Lov Voltage Air Circuit Breakers
Lov Voltage Air Circuit Breakers
FOR
     ELECTRONIC MCCBs
INSTRUCTION MANUAL
                      Notice
  Please retain this manual for future reference.
                                                    KRB-5308b
KRB-5308b
                                                  Table of Contents
                                                                                                                                     Page
1. SAFETY NOTICES.......................................................................................................... 3
5-1. Testing Procedure for Pickup Current Value for Long Time Delay Trip Function. 13
  5-2.      Testing Procedure for Trip Time Setting Value for Long Time Delay Trip Function
            ............................................................................................................................. 14
  5-3.      Testing Procedure for Trip Current Setting Value for Short Time Delay Trip
            Function (definite time characteristic) .................................................................. 15
  5-4. Testing Procedure for Trip Time Setting Value for Short Time Delay Trip Function
            (definite time characteristic) ................................................................................. 20
  5-5. Testing Procedure for Trip Time Setting Value for Short Time Delay Trip Function (I2t
            characteristic) ...................................................................................................... 21
  5-6.      Testing Procedure for Trip Current Setting Value for Instantaneous Trip Function
            ............................................................................................................................. 21
  5-7.      Testing Procedure for Trip Current Setting Value for Ground Fault Trip Function
            ............................................................................................................................. 24
5-8. Testing Procedure for Trip Time Setting Value for Ground Fault Trip Function ... 25
5-9. Adjustment........................................................................................................... 25
 The type TNS-2 OCR checker facilitates on-site testing of the OCR (overcurrrent release) installed on electronic
 MCCBs, TemBreak and TemBreak2. Carefully read this manual to ensure proper use of the OCR checker.
                                                                    1
                                                                                                                         KRB-5308b
            2
KRB-5308b
1. SAFETY NOTICES
 Thank you for purchasing the type TNS-2 OCR checker.
 This chapter gives you the important information on safety. Prior to the use of the Type TNS-2 OCR Checker, be sure to
 thoroughly read this and subsequent chapters of this instruction manual and all the other documents that come with this product.
 To ensure the proper use, gain the full knowledge of the OCR checker and familiarize yourself with all the safety information and
 precautions. This chapter classifies the following safety precautions as “ CAUTION”, which indicates a potentially hazardous
 situation that, if not avoided, may result in minor or moderate injury, or otherwise may result in physical property damage only.
 A failure in observing any instruction given under “ CAUTION” might lead to a more serious result depending on the situation.
 Be sure to observe these instructions, all of which include very important information.
                                                            CAUTION
  Common to transportation, operations, and storage
  • Do not store the OCR checker in an abnormal environment where it is exposed to high temperature, high humidity,
      excessive dust, corrosive gas, vibrations, shocks, or any other similar condition. Avoid direct sunlight and maintain the
      ambient temperature in a range between –20°C and 55°C and relative humidity in a range between 45% and 85% (without
      condensation). Otherwise, a failure may result.
     Transportation
  •   Do not drop the OCR checker, nor give a shock to it. The OCR checker is an electronic product requiring careful handling.
      Improper handling will result in a failure.
     Operations
  •   The test using the OCR checker shall be performed by a qualified operator who has the necessary expertise. The operator
      shall be familiar with the knowledge, safety information, and precautions on moulded case circuit breakers, OCRs, and
      OCR checkers. Improper handling may lead to an unexpected accident.
  •   Before testing an OCR, be sure to make preparations for the test in accordance with Chapter 4. Preparation Before the Test.
      Otherwise, undesired tripping or a failure may result.
  •   To insert the power plug into or remove it from the OCR checker, or to insert the signal plug into or remove it from the
      OCR, be sure to check in advance that the OCR checker is OFF. Otherwise, a failure may result.
  •   To use each switch located on the OCR checker, press it with your finger at a force of 2~4 N. Using excessive force or a
      sharp-tipped hard tool can cause a failure.
  •   Be sure to determine the current flowing through the OCR before using the OCR checker to test the OCR. An excessive
      current may result in damage to the OCR.
  •   After the test, be sure to put the set values on the OCR back to the previous ones. Otherwise, fire or undesired tripping may
      occur.
