VESDA VLF-250 Product Guide
VESDA VLF-250 Product Guide
VLF-250
Product Guide
September 7, 2007
Document Number: 07208_18
Part : 20295
LaserFOCUS VLF-250 Product Guide VESDA®
ii
VESDA® LaserFOCUS VLF-250 Product Guide
Intellectual Property and Copyright
This document includes registered and unregistered trademarks. All trademarks displayed are the trademarks of their respective owners.
Your use of this document does not constitute or create a licence or any other right to use the name and/or trademark and/or label.
This document is subject to copyright owned by Xtralis AG (“Xtralis”). You agree not to copy, communicate to the public, adapt, distribute,
transfer, sell, modify or publish any contents of this document without the express prior written consent of Xtralis.
Disclaimer
The contents of this document is provided on an “as is” basis. No representation or warranty (either express or implied) is made as to the
completeness, accuracy or reliability of the contents of this document. The manufacturer reserves the right to change designs or
specifications without obligation and without further notice. Except as otherwise provided, all warranties, express or implied, including
without limitation any implied warranties of merchantability and fitness for a particular purpose are expressly excluded.
General Warning
This product must only be installed, configured and used strictly in accordance with the General Terms and Conditions, User Manual and
product documents available from Xtralis. All proper health and safety precautions must be taken during the installation, commissioning
and maintenance of the product. The system should not be connected to a power source until all the components have been installed.
Proper safety precautions must be taken during tests and maintenance of the products when these are still connected to the power source.
Failure to do so or tampering with the electronics inside the products can result in an electric shock causing injury or death and may cause
equipment damage. Xtralis is not responsible and cannot be held accountable for any liability that may arise due to improper use of the
equipment and/or failure to take proper precautions. Only persons trained through an Xtralis accredited training course can install, test and
maintain the system.
Liability
You agree to install, configure and use the products strictly in accordance with the User Manual and product documents available from
Xtralis.
Xtralis is not liable to you or any other person for incidental, indirect, or consequential loss, expense or damages of any kind including
without limitation, loss of business, loss of profits or loss of data arising out of your use of the products. Without limiting this general
disclaimer the following specific warnings and disclaimers also apply:
Fitness for Purpose
You agree that you have been provided with a reasonable opportunity to appraise the products and have made your own independent
assessment of the fitness or suitability of the products for your purpose. You acknowledge that you have not relied on any oral or written
information, representation or advice given by or on behalf of Xtralis or its representatives.
Total Liability
To the fullest extent permitted by law that any limitation or exclusion cannot apply, the total liability of Xtralis in relation to the products is
limited to:
(i) in the case of services, the cost of having the services supplied again; or
(ii) in the case of goods, the lowest cost of replacing the goods, acquiring equivalent goods or having the goods repaired.
Indemnification
You agree to fully indemnify and hold Xtralis harmless for any claim, cost, demand or damage (including legal costs on a full indemnity
basis) incurred or which may be incurred arising from your use of the products.
Miscellaneous
If any provision outlined above is found to be invalid or unenforceable by a court of law, such invalidity or unenforceability will not affect the
remainder which will continue in full force and effect. All rights not expressly granted are reserved.
Document Conventions
The following typographic conventions are used in this document.
Convention Description
Convention Description
iii
LaserFOCUS VLF-250 Product Guide VESDA®
Contact Us
iv
VESDA® LaserFOCUS VLF-250 Product Guide
AFNOR
Table 3 on page 17: The maximum number of holes is 10.
Table 4 on page 18: The minimum hole size is 3mm; the maximum number of holes per branch is 5.
Table 5 on page 20: The minimum hole size is 3mm; the maximum number of holes per branch is 5.
Installation considerations on page 21: The maximum number of holes is 10.
Sampling Network on page 35: The maximum number of holes is 10.
If 20 holes are used, the minor low flow fault must be set to 90%.
EN 54-20
The product must use a power supply conforming to EN 54-4.
The product is compliant with EN 54-20 sensitivity requirements provided the following conditions are met:
- For a Class A detector, hole sensitivity must be better than 1.5% obscuration/m and transport time less than 60 seconds
- For a Class B detector, hole sensitivity must be better than 4.5% obscuration/m and transport time less than 60 seconds
- For a Class C detector, hole sensitivity must be better than 10% obscuration/m and transport time less than 60 seconds
The product is compliant with EN 54-20 flow monitoring requirements provided the following conditions are met:
- The minor low and minor high flow thresholds should be set at 80% and 120% respectively
- The flow through the detector predicted by ASPIRE2 should be in the range 12 to 24 lpm
These limits should be verified using ASPIRE2 during the design of the sampling pipe network.
