SPECIFICATION DATA
Infiniti™ Gas Transmitter
                                                                                                                           U9500
                                                                                                      Available gas sensors include:
                                                                                                               Catalytic Combustible
                                                                                                            PointWatch Hydrocarbon
                                                                                                             Hydrogen Sulfide (H2S)
                                                                                                                         NTMOS H2S
                                                                                                              Carbon Monoxide (CO)
                                                                                                                 Sulfur Dioxide (SO2)
                                                                                                              Nitrogen Dioxide (NO2)
                                                                                                                         Chlorine (Cl)
                                                                                                                         Oxygen (O2)
                         A PPL I C AT I O N S                                          B E N E FI TS A N D FE AT U R ES
The Model U9500 Infiniti™ Transmitter is designed to be used         Features
with Det-Tronics gas detectors for continuous monitoring of          •	 User-friendly setup
dangerous gases.
                                                                     •	 Non-intrusive calibration using the internal magnetic reed
Gas concentrations are displayed on an alphanumeric display in          switch, or an externally located pushbutton (not included)
%LFL, ppm, or %Vol, depending on the sensor. The transmitter         •	 Automatic fault diagnostics and annunciation
provides a 4 to 20 milliampere output signal that corresponds
to the detected gas concentration. An optional relay package is      •	 Sensor sensitivity and end of sensor life indication
available.                                                           •	 Optional relay package provides three alarm relays (high, low,
                                                                        and auxiliary) and one fault relay.
Each Infiniti transmitter is used with one sensor. The sensor may
be mounted directly to the explosion-proof Infiniti housing, or it   Application Flexibility
may be located remotely using a sensor separation kit.               •	 Compatible with a wide range of Det-Tronics sensors
Typical applications include:                                        •	 Field adjustable programming options include:
                                                                     	     Operating range (toxic sensors only)
—	Confined spaces where gas/vapor leaks can concentrate to           	     Alarm setpoints
  explosive or toxic levels or where oxygen levels need to be        	     Calibration gas concentration
  monitored (enclosed processing areas).                             	     Relay operation latching or non-latching, energized or
—	Known high risk leak locations (points within processing                 de‑energized coils (relay package optional)
  areas, compressor buildings).                                      	     Automatic or manual calibration
—	General open area coverage (storage areas).                        	     Current loop adjustment.
3.1	        © Detector Electronics Corporation 2007	                                               3/07	                        90-1099
                                                                                                       SPECIFICATIONS
Input Voltage	                                              24 Vdc. Operating range is 16 to 32 Vdc including       Relays (Optional)	   Three Alarm relays: 	 Form C, 5 amperes at 30
                                                               ripple.                                                                                         Vdc. Selectable normally
                                                                                                                                                               energized or de-energized as
Power Consumption with Sensor                                                                                                                                  a group. Low, auxiliary and
	 (Infiniti with alarm relays and sensor connected, 24 Vdc input voltage.)                                                                                     high alarm relays selectable
	 Toxic and Oxygen Models: 	                                                        3 watts nominal,                                                           as a group for latching or
		                                                                                  5 watts maximum.                                                           non-latching contacts.
	 Combustible Gas Model: 	                                                          4.6 watts nominal,              		                   One Fault relay: 		    Form C, 5 amperes at 30
		                                                                                  6.5 watts maximum.                                                          Vdc. Normally energized for
	 PIR9400 PointWatch Model: 	                                                       8.1 watts nominal,                                                          no fault condition with power
		                                                                                  10.1 watts maximum.                                                         applied to device.
	 PIRECL Eclipse Model: 	                                                           7.6 watts nominal,
		                                                                                  12.4 watts maximum.             Certifications	      FM/CSA:	       Explosion-proof for
                                                                                                                                                        Class I, Div. 1, Groups B, C, and D.
Current Output 	                                            Linear 4 to 20 mA output.                               			                                 Dust ignition-proof for
		                                                          Maximum loop resistance: 600 ohms.                                                          Class II/III, Div. 1, Groups E, F, and G.
