Flatpack2
Power Systems
                                                                                                        Overview:
                                                             The Eltek Valere Flatpack2 line consists of versatile,
                                                             scalable, and highly-configurable systems tailored to
                                                             customer requirements.         Use of established
                                                             components—including the efficient and reliable
                                                             Flatpack2 rectifier, the robust Smartpack controller,
                      Flatpack2 +24V 600A
                                                             and flexible distribution units—makes for optimal
                                                             system design and cost-effective deployment.
Flatpack2 Power System                                       Flatpack2 Rectifiers
The Flatpack2 (FP2) power core features an impressive         o New! Flatpack2 HE with 96% typical efficiency
array of distribution configurations and options. Its         o Input voltage range: 85 – 290 VAC
compact design and efficient use of space complement          o 2000W DC output (constant power)
sites with limited floor and rack space, opening room for     o 1U in height; 4.25” in width
better airflow and additional equipment. Flatpack2            o Hot-swap/hot-plug functionality
chassis are designed to mount in standard 19” or 23”          o Automatic active load sharing
telecommunications racks. Standard, fully-populated
configurations accommodate four to sixteen Flatpack2         Smartpack Controllers
rectifiers, yielding total power output ranges of 8kW to      o Provide comprehensive system monitoring and
32kW.                                                           control in a single unit
                                                              o Local and remote interfaces
Distribution Features                                         o PowerSuite software for computer interface
  o Breaker alarming                                          o Advanced battery-monitoring and thermal
  o Low-voltage disconnect (LVD) contactor options              compensation
  o Horizontal load landings, vertical bulk battery           o Various models providing up to six configurable
    landings                                                    alarm inputs and output relays
  o Three distribution options for different power levels:    o Web model for TCP/IP or SNMP communication
      o Small 175A, 19” wide, 1U shelf with controller        o Slave controller option for larger systems
        slot, LVD option, up to six breaker-protected
        output buses, and up to two bulk battery buses       Power Shelves
      o Three-bus, 600A, 19” wide, 4U high panel with         o Accommodate up to four rectifiers each
        20 positions for plug-in circuit breakers or fuse     o 1U height (1.75”); 19” width
        holders, up to two LVD contactors, and rear bulk      o Individual and dual AC feed options
        battery terminals                                     o Mounting brackets for 19” and 23” racks
      o Three-bus, 600A, 23” wide, 4U or 6U high panel
        with 24 positions for plug-in circuit breakers or
        fuse holders, emergency power-off (EPO)
        switch, up to two LVD contactors, and rear bulk
        battery terminals; an additional 23” distribution
        panel option doubles the number of cable
        landings
www.eltekvalere.com                                                                     Copyright © 2009, Eltek Valere
                                                                                                          2048206 R3
                                                                                                                                           Document
Flatpack2 Power Systems                                                                                                                  2048206 R3
Configurations
Flatpack2 Systems
  Standard Systems*                     -48V/150A                -48V/300A             -48V/600A              +24V/600A              +24V/1200A
  Image
  Output Power                                8kW                    14kW                    32kW                  16kW                   32kW
  Maximum Output
                                              168A                   294A                    672A                  672A                   1344A
   Current (DC)
  Total Height**                           2RU (3.5”)             6RU (10.5”)             9RU (15.75”)          7RU (12.25”)           10RU (17.5”)
  Controller Slots                              1                      1                       2                     2                        2
  Rectifier Slots                               4                      7                      16                     8                      16
                                    Height: 1RU (1.75”)       Height: 4RU (7.0”)    Height: 4RU (7.0”)     Height: 4RU (7.0”)      Height: 6RU (10.5”)
  Distribution
                                    Width: 19” (rack)         Width: 19” (rack)     Width: 23” (rack)      Width: 23” (rack)       Width: 23” (rack)
    Dimensions**
                                    Depth: 18.75”             Depth: 18.75”         Depth: 21.75”          Depth: 21.75”           Depth: 21.75”
  Configurable Load
                                          See page 3                   3                       3                     3                        3
    Buses
  Protected Load