                                                                3
                                                                                                                  KRB-5308b
2. Ratings and Specifications
  Tables 1 and 2 show the ratings and specification of the OCR checker.
  Table 1 Rating and specification 1 of the type TNS-2 OCR checker
                       Item                                                   Description
  Applicable breakers                 Electronic breakers TemBreak and TemBreak2
                                      Specify either 100 – 120 VAC or 200 – 240 VAC (both 50/60 Hz) when
  Rated voltage
                                      placing an order.
  Power consumption                   7 VA
  External dimensions of main unit    W250 mm × H85 mm × D160 mm
  Weight of main unit                 400 kg
  Force for pressing a switch         2–4N
  Allowable ambient temperature       –5 to 40°C during use, –20 to 55°C during storage
  Allowable humidity                  During use and storage: RH 45% – 85%
                                      Power cord with AC adaptor (approx. 2 m)
                                       • With 2P-to-3P conversion plug (for 100 – 110 VAC)
                                       • SE type (for 200 – 240 VAC)
  Accessories                         Signal cable (approx. 2 m)
                                       • For TemBreak (approx. 2 m)
                                          For TemBreak2: 250AF (approx. 2 m)
                                                              400AF (approx. 2 m)
                                                       TemBreak                                          TemBreak2
                                z Pickup current value for long time delay trip z Pickup current value for long time delay trip
                                    function◯ 1                                        function◯  1 ◯9
                                z Trip time setting value for long time delay trip z Trip time setting value for long time delay
                                    function◯ 2 ◯8                                     trip function ◯   2 ◯ 8 ◯10
                                z Trip current setting value for short time delay z Trip current setting value for short time
                                    trip function◯  3                                  delay trip function ◯      3 ◯
                                                                                                                    8
                                z Trip time setting value for short time delay     z Trip time setting value for short time delay
                                    trip function ◯  4 ◯
                                                       9                               trip function ◯  4 ◯ 8 ◯10
                                z Trip current setting value for instantaneous     z Trip current setting value for instantaneous
                                    trip function ◯  5                                 trip function ◯  5 ◯ 8
                                z Trip current setting value for ground fault trip z Trip current setting value for ground fault
                                    function ◯ 6                                       trip function ◯  6 ◯ 9
                                z Trip time setting value for ground fault trip    z Trip time setting value for ground fault trip
                                    function ◯ 7 ◯9                                    function ◯  7 ◯9 ◯11
◯1 0-140mA ◯1 0-200mA
◯2 0-750mA ◯2 0-750mA
                                ◯3 0-750mA                                         ◯3 0-1450mA
      Output signal value        4 0-800mA                                          4 0-1450mA
                                ◯                                                  ◯
      setting range
                                ◯5 0-800mA                                         ◯5 0-1450mA
◯6 0-140mA ◯6 0-140mA
                                   0-140mA                                          7 0-140mA
  Output for signals
                                ◯7                                                 ◯
      Accuracy of output
                                ±1% (at 100 mA)                                    ±1% (at 100 mA)
      signal value
                                                                                   ◯8 Half-wave rectification
      Output method             Full-wave rectification
                                                                                   ◯9 Full-wave rectification
      Output time
                                0.00–999 sec                                       0.00–999 sec
      measurement range
                                ◯8 0.00 – 99.9 sec: 0.1 sec or ±1%, whichever is ◯ 10 0.00 – 99.9 sec: 0.1 sec or ±1%, whichever
                                                              4
KRB-5308b
3. Parts Names and Functions
 Parts names and functions of the OCR checker are given below. Figs. 1 and 2 show the appearance of the OCR checker.
