University of Basrah for Gas and Oil
College of Oil and Gas Engineering
               Department of
Chemical and Petroleum Refining Engineering
        Process Dynamic and Control II
        Second Semester (Fourth Year)
            Dr. Seaar Al-Dabooni
                   Lecture(2)
                     Final Control Elements and Controllers
        1-2 IDEAL TRANSFER FUNCTIONS
 Control Valve
• A pneumatic valve always has some dynamic lag, which means that the stem position does not respond instantaneously
  to a change in the applied pressure from the controller. From experiments conducted on pneumatic valves, it has been
  found that the relationship between flow (Q) and valve-top pressure (P) for a linear valve can often be represented
• By a first-order transfer function; thus
• In many practical systems, the time constant of the valve is very small when compared with the time constants of other
  components of the control system (negligible dynamic lag)
                     Final Control Elements and Controllers
       Control Valve (Cont.)
 • Consider a first-order valve and a first-order process connected in series (no interaction), as shown
 • The relationship between the air pressure to the valve and the output from the process
  (perhaps a reactor temperature) is
• For a unit-step change in the valve-top pressure P
1) The response for the system with valve dynamic              2) The response for the system with neglected valve
lag is                                                         dynamic lag is
                                                                where the TF is
                           Final Control Elements and Controllers
                                Because the transducer and the converter will be lumped together with the controller for
        Controllers:
                                simplicity, the result is that the input will be the measured variable x (e.g., temperature and
                                fluid level) and the output will be a pneumatic signal p.
  1) ON–OFF CONTROLLERS
    a) Two-Point Control
        A good example of two-point control is a thermostatically controlled heating system for housing which the demand
        temperature is 70 °F (21 °C) as
       Up ( charge ) curve dependent on speed of heating element and the down ( discharge ) curve dependent on
       isolation the house , each charge and discharge is dependent on type of sensor.
*Another example is the valve is either fully open (on) or fully closed (off)
                       Final Control Elements and Controllers
    Controllers (Cont.)
a) Two-Point Control
   In practice, a dead band is inserted into the controller. With a dead band, the error reaches some finite positive value
   before the controller “turns on.” Conversely, the error must fall to some finite negative value before the controller “turns
   off.”
  where P is the control output (control signal) and   is the system error
  Expanding the width of the dead band makes the controller less sensitive to noise and prevents the phenomenon of
  chattering, where the controller will rapidly cycle on and off as the error fluctuates about zero. Chattering is detrimental
  to equipment performance.
                      Final Control Elements and Controllers
    Controllers (Cont.)
                         It's similar to two-point control, except in this case the controller has three states, such as
b) Three-Point Control
                         forward–off–reverse,(or up–off–down, hot–off–cold, and so on). Consider the case of a
                         floating oil-drilling platform that needs to stay over the wellhead on the ocean bottom.
 The platform must not drift more than 5 ft away from the center, or the pipe may break. Two motors, A and B, are used to
 keep the platform centered on the east-west axis (the north-south axis would be handled with other motors). If the
 platform drifts more than 5 ft east, motor A comes on and drives it back toward the center. Motor B will come on if the
 platform drifts more than 5 ft west. There are other cases in the above figures.
                         Final Control Elements and Controllers
      Controllers (Cont.)
2) PROPORTIONAL CONTROLLER (Present)
Our goal is to reduce the error between the process output and the set point. The proportional controller, as we will see, can
reduce the error, but cannot eliminate it. If we can accept some residual error, proportional control may be the proper
choice for the situation.
The proportional controller has only one adjustable parameter, the controller gain. The proportional controller produces an
output signal (pressure in the case of a pneumatic controller, current, or voltage for an electronic controller) that is
proportional to the error .
                                                 Laplace transform
                                               By using the deviation
                                                      variable
                          Final Control Elements and Controllers
       Controllers (Cont.)
  2) PROPORTIONAL CONTROLLER
      Example
If the set point is 30, and the initial value for the robot arm is 0, then the error is 30-0=30, let the proportional gain is 2, then
the output control is 2*30=60 ( means, at certain sampling time (Ts), the motor moves to 30. In the second TS, let the actual
angel for the robot arm is 10, then the error is 30-10=20, and output control is 2*20=40, then the motor moves the arm slower
toward 30, and so on.
If the motor were directed to return to 0°,a new negative error would appear, causing a new (negative) motor torque to be
generated: Error = SP – PV= 0°– 30°= –30°; Output controller= Kc*Error= 2 *30°= –60, The negative sign of the output would
result in a change in polarity of the applied voltage to the motor, which would cause it to run in the opposite direction.
                         Final Control Elements and Controllers
      Controllers (Cont.)
2) PROPORTIONAL CONTROLLER
    Example
    Proportional control is simple, makes sense, and is the basis of most control systems, but it has one fundamental
    problem—steady-state error. In practical systems, proportional control cannot drive the controlled variable to zero
    error because. This small force may not be enough to overcome friction. One way to decrease the steady-state error
    due to friction is to increase the system gain, high Kc can lead to instability problems (oscillations). Another source of
    steady-state error is the gravity problem, increasing the system gain can reduce the error, but proportional control
    alone can never completely eliminate it. One way to deal with the gravity problem is to have the controller add in a
    constant value (to its output) that is just sufficient to support the weight. This value is called the bias
                         Final Control Elements and Controllers
       Controllers (Cont.)
2) PROPORTIONAL CONTROLLER
  • The actual behavior of a proportional controller is
    depicted in figure
  •     The controller output will saturate (level out) at Pmax
       is 15 psig or 20 mA at the upper end and at Pmin is 3
       psig or 4 mA at the lower end of the output.
  • A special case of proportional control is on/off control. If the
    gain Kc is made very high, the valve will move from one
    extreme position to the other if the process deviates only
    slightly from the set point.