                                          See page 3               Up to 20                Up to 24               Up to 24               Up to 24
    Landings
                                    Two-hole 1/4-20 on        Two-hole 1/4-20 on    Two-hole 1/4-20 on      Two-hole 1/4-20 on     Two-hole 1/4-20 on
  Load Landing Lug Sizes            5/8” centers, up to       5/8” centers, up to   5/8” centers, up to     5/8” centers, up to    5/8” centers, up to
                                    #1 AWG                    #1 AWG                #1 AWG                  #1 AWG                 #1 AWG
                                               2
  Bulk Battery Landings                                                4                       8                     8                        8
                                     (option; see page 3)
  Battery Landing Lug               Two-hole 1/4-20 on        Two-hole 3/8-16 on    Two-hole 3/8-16 on     Two-hole 3/8-16 on     Two-hole 3/8-16 on
    Sizes                           5/8” centers              1” centers            1” centers             1” centers             1” centers
  LVD Contactor                              Up to 1                Up to 2                 Up to 2               Up to 2                Up to 2
  EPO Circuit and Service
                                               No                     No                      Yes                   Yes                    Yes
    Bypass Switch
  Additional Distribution
                                      No                      No                              Yes                   Yes                    Yes
     Panel Option
 *Please consult with a sales representative for other available configurations
 **Dimensions are approximate
  Applicable Standards
  NEBS                      Level 3 (GR-63-CORE, GR-1089-CORE)             EN 61000-4-2       Electrostatic discharge (ESD) immunity test
  IEC 60950-1                                                              EN 61000-4-3       Electromagnetic field immunity test
                            Electrical safety
  UL 60950-1                                                               EN 61000-4-4       Electrical fast transient/burst immunity test
                                                                           EN 61000-4-5       Surge immunity test
                            Radiated disturbance at enclosure port
  EN 55022                                                                 EN 61000-4-6       Conducted radio-frequency (RF) immunity test
                            Conducted emission at DC output ports
  (CISPER 22)                                                              EN 61000-4-8
                            Conducted emission at AC mains ports                              Power frequency magnetic field/pulse magnetic field
                                                                           EN 61000-4-9
  EN 61000-3-2
                            Harmonic current emissions                     EN 61000-4-11      Voltage dips, short interruptions and voltage variations
  EN 61000-3-3 20
www.eltekvalere.com
Headquarters:
    Eltek Valere                                                        PAGE 2 OF 2
    1303 E. Arapaho Rd. Richardson, TX. 75081, USA
    Phone: +1 (469) 330-9100         Fax: +1 (469) 330-2955
                                                                                                                                           Document
Flatpack2 Power Systems                                                                                                                  2048206 R3
Distributions
Flatpack2 150A
The -48V/150A system offers five standard distribution configurations that are defined by the number and types
of circuit protection accommodated. Distribution consists of up to six protected buses, with each bus having its
own front-access, plug-in breaker position (100A max rating) and rear-access cable landing. The buses are
organized into three sets of two parallel buses, permitting each pair to be linked together by a two-pole, plug-in
breaker rated up to 175A. If no front-access battery breakers are desired, an extra set of buses is installed for
bulk output to batteries. A low-voltage disconnect (LVD) contactor can be ordered. A 12-position, 65A GMT fuse
block is also available.
FP2 -48V/150A Configurations*                                     2B 2L     2B 2L GMT                 2B 4L         4L GMT                  6L
Battery breaker positions                                           2            2                      2               0                   0
Load breaker positions                                              2             2                     4               4                   6
Unprotected bulk battery landings                                   0             0                     0               2                   2
 12-position, 65A GMT fuse block                    No                  Yes                            No             Yes                   No
*Please consult with a sales representative for other available configurations
Flatpack2 300A, 600A, and 1200A
The larger Flatpack2 systems make use of a unique front-access distribution section that features three discrete,
parallel buses. Each bus has positions for moveable breaker holders that screw into the desired bus. This
arrangement facilitates a variety of convenient uses for each bus, such as protected battery connections, load-
shedding, and converter output. Kits are available for double-pole and triple-pole breakers. Bulk battery cable
landings are available in the rear of these distributions. There are also options for up to two LVD contactors.
