Power Transformer Protection Using Chirplet Transform
Power Transformer Protection Using Chirplet Transform
Research Article
                                                                                                                 ISSN 1751-8687
Power transformer protection using chirplet                                                                      Received on 6th December 2015
                                                                                                                 Revised on 20th February 2016
transform                                                                                                        Accepted on 4th March 2016
                                                                                                                 doi: 10.1049/iet-gtd.2015.1486
                                                                                                                 www.ietdl.org
Senthil Kumar Murugan 1 ✉, Sishaj Pulikottil Simon 1, Panugothu Srinivasa Rao Nayak 1,
Kinattingal Sundareswaran 1, Narayana Prasad Padhy 2
1
 Department of Electrical and Electronics Engineering, National Institute of Technology, Tiruchirappalli, India
2
 Department of Electrical and Electronics Engineering, Indian Institute of Technology, Roorkee, India
✉ E-mail: senthil.pse@gmail.com
Abstract: This study presents a novel differential protection algorithm (DPA) for power transformer using chirplet
transform (ChT). The proposed method combines the features of biased restraint characteristic (BRC) of the
conventional differential relay and out-turn of ChT in a two-stage algorithm. In the first stage, the BRC plane is divided
into three zones: namely, high-set (HS), non-trip and vulnerable zones. The tripping decisions are carried out in the first
two zones based on differential and biased current. However, if the operating condition of the power transformer falls
in the vulnerable zone, then there is an ambiguity in discriminating internal fault, inrush current and current
transformer saturation cases. Therefore, in the second stage, ChT is applied to differential current signal to obtain an
energy distribution on the time-frequency plane with respect to time, frequency and chirp rate. Then, using the mean
and standard deviation of the normalised energy, power transformer operating conditions are classified. Also, most of
the DPAs available in the literature are system dependent. However, the proposed novel DPA can be effectively used
for any system. The proposed scheme is validated for two power transformer systems using PSCAD to simulate
various operating conditions and MATLAB to implement the algorithm.
1      Introduction                                                      fault currents may have harmonic content during fault inception
                                                                         and produce low-magnitude differential current, respectively, the
The power transformer plays a vital role in power system, since it       sensitivity of the conventional relay is not enough to detect those
handles large amounts of power between generation and                    faults at the earliest.
distribution. Its outage rate has high impacts on power system              Though the newest techniques based on wavelet transform [7, 8],
reliability as well as power system economics. The outage rate of        neural network [9, 10], fuzzy logic [11, 12], adaptive relay [13, 14]
power transformer depends on several factors such as operating           and combination of the above methods [15–17] are proposed, still
condition of power transformer, periodical maintenance, power            the second-harmonic restraint method is widely used irrespective
transformer lifetime and maloperation of protection relay.               of its shortcomings [18]. Generally, the threshold setting for
However, the maloperation of the protection relay is the significant      tripping condition is to be changed according to the power
one. Therefore, it is necessary to use an appropriate protection         transformer rating (parameters). For instance, the percentage of
relay to ensure the reliability. Current differential relaying method    second-harmonic content to prevent the relay operation is to be
is the most commonly used approach for power transformer                 updated according to the transformer rating. Also, in case of neural
protection [1]. It measures the differential current in common base      network-based differential protection algorithm (DPA) [9, 10], the
value and operates when differential current reaches the preset          training data has to be created for each of the individual
value. Whenever the internal fault occurs in the power                   transformers separately. Therefore, in DPAs available in the
transformer, differential current flows through the relay initiating      literature, the protection system needs to be updated according to
the trip signal to the corresponding breakers. However in certain        the power transformer parameters and is not system independent.
cases, the magnitude of the magnetising inrush current becomes           Therefore, it is clear that there is a significant scope of research for
ten times of the full load current which leads to maloperation of a      developing new techniques in power transformer protection
differential relay [2, 3]. In addition, saturated current transformer    systems [19].
(CT) during severe external fault (SEF) may have high-magnitude             Recently, a new transform called chirplet transform (ChT) has
which will also cause a maloperation [4]. Therefore, discrimination      found its application in fields such as instantaneous frequency
between internal fault current and other disturbances during the         estimation, classification of seismic waveforms [20, 21] etc. The
operation of a power transformer has become a challenging task           ChT was introduced by Mann and Haykin in 1995 [22]. The ChT
for the protection engineers.                                            maps a mono-dimensional signal into a four-dimensional (4D)
   Since the inrush current possesses a significant amount of the         function: namely, time, scaling, chirping in frequency and
second-harmonic component, the conventional differential relay           chirping in time. The parameters are useful tools for properly
uses the second-harmonic restraint method to discriminate                shaping (rotating and shearing in frequency) each cell throughout
magnetising inrush current from internal fault current which is          the time–frequency (TF) plane. Since an additional parameter:
carried out through discrete Fourier transform [5]. It should be         namely, chirp rate is used along with time and frequency
noted that CT saturation can be identified by the presence of the         parameters, this paper attempts a new ChT-based method to
higher harmonic components. However, the core material of the            discriminate the internal fault from the inrush currents and CT
modern power transformer produces less second-harmonic content           saturation cases irrespective of the current magnitude based on
during energisation. Therefore, accuracy of the conventional relay       ChT energy distribution on the TF plane corresponding to time,
is not appreciable [5, 6]. Also, since the internal and the inter-turn   frequency and chirp rate.
