power factor leading at 220 kV
Solution
(a).The series impedance per phase is
Z (r j L)l
(0.15 j 2 x60 x1.3263 x103 )40
6 j 20
11 4/9/2019
The receiving end voltage per phase is
22000
VR 12700 kV
3
The apparent power is
SR (3 ) =381cos -1 0.8 =38136.870
304.8 j 228.6 MVA
From eqn. (5.5), the sending end voltage is
VS VR ZI R
12700 6 j 20 1000 36.87 0 103
144.334.930 kV
The sending end line-to-line voltage magnitude is
VS ( L L ) 3 VS 250 kV
12 4/9/2019
The sending end power is
S S (3 ) 3VS I S* 3x144.334.930 x100036.87 0 x10 3
322.8 MW j 288.6 MVar
433 41.80 MVA
Voltage regulation is
250 - 220
Percent VR x100 13.6%
220
Transmission line efficieny is
PR (3 ) 304.8
x100 94.4%
PS (3 ) 322.8
13 4/9/2019
(b) The current for 381 MVA with o.8 leading power factor is
S R* (3 ) 38136.87 0 x103
IR 100036.87 0
3VR* 3 x1270 0
The sending end voltage is
VS VR ZI R 12700 6 j 20 100036.87 0 10 3
121.399.290 kV
The sending end line-to-line voltage magnitude is
VS ( L L ) 3VS 210.26 kV
The sending end power is
S S (3 ) 3VS I S* 3 x121.399.290 x1000 36.87 0 x10 3
322.8 MW j168.6 Mvar
364.18 27.580 MVA
Voltage regulation is
210.26 220
Percent VR x100 4.43%
220
Transmission line efficiency is
PR (3 ) 304.8
x100 94.4%
14 PS (3 ) 322.8 4/9/2019
MEDIUM TRANSMISSION LINE
For the lines more than 80 km long and below 250 km in length are
treated as medium lines, and the line charging current becomes
appreciable and the shunt capacitance must be considered
For medium length lines, half of the shunt capacitance may be
considered to be lumped at each end of the line. This is referred to as
the nominal π model and is shown in figure 5.4.
Figure 5.4 nominal π model for medium length line
The sending end voltage and current for the nominal π model are
obtained as follows:
15 4/9/2019
From KCL the current in the series impedance designated by IL is
Y
IL IR VR (5.14)
2
From KVL the sending end voltage is
VS VR ZI L (5.15)
substituting for I L from (5.14), we obtain
ZY
VS 1 VR ZI R (5.16)
2
The sending end current is
Y
IS IL VS (5.17)
2
Substituting for I L and VS
ZY ZY
I S Y 1 VR 1 IR (5.18)
4 2
16 4/9/2019
Eqns. (5.16) and (5.18) can be written in matrix form
ZY
1 Z
VS 2 V
I
R
(5.19)
S Y 1 ZY ZY I R
1+
4 2
Therefore, the ABCD constants for the nominal model are given by
ZY
A 1 , BZ
2
ZY ZY
C Y 1 , D 1
4 2
Solving (5.1), the receiving end quantity can be expresses in terms
of the sending end quantities by
VR D B VS
I C A I (5.20)
R S
17 4/9/2019
Example 1
Determine the efficiency and regulation of a 3-phase, 150 km long, 50
Hz transmission line delivering 20 MW at a power factor of 0.8 lagging
and 66 kV to a balanced load. Resistance of the line is 0.075 Ω/km,
inductance of the line and capacitance per phase is 1.117 mH/km and
9.933 nF/km respectively. Use nominal π method.