Additional information:
- Class A detectors passed EN 54-20 approvals testing with 12 holes and 0.12% obscuration/m detector sensitivity
- Class B detectors passed EN 54-20 approvals testing with 12 holes and 0.35% obscuration/m detector sensitivity
- Class C detectors passed EN 54-20 approvals testing with 12 holes and 0.80% obscuration/m detector sensitivity
Product Listings
UL
ULC
FM
LPCB
VdS approval number G205060
NF
ActivFire (AS 1603.8)
CFE
CE (EN 50130-4 & EN 61000-6-3)
v
LaserFOCUS VLF-250 Product Guide VESDA®
vi
LaserFOCUS VLF-250 Product Guide VESDA®
Scope ................................................................................................................................................1
Installation ........................................................................................................................................1
Dimensions ..............................................................................................................................2
Detector mounting ..................................................................................................................3
Installing the smoke detector ...................................................................................................3
Installation procedure ..........................................................................................................4
Inverting the user interface display .....................................................................................5
Detector removal .....................................................................................................................6
Air inlet pipe connections ........................................................................................................7
Exhaust air pipe connections ..................................................................................................8
Wiring connections ..................................................................................................................8
Detector cabling requirements ............................................................................................8
GPI – General Purpose Input (Terminals 1 & 2) .................................................................9
Extra terminals (Terminals 3, 4, 5, 6 & 7) ..........................................................................11
Power supply (Terminals 8, 9, 10 & 11) ............................................................................11
Relays (Terminals 12 - 20) ................................................................................................12
Typical Wiring To Fire Alarm Control Panel (FACP) .........................................................13
Wiring To an Address Loop Module. .................................................................................13
Interface card ....................................................................................................................14
RS232 Compatible serial port ...............................................................................................14
Installation Checklist ..............................................................................................................15
Commissioning ..............................................................................................................................22
General ..................................................................................................................................22
AutoLearn Smoke ..................................................................................................................22
AutoLearn Flow .....................................................................................................................23
VESDA System Configurator (VSC) ......................................................................................23
Commissioning smoke test ...................................................................................................24
vii
VESDA® LaserFOCUS VLF-250 Product Guide
Specifications ................................................................................................................................ 35
Maintenance .................................................................................................................................. 38
Overview ............................................................................................................................... 38
Maintenance schedule .......................................................................................................... 39
Replace the Filter Cartridge (VLF) ........................................................................................ 39
Aspirator replacement ........................................................................................................... 40
Glossary ......................................................................................................................................... 48
viii
VESDA® LaserFOCUS VLF-250 Product Guide
1.1 Scope
This manual describes the features of the VESDA LaserFOCUS, the specifications and
functions, installation requirements, commissioning and operation procedures. A schedule for
preventative maintenance is also provided.
General notification
Note: Prior to carrying out any work or maintenance on the VESDA LaserFOCUS take the
necessary steps to advise the monitoring authority that power may be removed and
the system disabled.
Caution: Electrostatic discharge precautions need to be taken prior to removing the front
cover from the detector otherwise damage may occur to the unit.
1.3 Installation
The VESDA LaserFOCUS detector is shipped with all the components necessary for installation
with the exception of pipe and associated materials.
Components include:
• 1 LaserFOCUS detector with fitted exhaust deflector.
• 1 Mounting bracket.
• 1 End of Line resistor (see GPI – General Purpose Input (Terminals 1 & 2) on page 9)
• 2 M4 x 20 mm locking screws
• this Product Manual
Check all components for damage and refer any concerns to your VESDA distributor.
Note: Removing the rear cover of the detector will void your warranty.
Note: Opening or removing the sealed laser detection chamber will void your warranty.
1
LaserFOCUS VLF-250 Product Guide VESDA®
Dimensions
Legend
mm inches
A 256 10.08
B 182.8 7.20
C 134.0 5.28
D 204.0 8.03
E 36.0 1.42
F 25.5 1.00
G 27.0 1.06
H 92.1 3.63
I 182.8 7.20
J 180.0 7.09
Legend
mm inches
A 236.3 9.30
B 120.0 4.72
C 4.5 0.18
D 230.0 9.06
E 100.0 3.94
F 50.0 1.97
G 40.0 1.57
2
VESDA® LaserFOCUS VLF-250 Product Guide
Detector mounting
The VESDA LaserFOCUS can be installed upright, inverted or horizontally.
Note: Ensure the smoke detector is mounted away from obstructions and below ceiling
level.
Caution: An exhaust deflector must be fitted for upright mounting, unless the exhaust port is
connected to a return air pipe.
Caution: Do not install this unit on its side. There is a risk of particulate and condensation
collecting on critical elements of the detector chamber reducing the detectors
performance.
Ensure that there is sufficient clearance to mount the detector, noting the location of air sampling
pipes and cable entry points. Owing to the rigid nature of the plastic pipe, installation must
provide for sufficient movement in all pipework (air inlet, air exhaust and cable pipes) to allow
pipe ends to be easily fitted and removed.
