INSTALLATION
- Sri.J.M.Malik
Precautions:
Transformer oil is flammable beyond 1400 hence flames should never
kept near transformer
As far as possible no work should be carried out during monsoon
season to avoid moisture absorption.
While accessing interior parts workmen should empty their pockets
Fiber cleaning material should not be used as it reduces insulating
properties. [use clean dry cloth only]
All components shall be cleaned inside and outside before being fitted.
Inspection checks:
1. Main unit -Gas/oil filled (oil up to the mark level)
Dirt - Clean.
Rust - Clean & Paint
Loose bolts – Tighten
2. All Condenser bushings;
Physical checks
Visual cracks/breakage & oil leakage
Dirt cleaning
Oil level
Bushing leads available
3. Bushings
Any missing metal part & visual check damage
4. Pin/Post insulators
Dirt cleaning & Any breakage
5. Fans
Dirt cleaning, physical damage
6. All pipe work
7. Radiators
8. Check all other accessories
9. All other fabricated items, brackets/supports, check physical damage, rust
Verification of placement of main unit:
1
Physical damage, paint finish.
Control panels
Samples from oil drum
Installation of turrets:
Identify turret as per item no. on outline drawing.
Verify the terminal nos.of turret CT’s.
Test the CT for ratio, polarity and insulation resistance.
Installation of Bushings:
Verify that oil level indicator facing downwards.
Clean the bushing.
Physical check for crack/damage.
Measurement of tan delta & Capacitance
Ensure connection & verify tightness bushing connectors
Test tap always be earthed not to be open under any circumstances
Installation of other accessories:
Conservator with supports
Piping
Cooler bank
On load tap changer with Drive mechanism
CT terminal boxes
Installation of protective instruments:
Oil temperature Indicator (OTI),
Winding temperature indicator(WTI-HV,IV&LV),
Magnetic oil level gauge(MOG),
Pr relief device(PRV),
Buchholz Relay,
Breather, pumps, fans and RTCC.
Fire protection system.
2
Installation Check list:
Revivification of assembly as per check list.
List of Erection Equipments Tools:
Mobile crane,
Nylon ropes
Filter machine
Vacuum pump
Storage tank for oil
Tarpaulin for covering main unit during filtration,
Complete sets of fixed/ring ended spanners
Complete sets of Allen keys.
Set of screw drivers, pipe wrenches, pliers, hammers, ladders, hole
punches
Devcon putty and holdite
Oil tests set (BDV kit),
Meggers (2.5/5kV),
Multi meters[digital type],
Carbon tetra chloride,
Cotton waste,
Pulling winches/pulleys,
Steel ropes,
Steel plates,
Wooden sleepers,
Grease,
Measure tapes,
Level bottle / level tube,
Stainless steel bottles for oil samples,
Nitrogen cylinder with regulator & pr gauge,
Welding machine,
Gas cylinder with nozzles and tourch for gas cutting,
Adapters and valves
Bushing lifting equipments,
Vacuum gauge [0-50mbar]
3
Evacuation and oil processing
Evacuate the tank for 24 hrs or more at 760 mm of Hg.(Ensure
equalizing pipe between OLTC and main tank is open)
Ready the oil in a separate tank with filtration done with desired oil test
results.
Filling of oil under vacuum.
Circulation of oil till the desired values of BDV, ppm are achieved.