EN1I6190
EN1I6190
Operator Manual
1.      OVERVIEW ..........................................................................................................1
     1.1 INTRODUCTION ..................................................................................... 1
     1.2 CE CONFORMITY (EUROPE) NOTICE ...................................................... 3
2.      TECHNICAL SPECIFICATIONS..........................................................................4
     2.1 ENVIRONMENTAL CONDITIONS ............................................................... 4
3.      THEORY OF OPERATION ..................................................................................5
     3.1 BASIC OPERATION ................................................................................ 5
     3.2 CONFIGURATION TOOLS ........................................................................ 6
        3.2.1 Smart Field Communicator (SFC) for STT25M and STT25D Models........................................6
        3.2.2 HART Communicator Model 375, 475 or MC Toolkit FDC for STT25H (HART5/HART6)
              Models.............................................................................................................................................................7
        3.2.3 HART Communicator Model 375, 475 or FDC Toolkit for STT25T (HART5/HART6)
              Models.............................................................................................................................................................9
        3.2.4 HART Communicator Model 375 and 475 for STT25S Model...................................................11
        3.2.5 Smartline Configuration Toolkit (SCT)..................................................................................................13
        3.2.6 STT250 Firmware – DD Compatibility matrix....................................................................................14
4.      BENCH CHECK INSTALLATION/COMMISSIONING.......................................16
     4.1    UNPACKING........................................................................................ 16
     4.2    EQUIPMENT........................................................................................ 16
     4.3    INSTALLATION ..................................................................................... 16
     4.4    GROUNDING AND SHIELDING TECHNIQUES ............................................ 18
     4.5    STT250 CONFIGURATION ................................................................... 18
        4.5.1        Analog Output Configuration (based on STS103) for STT25M and STT25D Models.........18
        4.5.2        DE Digital Output Configuration.............................................................................................................21
        4.5.3        HART Configuration (Models STT25H and STT25S)...................................................................22
        4.5.4        HART Configuration (STT25T HART5/HART6 Models)..............................................................37
     4.6 MOUNTING ......................................................................................... 41
        4.6.1 DIN Rail Mounting......................................................................................................................................41
        4.6.2 Mounting Module in Housing..................................................................................................................42
     4.7 COMMISSIONING ................................................................................. 44
     4.8 START UP .......................................................................................... 45
     4.9 ADVANCED DIAGNOSTICS .................................................................... 45
        4.9.1        Install Date....................................................................................................................................................45
        4.9.2        Time in service............................................................................................................................................45
        4.9.3        Error Log.......................................................................................................................................................45
        4.9.4        Calibration records.....................................................................................................................................45
        4.9.5        Power up diagnostics................................................................................................................................45
        4.9.6        PV / SV monitoring.....................................................................................................................................45
        4.9.7        Sensor short detection (only for RTD)..................................................................................................46
        4.9.8        Model number.............................................................................................................................................46
        4.9.9        Serial number..............................................................................................................................................46
Model table
Model
                   STT25S           STT25H      STT25T          STT25D        STT25M
Name 
Protocol        HART6          HART5 &        HART5 &         4-20 mA       4-20 mA
                               HART6          HART6           analog OR     analog
                                                              DE
Configuration   MCToolkit,     MCToolkit,     MCToolkit,      MCToolkit,    MCToolkit,
Tool            Emerson’s      Emerson’s      Emerson’s       SFC & SCT,    SFC & SCT,
                375/475,       375/475,       375/475,        Honeywell’s   Honeywell’s
                Honeywell’s    Honeywell’s    Honeywell’s     FDM,          FDM,
                FDM,           FDM,           FDM,
                CodeWright’s   CodeWright’s   CodeWright’s
                DTM            DTM            DTM
Terminal        Blue           Blue           Blue            Black         Black
Assembly
colour
Whether SIL     Yes            No             Yes (HART6      No            No
certified?                                    version only)
About conformity and       This product is in conformity with the protection requirements
special conditions         of 2004/108/EC , the EMC Directive. Conformity of this
                           product with any other “CE Mark” Directive(s) not referenced
                           in this manual shall not be assumed.
                           Deviation from the installation conditions specified in this
                           manual, and the following special conditions, may invalidate
                           this product’s conformity with the EMC Directive.
                            • You must use shielded, twisted-pair cable such as Belden
                                9318 for all signal/power wiring.
                            • You must connect the shield to ground at the power supply
                                side of the wiring only and leave it insulated at the
                                transmitter side.
ATTENTION
                                                   ATTENTION
Humidity
Output current Current over range 3.8 to 20.8 mA. Failsafe limits < 3.8 and 21.8 mA
CE MARK compliance:
In compliance with EMC directive 89/336/ECC:
          - without shielded wires 10 V/m,  0.2% of Max span
          - with shielded wires and mounted in metallic housing: 10 V/m,
           0.1% of max span.
The data can be configured in the field by connecting a Communicator across the
4-20 mA input or by connecting to a PC via a HART or DE modem. The fail-safe link
between the U and D terminals determines where the output will drive when the STT250
detects an open sensor input or critical failure. The unit will drive upscale to 20.8 mA
(NAMUR = Off) and 20.5 mA (NAMUR = On) when the fail-safe link is in the U position
and downscale to 3.8 mA in the D position.