Legend
A Min. 200 mm (8 in.) below ceiling level
B Min. 500 mm (20 in.) from a wall or obstruction to allow access to the security tab
Warning: Prior to drilling the attachment holes for the mounting bracket, ensure
that all mounting surfaces (i.e. walls, cabinet sides, etc.). are clear of
electrical wiring and plumbing.
3
LaserFOCUS VLF-250 Product Guide VESDA®
Where the pipe network and cabling are already fitted, the bracket can be used to aid alignment
of the detector with the pipes. The Installation procedure below explains this process.
Installation procedure
o
Cut the air inlet pipe and exhaust pipe (if used) at 90 , and to the same length (for normal and
inverted mounting). Remove all rough edges. This is critical to obtain an air tight seal with the
smoke detector.
1. Position the air inlet centerline mark (A), see Figure 4, of the mounting bracket against the
end of the air inlet pipe.
2. In the cut out section of the mounting bracket mark a line across the top of the cut out if
metric size pipe is used or mark a line across the bottom of the cut out if Imperial size pipe
is used.
3. Slide the mounting bracket down (up for inverted mounting) until the top of the bracket
aligns with the marked line.
4. Mark off and drill the 2 bracket mounting holes (H).
5. Screw the bracket to the wall.
6. Hook the smoke detector onto the mounting bracket tabs and pull it down into place.
7. Use the two M4 x 20 mm locking screws provided and screw them into the screw holes on
the left and right side of the detector. See the items marked (F) in the Figure Detector
removal on page 7.
8. The air sampling pipe can now be attached and power connected.
(See section Wiring connections on page 19 for connection information).
4
VESDA® LaserFOCUS VLF-250 Product Guide
For inverted installation, to mark off the location of the mounting holes, follow steps 1 – 4 with the
mounting bracket inverted to that shown in figure 4, “Mounting bracket orientation for upright and
inverted mounting,” on page 5. Also see Inverting the user interface display on page 5.
A B C D D E Legend
A Air inlet port centerline
G C Cutout
I Centerline of detector
J Anti-tamper clip
Legend
C
A Security tab
D
B Finger clip
A
C Mounting tab
B D Anti-tamper clip
E Centerline of detector
For inverted mounting applications, the VESDA LaserFOCUS will require the user interface
o
display to be turned through 180 . This is carried out prior to installing the detector. Also see
Mounting bracket orientation for upright and inverted mounting on page 5.
Inverting the user interface display:
5
LaserFOCUS VLF-250 Product Guide VESDA®
1. Place the detector on its back, push in the securing tab and lift up the field service access
door. (See Figure 25, “Field Service Access Door security tab and clip,” on page 28).
2. Remove the 2 retaining screws and lift off the main cover.
3. Disconnect the restraining strap from the clip (C) and the ribbon cable from the user
interface card (B) and place the cover aside.
4. Open the clips (E).
o
5. Lift out the user interface display card, carefully turn it through 180 and then clip it back into
place.
6. Reconnect the ribbon cable and the restraining strap.
7. Replace the main cover and screw down the 2 retaining screws.
8. Close the field service access door.
The detector is now ready for inverted installation.
A C
B
E
D
E
B
Legend
A Ribbon cable clip D Interface card
Figure 6 - Inside view of the front cover (as it would appear inverted)
Detector removal
Caution: Electrostatic discharge precautions need to be taken prior to removing the front
cover from the detector otherwise damage may occur to the unit.
Note: Take the necessary steps to advise the monitoring authority of work being carried
out and that the system needs to be disabled.
6
VESDA® LaserFOCUS VLF-250 Product Guide
1. Turn off the power to the detector.
2. Disconnect the sampling pipes.
3. Push in the security tab and lift up the field service access door, see Figure 25, “Field
Service Access Door security tab and clip,” on page 28.
4. Unscrew the front cover retaining screws (E).
5. Lift off and swing down the front cover, a restraining strap will take the load. For inverted
mounted detectors the cover should be removed and placed aside.
6. Disconnect all field wiring from the terminal block.
7. Unscrew the two M4 x 20 mm locking screws on the left and right side of the detector. See
the items marked (F) in the Figure Detector removal on page 7
8. Use a screw driver to push down the anti-tamper clip in hole (A), at the same time, push the
detector base up.
9. Lift the detector off the mounting bracket.
Once the detector has been removed re-fit the front cover to keep the internal components safe
from damage and the electrical cabling safe.
Note: For inverted mounted detectors, the front cover will need to be removed prior to
unhooking the detector from the mounting bracket. Disconnect the retaining strap
and the ribbon cable from the user interface card and place the cover aside.
A F
E E
F
C
D
Legend
A Anti-tamper clip access hole D Aspirator
7
LaserFOCUS VLF-250 Product Guide VESDA®
Wiring connections
Caution: Electrostatic discharge precautions need to be taken prior to removing the front
cover from the detector otherwise damage may occur to the unit.