          ◯
          20
          ◯
          2
                                                                                                                    ◯
                                                                                                                    16
          ◯
          1
          ◯
          3
                                                                                                                    ◯
                                                                                                                    13
          ◯
          4
          ◯
          7
                                                                                                                    ◯
                                                                                                                    14
          ◯
          6
          ◯
          5
                                                                                                                    ◯
                                                                                                                    15
                                                                                                                    ◯
                                                                                                                    12
                                                                                                                    ◯
                                                                                                                    11
                                                                                           ◯
                                                                                           8     ◯
                                                                                                 9            ◯
                                                                                                              10
                           ◯
                           17
                           ◯
                           18
                           ◯
                           19
      ◯
      1        Signal connector (round type): A signal cable connector for the OCR checker
      ◯
      2        Power connector (square type): A power cable connector for the OCR checker
      ◯
      3        Signal cable (approx. 2 m): A cable connecting between the OCR and the OCR checker. The OCR checker gives
               the output for power and signals to the OCR and receives the trip signal and pretrip alarm signal from the OCR via
               this cable.
      ◯
      4        Power cord (approx. 2 m): A cord used to supply power to the OCR checker.
                                                                 5
                                                                                                                   KRB-5308b
       5 Signal connector (square type): A signal cable connector for the OCR. Available in three types:
       ◯
       6 Power plug: A power cord plug for the power outlet. Available in two types:
       ◯
                                                            6
KRB-5308b
4. Preparation Before the Test
                                                              CAUTION
      • Before testing an OCR, be sure to make preparations for the test in accordance with Chapter 4 Preparation Before the
         test. Otherwise, undesired tripping or a failure may result.
      • To insert the power plug into or remove it from the OCR checker, or to insert the signal plug into or remove it from the
         OCR, be sure to check in advance that the OCR checker is OFF. Otherwise, a failure may result.
This chapter describes the preparations for the test. Make the preparations in accordance with the following steps.
       Make sure that the square signal connector at the other end of the signal cable is matched to the breaker subject to testing.
       See Fig. 3.
   3) Check the rated supply voltage indicated beside the power terminal port in the side of the OCR checker and plug the square
      power connector into the power terminal port. See Fig. 6
                Square power
                connector
                                                                 7
                                                                                                                    KRB-5308b
4-2. Preparation Before the Test (2)
        After completion of a test, be sure to reinstall the OCR cover with the mounting screw and seal the screw with a spare
        sealing sticker.
        Spare sealing stickers are in the rear pocket of the OCR cover.
   2) Make sure that the power switch of the OCR checker is in the OFF position and the current adjusting knob is turned full
      counterclockwise. See Fig. 8.
                 Power
                                                                                                             Current adjusting knob
                 switch
                                                                8
KRB-5308b
3) Set the breaker selector switch to the TemBreak position. See Fig. 9.
4) Make sure that the display of the OCR checker provides no indications and all lamps are off. Plug the square signal
   connector of the signal cable into the TEST IN port of the breaker. See Fig. 10.
                                                             9
                                                                                                               KRB-5308b
4-2-2. For TemBreak2
   1) If the breaker subject to testing is located in a system, open the breaker and turn off an upstream breaker or the like to
      isolate the breaker main and control circuits from any power.
   2) For a 250AF breaker, use a flatblade screwdriver to pry off the test terminal cap. See Fig. 11.
   3) For a 400AF breaker, peel off the sealing sticker on the OCR cover, pry the OCR cover with a flatblade screwdriver and
      slide it to remove. See Figs. 12 and 13.
Sealing sticker
                                                             10
KRB-5308b
                               OCR cover
                                                   Fig. 13 Removing the OCR cover
   After completion of a test, be sure to reinstall the OCR cover and seal it with a spare sealing sticker.
   Spare sealing stickers are in the rear pocket of the OCR cover.
4) Make sure that the power switch of the OCR checker is in the OFF position and the current adjusting knob is turned full
   counterclockwise. See Fig. 8.
5) Set the breaker selector switch to the TemBreak2 position. See Fig. 14.
                                                            11
                                                                                                               KRB-5308b
  6) Make sure that the display of the OCR checker provides no indications and all lamps are off. Plug the square signal
     terminal of the signal cable into the TEST IN port of the breaker. See Fig. 15.
  8) The test involves changes in OCR settings. It is recommended that OCR settings be noted before testing so that the settings
     can be returned to the original values after testing.
                                                          12
KRB-5308b
5. TESTING PROCEDURES
  This chapter describes the procedures for testing the OCR checker.