The output of the STT250 can be configured for either analog or digital modes for DE
protocols (with the exception of STT25M, which is analog-only). This improves
performance by avoiding conversion to/from an analog signal and offers full database
integration of field transmitters with the central control system.
(1) To protect the integrity, write protect is software configurable and accessible through
a password. The fall-back password is an algorithm based on the unit serial number. If
the password is lost, contact your regional Technical Assistance Center (TAC) with the
unit serial number.
(1)
      Not available on STT25D
Advanced Diagnostics
Advanced Diagnostics
 Read Install Date
 Write Install Date
 Read Calibration Date and Time
 Write Correct LRV Date and Time
 Write Correct URV Date and Time
 Read Time in service value
 Read first set of Error log data
 Read second set of Error log data
 Read Error Log option status
 Write Error Log option status
 Reset Error Log
 Read PV tracking data
 Read SV tracking data
 Write high and low alarm limits for PV and SV
 Reset tracking data
 Read power up count
 Reset power up count value
 Read device model number
 Read Sensor1 and Sensor2 limits
 Read middle range value (MRV)
 Write middle range value (MRV)
 Read Loop Control option value
 Write Loop Control option value
 Read hysteresis
 Write hysteresis value
 Read damping value for bump less transfer (applicable to Split Range option)
 Write damping value for bump less transfer (applicable to Split Range option)
The SCT supports several Smartline products which use the DE protocol, including the
STT350, STT25M and STT25D. Since the STT25M and STT25D configuration/data are
a subset of the STT350, most functions are supported by the current version of the SCT
software. The only confusion which may occur is if you try to configure the STT25_ for
functions which are available only with the STT350 transmitter, as shown below.
   Sensor types C, D, Ni/NiMo, Radiamatic, Pt500, Ni500, Cu10 and Cu25 are only
    available with STT350.
   External cold junction compensation is only available with STT350.
   SCT does not support HART protocol and should not be used with Model STT25H,
    STT25S, and STT25T.
   The STT25M cannot be changed from analog to digital DE mode.
To access to the new functionalities of the STT25M and STT25D, you need a SCT3000
Version 5.11.302 or greater.
This compatibility matrix includes a listing of the DD files that should be used with a
revision of the transmitter firmware.
MC Toolkit FDC625: Copy the files to the following Library folder structure under
FDC625 installation directory on the Pocket PC.
For example …\ Library\000017\0004 is for STT25H
              …\ Library\000017\0009 is for STT25S
Refer to the above firmware table for sub folders for the other device types.
         For Rosemount 375 (with system software versions prior to 3.2) copy
          the files to the 375 Easy Upgrade Utility installation folder:
          C:\Program Files\375 Easy Upgrade Utility\PC Database\DD\HART
         For both the 375 (with system software versions 3.2 and greater) and the
          475 copy the files to the Field Communicator Upgrade Utility installation
          folder:
          C:\Program Files\Field Communicator Easy Upgrade Utility 3.3\PC
          Database\DD\HART\en\
 Update the DD files on the SD Card following the Easy Upgrade instructions
4.1     Unpacking
Unpack the unit and verify the contents are as ordered.
4.2     Equipment
If a bench check is intended, the equipment needed is:
 an input sensor(s) suitable for the required application or an equivalent calibrator
     which can simulate milli-volts, resistance temperature detector, thermocouple or
     resistance (ohms) inputs,
 a nominal 24 Vdc power supply with less than 100 mV peak ripple and able to
     supply at least 40 mA,
 a Smart Field Communicator (SFC) with STT25M or STT25D or HART
     Communicator (model 375 or 475) with STT25H, STT25S, or STT25T,
 connection wiring and 250 ohms resistor,
 a Digital Voltmeter (DVM) with range covering 0-5 Vdc. If a high speed sampling
     DVM is used, a 1 Hz (160 msec.) averaging filter is recommended.
NOTE: If you are going to check calibration using a thermocouple input, ensure
that the cold junction temperature is stabilized. After connecting and powering up
all equipment, including the transmitter, protect the transmitter from air drafts and
allow at least 1 hour before taking readings.
4.3     Installation
Connect the equipment as in Figure 2 and Figure 3 and. For more detailed wiring
drawings, refer to drawings listed in Section 5.4
ATTENTION: Do not connect power supply to sensor wiring terminals.
                                                           SFC
                                                            or
                                                          HART
                                                       communicator
                                            250 ohms       +
                                                                DVM
                              4-20 mA
                                        + 24 Vdc
                                                   -       -
                                        Power supply
                                        Red                    Red
                   2 wires RTD               3 wires RTD      4 wires RTD
                  or 2 wires ohm            or 3 wires ohm   or 4 wires ohm
See SFC Operating Card 34-ST-11-16 for more details on Latching, NAMUR and Write
Protection functionalities.
In summary:        - Press "Next" (or     ) and "Prev" (or      ) to scroll through the
                    different categories.
                   - Press "Menu Item" to access the possible selections of any
                     category: the  key steps on to the next selection while the
                      key steps back to the previous selection.
Note that with the "Menu Item" key you can only move to the right.
               A
     ID                DE READ
               B
     CONF                          CHANGE     Enter
                                                         PROBE (J, K, etc...)