                                                                         IET Gener. Transm. Distrib., 2016, Vol. 10, Iss. 10, pp. 2520–2530
2520                                                                              & The Institution of Engineering and Technology 2016
2     Chirplet transforms                                                             The resultant of the first stage of the algorithm can make accurate
                                                                                      decisions in three zones: namely, no-trip, trip and vulnerable zone.
The short-time Fourier transform (STFT) consists of a correlation of                  Since no tripping decision is possible in the vulnerable zone,
the signal with constant-size portions of a wave, whereas the wavelet                 further examination is needed. That is, in order to discriminate the
transform consists of correlations with a constant-Q family of                        operating conditions of the power transformer in the vulnerable
functions. The two transforms attempt to localise the signal in the                   zone, time domain to TF-domain transformation technique (ChT)
TF plane. Both the modulated window of the STFT and the                               is applied to extract some useful information in the second stage
wavelet of the wavelet transform may be considered as ‘portions                       of the proposed DPA.
of waves’. Similarly, chirplet may be considered as ‘portions of
chirps’. The mother chirplets are generated by different windowing
function, much like the mother wavelet of wavelet theory. The                         3.1   Division of zones on BRC plane
family of Gaussian chirplet is given by the harmonic oscillation
                                                                                      The first stage of the proposed DPA works based on the BRC with
(wave) with a linear frequency modulation chirp
                                                                                      dual slopes whose operation is based on two quantities, i.e. ID and
                                                                                      IB. The ID is the difference between CT secondary current of high
                                  1                  2 j2p[c(t−t)2 +fc (t−t)]
             gt, fc , s, c (t) = √ e−(1/2)(t−t/s) e                         (1)   voltage (HV) and low voltage (LV) sides of the power transformer
                                s 2p                                                  in common base value. The IB is the average current flowing
                                                                                      through the power transformer [25, 26].
where t, fc, σ and c are the time-shift, centre-frequency, window                        The BRC plane is divided as three zones: namely, no-trip zone, HS
spread and chirp rate, respectively. The continuous ChT may be                        zone and vulnerable zone as shown in Fig. 2b. The no-trip zone
formulated as an inner product of the signal with the Gaussian                        extends its periphery underneath the slope-1 and slope-2. Most of
chirplet functions as follows                                                         the CT saturated cases will be plunged into this zone. The worst
                                                                                      case of CT saturation due to high remanent flux may enter into the
                                         1                                           vulnerable zone. The vulnerable zone covers a major part of the
                          Ct, fc , c =        x(t)gt∗, fc , s, c (t) dt         (2)   tripping region of the BRC which includes the cases of the inrush,
                                         −1
                                                                                      major CT saturation and minor and moderate internal faults.
                                                                                      Therefore, it requires an accurate discriminating algorithm to avoid
From (2), it can be understood that ChT is an extension of the Gabor                  maloperation. Hence, the ChT technique is applied to ID signal for
transform, STFT and continuous wavelet transform. The                                 accurate discrimination in the second stage of the proposed DPA.
time-shifting parameter ‘t’ is responsible for shifting the window                       In fact, the HS zone occupies the sliced area of the upper part of
along with a time axis. Here, ‘fc’ is the centre-frequency operator                   tripping region on the BRC plane which covers the area of severe
to shift frequency. Here, ‘σ’ determines the window width                             faults. The required current for HS operation (IHO) is having a
corresponding to the frequency band. The chirp rate parameter ‘c’                     constant HS threshold (IHS) till IR2 and follows the 100% slope
causes a rotation of each cell on the TF plane as well as their                       (HS-slope) with respect to IB. Here, the HS-slope ensures that no
shear along the frequency axis (Fig. 1) [23].                                         CT saturation current enters into the HS zone.