                                                              CAUTION
    z To use each switch located on the OCR checker, press it with your finger at a force of 2~4 N. Using excessive force or a
        sharp-tipped hard tool can cause a failure.
    z Be sure to determine the current flowing through the OCR before using the OCR checker to test the OCR. An excessive
        current may result in damage to the OCR.
    z After the test, be sure to put the set values on the OCR back to the previous ones. Otherwise, fire or undesired tripping may
        occur.
   1)    Press the power switch of the OCR checker to turn on the power. See Fig. 1.
   2)    Press the reset switch. "O" will be indicated on the display. See Fig. 1.
5-1. Testing Procedure for Pickup Current Value for Long Time Delay Trip
     Function
  The OCR should have been so adjusted as to trip open the breaker when the current flowing through the breaker reaches a
  setpoint that is between 105% and 125% of the rated current. When the current flowing through the breaker reaches the setpoint,
  a red LED for the breaker OCR turns on. See Fig. 16.
   1)    Calculate the criterion value of the current flowing through the breaker as follows:
         (For TemBreak)
           [ I1 / ICT × 50 × 1.05 ] < IT ≤ [ I1 / ICT × 50 ×1.25 ] (mA)
         (For TemBreak2)
           [ I1 / ICT × 100 × 1.05 ] < IT ≤ [ IR / ICT × 100 ×1.25 ] (mA)
                                                              13
                                                                                                                 KRB-5308b
   5)   Turn the current adjusting knob counterclockwise to decrease the current until the LED turns off. See Fig. 1.
   6)   Repeat steps 4 and 5 a few times and note the value at which the LED turns on. *2
                           *2: If the breaker has the pretrip alarm (PTA) function, the LED for the breaker OCR starts blinking
                                 when the current flowing through the breaker reaches the PTA pickup current setting (IP).
                                 The LTD trip pickup function will be activated if the current continues exceeding the trip pickup
                                 current setting.
   7)   Compare the LTD trip pickup current indicated on the display of the OCR checker with the criterion value calculated in
        step 1) above. The OCR has passed the test if the indicated value falls within the range of criterion values.
   8)   After completion of the test, turn the current adjusting knob to the MIN position without delay. See Fig. 1.
   9)   Press the reset switch. See Fig. 1. "0" will be indicated on the display of the OCR checker.
5-2. Testing Procedure for Trip Time Setting Value for Long Time Delay
     Trip Function
   1)   Consult the table below to change the OCR setting as appropriate.
        After completion of the test, be sure to return the setting to the original value.
                       Breaker                                     OCR setting to be changed
                      TemBreak                                If I2 is set to 6 or less, change it to 10.
                      TemBreak2                   If "Characteristics" is set to 3 or less, change it to 4 or more.
                                                              14
KRB-5308b
5-3. Testing Procedure for Trip Current Setting Value for Short Time Delay
     Trip Function (definite time characteristic)
  Before testing a TemBreak, make sure that the SHORT TIME I2t switch on the OCR is in the OFF position. If this switch is in
  the ON position, turn it OFF. After completion of the test, return the switch position to ON.
   1)    Criterion value
         (For TemBreak)
          Calculate the criterion value as follows:
IT = I2 / ICT × 50 (mA)
          (For TemBreak2)
           Select the criterion value from Table 3 of Page 16 to 19.