8
VESDA® LaserFOCUS VLF-250 Product Guide
To reach the terminal block, open the field service access door, see Controls and indicators on
page 28, and then unscrew the front cover retaining screws. Lift off and swing down the front
cover. The terminal block is located on the right hand side of the detector.
Legend
A Terminal block, connectors 1 to 20
1
A
20
Caution: These terminal blocks come assembled and should NOT be disassembled.
Legend
1 GPI pin 1
2 GPI pin 2
9
LaserFOCUS VLF-250 Product Guide VESDA®
The GPI function parameter can be set to the values shown in the table below to achieve several
different functions:
GPI function
Result
parameter value
None GPI is disabled. If GPI will not be used we recommend that you
leave the EOL resistor assembled.
Disable Detector is disabled while GPI is active (contact closed) and reset
on de-activation of the input (contact open).
External Detector indicates a fault while the GPI is active (contact closed).
Typically this is used to monitor external power supply units.
Note: If the contact is closed it will raise an Instant Fault Finder
No.6 fault. If wire is broken to the monitoring device it will raise an
Instant Fault Finder No.8 fault.
The GP input detects a short circuit (e.g. the PSU fault relay) at or below 100 Ohms.
Legend
C
A End of Line Resistor (2.7k)
A B B External device (1 to N)
C GPI Pin 1
D
D GPI Pin 2
10
VESDA® LaserFOCUS VLF-250 Product Guide
Legend
3 Display Tx
4 Display Rx
6 Display Power -
7 Display Power +
It is recommended that the power supply be compliant with local codes and standards required
by the regional authority. For code-specific information, see Codes and Standards Information for
Air Sampling Smoke Detection on page iv.
Caution: Check the product termination wiring label during installation and subsequent
maintenance visits.
Legend
8 Power Return 0 VDC From power supply unit
9 Power in 24 VDC
11
LaserFOCUS VLF-250 Product Guide VESDA®
18 NC Fire 1 relay
19 Common
20 NO
Note: By default, the Fault relay is normally energized when no fault is present. For
example when there is no fault present, terminal 12 is held open and terminal 14 is
held closed. When there is a fault present, terminal 12 is held closed and terminal
14 is held open.
12
VESDA® LaserFOCUS VLF-250 Product Guide
To next detector
or EOL resistor
EOL (NC)
GPI Reset (C)
(Set to reset) (NO)
13
LaserFOCUS VLF-250 Product Guide VESDA®
Interface card
The VESDA LaserFOCUS allows for the installation of a variety of interface cards. Refer to the
specific interface card installation sheet, product guide, or your local VESDA support person for
further information regarding installation and configuration of this card.
Legend
A 9 Pin DB9 PC COM Serial
extension cable (male)
14
VESDA® LaserFOCUS VLF-250 Product Guide
Installation Checklist
Site Name
Address
Name of Installer
Signature
Date
Perform the following checks listed below to ensure that all the necessary items are completed
before handing over to a commissioning engineer.
1. Were the detector and the mounting bracket intact in the box?
3. Is the sampling air pipe firmly connected to the air inlet port?
Ensure the pipe is NOT glued.
8. Has the plug at the exhaust port been removed and the exhaust
pipe (if fitted) not glued?
11.Is the air sampling pipework installed and checked as per the site
plans?
15
LaserFOCUS VLF-250 Product Guide VESDA®
Parameter Value
Suction pressure greater than or equal to 25 Pa across holes and capillary tubes
For alternate or complex pipe network designs including end caps with sampling holes use the
ASPIRE2 pipe modeling software to verify pipe performance. For code-specific information, see
Codes and Standards Information for Air Sampling Smoke Detection on page iv.
16
VESDA® LaserFOCUS VLF-250 Product Guide
Hole Size (mm) Length (m) Hole Size (in.) Length (ft.)
Legend
A Smoke detector B Sampling hole C End cap (no hole)
17
LaserFOCUS VLF-250 Product Guide VESDA®
The set up below shows a single pipe arrangement with 6 capillary drop pipes and a fitted end
cap without a sampling hole.
Legend
A Smoke detector B Capillary tube C End cap (no hole)
Hole Size (mm) Length (m) Hole Size (in.) Length (ft.)
18
VESDA® LaserFOCUS VLF-250 Product Guide
The set up below shows a branched pipe arrangement with 5 sampling holes per branch and
fitted end caps without sampling holes.
Legend
A Smoke detector B Sampling hole C End cap (no hole)
C
A
Legend
A Smoke detector B Capillary tube C End cap (no hole)
19
LaserFOCUS VLF-250 Product Guide VESDA®
Return Air Sampling – U Shaped design with equal holes on each side
4 3.0 – 4.0 1 5
/8 – /32
6 3.0 – 3.5 1
/8
8 3.0 3
/32
10 2.5 3
/32
A C
Legend
A Sampling pipe C Return grille
20
VESDA® LaserFOCUS VLF-250 Product Guide
Installation considerations
Note: For code-specific information, see Codes and Standards Information for Air
Sampling Smoke Detection on page iv.