                         Enter
                                   CONF
                                                          CJ Ext / Int
                                                           Line Filter
                                    Next                   Inp Fault Det
                                                           O/P Linear
     LRV           E
                                      LRL             * Not available on STT25D
     URV           F
                                    READ CJ
                   G                 SER #
     SET
NEXT H
MENU ITEM I
     OUTPUT        J    INPUT
     CORRECT       K    RESET
     PREV          L
--> M
7 N
     8             O
                   P
     9
     <--           Q   A <--> DE
     4             R
                   S
     5
     6             T
2 W
     3           X     SW VER
     SPAN        Y      URL
     0            Z
                      SCR PAD
     .
     +/-
     NUM / ALPHA
                 
     SHIFT
     CLR (NO)
     ENTER (YES)       NON-VOL
ADDITIONAL NOTE:
1. Not all failsafe mode selections apply for given type of transmitter operation.
2. SET LRV and SET URV commands are available on STT25D.
3. CONFIG NAMUR command is not available on STT25D.
                I                                     1
MENU ITEM               DE CONF       Enter    Type of
                                               transmitter
                                              operation (single
                                              range, dual range
                                              STDC, single range
                                              W/SV)
                                               Message format
                                              (W/O DB - 4 bytes
                                               W/DB - 6 bytes)
                                                             1
                                               Failsafe mode
                                              (B/O Lo, B/O Hi,
                                              LKG, FSO)
                    Q
<--                     A <--> DE               Change to DE?                Are you
                                                                                   2
                                      Enter                        Enter     sure?
1: These parameters are only required for older applications with ST/DC interface
cards. They are not used in STI, STIM or STI-MV interface card installations except for
selection of with/ without Secondary Variable (SV).
You can now customize the unit to your specific application. The flow chart in Figure 7
gives a simplified overview of selections and key strokes.
                        PV
                        %range
                        AO
                        Sensor1 (25T
                        Only)
                        Sensor2 (25T
                        Only)
                        CJ Temperature
                        Delta (25T Only)
                        LRV
                        MRV (25T Only)
                        URV
                        Loop Controlled
                        by (25T only)
                        Loop Control
                        Mode (25T only)
                                           PV Gauge Chart
 Device     Process                                            PV Meter
 Setup      Variables                      Sensor1 Gauge
                                           Chart (25T Only)
                                                               Sensor 1 Meter
                        Gauge charts                           (25T Only)
                                           Sensor2 Gauge
                                           Chart (25T Only)
                                                               Sensor 2 Meter
                                                               (25T Only)
                                           mA Gauge Chart
                                                               mA Meter
                                           PV Trend
                                                               Trend of PV
                                           CJ Trend
                                                               Trend of CJ
                                           Sensor 1 Trend
                        Trends             (25T Only)
                                                               Trend of S1
                                           Sensor 2 Trend
                                           (25T Only)
                                                               Trend of S2
                                           AO Trend
                                                               Trend of AO
                                            Error Log
                                            Flag
                                            Show Error
                            Error Log
                                            Log
                                            Reset Error
                                            Log
                                            Power Up
                            Power Up        Count
                            Count           Reset Power
                                            Up Count
  Device
              Diagnostics
   setup                    Time In
(continued)                 Service
                                                              PV High-Low
                                                              values
                                                                            PV Low Value
                                                                            PV High Value
                                                              PV High-Low
                                                              Alm &
                                                              Counter
                                                                            PV Low Alarm
                                                                            Limit
                            Variables
                                                                            PV Low Alarm
                            Monitoring       PV tracking
                                                                            Counter
                                                                            PV High Alarm
                                                                            Limit
                                                                            PV High Alarm
                                                                            Counter
                                                                            Change PV
                                                                            Alarm Limits
                                                              Reset PV
                                                              Tracking
                                                              Values
                             Master Reset
                             Loop Test
  Device
   setup                                     Write Protect
                Services
(continued)
                                             Write
                             Write
                                             Protection
                             Protection
                                             On/Off
                                             Change
                                             Password
Apply Values
LRV
URV
                                             MRV (25T
                             Enter Values
                                             only)
                                             LRL
               Calibration
                                             URL
                             Correct Input
                             LRV (Not
                             25T)
                                             LRV Correct :
                             History of
                                             Recent
                             LRV corrects
                             (Not 25T)       LRV Correct :
                                             Previous
                              Sensor Limit
                              Values (25T
                              only)
                              Install Date
                              Dev id
                              Model Number
                              Tag
                              Descriptor
                              Date
                              Message
  Device
                              Namur
   Setup
                              Damp
(continued)
                Device        Hysteresis band
                              (25T only)1
              Configuration
                              Damp-Bumpless
                              Transfer (25T
                              only)5
                              Poll Addr
                              Line Filter
                              LRV
                              MRV (25T only) 2
                              URV
                              Honeywell logo
                              Device image
                              Sensor Selection
                              (Not for 25T)
                              Sensor Type
                              (Not for 25T)
                              Mode Selection
                Sensor
                              (25T only)
              Configuration
                              Mode (25T only)
                              Sensor 1 Type
                              Code (25T only)
                              Sensor 2 Type
                              Code (25T only)
                               Delta (25T
                               only)
                               Delta Alarm
                               (25T only)
                               Match PV
                               (25T only)
                               Damp-
                               Bumpless
                               Transfer
                               (25T only) 5
                               Wiring
                               diagrams
                                                  Sensor1
                                                  Adapter
  Device          Sensor                                    RTD
   Setup       Configuration                                adapter 1
(continued)     (continued)                                 Selection
                                                            Sensor1
                                                            +ve Coeffs
                                                                          B-Postv rng
                                                                          (1)
                                                                          C-Postv rng
                                                                          (1)
                                                                          D-Postv rng
                                                                          (1)
                                                                          E-Postv rng
                                RTD Adapter                               (1)
                               (for S and H, it                           F-Postv rng
                                 is only for 1                            (1)
                                   sensor)6                               G-Postv rng
                                                                          (1)