		                                                          Selectable isolated or non-isolated operation.          		                   	              Non-incendive for
		                                                          Factory-set 2.0 mA output indicates unit is in                                              Class I, Div. 2, Groups A, B, C,
                                                               Calibration mode (field adjustable).                                                     and D (T4).
                                                                                                                                                        Class II/III, Div. 2, Groups F and
		                                                          Less than 1.0 mA output indicates fault condition.
                                                                                                                                                        G (T4A).
                                                                                                                    			                                 NEMA/Type 4X.
Display	                                                    Eight character alphanumeric display indicates
                                                            power on, gas concentration, alarm and fault            			                                 Performance verified per
                                                            conditions. It also enables field adjustment of alarm                                       FM 6320 and FM 6341;
                                                            setpoints, calibration gas concentration, full scale                                        CSA C22.2 #152.
                                                            measurement range and gas type to be detected.
                                                                                                                    	 	 CENELEC: 	     0539 II 2 G
                                                                                                                    			            EEx d IIC T5-T6
Detection Range 	                                           Hydrocarbon: 	       0 to 100% LFL for PointWatch
                                                                                                                                   DEMKO 02 ATEX 131327 X
                                                                                 IR detector. (FM/CSA verified)
                                                                                                                    			            T6 (Tamb = –55°C to +60°C),
	                                                           Calalytic: 	         0 to 100% LFL.
                                                                                                                                   T5 (Tamb = –55°C to +70°C),
	                                                           H2S (EC sensor): 	   0 to 100 ppm, 0 to 20 ppm,                        IP66.
                                                                                 0 to 50 ppm. (FM/CSA verified)
	                                                           H2S (NTMOS sensor):	0 to 100 ppm                        	 	                  RUSSIAN:	      1Ex d IIC T6
                                                                                                                                                        (Tamb = –60°C to +50°C),
	                                                           Chlorine: 	          0 to 10 ppm.
                                                                                                                                                        T5 (Tamb = –60°C to +65°C),
	                                                           Oxygen: 	            0 to 25% by volume.                                                    T4 (Tamb = –60°C to +75°C).
	                                                           Carbon Monoxide:	 0 to 100 ppm, 0 to 500 ppm,
                                                                              0 to 1000 ppm.                        Shipping Weight 	    Aluminum:			       4.15 pounds (1.88 kilograms).
	                                                           Nitrogen Dioxide: 	 0 to 20 ppm.                        		                   Stainless Steel:	 10.5 pounds (4.76 kilograms).
	                                                           Sulfur Dioxide: 	    0 to 100 ppm.
                                                                                                                    Enclosure	           Epoxy coated 356 aluminum or 316 stainless steel
Temperature Range 	                                         Operating:		   –40°F to +167°F (–40°C to +75°C).                             NEMA Type 4X and IP66.
		                                                          Storage:		     –67°F to +185°F (–55°C to +85°C).
                                                                                                                    Dimensions 	         Height: 	 6.57 inches (16.7 cm)
Wiring 	                                                    18 AWG minimum is recommended for power                 		                   Base: 	     5.86 inches (14.9 cm) by
                                                            wiring to the transmitter. Larger diameter wire may                          	           4.7 inches (11.9 cm)
                                                            be required to maintain a minimum of 16 Vdc at the
                                                            transmitter for all operating conditions. Maximum       		                   Aluminum models: 3/4" NPT or M20/M25 threads.
                                                            wire size for terminals is 12 AWG.                      		                   Stainless steel models: 3/4" NPT or M20 threads.
            IS
               TE
                 RED
                            BY UL
                                         AN
                                               D
                                                         Detector Electronics Corporation
        G
                                                BS
                                                         6901 West 110th Street • Minneapolis, Minnesota 55438 USA
     RE
     ISO 9001
                                                         Operator: (952) 941-5665 or (800) 765-FIRE