   The discrete version of the ChT (2) is given by [24]
                       
                       M −1
                                                1      −(1/2)(((M /2)−m)/s)
                                                                            2         3.2   Chirplet-based differential protection algorithm
        C[n, k, l] =        x[n − m] ∗   √ e
                       m=0                    2s p                                    The second stage of the proposed DPA uses the chirplet-based
                                                                     
                                                                                      differential protection algorithm (CDPA). Applying ChT involves
                       × ej2p (l/L)dmax ((M /2)−m )+((k((M /2)−m))/K )
                                                  2
                                                                                (3)   two steps: (i) selection of the ChT parameters such as time-shift,
                                                                                      centre-frequency and chirp rate and (ii) decomposition of a signal
where n, k and l are the time, frequency and chirp rate indices,                      into a sum of weighted chirps.
respectively. K is the number of frequencies and ‘k’ is the                              All the chirplet parameters are not fully independent to each other.
frequency bin index. The chirp rate index ‘l’ is ranging from 0 to                    Therefore, the selection process is carried out in a sequential manner
L. The discrete smoothing window has M points.                                        with respect to other parameters. The centre-frequency translation
                                                                                      parameter for the kth level ‘fck ’ is chosen so that it is possible to
                                                                                      cover the Fourier domain of interest with an appropriate
3     Proposed methodology                                                            resolution. When the frequency domain of interest is wide, it can
                                                                                      be explored in a logarithmic (log 10) or dyadic (log 2) basis in
The proposed DPA is implemented in two stages as shown in                             order to reduce computational effort. Here, the signal is sampled at
Fig. 2a. In the first stage, the traditional dual slope biased restraint               the rate of 1600 Hz and thereby the maximum frequency of the
characteristic (BRC) is implemented with the division of zones.                       sampled signal will be 800 Hz according to the Nyquist sampling
IET Gener. Transm. Distrib., 2016, Vol. 10, Iss. 10, pp. 2520–2530
& The Institution of Engineering and Technology 2016                                                                                                   2521
                                                                       consecutive centre-frequencies. Therefore, each centre-frequency
                                                                       will have its own distinct chirp rate. That is, the first sample
                                                                       instant will have fck as the instantaneous frequency and the Mth
                                                                       sample will have fck+1 as the instantaneous frequency. For
                                                                       example, the chirp rate of the fourth level will have values
                                                                       between 0 and 3.125 in order to vary the instantaneous frequency
                                                                       from 50 to 100 Hz with respect to the sampling instant. The
                                                                       choice of the chirp rate vector size depends on the trade-off
                                                                       between accuracy and computation burden. Here, the size of the
                                                                       chirp rate vector (vk) is chosen as five. Therefore, the chirp rate
                                                                       vectors for the four levels are given as follows
                                                                                                             L 
                                                                                                              C [n, k, l]
                                                                                                   mC[n,
                                                                                                     k] =                                  (4)
                                                                                                              l=1
                                                                                                                     L
                                                                                                             
                                                                                                             K
                                                                                                               mC[n,
                                                                                                                 k]
                                                                                                   mC[n]
                                                                                                        =                                  (5)
                                                                                                             k=1
                                                                                                                    K
                                                                                              
                                                                                              
         K                  	2
                                                                                                                                
                                                                                              
    1 
                                                                                    sC[n]
                                                                                           =               m      − mC[n]
                                                                                                                                           (6)
                                                                                                 K − 1 k=1 C[n, k]
                                                                       It should be noted that the value of z-score of the second, third and
                                                                       fourth (fundamental) level NEs are used as a key factor to
Fig. 2 Proposed DPA implementation                                     discriminate the internal faults from other disturbances. It is
a Flowchart                                                            obvious that the domains of internal fault, inrush current and CT
b Division of zones on BRC plane                                       saturation will have its own distinct characteristics with respect to
c Gaussian energy distribution curve                                   the chirp rate. These characteristics can be deciphered from the
                                                                       distribution of z-scores of each level on the Gaussian curve as in
                                                                       Fig. 2c.
criteria. Moreover, the frequency spectrum of power transformer           The Gaussian curve is divided into two regions with one region
transient signals will have the useful information up to fifth          enveloping half energy bandwidth (HEBW), i.e. (0 dB ≥ mC[n,    k] ≥
harmonic. Therefore, ChT centre-frequency is chosen in a dyadic        −3 dB) and other lies outside of HEBW, i.e. (mC[n,     k] < −3 dB).
base for four levels as 400, 200, 100 and 50 Hz.
                                                                       The HEBW is calculated by the following equation given in (8)
   The time-shift ‘t’ describes the position of the chirplet. It is
mainly controlled by the time interval of interest and the sampling                                           √
rate of the signal. Time-shift has been chosen in such a way that it                          HEBW = sC[n]
                                                                                                          · 2 2 ln 2                       (8)
has an equal volume on TF plane.