                                                               15
                                                                                                               KRB-5308b
  Table 3-1 Criterion value for Short Time Delay Trip Function (1)
    Breaker     Rated Current   Setting value of rated current   Setting value of characteristics   Criterion value for Short
    Types       [A]             adjustment dial for Breakers     adjustment dial for Breakers       Time Delay Trip function
                                                                                                    [mA]
    S250-NE           40                                                       1,2                              100
    S250-GE           125                    0.4                                3                               200
    S250-PE           160                                                      4,5                              400
    H250-NE           250                                                      1,2                              125
                                             0.5                                3                               250
                                                                               4,5                              500
                                                                               1,2                              158
                                             0.63                               3                               315
                                                                               4,5                              630
                                                                               1,2                              200
                                             0.8                                3                               400
                                                                               4,5                              800
                                                                               1,2                              225
                                             0.9                                3                               450
                                                                               4,5                              900
                                                                               1,2                              238
                                             0.95                               3                               475
                                                                               4,5                              950
                                                                               1,2                              250
                                              1                                 3                               500
                                                                               4,5                             1000
    S400-NE           400                                                      1,2                              100
    S400-GE                                  0.4                                3                               200
    H400-NE                                                                  4,5,6,7                            400
    L400-NE                                                                    1,2                              125
                                             0.5                                3                               250
                                                                             4,5,6,7                            500
                                                                               1,2                              158
                                             0.63                               3                               315
                                                                             4,5,6,7                            630
                                                                               1,2                              200
                                             0.8                                3                               400
                                                                             4,5,6,7                            800
                                                                               1,2                              225
                                             0.9                                3                               450
                                                                             4,5,6,7                            900
                                                                               1,2                              238
                                             0.95                               3                               475
                                                                             4,5,6,7                            950
                                                                               1,2                              250
                                              1                                 3                               500
                                                                             4,5,6,7                           1000
                                                           16
KRB-5308b
Table 3-2 Criterion value for Short Time Delay Trip Function (2)
  Breaker     Rated Current   Setting value of rated current      Setting value of characteristics   Criterion value for Short
  Types       [A]             adjustment dial for Breakers        adjustment dial for Breakers       Time Delay Trip function
                                                                                                     [mA]
  S630-CE           630                                                         1,2                              100
  S630-GE                                  0.4                                   3                               200
                                                                              4,5,6,7                            320
                                                                                1,2                              125
                                           0.5                                   3                               250
                                                                              4,5,6,7                            400
                                                                                1,2                              158
                                           0.63                                  3                               315
                                                                              4,5,6,7                            504
                                                                                1,2                              200
                                           0.8                                   3                               400
                                                                              4,5,6,7                            640
                                                                                1,2                              213
                                           0.85                                  3                               425
                                                                              4,5,6,7                            680
                                                                                1,2                              225
                                           0.9                                   3                               450
                                                                              4,5,6,7                            720
                                                                                1,2                              238
                                           0.95                                  3                               475
                                                                              4,5,6,7                            760
                                                                                1,2                              250
                                            1                                    3                               500
                                                                              4,5,6,7                            800
  S800-NE           800                                                         1,2                              100
                                           0.4                                   3                               200
                                                                              4,5,6,7                            320
                                                                                1,2                              125
                                           0.5                                   3                               250
                                                                              4,5,6,7                            400
                                                                                1,2                              158
                                           0.63                                  3                               315
                                                                              4,5,6,7                            504
                                                                                1,2                              200
                                           0.8                                   3                               400
                                                                              4,5,6,7                            640
                                                                                1,2                              225
                                           0.9                                   3                               450
                                                                              4,5,6,7                            709
                                                                                1,2                              238
                                           0.95                                  3                               475
                                                                              4,5,6,7                            742
                                                                                1,2                              250
                                            1                                    3                               500
                                                                              4,5,6,7                            776
                                                             17