                                                            Sensor1 -ve
                                                            Coeffs
                                                                          B-Negtv rng
                                                                          (1)
                                                                          C-Negtv rng
                                                                          (1)
                                                                          D-Negtv rng
                                                                          (1)
                                                                          E-Negtv rng
                                                                          (1)
                                                                          F-Negtv rng
                                                                          (1)
                                                                          G-Negtv rng
                                                                          (1)
                                                                          B-Postv rng
                                                                          (2)
                                                                          C-Postv rng
                                                                          (2)
                                                                          D-Postv rng
                                                                          (2)
                                                                          E-Postv rng
                 Sensor         RTD Adapter                               (2)
              Configuration    (for S and H, it                           F-Postv rng
               (continued)       is only for 1                            (2)
                                   sensor) 6                              G-Postv rng
                                                                          (2)
                                                            Sensor2 -ve
                                                            Coeffs
                                                                          B-Negtv rng
                                                                          (2)
  Device                                                                  C-Negtv rng
   Setup                                                                  (2)
(continued)                                                               D-Negtv rng
                                                                          (2)
                                                                          E-Negtv rng
                                                                          (2)
                                                                          F-Negtv rng
                                                                          (2)
                                                                          G-Negtv rng
                                                                          (2)
                              Break detect
                              XSDelta detect
                              (25T only)
                              Latching alarm
                 Alarm
                              Latch clear
                              Alarm direction
                              Suspect Input
                              (not 25T)
                              Model
                              Distributor
                              Manufacturer
                              Dev id
                Review        Tag
                              Message
                              Descriptor
                              Serial Number
                              Poll address
PV
%range
AO
Sensor1 (25T
only)
Sensor2 (25T
only)
CJ
Temperature
Delta (25T
only)
LRV
URV
Loop
Controlled by
(25T only)
Loop Control
Mode (25T
only)
                       PV
                       %range
                       AO
                       Sensor1 (25T
                       Only)
                       Sensor2 (25T
                       Only)
                       CJ
                       Temperature
                       Delta (25T
                       Only)
                       LRV
                       MRV (25T
                       Only)
                       URV
                       Loop
                       Controlled by
                       (25T only)
                       Loop Control
                       Mode (25T
                       only)
                                       PV Trend
                                                          Trend of PV
                                       CJ Trend
                                                          Trend of CJ
                                       Sensor1 Trend
                       Trends          (25T Only)
                                                          Trend of S1
                                       Sensor2 Trend
                                       (25T Only)
                                                          Trend of S2
                                       AO Trend
                                                          Trend of AO
                                         Power Up Count
                            Power Up
                                         Reset Power Up
                            Count
                                         Count
                            Time In
                            Service
                                                           PV High-Low
                                                           values
                                                                           PV Low Value
                                                                           PV High Value
                                                           PV High-Low
                                                           Alm & Counter
                                                                           PV Low Alarm
  Device      Diagnostics                                                  Limit
   setup                                                                   PV Low Alarm
(continued)                                 PV tracking                    Counter
                                                                           PV High Alarm
                                                                           Limit
                                                                           PV High Alarm
                                                                           Counter
                                                                           Change PV
                                                                           Alarm Limits
                                                           Reset PV
                            Variables                      Tracking
                            Monitoring                     Values
                                                           CJ High-Low
                                                           values
                                                                           CJ Low Value
                                                                           CJ High Value
                                                           CJ High-Low
                                                           Alm & Counter
                                                                           CJ Low Alarm
                                                                           Limit
                                                                           CJ Low Alarm
                                           CJ Tracking                     Counter
                                                                           CJ High Alarm
                                                                           Limit
                                                                           CJ High Alarm
                                                                           Counter
                                                                           Change CJ
                                                                           Alarm Limits
                                                           Reset CJ
                                                           Tracking
                                                           Values
Write Protect
                Services                        Write
                             Write Protection   Protection
                                                On/Off
                                                Change
                                                Password
                             Lock/Unlock
                             Device
Apply Values
LRV
URV
                                                MRV (25T
                               Enter Values
                                                only)
  Device
                                                LRL
   Setup       Calibration
(continued)
                                                URL
                             Correct Input
                             LRV (Not 25T)
                                                LRV Correct :
                             History of LRV
                                                Recent
                             corrects (Not
                                                LRV Correct :
                             25T)
                                                Previous
                             Correct Input
                             URV (Not 25T)
                                                URV Correct :
                             History of URV
                                                Recent
                             corrects (Not
                                                URV Correct :
                             25T)
              Calibration                       Previous
              (continued)    Reset Corrects
                             (Not for 25T)
                             D/A Trim
                             Sensor Limit
                             Values (25T
                             only)
                                Break detect
                                XSDelta detect
                                (25T only)
                                Latching alarm
                   Alarm
                                Latch clear
                                Alarm direction
                                Suspect Input (not
  Device                        STT25T)
   Setup
(continued)                     Model
  Device                        Distributor
   Setup
                                Manufacturer
(continued)
                                Dev id
                                Tag
                                Message
                                Descriptor
                                Serial Number
                                Poll address
                                Loop Current Mode
                                Long Tag
                                Final Assembly
                  Review
                                Number
                                Config Change
                                Cntr
                                Num req preams
                                Date
                                Power Up Count
                                Install Date
                                Write Protect
                                Universal Rev.