Solution
R 0.075 x150 11.25
Inductive reactance per phase is
since, L 1.117 mH per phase/per km
X 2 x x50 x150 x0.1.117 x10 3 52.62
and the capacitance per phase per unit length is given as
C 9.933 nF/km
The capacitance per phase is
18
C 9.933 nF/km x 150 =1.49 F 4/9/2019
Y jC j 2 x50 x1.49 x106 mho
j 468.1x106 mho
Y
j 234 x10 6 mho
2
Z 11.25 j 52.62 53.80977.90
Now
cos
*
P
S*R(3 ) 20MW-36.87 0
IR = = =
3V*R 3V*R
3x0.8x
66
kV 00
3
= 218.7 36.87 0 Amp
I R 218.7 Amp. at 0.8 pf lagging
Receiving end phase voltage
66
VR 38.104 kV
19 3 4/9/2019
From eqn. (5.19), we have
ZY
VS 1 VR ZI R
2
I R 218.7 36.870
VR 38.10400
53.809 x 234 x106 77.90 900
ZY
2
0.01259167.90 0.0123 j 0.00264
VS 1 0.0123 j 0.00264 x38.10400
53.80977.9 x 218.7 36.87
0 0
1000
0.9877 j 0.00264 x38.10400 11.7641.030
37.63 j 0.1 8.87 j 7.72
46.5 j 7.82 47.159.540 kV
20 4/9/2019
VS ( L L ) 3 x 47.159.540 kV 81.669.540 kV
VS
VR 81.66
66
A
Voltage regulation VR 0.9877 25.26%
VR 66
Power loss per phase I R 218.7 x11.25 x10 6 MW 0.538 MW
2 2
Per phase receiving end power
20
PR MW
3
Per phase sending end power
20
PS 0.538 7.204 MW
3
Transmission efficiency
20
= 3 x100 92.54%
21 7.204 4/9/2019
Example 2
Determine the voltage, current and power factor at the sending end of a 3
phase, 50 HZ, overhead transmission line 160 km long delivering a load of
100 MVA at 0.8 pf lagging and 132 kV to a balanced load. Resistance per
km is 0.16 Ω, inductance per km is 1.2 mH and capacitance per km per
conductor is 0.0082 μF . Use nominal π method.
Solution
R 0.16 x160 25.6
X 1.2 x103 x 2 x50 x160 60.3
Y j 2 x50 x 0.0082 x106 x160 j 4.12 x104 mho
Z R jX 25.6 j 60.3 65.5167 0
ZY
VS 1 VR ZI R
2
Phase voltage at the receiving end,
132
VR 00 kV 76.2100 kV
22 3 4/9/2019
Receiving end current
100 x106
IR 3
Amp 437.38 Amp
3 x132 x10
Load has lagging power factor of 0.8, i.e., R 36.87 0
I R 437.38 36.870 Amp
ZY
65.51670 x 4.12 x104 900
2
0.0124 j 0.0053
65.5167 0 x 437.38 36.87 0
VS 1 0.0124 j 0.0053 x 76.210 0
1000
VS 101.078.180 kV
Sending end line to line voltage
VS ( L L ) 3x101.078.180 kV
175.058.180 kV
From equation
ZY ZY
I S Y 1
R
V 1 IR
4 2
23 4/9/2019
ZY
0.00675157 0
4
ZY
1 0.99380.150
4
ZY 4
Y 1 4.12 x10 x 0.993890.15 0
4
4.094 x104 90.150
4
I S 4.094 x10 90.15 x76.210
0 0
1 0.0124 j 0.0053 x 437.38 36.87 0
1000
I S 0.031190.150 0.432 36.560
0.414 33.060 kAmp
414 33.060 Amp
Sending end power factor angle 8.180 33.06 0 41.240
Sending end power factor cos 41.24 0 0.752
24 4/9/2019
LONG TRANSMISSION LINE
For the short and medium length lines reasonably accurate model were
obtained by assuming the line parameters to be lumped
In case the lines are more than 250 km long, for accurate solutions the
parameters must be taken as distributed uniformly along the length as a
result of which the voltage and currents will vary from point to point on
the line
In this section, expressions for voltage and current at any point on the
line are derived. Then, based on these equations, an equivalent π model
is obtained for long transmission line.
