Abb
Abb
                                                Basic standards
           (definitions of personal protection, calculation and test procedures, assessment bases)
	             IEC 60364-4-41	                    IEC / TR 60664-2-1	                 IEC 60529
	    Protection against electric shock	      Insulation co-ordination	    Test devices and test procedures
    Prepared by:
    Matthias Kratzke
    Jürgen Dufner
     –	   Personal protection
     –	   Property protection
     –	   High operational and functional safety
     –	   Ease of use
     Health of the individual is regarded as fundamental     duced a defective product to the market and that
                                                                                                                                  1
     asset within the economic space of the European         there is causality between the defective product,
     Union.                                                  the violation of legal rights and the damage. The
                                                             question whether a manufacturer is responsible for
     The EU-Commission has therefore made it its goal        product defects puts an unacceptable burden of
     to elaborate directives, which are then transposed      proof on the injured party.
     into national law by Member States.
                                                             This is the reason why a reversed burden of proof
     Thus, the low voltage directive is implemented in       is applied here. Meaning that the manufacturer has
     the German Product Safety Act.                          to prove that the product was free from defects
                                                             in design, workmanship and instructions upon
     Next to the German Product Safety Act, there is         marketing.
     the Product Liability Act which is designed to pro-
     tect the user in case of damages.
Builders
Builders
       System manufacturer
                                                                                          Builders
             The new standard describes three design verification processes for ASSEMBLIES and requires a
             routine verification for every marketed product.
             These processes are essentially implemented                                                    manufacturer will become original manufactur-
             by the original manufacturer. In case that the                                                 er for that alteration and will have to carry out
             ASSEMBLY manufacturer does not install an                                                      the design verification in accordance with the
             ASSEMBLY in compliance with the instructions                                                   described procedures.
             of the original manufacturer, the ASSEMBLY
                   IEC 61439
                                                                                                                ASSEMBLY
                                                                                                          Low-voltage ASSEMBLY
                                                                                                                                                Application of constructive
                                                                         Testing                   Calculation / measurement
                                                                                                                                                           rules
                     Original manufacturer
Routine verification
     The new standard does not only precisely define the responsibilities of
                                                                                                                                1
     the market participants, but also specifies the dimensions of low-voltage
     switchgear and controlgear ASSEMBLIES.
     In addition it presents the possibilities and limits for the market participants in
     order to guarantee to the user safe low-voltage switchgear and controlgear
     ASSEMBLIES.
     One important aspect emphasised in the IEC 61439 is the earthing system as
     this has important consequences for planing the electrical circuits.
         Installation and
      3 environmental conditions
                                                          Operating and
                                                     4 servicing
                                      L1         L1
                                      L2         L2
                                      L3         L3
                                      PEN        N
                                                 PE
                                            L1
                                            L2
                                            L3
                                            N
                                            PE
                                      L1              L1
                                      L2              L2
                                      L3              L3
                                      N               PE
TN system
      Benefits:                                  Fast shut-up in case of faults and/or Short-circuits, lowest risk to people
                                                 and property
      Disadvantages:                             High line and cabling overheads due to installed protective conductor,
                                                 every fault leads to system downtimes
      Preferred application:                     Power plants, public power supply and grids
      TT system
     –	 ensure basic protection (protection against direct contact) by basic insulation of the live parts or by
        covering or sheathing in line with ANNEX A and
     –	 and fault protection (protection against indirect contact) by protective equipotential bonding by the
        main earthing bar and automatic disconnection in case of faults, […]
     –	 ensure basic protection (protection against direct contact) by basic insulation and fault protection
        (protection against indirect contact) by an additional insulation
     	or
     –	 ensure basic protection and fault protection by a reinforced insulation between live parts and
        accessible parts.
     Protection classes
     Protection class I
     The protection target of protection class I is achieved by insulation of the live parts and
     connection of the accessible metal parts to the protective conductor.
     The protective conductor terminal is identified by ..
     P rotection class II
     The protection target of protection class II is achieved by double insulation.
     Protection class II is identified by ,.