The VESDA LaserFOCUS VLF-250 smoke detector provides very early warning smoke
detection specifically for small environments.
The pre-engineered pipe network designs can support up to 6 sampling holes for single pipes
and 8 sampling holes for branched pipe arrangements. The number of sampling holes used can
1
be increased to 12 , however, ASPIRE2 will need to verify that the additional sampling holes can
be supported. Sampling holes are positioned according to the standards relating to conventional
point detector placement.
The pre-engineered pipe network solutions described in sections Single pipe network on page 10
and Branched pipe network on page 11 achieved transport times of less than 60 seconds for
open hole sampling and less than 90 seconds for capillary sampling.
Where the VESDA LaserFOCUS is located outside the protected area (e.g. in a corridor outside
the room), consideration must be given to returning the detector exhaust air to the protected
environment to balance the pressure differences that may exist. In the majority of applications,
this is not necessary as pressure differences are minimal. The exhaust should also be returned
to the protected area in cases where there are hazardous substances inside the protected area,
eg hospital operating theatres. Where practical considerations fall outside pre-engineered
designs or where pressure differences exceed 50 Pa, in situations where the detector is located
outside the protected area, the solutions presented in this manual may not be suitable and it is
recommended that alternate designs are verified by a suitably qualified installer using ASPIRE2.
The following points should be considered when installing the sampling pipe:
• minimize flexing in sampling pipes by supporting the pipe every 1.5 m (5 ft) or less, or at a
distance described in local codes and standards.
• evenly arrange the sampling pipe network over return air grilles
• sampling pipes fit firmly into the tapered detector ports, DO NOT glue this connection
• allow sufficient movement at the detector to permit pipe removal for maintenance
• keep the exhaust deflector fitted to prevent foreign objects falling into the detector
• keep the return air pipe as short as possible to minimize airflow resistance in the pipe
• pipe ends must be made smooth for bonding
• sampling holes must be drilled in line and perpendicular to the pipe.
• sample holes must be clear of rough edges and debris
• pipes are free of debris
• all joints must be bonded except the endcaps and pipes entering the detector
Note: In protected areas sampling holes should face into the direction of airflow, or point
downwards in static airflow situations.
Note: You should try to keep the sampling holes evenly spaced.
Note: For code-specific information, see Codes and Standards Information for Air
Sampling Smoke Detection on page iv.
1. For code-specific information, see Codes and Standards Information for Air Sampling Smoke De-
tection on page iv
21
LaserFOCUS VLF-250 Product Guide VESDA®
1.5 Commissioning
General
The VESDA LaserFOCUS has been designed to simplify commissioning processes. The
AutoLearn function allows the unit to assess its environment and setup appropriate alarm and
flow thresholds. The unit may also be programmed through VESDA System Configurator (VSC)
software, for all programmable settings. For further information see Factory Defaults on page 34.
Note: Detectors should be commissioned with a smoke test.
Prior to commissioning the detector, check:
1. That the power is connected and on.
2. That the pipe network is clean and correctly fitted with all joints correctly seated and sealed
(except the endcaps and pipe which enters the detector which must not be glued).
3. That the exhaust deflector is fitted.
For code-specific information, see Codes and Standards Information for Air Sampling Smoke
Detection on page iv.
Legend
A AutoLearn Smoke button.
AutoLearn Smoke
AutoLearn Smoke is initiated by pressing the recessed button numbered 1, which is located
under the field service access door.
During the AutoLearn Smoke process, the VESDA LaserFOCUS determines the average smoke
and peak smoke obscuration levels and sets suitable alarm thresholds for the operating
environment. This process will minimize false alarms due to normal environment smoke variations.
22
VESDA® LaserFOCUS VLF-250 Product Guide
The AutoLearn Smoke LED will remain on for the duration of the AutoLearn process. At the start
of the process the alarm thresholds are set to the default values. During this learning cycle, alarm
conditions can be reported. If an alarm condition occurs (Alert or higher alarm) AutoLearn will not
complete its cycle. In this situation restart the AutoLearn process. If AutoLearn is stopped by you
or due to an alarm condition, the alarm thresholds will be left at the default settings.
Conditions during learning are assumed to be representative of normal operating
conditions.
The AutoLearn Smoke learning times range from above 15 minutes to 15 days, with the default
being set to 14 days.
If AutoLearn is running during the changeover period from Day and Night Thresholds function,
make sure that AutoLearn runs for at least an hour in both the Day and Night.
AutoLearn Flow
AutoLearn Flow process is initiated by pressing the recessed button numbered 2, which is
located under the field service access door. During the AutoLearn Flow process, the VESDA
LaserFOCUS determines the average and peak air flow levels monitored over time and sets
suitable air flow thresholds that will not give rise to false flow rates due to normal flow variations
(such as might arise through air-conditioning related false alarms). The system will normalize the
flow and then monitor the flow trend to set the flow fail thresholds.