Figure 5.6 shows one phase of a distributed line of length l km, the
series impedance per unit length is shown by the lowercase letter z, and
the shunt admittance per phase is shown by the lowercase letter y,
where z r j L and y g jC
25 4/9/2019
Figure 5.5: Long line with distributed parameters
Consider a small segment of line ∆x at a distance x from the receiving
end of the line
From Kirchhoff's voltage law
V ( x x ) V ( x ) z xI ( x ) (5.21)
or
V ( x x ) V ( x )
zI ( x ) (5.22)
x
Taking the limit as x 0, we have
dV ( x )
zI ( x ) (5.23)
dx
26 4/9/2019
Also, from KCL
I ( x x ) I ( x ) y xV ( x x ) (5.24)
or
I ( x x) I ( x)
yV ( x x ) (5.25)
x
Taking the limit as x 0, we have
dI ( x )
yV ( x ) (5.26)
dx
Differentiating (5.23) and substituting from (5.26), we get
d 2V ( x) dI ( x )
z
dx 2 dx
zyV ( x ) (5.27)
Let
2 zy (5.28)
27 4/9/2019
The following second-order diffrent equation will result
d 2V ( x) 2
2
V ( x) 0 (5.29)
dx
The solution of the above equation is
V ( x ) A1e x A2e x (5.30)
where , known as the propagation constant, is a complex expression given by (5.28) or
j zy r j L g jC (5.31)
The real part is known as the attenuation constant, and the imaginary component
is known as the phase constant, is measured in radian per unit length
From (5.23), the current is
1 dV ( x)
I ( x) A1e x A2e x
z dx z
y
z
A1e x A2 e x (5.32)
28 4/9/2019
or
I ( x)
1
Zc
A1e x A2e x (5.33)
Where Z c is known as the characteristic impedance, given by
z
Zc (5.34)
y
To find the constants A1 and A2 we note that when x 0, V ( x) VR , and
I ( x) I R . From (5.30) and (5.33) these constants are found to be
VR Z c I R
A1 =
2
V Zc I R
A2 = R (5.35)
2
upon substitution in (5.30) and (5.33), the general expression for voltage and current along a long
trnsmission line become
VR Z c I R x VR Z c I R - x
V ( x) e + e (5.36)
2 2
VR VR
IR IR
Z Z
I ( x) c e x - c e - x (5.37)
29 2 2 4/9/2019
The equations for voltage and currents can be rearranged as follows:
e x e x e rx e rx
V ( x) VR Z c IR (5.38)
2 2
1 e x e x e x e x
I ( x) VR IR (5.39)
Z 2 2
Recognizing the hyperbolic functions sinh, and cosh, the above equations are
written as follows:
V ( x) cosh xVR Z c sinh xI R (5.40)
1
I ( x) sinh xVR cosh xI R (5.41)
Zc
we are particularly intersted in the relation b/n the sending end and the
receiving end of the line. Setting x l , V (l ) VS and I (l ) I S , the result is
VS cosh lVR Z c sinh lI R (5.42)
1
IS sinh lVR cosh lI R (5.43)
Zc
30 4/9/2019
Rewriting the above equations in terms of the ABCD constants as before, we have
VS A B VR
I C D I
S R
Where
A cosh l B Z c sinh l (5.44)
1
C sinh l D cosh l (5.45)
Zc
Note that, as before, A D and AD BC 1
It is now possible to find an accurate equivalent model, shown in
figure 5.6, to replace the ABCD constants of the two-port network
for the equivalent model we have
Z 'Y '
VS 1 VR Z ' I R (5.46)
2
Z 'Y ' Z 'Y '
I S Y ' 1 R 1
V IR (5.47)
4 2
31 4/9/2019
Comparing (5.46) and (5.47) with (5.42) and (5.43), respectively,
and making use of the identity
l cosh l 1
tanh (5.48)
2 sinh l
the parameters of the equivalent model are obtained
sinh l
Z ' Z c sinh l Z (5.49)
l
l
Y' 1 l Y tanh
2
tanh (5.50)
2 Zc 2 2 l
2
32 4/9/2019
Q?
Thank you
33 4/9/2019