                                Field Dev Rev
                                Software Rev.
                                Hardware Rev.
                                DD Revision
Figure 8 HART 6 DD Menu Structure for STT25H, STT25S and STT25T Configuration
1
  Hysteresis, Damp-bumpless transfer are applicable to STT25T only and also depending on loop
  control option selected
2
  Depending on loop control option selected
3
  Wire connection - for other variants than 25T, Applicable for RTD sensor type only
4
  Compensation - Applicable for TC sensor type only
5
  Damp bumpless transfer - applicable for STT25T in redundant and split range loop control options
6
  RTD Adapter - Applicable only if sensor is RTD type
You can now customize the unit to your specific application. The flow chart in Figure 7
HART 5 DD Menu Structure for HART 5 and Figure 8 for HART 6 DD Menu Structure
for STT25T Configuration gives a simplified overview of selections and key strokes.
3.   Press 6 (or use DOWN arrow key) to select    4.   First menu on this page is Mode selection.
     Sensor Configuration.                             Press 1 (or) to enter this method.
5. Warning will be displayed. Press OK. 6. Select TC/ TC mode and press ENTER.
9.    Warning will be displayed. Press OK.        10.Verify on sensor configuration menu that
                                                        mode is TC/TC, sensor1 & sensor2 are
                                                        TC K.
11.      In sensor configuration menu, press      12.    Enter desired value of Delta Alarm. Hit
        DOWN arrow key 10 times to reach Delta          ENTER.
        Alarm. Press  to enter.
15.In the alarm menu, option 1 is XSDelta             16.Make this detection ON. Hit ENTER.
     detect. (NOTE: Make sure that device’ loop
     control mode is Redundant mode. XS Delta
     Detection is not displayed in other Loop
     control modes.) Press  to enter.
17.Now, send this to device.                          Verify that this value is sent and alarm is
                                                      ON.
4.6        Mounting
4.6.1       DIN Rail Mounting
If the STT250 is to be installed on DIN Rail then the main considerations are electrical
connections and mechanical fixing. Electrical connections are identical to the bench test
instructions (Section 4.3) except that thermocouple wire is likely to be used with
thermocouples. Mechanical fixing of the module is by means of the snap-in DIN Rail
Clips which are screwed to the bottom lugs of the module.
      INSTALLATION WITH "G" DIN           TOP HAT/ " " DIN RAIL
           RAIL RIGHT VIEW
            31
          (1.22)                           "G" DIN RAIL
            41.4
           (1.63)
                                                PROTECTIVE CAP
             44.4                                                        46188464-201
            (1.75)
                                                                                                 142
                                                                                                 (5.59)
                                                                               (1.57)
                                                                      40
                                                                                                                (2.34)
                                                                                                                 59.5
                                                                        (2.36)
                                                                          60
                      A                                 A                                       94
                                                                                         115 (3.7)
                     B                                  B                                (4.53)    46188467-201
                                                                                                            [2.43]
                                                                                                             61,8
                                                                       [2.36]
                                                                         60
                 A                              A
                                                                             [1.54]
                                                                               39
             B                                 B
     CLEARANCE FOR CAP                                                                         94
                                   CLEARANCE FOR CAP                                         [3.7]
          REMOVAL                                                             14,9
                                        REMOVAL
                                                                             [0.59]              115
                                                                                        129,5 [4.53]
                                                                                         [5.1]            46188468-201
                             SPRINGS                  33 mm
                           FEED-THROUGH
                             HOLE FOR
                           SENSOR WIRES
                              STT250
                             SENSOR PLATE
                              ASSEMBLY
CIRCLIPS
46188463-201
                                                                                                          or M20
                                                                  AA section
                  (33)                                                            (40)
                                                                                  2 x M3
2 x M4
                                                                   (41)
                                                                                           1/2" NPT
                                                                     AA section
     BB section
                                                                                      ( 104)
2 x M4
                                                                                                                       NPT or
                                                                                                                        M20
                                                                                                                        1/2"
                            33 mm
                                         2 x M4
                                                 (111)
                                         (41)
                                                                                                      1/2" NPT
                                                                                                                    46188453 -0XX
For more detailed installation drawings, refer to the list in section 5.4.
4.7        Commissioning
Commissioning is carried out after installation and wiring have been completed. Power
up the STT250 transmitter and verify via the SFC or HART Communicator that it is
configured as required. If a bench check and configuration were completed, the
procedure will be clear. If no bench check and configuration was done, refer to Section
4.4 and carry it out now. Verify also that the receiving device is actually receiving the
output signal and use the SFC or HART Communicator in output mode to vary the
output signal and verify loop calibration. If small errors exist in the loop then they should
be identified and the out of specification device calibrated. However, if no adjustment is
possible (e.g. with voltage developing resistors or active barriers) then the STT250
output can be recalibrated to compensate for loop zero and span errors. For calibration
of the STT250, refer to the SFC Operating Guide 34-ST-11-16.
4.9.6    PV / SV monitoring
The variables listed below will be stored in NVM:
 -    Number of times PV/SV exceeded user-configured alarm limits.