The AutoLearn Flow indicator LED will remain on for the duration of the AutoLearn process. At
the start of the process the flow thresholds are set to the default values. During this learning
cycle, alarm conditions can be reported. If a flow fault is reached, AutoLearn will not complete its
cycle. In this situation restart the AutoLearn process. If AutoLearn is stopped by you or due to a
flow fault condition, the flow thresholds will be left at the default settings.
Conditions during learning are assumed to be representative of normal operating
conditions.
The AutoLearn Flow learning times range from 15 minutes to 15 days, with the default being set
to 14 days.
23
LaserFOCUS VLF-250 Product Guide VESDA®
Description
The Instant Recognition Display of the VESDA LaserFOCUS smoke detector shows alarm levels
and detector status information. The Smoke Dial, (see (F) in figure 23, “LaserFOCUS detector
front view,” on page 26, a part of the Instant Recognition Display, provides clear information of a
smoke event, relative to the Fire 1 Alarm Threshold. This display also identifies system and
operational faults, when using the Instant Fault Finder function. Each segment of the Smoke Dial
also corresponds to a specific fault condition.
A Field Service Access Door is provided to allow easy access to AutoLearn functions for detector
commissioning. It provides access for filter replacement and connecting a PC for comprehensive
configuration and diagnostics processes.
The detector uses Ultrasonic Flow Sensing to monitor the integrity of the sampling pipe network
by detecting pipe air flow change. Ultrasonic flow sensing is not affected by temperature,
humidity or pressure.
Detector history is provided by the non-volatile Event Logging feature. Smoke trend data, flow
trend data, fault events, configuration events and operational events are recorded. Using VSC
these event types can be filtered individually.
24
VESDA® LaserFOCUS VLF-250 Product Guide
Applications
The VESDA LaserFOCUS can be used for open areas, return air grilles, or for cabinet protection
in many small areas including:
• telecommunication facilities
• computer rooms
• control rooms
• storage facilities
• electrical and switching cabinets
For code-specific information, see Codes and Standards Information for Air Sampling Smoke
Detection on page iv.
25
LaserFOCUS VLF-250 Product Guide VESDA®
Front view
Front view of the detector as installed and operating. This view shows cable and air sampling
pipe entry points, the Instant Recognition display and the fitted exhaust deflector.
B C
Legend
A Air inlet port D Rear cable entry (not shown)
C Cable entry ports (x2) F Smoke Dial (includes Instant Fault Finder)
26
VESDA® LaserFOCUS VLF-250 Product Guide
A
B
C
D
G
E
Legend
Option Definition LED Color
E DISABLED Indicates the unit has been disabled (solid) or is in standby mode (flashing). Yellow
G FAULT Fault light continuously on indicates a Major Fault . When flashing indicates a Yellow
Minor fault.
27
LaserFOCUS VLF-250 Product Guide VESDA®
Legend
C A Security tab
B Finger clip
28
VESDA® LaserFOCUS VLF-250 Product Guide
E
C
F
D
G
H
Legend
A Instant Fault Finder fault descriptions.
H Security tab.
29
LaserFOCUS VLF-250 Product Guide VESDA®
Reset Resets the Press and hold down this button to test
system and the function of LEDs on the unit.
resumes normal
To enable or lockout this button VESDA
operation.
System Configurator (VSC) software is
required.
Release this button to clear latched faults
and alarms. Alarm and fault lights will
switch off, and if the system is still in
alarm or fault mode, the lights will
reappear after the appropriate delay.
Disable Disables the fire This button allows the operator to toggle
relay outputs between disable and normal modes.
from actuating When disabled smoke and air flow are not
and reports a reported to the system (e.g. FACP).
fault.
To enable or lockout this button VESDA
Pressing Disable System Configurator (VSC) software is
for 6 seconds will required.
put the detector
The fan continues to run when VLF is
into Stand-by
disabled but stops when it is in stand-by
mode.
mode.
Instant Fault Indicates current Pressing and holding in the Reset button
Finder active faults on and the Disable button together will show
the detector. the fault type, by number, on the Smoke
Dial.
See “VLF Troubleshooting with Instant
Fault Finder” on page 33. for the fault
definitions.
30
VESDA® LaserFOCUS VLF-250 Product Guide
31
LaserFOCUS VLF-250 Product Guide VESDA®
C
A
D
Legend
A Smoke Dial and Fault Type indicator. C Disable button.
32
VESDA® LaserFOCUS VLF-250 Product Guide
1 Filter Air filter needs replacement Replace the air filter with a new
due to dust or smoke unit remembering to reset the filter
contamination or has reached fault.
the end of its life.
2 Aspirator Aspirator fault has occurred. Initially replace the aspirator. If the
fault remains replace the VESDA
unit.