   The dimensionless parameter, chirp rate ‘c’ allows linear           The pseudo-code for the proposed DPA is given below (see Fig. 3).
frequency modulation and shaping of each cell on the TF plane.            The NE during internal fault highly concentrates on the
Its value permits to calculate the frequency range of the chirp        fourth-level centre-frequency ‘fc4 ’, particularly on the zero chirp
around its centre-frequency ‘fck ’ within the time boundaries          rate. The energy level decreases along the chirp rate from the zero
imposed by σ. Since the centre-frequency is chosen as a dyadic         chirp rate. Since the energy distribution during the internal fault
base, the frequency translation has distinct translation between       highly concentrates on fc4 , the mC[n]
                                                                                                             will be far away from mC[n,
                                                                                                                                       4] .
                                                                       IET Gener. Transm. Distrib., 2016, Vol. 10, Iss. 10, pp. 2520–2530
2522                                                                            & The Institution of Engineering and Technology 2016
                                                                          Fig. 4 Single line schematic diagram of PTM-1
IET Gener. Transm. Distrib., 2016, Vol. 10, Iss. 10, pp. 2520–2530
& The Institution of Engineering and Technology 2016                                                                                      2523
Fig. 5 Internal fault case
a ID waveform
b ID trajectories
c NE distribution on Gaussian curve during MIF
algorithm. A cross-country fault is one where there are two faults        PTM-1 and PTM-2 is shown in Fig. 5a. The three-phase SIF on
affecting the same circuit, but in different locations and possibly       the LV terminal of the power transformer with a fault resistance
involving different phases [31]. The simulation is carried out by         Rf = 0.5 Ω has ID ≥ IHS (6.0 pu) and IB < 3.0 pu. Since ID falls on
creating an external fault which causes an internal fault such that       the HS zone, the trip command is enabled in the first stage of the
both external and internal exist.                                         algorithm.
                                                                             Also, the single-phase MIF (at 80% winding from phase end) has
                                                                          ID < IHO and ID ≥ IDO. Since ID falls on the vulnerable zone, the
5      Results and discussion                                             second stage of the DPA is enabled. The trajectories (starting with a
                                                                          diamond head and ending with a round head) of ID for both PTM-1
The validation of the proposed DPA is carried out for individual events   and PTM-2 are plotted in the BRC plane and are shown in Fig. 5b.
of internal faults, inrush currents, CT saturations and occurrence of        The resultant of the CDPA gives the mean of NE for three levels:
the above multiple events on PTM-1, PTM-2 and PATM.                       mC[n,
                                                                             2] , mC[n,
                                                                                      3] and mC[n,
                                                                                                   4] which are shown in Fig. 5c. Here, the
                                                                          z-score of mC[n,
                                                                                          4] always falls outside HEBW and z-scores of
5.1    Internal fault                                                     mC[n,
                                                                             3] and mC[n,
                                                                                          2] lie on the negative side of HEBW. Even though
                                                                          the current trajectories of PTM-1 and PTM-2 follow different
Depending on the magnitude of the internal fault currents, ID may         paths, the energy distributions on the Gaussian curve remains in
fall either on vulnerable or HS zone of the BRC plane. Therefore,         the same region. Therefore, it is obvious that the change in the
two typical cases of internal faults: namely, severe internal fault       z-score is independent of the fault current magnitude and
(SIF) and minor internal fault (MIF) are illustrated to validate          represents explicitly the waveform characteristics. Similarly, the
tripping decision for HS zone and vulnerable zone, respectively.          proposed DPA is able to successfully discriminate various cases of
The ID obtained during the simulation of the SIF and MIF for              internal faults as discussed in Section 4.2.
                                                                          IET Gener. Transm. Distrib., 2016, Vol. 10, Iss. 10, pp. 2520–2530
2524                                                                               & The Institution of Engineering and Technology 2016
Fig. 6 Inrush current case
a ID waveform
b ID trajectories
c NE distribution on Gaussian curve
5.2    Inrush                                                          Though, the maximum inrush current of PTM-2 is less than the
                                                                       PTM-1, the NE distribution on the Gaussian curve remains same.
The switching on the power transformer from the HV side (primary       This characteristic of the proposed DPA makes the relay stable
of power transformer) before closing the LV breaker is an usual        during inrush. In addition, the proposed DPA is validated with the
practice in a real-time power system operation. While energising       various cases of the inrush currents as discussed in Section 4.2.
the power transformer, the inrush current will always fall on the      However, the conventional method issue the tripping command
vulnerable zone of the BRC plane. Here, a typical case of the          when the SHR fall below the second-harmonic setting at 0.13 and
inrush current is illustrated with a remanent flux of ±80% and a        0.14 s in PTM-1 and PTM-2, respectively.
switching angle of 30°. The ID during inrush currents for PTM-1
and PTM-2 are shown in Fig. 6a.