                                                                                                                                          Return
                                                                                                                                         Landings
   Breaker
   Holder                                                                                                                                  Cable
                                                                                                                                          Landing
    BUS 1
    BUS 2
    BUS 3
Distributions*                                          300A                                600A                              1200A
                                      Height: 4RU (7.0”)                      Height: 4RU (7.0”)                 Height: 6RU (10.5”)
Distribution Dimensions               Width: 19” (rack)                       Width: 23” (rack)                  Width: 23” (rack)
                                      Depth: 18.75”                           Depth: 21.75”                      Depth: 21.75”
Controller Slot(s)                    One (1) in power shelf                  Two (2) in dedicated shelf         Two (2) integrated in distribution
Alarm Card(s)                         Integrated                              Separate shelf                     Integrated
Configurable Load Buses                                       3                                3                                  3
Protected Load Landings                               Up to 20                             Up to 24                           Up to 24
                                     Two-hole 1/4-20 on 5/8” centers,        Two-hole 1/4-20 on 5/8” centers,    Two-hole 1/4-20 on 5/8” centers,
Load Landing Lug Sizes
                                     up to #1 AWG                            up to #1 AWG                        up to #1 AWG
Bulk Battery Landings                                         4                                8                                  8
                                     Two-hole 3/8-16 on 1” centers, up       Two-hole 3/8-16 on 1” centers, up   Two-hole 3/8-16 on 1” centers, up
Battery Landing Lug Sizes
                                     to 250 MCM                              to 777 MCM                          to 777 MCM
LVD Contactors                                         Up to 2                              Up to 2                            Up to 2
EPO Circuit and Service
                                                          No                                   Yes                               Yes
  Bypass Switch
 Optional Auxiliary
                                               No                                              Yes                               Yes
   Distribution Panel
*Please consult with a sales representative for other available configurations
www.eltekvalere.com
Headquarters:
    Eltek Valere                                                          PAGE 3 OF 3
    1303 E. Arapaho Rd. Richardson, TX. 75081, USA
    Phone: +1 (469) 330-9100         Fax: +1 (469) 330-2955
                                                                                                                               Document
Flatpack2 Power Systems                                                                                                      2048206 R3
Power Modules
Flatpack2 HE Rectifiers
Flatpack2 HE rectifiers are available in two voltages: 48V and 24V. They are hot-swap, switched-mode power
supply units.
Flatpack2 Rectifiers*                                         48V/2000W HE                                24V/1800W HE
Module Image
                                      Range: 85-300 VAC                                 Range: 85-290 VAC
AC Input Voltage
                                      Nominal: 185-275 VAC                              Nominal: 176-275 VAC
Maximum AC Current                    11.6 Arms                                         11.25 Arms
DC Output Voltage                     43.5-57.6 VDC                                     21.0-29.0 VDC
Maximum DC Current                    41.7A                                             75A
Typical Efficiency                    >96%                                              >95%
Operating Temperature                 -40ºC to +75ºC (-40ºF to +167ºF)                  -40ºC to +75ºC (-40ºF to +167ºF)
Storage Temperature                   -40ºC to +85ºC (-40ºF to +185ºF)                  -40ºC to +85ºC (-40ºF to +185ºF)
Cooling                               One fan, front-to-back airflow                    One fan, front-to-back airflow
                                      Height: 41.5 mm (1.63”)                           Height: 41.5 mm (1.63”)
Dimensions                            Width: 109 mm (4.29”)                             Width: 109 mm (4.29”)
                                      Depth: 327 mm (12.87”)                            Depth: 327 mm (12.87”)
 Weight                        1.95 kg (4.30 lbs)                                       1.95 kg (4.30 lbs)
*Please consult with a sales representative for other available models, such as the non-HE rectifiers
Flatpack Converters
Flatpack DC-DC Converters can be ordered for Flatpack2 systems. Converter shelves are delivered in sets of two
or four shelves (four or eight converters, respectively). Each shelf accommodates up to two converter modules.