                                                                                                                 KRB-5308b
  Table 3-3 Criterion value for Short Time Delay Trip Function (3)
    Breaker     Rated Current   Setting value of rated current   Setting value of characteristics   Criterion value for Short
    Types       [A]             adjustment dial for Breakers     adjustment dial for Breakers       Time Delay Trip function
                                                                                                    [mA]
    S1000-NE          1250                                                     1,2                              100
                                             0.4                                3                               200
                                                                             4,5,6,7                            320
                                                                               1,2                              125
                                             0.5                                3                               250
                                                                             4,5,6,7                            400
                                                                               1,2                              158
                                             0.63                               3                               315
                                                                             4,5,6,7                            504
                                                                               1,2                              200
                                             0.8                                3                               400
                                                                             4,5,6,7                            640
                                                                               1,2                              225
                                             0.9                                3                               450
                                                                             4,5,6,7                            709
                                                                               1,2                              238
                                             0.95                               3                               475
                                                                             4,5,6,7                            742
                                                                               1,2                              250
                                              1                                 3                               500
                                                                             4,5,6,7                            776
    S1250-NE          1250                                                     1,2                              100
    S1250-GE                                 0.4                                3                               200
                                                                             4,5,6,7                            400
                                                                               1,2                              125
                                             0.5                                3                               250
                                                                             4,5,6,7                            500
                                                                               1,2                              158
                                             0.63                               3                               315
                                                                             4,5,6,7                            630
                                                                               1,2                              200
                                             0.8                                3                               400
                                                                             4,5,6,7                            800
                                                                               1,2                              225
                                             0.9                                3                               450
                                                                             4,5,6,7                            900
                                                                               1,2                              238
                                             0.95                               3                               475
                                                                             4,5,6,7                            939
                                                                               1,2                              250
                                              1                                 3                               500
                                                                             4,5,6,7                            977
                                                           18
KRB-5308b
Table 3-4 Criterion value for Short Time Delay Trip Function (4)
  Breaker     Rated Current   Setting value of rated current      Setting value of characteristics   Criterion value for Short
  Types       [A]             adjustment dial for Breakers        adjustment dial for Breakers       Time Delay Trip function
                                                                                                     [mA]
  S1600-NE          1600                                                        1,2                              100
                                           0.4                                   3                               200
                                                                              4,5,6,7                            400
                                                                                1,2                              125
                                           0.5                                   3                               250
                                                                              4,5,6,7                            500
                                                                                1,2                              158
                                           0.63                                  3                               315
                                                                              4,5,6,7                            630
                                                                                1,2                              200
                                           0.8                                   3                               400
                                                                              4,5,6,7                            758
                                                                                1,2                              225
                                           0.9                                   3                               450
                                                                              4,5,6,7                            833
                                                                                1,2                              238
                                           0.95                                  3                               475
                                                                              4,5,6,7                            870
                                                                                1,2                              250
                                            1                                    3                               500
                                                                              4,5,6,7                            908
                                                             19
                                                                                                                 KRB-5308b
    2)    Set the element selector switch to the SHORT TIME-I ◯
                                                              3 position. See Fig. 1.
    3)    Turn the current adjusting knob a bit clockwise from the MIN position. See Fig. 1.
    4)    Press the start switch to start energization. See Fig. 1. *6
                              *6: ◯  1   The duration of energization is as short as approx. 1500 ms. The current turns off
                                      automatically after such a duration of time and the display of the OCR checker provides
                                      indication of the value of current applied.
                                    ◯
                                    2 Repeat the following steps to increase/decrease the current:
                                      1) Press the reset switch.
                                      2) Use the current adjusting knob to adjust the current. See Fig. 1.
                                      3) Press the start switch. See Fig. 1.
                                      4) Check the current flowing through the OCR
                                    ◯
                                    3 Turning off the breaker will facilitate adjusting the current. If the breaker is on while the
                                      current is adjusted, RESET and then ON operation will be required after the breaker trips
                                      open.
    5)    The breaker will trip open when the current flowing thought the OCR exceeds the trip pickup current setting. The
          NORMAL lamp will turn on and the display provide indication of the STD trip pickup current setting. See Fig. 1.
    6)    Compare the STD trip pickup current indicated on the display of the OCR checker with the criterion value calculated in
          step 1) above. The OCR has passed the test if the indicated value falls within the range of criterion value ±15%.
    7)    Return the current adjusting knob to the MIN position. See Fig. 1. *7
                              *7: This step is not required if this test is followed by a test for STD trip pickup timing.
8) Press the reset switch. See Fig. 1. "0" will be indicated on the display of the OCR checker.
5-4. Testing Procedure for Trip Time Setting Value for Short Time Delay
     Trip Function (definite time characteristic)
  Before testing a TemBreak, make sure that the SHORT TIME I2t switch on the OCR is in the OFF position.
  If the short time delay trip function is selected, the OCR operates at a definite time when the current flowing through the OCR
  exceeds the trip pickup current setting.
  During a test for short time delay trip timing, approx. 120% of the short time delay trip pickup current setting is applied to the
  breaker.