   The inrush current magnitude in the case of low remanent flux will
be always less than the case of high remanent flux. However, the        5.3   Internal fault with inrush
operating zones on the BRC plane remain same (see Fig. 6b) and
the current trajectories lie on the single end feed line of the        When the power transformer is energised with an SIF, the ID is
vulnerable zone. Since ID lies on the vulnerable zone, the CDPA        highly dominated by the internal fault current than the inrush
is enabled.                                                            current. Fig. 7a shows that the ID during inrush with internal fault
   The resultant of the CDPA gives the mean of NE for three levels,    for PTM-1 and PTM-2. The current trajectory of ID lies on the
mC[n,
   2] , mC[n,
            3] and mC[n,
                         4] which are shown in Fig. 6c. Here, the     vulnerable zone and enables the CDPA. The resultant of the
z-score of mC[n,
              4] always falls within the positive side and near to
                                                                       CDPA gives the mean of NE for three levels: mC[n,  2] , mC[n,
                                                                                                                                  3] and
IET Gener. Transm. Distrib., 2016, Vol. 10, Iss. 10, pp. 2520–2530
& The Institution of Engineering and Technology 2016                                                                                  2525
Fig. 7 Internal fault with inrush case
a ID waveform
b NE distribution on Gaussian curve
CT saturation (minor and major levels) may occur due to SIF and       When the power transformer is energised with an SIF, CT saturation
external fault on the power transformer, which produces the           may occur. As a result of CT saturation, the ID waveform is distorted
transient ID in the protection relay. The distorted CT secondary      as shown in Fig. 10. The root mean square value of the ID forces the
current (I1) during CT saturation is shown in Fig. 8a. In case of     current trajectory to fall on the HS zone. Therefore, the trip
CT saturation due to SIF, IB will be low, and therefore ID enters     command is enabled at 0.105 ms in the first stage of the algorithm.
into the HS zone enabling the tripping condition. However, CT
saturation during SEF may lead ID to fall on either vulnerable or
non-trip zone. During SEF, the minor level of CT saturation will      5.7   Cross-country fault
fall on the non-trip zone. However, the major CT saturation will
not fall on the HS zone, since HS zone adopts HS-slope in the         When a cross-country fault occurs in a power transformer, CT
area of CT saturation, i.e. IB ≥ IR2.To illustrate, a typical CT      saturation leads to spurious and distorted ID waveform during
saturation case due to SEF with 80% remanent flux and 5 Ω              external and internal faults, respectively. Fig. 11a shows the ID
burden is considered. The trajectories of ID for PTM-1 and            during the cross-country fault with CT saturation. The external and
PTM-2 during major CT saturation pass through the vulnerable          internal faults occur at 0.1 and 0.2 s, respectively.
zone, but do not enter into the HS zone (see Fig. 8b) and                The resultant of the CDPA gives the mean of NE for three levels:
enabling the CDPA.                                                    mC[n,
                                                                         2] , mC[n,
                                                                                  3] and mC[n,
                                                                                               4] which are shown in Fig. 11b during
   The resultant of the CDPA gives the mean of NE for three           internal fault consequence event of external fault. Here, the
levels: mC[n,
           2] , mC[n,
                   3] and mC[n,
                                4] which are shown in Fig. 8c.       z-score of mC[n,
                                                                                     4] always falls outside HEBW and the z-scores of
Here, the z-scores of mC[n, 2] and mC[n,
                                         4] always fall on the
                                                                      mC[n,
                                                                         3] and mC[n,
                                                                                      2] lie on the negative side of HEBW during the
positive side and negative side of HEBW, respectively.                internal fault condition. Since the trip conditions are satisfied, a
Similarly, the z-score of mC[n,
                             3] lie on both sides of HEBW, i.e.      trip command is enabled during the internal fault. However,
around mC[n]
           . Therefore, the trip conditions are not satisfied and     during the external fault, the z-scores of mC[n,     2] , mC[n,
                                                                                                                                   3] and
maloperation is prevented.                                            mC[n,
                                                                         4] do not satisfy the trip conditions. Therefore, the trip
                                                                      command is prevented during the external fault. It should be
                                                                      noted that the conventional method initiates false tripping for
                                                                      PTM-2 at 0.12 ms.