  -     Maximum/minimum PV/SV
  -     A timestamp indicating the last time the PV/SV exceeded the user-configured
        alarm limits.
RTD sensors with Callendar – van Dusen coefficients are expensive and they are used
in critical applications. For other applications normal sensor is used. To get improved
RTD accuracy, RTD sensors with CVD coefficients can be used.
If RTD sensor with Callendar – van Dusen coefficients to be used, the RTD Adapter
option has to be enabled. After enabling this option, the Callendar – van Dusen
coefficients for the respective RTD sensor must be used to calculate the RTD Adapter
constants required to be stored in device NVM for improved RTD accuracy. A Microsoft
Excel utility provided by Honeywell, is required to generate these RTD Adapter
constants. Using this utility, total 14 constants - 7 for positive RTD range and 7 for
negative RTD range are generated. Different commands are provided for enable/disable
of RTD Adapter option and for entering these constants to the device NVM storage.
For STT25T model, if both the sensors are RTD type then two sets of these constants
are required to be generated and used appropriately for the respective sensor. The
STT25T model is provided with additional commands to enter these RTD Adapter
constants to the device NVM storage for both the RTD sensors.
The RTD Adapter feature is available for all STT250 HART models using RTD as
sensor.
* CVD (Callendar-Van Deusen)
5.2     Troubleshooting
5.2.1    Troubleshooting with SFC (STT25M and STT25D Models)
Troubleshooting the STT250 loop is greatly simplified by connecting the SFC in the
termination area near the receiving instrument. Also connect a DVM, at the termination
area for the receiving instrument, to confirm a similar signal is coming from the field and
power is available on the two wires of the 4-20 mA loop. This isolates the problem to
either field loop or receiving instrument/power supply/wiring/safety barriers etc. If the
original symptom was an unstable input, it could be a loose connection on the receiving
side. Assuming the above confirms a field loop problem, the likely causes/actions are
given below.
For any step the first action is to hook up the SFC to the transmitter and press "ID", then
"STATUS".
Fail-safe output    RAM FAILURE         The device has         Try to restart the
signal                                  detected               device. If the status
                                        corruption in a        persists, contact your
                                        RAM memory             vendor.
                                        location.
Fail-safe output     ROM FAILED         The device has         Try to restart the
signal                                  detected               device. If the status
                                        corruption in a        persists, contact your
                                        ROM memory             vendor.
                                        location.
Fail-safe output   FLOW CONTROL         The device has         Try to restart the
signal                FAULT             detected an            device. If the status
                                        interruption in the    persists, contact your
                                        proper flow of         vendor.
                                        functional
                                        operations.
Informational Status
The following      INPUT OPEN (1/2)     The device is          Verify the applicable
message is                              indicating an open     sensor wiring and
displayed                               connection for         check the sensor for
                                        sensor input. For      failure.
                                        STT25T devices,
                                        the relevant input
                                        will be specified
                                        (Input 1 or Input 2)
The following      RTD SHORT (1/2)      The device is          Verify the applicable
message is                              indicating a           sensor wiring and
displayed                               shorted connection     check the sensor for
                                        for an RTD sensor      failure.
                                        input. For STT25T
                                        devices, the
                                        relevant input will
                                        be specified (Input
                                        1 or Input 2)
6.1        Introduction
Integral meters are supplied already installed by the factory and provide a display of the
transmitter output. Table II selection _ _ M gives a 4-20 mA analog output on a moving
coil display to 2% accuracy. A diode fitted across the meter enables loop continuity in
the event of a moving coil failure. To ensure adequate loop power availability in this
event, add 0.7 V power supply to the loop in addition to 10.8 V for the transmitter (i.e.
11.5 V minimum supply Volts).
Table II selection _ _ S is the Smart Meter with LCD which accepts either the Digital DE
or the 4-20 mA analog signal. Regardless of signal type, the Smart Meter displays a
large bargraph accurate to 3% and visible from 10 meters away. The 4 ½ digit display
shows the output in % of span or in engineering units (except with STT25H and
STT25S HART). With the 4-20 mA signal, this digital display is accurate to 0.5% of
span. With the Digital DE signal, the display has no error; displaying the digital output
exactly within its resolution of 0.05% for a 199.9 reading range, 0.5% for a 1999
reading range and 5% for a 19990 reading range.
The Smart Meter includes various status message and engineering unit information on
the LCD screen.
The Smart Meter obtains its power in series with the transmitter and requires
2.25 V power supply in addition to the transmitter’s 10.8 V (i.e. 13.05 V minimum supply
Volts). The minimum loop operating current is <3.8 mA.
10V
0 % 100
                       RED                                   YEL
                       YEL
                                                              RED
                       BLUE
                                                                                   DIODE
                      WIRING FOR SMART
                                                         WIRING FOR ANALOG METER
                           METER
                                                                                   46188461-201
                                   Figure 15: Meters Connections
                      17-SEGMENT BARGRAPH
                           (0 to 100%)
1. At power up, the LCD stays completely blank. Either the self check failed or the
   meter is not receiving power. Check the connections.
   Note that the Smart Meter requires 2.25 Volts supply in addition to the minimum
   10.8 Volts for the STT250 transmitter (i.e. minimum of 13.05 V across the
   meter/transmitter terminals). Verify adequate loop power is available.