In 300A, 600A, and 1200A distributions, converter output can be routed to one of the three parallel load buses.
Flatpack DC-DC
                                                               48V to 24V                                    24V to 48V
   Converters*
Module Image
Input Voltage                         40-60 VDC                                        19.8-32.0 VDC
Input Current                         32A at 40 VDC                                    73A at 19.8 VDC
Output Voltage                        24-28 VDC                                        55 VDC
Output Current                        40A at 24 VDC                                    23A
Output Power                          1100W at 27.5 VDC                                1250W
Typical Efficiency                    90%                                              90%
                                      -40ºC to +75ºC (-40ºF to +167ºF)                 -40ºC to +75ºC (-40ºF to +167ºF)
Operating Temperature
                                      Power limiting may occur above +65ºC (+149ºF)    Power limiting may occur above +65ºC (+149ºF)
Storage Temperature                   -40ºC to +85ºC (-40ºF to +185ºF)                 -40ºC to +85ºC (-40ºF to +185ºF)
                                      Height: 43 mm (1.69”)                            Height: 43 mm (1.69”)
Dimensions                            Width: 218 mm (8.58”)                            Width: 218 mm (8.58”)
                                      Depth: 240 mm (9.45”)                            Depth: 240 mm (9.45”)
Weight                                <3 kg (<6.6 lbs)                                 <3 kg (<6.6 lbs)
*Please consult with a sales representative for other available models
www.eltekvalere.com
Headquarters:
    Eltek Valere                                                       PAGE 4 OF 4
    1303 E. Arapaho Rd. Richardson, TX. 75081, USA
    Phone: +1 (469) 330-9100         Fax: +1 (469) 330-2955
                                                                                                                   Document
Flatpack2 Power Systems                                                                                          2048206 R3
Controller Modules
Smartpack Controller
Smartpack is a robust, comprehensive control and monitoring device used for Eltek Valere’s Flatpack2 systems.
The controller communicates with each Flatpack2 rectifier through a CAN bus and provides real-time monitoring
and control information. The Smartpack controller is accompanied by the PowerSuite software program for PC
interface. Alarm inputs and output relays can be increased by using a master/slave configuration in systems that
can accommodate two controllers.
Smartpack Modules*                                                     Web/SNMP 6+6                  Slave
Module Image
                                                                           Rear View                Front View
Input Voltage                                                            24 – 60 VDC              24 – 60 VDC
Configurable Alarm Inputs                                                     6                         6
Form C Output Relays                                                          6                         6
                                                                            USB
Computer Interface                                                                                    USB
                                                                          Ethernet
Front Display                                                                Yes                       No
Battery Symmetry Inputs                                                       4                         8
Temperature Sense Inputs                                                      1                         2
Battery Current Monitor Input                                                 1                         2
Fuse Fail Monitor Input                                                       1                         2
LVD Control                                                   Up to 2 contactors       Up to 2 contactors
                                                              Height: 44 mm (1.73”)    Height: 44 mm (1.73”)
Dimensions                                                    Width: 109 mm (4.29”)    Width: 109 mm (4.29”)
                                                              Depth: 140 mm (5.51”)    Depth: 140 mm (5.51”)
*Please consult with a sales representative for other available models
www.eltekvalere.com
Headquarters:
    Eltek Valere                                                       PAGE 5 OF 5
    1303 E. Arapaho Rd. Richardson, TX. 75081, USA