5.5    Inrush with CT saturation
                                                                      5.8   Performance comparison
During energisation of the power transformer, the low-rated
high-burden CT may get saturated due to inrush current. It causes     The proposed DPA is compared with the conventional
the distortion in CT response, thereby increasing the magnitude of    second-harmonic method in terms of trip time and accuracy. The
ID in irregular form as shown in Fig. 9a. The waveform resembles      trip time results in various cases of internal faults as given in
the characteristic of both inrush and CT saturation currents. This    Table 1. The conventional method generally introduces a time
phenomenon leads the current trajectory to fall on the vulnerable     delay greater than one cycle period due to the presence of the
zone enabling the CDPA.                                               second-harmonic component during the fault inception [6].
   The resultant of the CDPA gives the mean of NE for three levels:      In the proposed DPA, the trip time for the HS and vulnerable
mC[n,
   2] , mC[n,
            3] and mC[n,
                         4] which are shown in Fig. 9b. Here, the    zones varies between 5 to 10 and 10 to 15 ms, respectively. It
z-scores of mC[n,
                3] and mC[n,
                           4] always fall on the positive side and   should be noted that the overall trip time of the proposed method
negative side of HEBW, respectively. Similarly, the z-score of        will not be delayed >15 ms even in the worst case of an MIF and
mC[n,
   2] lies on both sides of HEBW. Therefore, the trip conditions     internal fault with inrush current (Fig. 7). It is evident that the
are not satisfied preventing maloperation. It should be noted that     proposed DPA has a faster response time than the conventional
the conventional method initiates false tripping for PTM-1 and        method. The computational burden of the algorithms is also
PTM-2 at 0.12 and 0.11 ms, respectively.                              evaluated in terms of time taken to estimate their respective output
                                                                      IET Gener. Transm. Distrib., 2016, Vol. 10, Iss. 10, pp. 2520–2530
2526                                                                           & The Institution of Engineering and Technology 2016
Fig. 8 CT saturation due to external fault case
a I1 waveform
b ID trajectories
c NE distribution on Gaussian curve
coefficients. The time taken to process a one window sample for the   than the conventional method, the trip time and accuracy of the
proposed and conventional methods is 2 and 0.1 ms, respectively.     proposed method is found to be advantageous. The evaluation of
Though the computation time of the proposed method is greater        the computation time is carried out with Intel core i7260 central
IET Gener. Transm. Distrib., 2016, Vol. 10, Iss. 10, pp. 2520–2530
& The Institution of Engineering and Technology 2016                                                                             2527
Fig. 10 ID waveform during inrush with internal fault and CT saturation
processing unit at 3.40 GHz, 3.23 GB of random access memory and            (TP), true negative, false positive and false negative is carried out.
MATLAB 2011b.                                                               The accuracy (% μ) is defined as the ratio of TP to the total
   The accuracy of the proposed DPA and the conventional method             number of cases. It is observed from Table 2 that the proposed
is presented in Table 2. The accuracy of the algorithm is evaluated         DPA for all the cases of PTM-1, PTM-2 and PATM gives a better
through confusion matrix analysis [32]. Here, more detailed                 performance when compared with the conventional method.
analysis of the accuracy of an algorithm based on the true positive         Moreover, the inrush current and CT saturation cases are very
                                                                             IET Gener. Transm. Distrib., 2016, Vol. 10, Iss. 10, pp. 2520–2530
2528                                                                                  & The Institution of Engineering and Technology 2016
Table 2 Confusion matrix analysis
Cases                                                            Total cases                           Proposed DPA                               Conventional method
TP %μ TP %μ
internal fault                                            288         288          288       288        288         288         100        265          261         263       91.32
inrush current                                            96          96           96         96        96          96          100        76           75          77        79.17
internal fault with inrush                                48          48           48         48        48          48          100        41           40          42        85.41
CT saturation                                             40          40           40         38        39          39         96.67       31           30          30        77.5
inrush and CT saturation                                  48          48           48         47        46          47         97.22       39           40          38        81.25
internal fault with inrush and CT saturation              48          48           48         48        48          48          100        41           41          40        84.72
cross-country fault                                       32          32           32         32        32          32          100        27           28          26        84.37
total cases                                               600         600          600       587        587         588        99.55       520          515         516        86
prone for maloperation in the conventional method. However, the                                8 Ghunem, R.A., El-Shatshat, R., Ozgonenel, O.: ‘A novel selection algorithm of a
proposed DPA offers a promising accuracy of 99.55%.                                              wavelet-based transformer differential current features’, IEEE Trans. Power Deliv.,
                                                                                                 2014, 29, (3), pp. 1120–1126
   Generally, the conventional relays maloperate when ID has a low                             9 Perez, L.G., Flechsig, A.J., Meador, J.L., et al.: ‘Training an artificial neural