    1)     Turn the current adjusting knob a bit more clockwise than for the test in section 5.3. See Fig. 1. *8
                               *8: When testing a TemBreak, make sure that the test current does not exceed the instantaneous trip
                                    pickup current setting (I3). If the short time delay trip pickup current setting (I2) is too close to the
                                    instantaneous trip pickup current setting (I3) to set the test current, however, maximize the
                                    instantaneous trip pickup current setting for convenience of testing, and return it to the original
                                    value after completion of the test.
    2)     Set the element selector switch to the SHORT TIME-T ◯       4 position. See Fig. 1.
    4)    The breaker will trip open when the trip pickup time setting has elapsed. The NORMAL lamp will turn on and the display
          provide indication of the STD trip pickup time setting. See Fig. 1.
    5)    Compare the STD trip pickup time indicated on the display of the OCR checker with the STD trip pickup time setting.
          The OCR has passed the test if the indicated value falls within the range of setting ±20 ms.
    6)    Return the current adjusting knob to the MIN position. See Fig. 1.
    7)    Press the reset switch. See Fig. 1. "0" will be indicated on the display of the OCR checker.
                                                                 20
KRB-5308b
5-5. Testing Procedure for Trip Time Setting Value for Short Time Delay
     Trip Function (I2t characteristic)
  This section describes how to test the OCR when the SHORT TIME I2t switch on the OCR is in the ON position.
Tx = 102 × T2 / I22
   2)    Adjust the test current so that the short time delay trip pickup current I2 is in a range of I1 × 6 to 8 according to steps 2 to 4
         in section 5.3.
   3)    Set the element selector switch to the SHORT TIME-T ◯       4 position. See Fig. 1.
5-6. Testing Procedure for Trip Current Setting Value for Instantaneous
     Trip Function
        1)   Criterion value
             (For TemBreak)
              Calculate the criterion value as follows:
                        IT = I3 / ICT × 50 (mA)
             (For TemBreak2)
              Select the criterion value from Table 5 of Page 22 and 23.
                                                                   21
                                                                                                                        KRB-5308b
  Table 5-1 Criterion value for Instantaneous Trip Function (1)
    Breaker     Rated Current   Setting value of rated current   Criterion value for Instantaneous
    Types       [A]             adjustment dial for Breakers     Trip function [mA]
    S250-NE            40                    0.4                                560
    S250-GE                                  0.5                                700
    S250-PE                                  0.63                               882
    H250-NE                                  0.8                               1098
                                             0.9                               1184
                                             0.95                              1196
                                              1                                1196
                      125                    0.4                                560
                      160                    0.5                                700
                      250                    0.63                               882
                                             0.8                                998
                                             0.9                               1090
                                             0.95                              1105
                                              1                                1105
    S400-NE           400                    0.4                                560
    S400-GE                                  0.5                                700
    H400-NE                                  0.63                               882
    L400-NE                                  0.8                               1081
                                             0.9                               1197
                                             0.95                              1209
                                              1                                1209
    S800-NE           800                    0.4                                630
                                             0.5                                200
                                             0.63                               400
                                             0.8                                800
                                             0.9                                225
                                             0.95                               450
                                              1                                 900
    S1000-NE          1000                   0.4                                560
                                             0.5                                672
                                             0.63                               829
                                             0.8                                885
                                             0.9                                885
                                             0.95                               885
                                              1                                 885
                                                           22
KRB-5308b
Table 5-2 Criterion value for Instantaneous Trip Function (2)
  Breaker     Rated Current   Setting value of rated current      Criterion value for Instantaneous
  Types       [A]             adjustment dial for Breakers        Trip function [mA]
  S1250-NE          1250                   0.4                                   560
  S1250-GE                                 0.5                                   700
                                           0.63                                  856
                                           0.8                                  1047
                                           0.9                                  1107
                                           0.95                                 1107
                                            1                                   1107
  S1600-NE          1600                   0.4                                   532
                                           0.5                                   641
                                           0.63                                  767
                                           0.8                                   938
                                           0.9                                   996
                                           0.95                                  996
                                            1                                    996
                                                             23
                                                                                                      KRB-5308b
     2)   Set the element selector switch to the INST-I ◯
                                                        5 position. See Fig. 1.