3 High flow High flow fault present (urgent Check the pipe network for
or non-urgent). Flow readings breakages. Also check the
are above user set flow limits suitability of the pipe network in
or the detector maximum flow ASPIRE2.
4 Low flow Low flow fault present (urgent Check the pipe network for
or non-urgent). Flow readings blockages. Also check the
are below user set flow limits suitability of the pipe network in
or the detector maximum flow ASPIRE2.
5 Not in use
10 Detector A fault has occurred that Contact the supplier and replace
failure cannot be fixed. the detector.
33
LaserFOCUS VLF-250 Product Guide VESDA®
34
VESDA® LaserFOCUS VLF-250 Product Guide
1.9 Specifications
Power Supply
*For code-specific information, see Codes and Standards Information for Air Sampling Smoke
Detection on page iv.
Case
IP Rating IP30
Operating Conditions
Detector Ambient o o o o
0 C to 40 C (32 F to 104 F)
Sampled Air o o o o
0 C to 40 C (32 F to 104 F)
Humidity (non-condensing) 5% to 95 %
Sampling Network
Air inlet pipe OD 25 mm (ID 21 mm) / IPS ¾ in. (OD 1.05 in.)
Alternate pipe sizes can be modelled with ASPIRE2
35
LaserFOCUS VLF-250 Product Guide VESDA®
1. For code-specific information see Codes and Standards Information for Air Sampling
Smoke Detection on page iv
Area Covered
VLF-250 2
250 m (2500 sq. ft.)
Field Wiring
Terminals 2 2
0.2 mm - 2.5 mm (30 - 12 AWG)
Interfaces
Power In/Out.
Alarm Ranges
For code-specific information, see Codes and Standards Information for Air Sampling Smoke
Detection on page iv.
Display
36
VESDA® LaserFOCUS VLF-250 Product Guide
Event Log
Smoke trend, flow trend, faults events, configuration events and operational events.
Referencing
Reference smoke level source for networked detectors (requires a VESDAnet Interface
card).
Ordering Information
Aspirator VSP-715
37
LaserFOCUS VLF-250 Product Guide VESDA®
1.10 Maintenance
Overview
The VESDA LaserFOCUS smoke detector continuously monitors its own operation and conducts
frequent health checks. There are two serviceable items, the air filter cartridge and the aspirator.
Caution: Electrostatic discharge precautions need to be taken prior to removing the front
cover from the detector otherwise damage may occur to the detector.
A Legend
A Dual stage air filter
cartridge
B Aspirator
38
VESDA® LaserFOCUS VLF-250 Product Guide
Maintenance schedule
To maintain the VESDA LaserFOCUS smoke detector in peak working order follow the
maintenance standards for your region and where no recommended standard exists see the
table below. Please note, for environments that experience high levels of contamination, the
frequency of maintenance will need to be increased. Maintenance should be conducted by a
qualified service contractor.
Check pipe 6 monthly Check pipe connections to ensure all pipe runs are
network intact and that pipe supports and joints are firm.
Airflow Yearly Check air flow via VSC software (refer to the VESDA
System Configurator Manual). Compare the current
reading with previous reading to determine if the flow
rate has reduced.
Smoke test Yearly Conduct smoke tests and verify detector performance
(refer to the System Design Manual).
Compare response times with those previously
recorded and investigate any discrepancies.
Filter 2 Yearly Recommended change out period. The filter status can
replacement be checked via VSC software. Depending on the
environment, the filter may require more frequent
checking.
Clean As necessary If frequent low flow faults occur clean the sampling pipe
sampling network by back flushing (refer to the System Design
holes Manual).
39
LaserFOCUS VLF-250 Product Guide VESDA®
Legend
A
C A Field service access door
D Filter switch
Aspirator replacement
Note: Prior to replacing the aspirator advise the monitoring authority that power will be
removed and the system disabled.
Caution: Electrostatic discharge precautions need to be taken prior to removing the front
cover from the detector otherwise damage may occur to the unit.
40
VESDA® LaserFOCUS VLF-250 Product Guide
Note: Any time the aspirator is removed ensure the area surrounding the aspirator is clear
of dirt and debris prior to replacement.
Note: Care must be taken during aspirator replacement. The aspirator must be correctly
seated; this is essential so that gaskets are not damaged or dislodged from the
underside of the aspirator.