magnitude of the second-harmonic component in modern power                                       network to discriminate between magnetizing inrush and internal faults’, IEEE
transformers during energisation [6]. However, the proposed DPA                                  Trans. Power Deliv., 1994, 9, (1), pp. 434–441
discriminates the operating conditions based on the time-varying                              10 Tripathy, M., Maheshwari, R.P., Verma, H.K.: ‘Probabilistic neural-network-based
frequency characteristics irrespective of magnitude of the                                       protection of power transformer’, IET Electr. Power Appl., 2007, 1, (5),
                                                                                                 pp. 793–798
second-harmonic component. Also, the CDPA discriminates the                                   11 Shin, M.C., Park, C.W., Kim, J.H.: ‘Fuzzy logic-based for large power transformer
disturbances with respect to energy distribution on the Gaussian                                 protection’, IEEE Trans. Power Deliv., 2003, 18, (3), pp. 718–724
curve, which is not influenced by the magnitude of ID. Moreover,                               12 Barbosa, D., Netto, U.C., Coury, D.V., et al.: ‘Power transformer differential
the proposed DPA does not require any threshold settings for its                                 protection based on Clarke’s transform and fuzzy systems’, IEEE Trans. Power
discrimination process. Therefore, the proposed DPA exhibits the                                 Deliv., 2011, 26, (2), pp. 1212–1220
                                                                                              13 Zhang, W., Tan, Q., Miao, S., et al.: ‘Self-adaptive transformer differential
system independent feature.                                                                      protection’, IET Gener. Transm. Distrib., 2013, 7, (1), pp. 61–68
                                                                                              14 Dashti, H., Sanaye-Pasand, M.: ‘Power transformer protection using a multiregion
                                                                                                 adaptive differential relay’, IEEE Trans. Power Deliv., 2014, 29, (2), pp. 777–785
                                                                                              15 Pan, C., Chen, W., Yun, Y.: ‘Fault diagnostic method of power transformers based
6     Conclusion                                                                                 on hybrid genetic algorithm evolving wavelet neural network’, IET Electr. Power
                                                                                                 Appl., 2008, 2, (1), pp. 71–76
                                                                                              16 Barbosa, D., Coury, D.V., Oleskovicz, M.: ‘New approach for power transformer
This paper concludes that the proposed DPA is a system independent                               protection based on intelligent hybrid systems’, IET Gener. Transm. Distrib.,
approach for detecting the power transformer internal faults without                             2012, 6, (10), pp. 1009–1018
any maloperation. This algorithm possesses the advantages of both                             17 Shah, A.M., Bhalja, B.R.: ‘Discrimination between internal faults and other
BRCs in the first stage and ChT technique in the second stage.                                    disturbances in transformer using the support vector machine-based protection
                                                                                                 scheme’, IEEE Trans. Power Deliv., 2013, 28, (3), pp. 1508–1515
The BRC improves the speed of operation in the HS zone and                                    18 Baoming, G., Almeida, A.T., Qionglin, Z., et al.: ‘An equivalent instantaneous
non-trip zone, whereas the second stage of the proposed DPA                                      inductance-based technique for discrimination between inrush current and
ensures the discrimination accuracy based on time-varying                                        internal faults in power transformers’, IEEE Trans. Power Deliv., 2005, 20, (4),
frequency characteristics. Since the operating conditions of power                               pp. 2473–2482
transformers have its own distinct characteristics, with respect to                           19 Tripathy, M., Maheshwari, R.P., Verma, H.K.: ‘Advances in transformer
                                                                                                 protection: a review’, Electr. Power Compon. Syst., 2005, 33, (11), pp. 1203–1209
the chirplet parameters irrespective of the current magnitude, the                            20 Peng, Z.K., Meng, G., Chu, F.L., et al.: ‘Polynomial chirplet transform with
proposed DPA is robust. The simulation studies show that the                                     application to instantaneous frequency estimation’, IEEE Trans. Instrum. Meas.,
proposed algorithm has high sensitivity toward MIFs, faster                                      2011, 60, (9), pp. 3222–3229
response during SIFs and good stability during CT saturation and                              21 Bardainne, T., Gaillot, P., Dubos-Sall, N., et al.: ‘Characterization of seismic
inrush currents. In view of the fact that ChT is capable of                                      waveforms and classification of seismic events using chirplet atomic
                                                                                                 decomposition. Example from the Lacq gas field (Western Pyrenees, France)’,
analysing the power transformer transient signals, the proposed                                  Geophys. J. Int., 2006, 166, (2), pp. 699–718
algorithm can be effectively implemented for a wide range of                                  22 Mann, S., Haykin, S.: ‘The chirplet transform: physical considerations’, IEEE
power transformer ratings.                                                                       Trans. Signal Process., 1995, 43, (11), pp. 2745–2761
                                                                                              23 Angrisani, L., D’Arco, M.: ‘A measurement method based on a modified version of
                                                                                                 the chirplet transform for instantaneous frequency estimation’, IEEE Trans.