     3)   Turn the current adjusting knob a bit clockwise from the MIN position. See Fig. 1
     4)   Press the start switch to start energization. See Fig. 1. *11
                           *11: ◯ 1 The duration of energization is as short as approx. 50 ms. The current turns off
                                  automatically after such a duration of time and the display of the OCR checker provides
                                  indication of the value of current applied.
                                2 Repeat the following steps to increase/decrease the current:
                                ◯
                                  1) Press the reset switch.
                                  2) Use the current adjusting knob to adjust the current. See Fig. 1.
                                  3) Press the start switch. See Fig. 1.
                                  4) Check the current flowing through the OCR.
                                3 Turning off the breaker will facilitate adjusting the current.
                                ◯
                                  If the breaker is on while the current is adjusted, RESET and then ON operation will be
                                  required after the breaker trips open.
     5)   The breaker will trip open when the current flowing thought the OCR exceeds the trip pickup current setting. The
          NORMAL lamp will turn on and the display provide indication of the instantaneous trip pickup current setting. See
          Fig. 1.
     6)   Compare the INST trip pickup current indicated on the display of the OCR checker with the criterion value calculated
          in step 1) aboveThe OCR has passed the test if the indicated value falls within the range of criterion value ±20%. *12
                         *12: For TemBreak, saturation characteristics of the built-in CT may cause larger measurement error
                               when the instantaneous trip pickup current (I2) is set to the max value.
     7)   Return the current adjusting knob to the MIN position. See Fig. 1.
     8)   Press the reset switch. See Fig. 1. "0" will be indicated on the display of the OCR checker.
5-7. Testing Procedure for Trip Current Setting Value for Ground Fault Trip
     Function
     1)   Criterion values for the ground fault trip pickup current are shown in table 6 below:
             Table 6 Criterion values for ground fault trip pickup current
              Breaker                            Setting                       Criterion value (mA)
             TemBreak           IG dial position      0.1                                23
                                                      (0.15)*13                          36
                                                      0.2                                49
                                                             *13
                                                      (0.25)                             62
                                                      0.3                                75
                                                             *13
                                                      (0.35)                             87
                                                      0.4                               100
              TemBreak2                     ICT × 0.2 (fixed)                            20
                         *13: Values in parentheses "( )" are intermediates between calibration marks.
     2)   Set the element selector switch to GROUND FAULT-I ◯      6 position. See Fig. 1.
8) Press the reset switch. See Fig. 1. "0" will be indicated on the display of the OCR checker.
                                                          24
KRB-5308b
5-8. Testing Procedure for Trip Time Setting Value for Ground Fault Trip
     Function
  If the ground fault trip function is selected, the OCR operates at a definite time when the current flowing through the OCR
  exceeds the trip pickup current setting. During a test for ground fault trip timing, approx. 120% of the ground fault trip pickup
  current setting is applied to the breaker.
        1)    Turn the current adjusting knob a bit more clockwise than for the test in section 5.3. See Fig. 1.
        2)    Set the element selector switch to GROUND FAULT-T ◯      7 position. See Fig. 1.
        4)    The breaker will trip open when the trip pickup time setting has elapsed. The NORMAL lamp will turn on and the
              display provide indication of the GF trip pickup time setting. See Fig. 1.
        5)    Compare the GF trip pickup time indicated on the display of the OCR checker with the GF trip pickup time setting
              (TG). The OCR has passed the test if the indicated value falls within the range of setting TG ±20%.
        6)    Return the current adjusting knob to the MIN position. See Fig. 1.
        7)    Press the reset switch. See Fig. 1. "0" will be indicated on the display of the OCR checker.
5-9. Adjustment
  The type TNS-2 OCR checker is a mesuring instrument. It is recommended that adjustment be performed approximately once
  for a correct testing. If adjustment is necessary, contact us.
                                                                   25
                                                                                                                     KRB-5308b
            26
KRB-5308b
Circuit Breaker Division
7-2-10 Kamihigashi, Hiranoku, Osaka 547-0002, Japan
KRB-5308b