Legend
A Aspirator securing screw
D E
41
LaserFOCUS VLF-250 Product Guide VESDA®
Customer Name
Site Address
Checks Date:
1. Wiring Checked 1.
2. Detector Diagnostics 2.
3. Display Diagnostics 3.
4. Test Relay 4.
Test Witnessed By
Date:
Customer’s Signature
Date:
Commissioner’s Signature
Date:
42
VESDA® LaserFOCUS VLF-250 Product Guide
Address (VESDA
Zone)
Firmware version #
Fire2 Dilution%
Fire1 Delay
(seconds)
Networked
Fire2 Flow
Averaging
Period
(sec)
Standalone
43
LaserFOCUS VLF-250 Product Guide VESDA®
Fire1 % Flow %
Display/Relay Configuration
Button Lockout Enabled/Disabled
Smoke Test
Reset
Isolate
AutoLearn Smoke
AutoLearn Flow
GPI Function
Fault 9
Action 9
Fire1 9
D= Normally De-energized; E= Normally Energized
44
VESDA® LaserFOCUS VLF-250 Product Guide
Alert 9 9
Fire2 9
Disabled
Standby
Disable MPO
Monitor
External
Device
Ancillary Devices
Ancillary devices includes any remote displays, remote relay cards, AOM and
SRM assigned to this LaserFOCUS detector
Device Name
Firmware Version
Location
45
LaserFOCUS VLF-250 Product Guide VESDA®
ASPIRE2 Data
Group 1 Group 2 Group 3 Group 4
Aggregate Sensitivity
Balance
Smoke Test
Test Results
Test Method
Type of Smoke
Test Date
46
VESDA® LaserFOCUS VLF-250 Product Guide
Alert
Action
Fire 1
Fire 2
Peak Smoke
Alert
Action
Fire 1
Fire 2
Peak Smoke
47
LaserFOCUS VLF-250 Product Guide VESDA®
1.12 Glossary
A Aspirator Impeller type fan used to draw sampled air into the
detector.
C Capillary Tubes Flexible tubes attached to the sampling pipe network for
sampling specific areas or objects away from the
sampling pipe.
Dual Stage Air Filter A disposable air filter cartridge used in VESDA
Cartridge LaserFOCUS detectors that removes dust
contamination from sampled air and provides a clean air
bleed to maintain the Laser chamber optics.
Fire Alarm Control A panel which all fire detection products report their
Panel (FACP) status to.
H High Airflow Where there are 10 or more air exchanges per hour.
Environment
I Instant Fault Finder Illuminates one or more segments of the Smoke Dial
with corresponding fault numbers.
48
VESDA® LaserFOCUS VLF-250 Product Guide
49
LaserFOCUS VLF-250 Product Guide VESDA®
You have not pressed BOTH the RESET button and the DISABLE buttons simultaneously, you
have ONLY pressed the DISABLE button. To put the VLF into STANDBY you press and hold
down the DISABLE button until the AutoLearn LEDS and DISABLED LED blink. This means
keeping the button pressed for about 6 seconds. You do the same again to take the detector out
of STANDBY. So, what you are doing is the 1st stage of putting the detector into/out of
STANDBY. To make IFF work reliably, you need to press the RESET button BEFORE the
DISABLE BUTTON. Several seconds can elapse between pressing these buttons but take care
that you do not RESET the detector by accident.
Can the deflector be removed from the VESDA LaserFOCUS exhaust?
It is a tight fit but it can be removed. With all VESDA detectors, we recommend returning all
sampled air from the exhaust into the sampled environment.
How do I change the filter on my VESDA LaserFOCUS?
Refer to the VESDA Maintenance Guide, available on the website under www.xtralis.com for full
details. VLF detectors need to have the front cover lifted. Secure the replacement filter and
acknowledge the action via a configuration tool (VSC, VSM or programmer).
What do you recommend that the four VESDA LaserFOCUS alarm relays be used for?
‘Alert’, ‘Action’, ‘Fire 1’ and ‘Fire 2’. Check whether your local codes require specific relays to be
fixed. VLF has action and fire set to specific relays.
What are the order numbers for the VESDA LaserFOCUS demo kits?
All model numbers provided are Xtralis model numbers, check with your local distributor.
VKT-020 is the VLF-250-00 Demo Kit.
VKT-021 is the VLF-250-01 Demo Kit.
VKT-022 is the VLF-250-02 Demo Kit.
VKT-050 is the VLF-500-00 Demo Kit.
VKT-051 is the VLF-500-01 Demo Kit.
VKT-052 is the VLF-500-02 Demo Kit.
50
VESDA® LaserFOCUS VLF-250 Product Guide
Index
A I
C M
D P
Pipe connections
Default settings ...................................34
Air inlet ............................................ 7
Detector removal ................................... 6
Exhaust ........................................... 8
Pipe network ....................................... 16
F Branched pipe ................................. 18
Duct .............................................. 21
FAQ ................................................... 49 Installation considerations .................. 21
Return air ....................................... 19
Features .............................................
24 Single pipe ..................................... 17
Field service access door ..................... 28
Frequently Asked Questions ................. 49 S
51
LaserFOCUS VLF-250 Product Guide VESDA®
Specifications ..................................... 35 W
U Wiring .................................................. 8
General Purpose Input ........................ 9
User interface...................................... 25 Power supply .................................. 11
Relays ........................................... 12
Spare terminals ............................... 11
V
52
LaserFOCUS VLF-250 Product Guide VESDA®
53