2. At power up after showing all LCD segments, the display shows "BAD XMTR
   STATUS" and "_ _ _" instead of the digital engineering unit display. This means that
   the meter received a critical status diagnostic message from the transmitter at
   power up. Use the configuration tool to determine the critical status cause and
   correct.
3. After successful power up, the display shows "BAD XMTR STATUS" and the
   bargraph flashes. This means that a critical status condition occurred during
   operation. The display value may not be correct. Use the configuration tool to
   determine the cause and correct.
4. After successful power up, the display shows "FAULT-LAST KNOWN VALUE" and
   the bargraph flashes. This means that the on-going self diagnostics of the meter
   detected an internal fault or that communications from the transmitter were lost or
   that 5 or more corrupted messages were received from the transmitter operating in
   the digital output mode. Cycle the power to see if the condition self clears. If it
   recurs, check loop wiring for adequate loop power, ensure presence of the 250 ohm
   communications resistor and minimize electrical noise in the loop.
5. After successful power up, the display shows "OUTPUT MODE" and the bargraph
   flashes while the digital display flashes a value 0.0% to 100.0%. This means that
   the transmitter went to fixed output mode while operating as a digital output device.
   Connect the configuration tool and press "OUTPUT", "CLEAR" to revert to normal
   operation.
6. The display shows "ANALOG", "0.0%" and no bargraph segments switch on. This
   means that the Smart Meter requires calibration to the transmitter operating in
   4-20 mA analog output mode. See Section 6.4.3.
    Step 1 - Put control loop to Manual and use the configuration tool to establish
     communications. Put the transmitter into 0% output mode by pressing "OUTPUT",
     "0", "ENTER" for "0.0%" on SFC.
    Step 2 - Press and hold side button on meter. Release the button when "CAL"
     appears on the display. The meter will now carry out a zero (LRV) calibration and
     revert to normal operation. Press "OUTPUT", "CLEAR" to revert transmitter to
     continuous output operation.
    Step 3 - Change output mode value to 100% by pressing "OUTPUT", "1", "0", "0",
     "ENTER".
    Step 4 - Press and hold side button on meter. Release button when "CAL" appears
     on the display. The meter will now carry out a span (URV) calibration and revert to
     normal operation. Press "OUTPUT", "CLEAR" to revert transmitter to continuous
     output operation. Return loop to Automatic operation.
ATTENTION - If "bAd" appears on the meter display after Step 2 or 4 then the
4 mA or the 20 mA signal was not within the meter's acceptable accuracy range and
calibration was aborted. Check the mA values and repeat calibration steps as required.
        Earth Ground
                                                                      46188469-201
 Inclusions       To ensure that all required information will be available to the user, the following
                  items are included with this Addendum for reference:
                   1.   Declaration of Conformity – ATEX CE0344 (Honeywell document number
                        51453718 Revision A).
                   2.   Certificate of Manufacturer II 3 G EEx nA ATEX CE (Honeywell document
                        number 51453719 Revision A).
                Details regarding certification marks that appear in labeling for this product are
                given in this addendum.
Attention
Attention
CE Conformity   The STT 3000 Smart Temperature Transmitter, Models STT250, are in conformity
                with the protection requirements of the following European Council Directives:
                94/9/EC, the Explosive Atmospheres (ATEX) Directive, and 2004/108/EC, the
                Electromagnetic Compatibility (EMC) Directive.
                In conformity with the ATEX directive, the CE mark on the certification nameplate
                includes the Notified Body identification number 0344 (KEMA 01ATEXQ3199)
                adjacent to the EC Type Examination Certificate number.
                Deviation from the installation conditions in this manual may invalidate this
                product’s conformity with the Explosive Atmospheres, Pressure Equipment, and
                EMC Directives.
                Conformity of this product with any other “CE Mark” Directive(s) shall not be
                assumed.
              STT25M         4-20 mA
              STT25H
                             HART-5 protocol and 4-20 mA
              (HART5)
              STT25H
                             HART-6 protocol and 4-20 mA
              (HART6)
              STT25S         HART-6 protocol and 4-20 mA
              STT25T
                             Dual Input, HART-5 / 4-20 mA
              (HART5)
              STT25T
                             Dual Input, HART-6 / 4-20 mA
              (HART6)
The process variable can be observed locally when the ME, SM or EU indicators (when
compatible with the communications protocol) installed in the metal enclosure.
                           For complete model number, see the Model Selection Guide 34-44-16-03
                            for the particular model of temperature transmitter.
                           The serial number of the transmitter is located on the module label. For
                            models STT25M and STT25D the serial number is 10 characters (0
                            through 9) long. The last two characters are fixed 37. The first character
                            (0) is a B. Characters 2 and 3 are the week of manufacture and the single
                            character 4 is the year of manufacture. The serial number consists of
                            characters 1, 5, 6, and 7.
                           For models STT25H, STT25S and STT25T the new serial number has
                            characters 0 through 3 as the serial number, characters 4 and 5 are the
                            week of manufacture and characters 6 and 7 are the year of manufacture.
Apparatus           The user must determine the type of protection required for installation the
Marked with         equipment. The user shall then check the box [] adjacent to the type of
Multiple Types of   protection used on the equipment certification nameplate. Once a type of
                    protection has been checked on the nameplate, the equipment shall not then be
Protection          reinstalled using any of the other certification types.