                                                                                                 Instrum. Meas., 2002, 51, (4), pp. 704–711
                                                                                              24 Millioz, F., Davies, M.: ‘Sparse detection in the chirplet transform: application to
7     References                                                                                 FMCW radar signals’, IEEE Trans. Signal Process., 2012, 60, (6), pp. 2800–2813
                                                                                              25 IEEE Std. C37.91™-2008: ‘IEEE guide for protecting power transformers’, 2008
 1 Guzman, A., Zocholl, S., Benmouyal, G., et al.: ‘A current based solution for              26 ‘Transformer Protection RET650, Application Manual, 1MRK 504 134-UEN,
   transformer differential protection – part I: problem statement’, IEEE Trans.                 Product version 1.3’, (ABB Inc., 2012.)
   Power Deliv., 2001, 16, (4), pp. 485–491                                                   27 Brandwajn, V., Dommel, H.W., Dommel, I.I.: ‘Matrix representation of
 2 Sonnemann, W.K., Wagner, C.L., Rockefeller, G.D.: ‘Magnetizing inrush                         three-phase N-winding transformers for steady-state and transient studies’, IEEE
   phenomena in transformer banks’, AIEE Trans., 1958, 77, (III), pp. 884–892
                                                                                                 Trans. Power Appl. Syst., 1982, 101, (6), pp. 1369–1378
 3 Guzman, A., Zocholl, S., Benmouyal, G., et al.: ‘A current based solution for
                                                                                              28 Bastard, P., Bertrand, P., Meunier, M.: ‘A transformer model for winding fault
   transformer differential protection – part II: relay description and evaluation’,
                                                                                                 studies’, IEEE Trans. Power Deliv., 1994, 9, (2), pp. 690–699
   IEEE Trans. Power Deliv., 2002, 17, (4), pp. 485–491
 4 Gangadharan, P.K., Sidhu, T.S., Klimek, A.: ‘Influence of current transformer               29 Chiesa, N., Mork, B.A., Hoidalen, H.K.: ‘Transformer model for inrush current
   saturation on line current differential protection algorithms’, IET Gener. Transm.            calculations: simulations, measurements and sensitivity analysis’, IEEE Trans.
   Distrib., 2007, 1, (2), pp. 270–277                                                           Power Deliv., 2010, 25, (4), pp. 2599–2608
 5 Sharp, R.L., Glassburn, W.E.: ‘A transformer differential relay with                       30 Lucas, J.R., McLaren, P.G., Keerthipala, W.W.L., et al.: ‘Improved simulation
   second-harmonic restraint’, AIEE Trans., 1958, 77, (III), pp. 913–918                         models for current and voltage transformers in relay studies’, IEEE Trans. Power
 6 Liu, P., Malik, O.P., Chen, D., et al.: ‘Improved operation of differential protection        Deliv., 1992, 7, (1), pp. 152–159
   of power transformers for internal faults’, IEEE Trans. Power Del., 1992, 17, (4),         31 Lin, X., Weng, H., Wang, B.: ‘Identification of cross-country fault of power
   pp. 1912–1919                                                                                 transformer for fast unblocking of differential protection’, IEEE Trans. Power
 7 Gaouda, A.M., Salama, M.M.A.: ‘DSP wavelet-based tool for monitoring                          Deliv., 2009, 24, (3), pp. 1079–1086
   transformer inrush currents and internal faults’, IEEE Trans. Power Deliv., 2010,          32 Ting, K.M.: ‘Confusion matrix’, in Sammut, C., Webb, G.I. (Eds.): ‘Encyclopedia
   25, (3), pp. 1258–1268                                                                        of Machine Learning’ (Springer, New York, NY, USA, 2010), p. 209
IET Gener. Transm. Distrib., 2016, Vol. 10, Iss. 10, pp. 2520–2530
& The Institution of Engineering and Technology 2016                                                                                                                          2529
8      Appendix                                          PTM-2: 50 MVA, 132/12 kV, 50 Hz, YNd1, %Z = 35.64%,
                                                         magnetising current = 0.14%.
PTM-1: 40 MVA, 132/11.5 kV, 50 Hz, Dyn11, %Z = 13.56%,   PATM: 100 MVA, 230/110/11 kV, 50 Hz, YNynd1, %Z = 11.41%,
magnetising current = 0.10%.                             magnetising current = 0.1%.
                                                         IET Gener. Transm. Distrib., 2016, Vol. 10, Iss. 10, pp. 2520–2530
2530                                                              & The Institution of Engineering and Technology 2016