Label 50019639-001, ia, 4-20 mA / DE, is mounted on the module. The following is a representation of this label:
Nameplate 50019640-001, (ia) 4-20 mA / DE / HART, nameplate. The following is a representation of this
nameplate:
Nameplate 50019642-001, (d) 4-20 mA / DE / HART, nameplate. The following is a representation of this
nameplate:
Co ≤ 2.08 µF Lo ≤ 20mH
 Special             The Smart Temperature Transmitter is an intrinsically safe apparatus that can be
                     installed in potentially explosive atmospheres.
 conditions
 for safe use,       The supply terminals (+, -) must be connected only to a certified associated
                     intrinsically safe apparatus.
 Intrinsic           The sensor entry terminals (1, 2, 3, and 4) must be connected only to certified
 Safety (X)          intrinsically safe equipment or according to paragraph 1.3 of standard EN 50014.
                     The electrical parameters (U, I, and P) of the associated apparatus connected to the
                     power terminals (+, -) must not exceed the following values:
                     Ui  30V                   Ii  165 mA             Pi  1,2 W
                     The electrical parameters (L and C) of the apparatus connected to the sensor entry
                     terminals (1, 2, 3, and 4) (cabling parameters included) must not exceed the following
                     values:
                     Cext = 2 µH               Lext = 2 mH
                     Certification ambient operating temperature : -50oC to 85 oC
                     Standard specification ambient limits : -40oC to 85 oC.
                     Temperature classifications:
T6 up to Ta  40ºC T6 up to Ta  80ºC
T5 up to Ta  55ºC T5 up to Ta  85ºC
T4 up to Ta  90ºC
T5 at Ta ≤ 85oC
                       ATEX                                              0344
We declare under our sole responsibility that the following products,
to which this declaration relates, are in conformity with the protection requirements of Council
Directive: 94/9/EC (ATEX Directive) on the approximation of the laws of the Member States
concerning equipment and protective systems intended for use in potentially explosive
atmospheres, and 89/336/EEC (EMC Directive) as amended by 92/31/EEC, 93/68/EEC and
2004/108/EC on the approximation of the laws of the Member States relating to Electromagnetic
Compatibility.
The models covered by this Declaration and evidence of conformity with the ATEX Directive are
listed below. Conformity to the ATEX Directive is in accordance with the following European
standards.
The authorized signatory to this declaration, on behalf of the manufacturer, and the
Responsible Person is identified below.
II 3 G Ex nA IIC ATEX
2.    Before commissioning this equipment, it must be verified that the power supply voltage cannot exceed the
      30 Vdc maximum for the STT15S transmitters.
3.    The temperature transmitter is a non-repairable item, and if faulty, must be replaced. The electrical power
      supply must be switched off before any replacement and during any time that the wiring terminations are
      being connected or disconnected.
4.    The technical data supplied by the manufacturer must be adhered to. Install per Operator manual EN1l-
      6190.
                                                      Issue Date:            11
                                                                             September
                                                                             2007
The aim of the IECEx Scheme and its Programs is to ease international trade of
Explosion Protected Equipment (termed Ex equipment) by eliminating the need for
duplication of testing and certification, while preserving safety. IECEx operates as an
International Certification System covering products and services associated with the
Ex industries.
                  STT25M          4-20 mA
                  STT25H
                                  HART-5 protocol and 4-20 mA
                  (HART5)
                  STT25H
                                  HART-6 protocol and 4-20 mA
                  (HART6)
                  STT25S          HART-6 protocol and 4-20 mA
                  STT25D          Digital DE / 4-20 mA
                  STT25T
                                  Dual input HART-5 / 4-20 mA
                  (HART5)
                  STT25T
                                  Dual input HART-6 / 4-20 mA
                  (HART6)
The process variable can be observed locally when the ME, SM or EU indicators (when
compatible with the communications protocol) installed in the metal enclosure.
The transmitter module may also be installed in a flameproof stainless steel or aluminum
enclosure. The aluminum alloy contains < 6% magnesium.
                 STT25M           4-20 mA
                 STT25H           HART-5 protocol and 4-20 mA
                 (HART5)
                 STT25H           HART-6 protocol and 4-20 mA
                 (HART6)
                 STT25S           HART-6 protocol and 4-20 mA
                 STT25D           Digital DE / 4-20 mA
                 STT25T           Dual input HART-5 / 4-20 mA
                 (HART5)
                 STT25T           Dual input HART-6 / 4-20 mA
                 (HART6)
The process variable can be observed locally when the ME, SM or EU indicators (when
compatible with the communications protocol) installed in the metal enclosure. The
transmitter module may also be installed in a flameproof stainless steel or aluminum
enclosure. The aluminum alloy contains < 6% magnesium.
CONDITIONS OF CERTIFICATION:
   This certificate (which requires annual renewal) covers all units sold / used /
    purchased from the date of this certificate to its expiration date.
     The apparatus must be additionally marked in a clear, legible, visible and
      indelible manner with the SAEx marking details above.
     This certificate of approval only covers the equipment as certified above and does
      not include any scheduled additions or variations / amendments / new issues to
      the certificate(s), made after the above date.
     The equipment does not need to be retested when used on the conditions and
      with such restrictions as prescribed by ITACS and in this approval.
     The ITACS certification must remain valid.
                                                                    Venezuela
                                                                    Honeywell CA
                                                                    Phone: +(58-2) 238-
                                                                    0211
                                                                    FAX: +(58-2) 238-3391