     Overvoltage categories
     Category to describe overvoltages that might be generated by lightning or
     switching operations at the place of installation.
    Nominal values
                                                                                                                                   1
    … are defined in DIN 40200 and specify a suitable, rounded parameter value used to
    describe or to identify an element, a group or installation. (Example: a general information
    describing a motor: Nominal current 25 A/nominal voltage 400 V)
    Rated values
    … are defined as applicable parameter value at specific operating conditions which are
    defined by the manufacturer of a given component, group or installation.
    (Example: Rated current of 630 A of a fuse switch disconnector for fuse links according
    to DIN 43620 size 3 at a rated operational voltage of 690 V and a rated insulation voltage
    of 690 V.)
    … From below
    … From above
    … Single-core cable
    … Multi-core cable / number /section in mm²
     Rated voltage Un
                                                                                                                                  1
     ... is the highest stated nominal voltage of a system (AC voltage (effective) or DC voltage) to which the
     main circuits are designed.
     For multi-phase systems this is the voltage between the phase conductors.
     Rated frequency ƒn :
     ... is the frequency value stated by the ASSEMBLY manufacturer to which the ASSEMBLY is assigned
     and to which the operating conditions refer. NOTE: A number or a range of rated frequencies can be
     assigned to a circuit and be rated for AC or DC power.
     The limits are between 98 % and 102 % of the rated frequency.
     In practice, the usual rated frequency is 50 Hz.
     	
     Under 0 Hz (DC current), special switching devices with specific arc quenching systems are needed.
     Busbars can support higher loads.
Under 16 2/3 Hz the switching devices for 50 Hz have reduced switching capacities.
     A switching device's switching capacity is reduced at 400 Hz due to the shorter arc quenching time.
     Busbars can only support reduced loads due to the skin effect.
     The rated current for busbars under a rated frequency above 50 Hz is calculated by the following
     formula:
     In= rated current; Inf= rated current under a defined frequency; fn= rated frequency; fN= nominal
     frequency of the system to which the low voltage switchgear and controlgear ASSEMBLY is to be
     connected
     in the 3 s range the rated peak withstand current can be calculated using the same formula I²t, provided that the peak value does not exceed the
     rated peak withstand current).
         Installation and
      3 environmental conditions
                                                          Operating and
                                                     4 servicing
      1)
          ated peak withstand current IpK /
         R
         Rated short-time withstand current Icw of the busbar system or
      2)
         rated short-circuit current stated by the manufacturer Icp
         in case of the use of a protection by SCPD required by the manufacturer
      3)
         SCPD = short-circuit protective device
      The conductors in a panel (including the distribution busbar systems) between the main busbars
      and the supply side of functional units including the components of these units must be rated
      for the same reduced short-circuit load1) occurring at the outlet side2) of the short-circuit protec-
      tive device of this unit, provided that these connections are arranged in such a manner that no
      short-circuit between phases or between phase and earth is to be expected (see 8.6.4). […]
Bar connection
      Live conductors in an ASSEMBLY which are not protected by a short-circuit protective device
      (see 8.6.1 and 8.6.2) are to be selected and installed throughout the entire ASSEMBLY in such a
      manner that no short-circuit between phases or between phase and earth is to be expected.
      Conductor type examples and requirements are specified in Table 4. Non-protected live con-
      ductors selected and installed in compliance with Table 4 must not exceed a total length of 3 m
      between the main busbar and each associated SCPD.
max. 3 m
F = Functional unit
      Consumer / circuit       Information provided by the planner / customer                           Data to be derived from step 2 by
      types                                                                                             manufacturer
                               Number of circuits      Type of protective device   Distribution board   Circuit ratings          Type of protective
                                                                                   ratings
                                                                                                                                 device
                                                                                                        Rated Diversity Factor
                                                                                                        (RDF) = ________ %
      Distribution circuits
                                                       ___ fuse
      for downstream
      subdistribution boards                           ___ MCB
                                                       ___ MCCB
      Final circuits
                               Number of circuits      Type of the protective      Consumer ratings     Circuit ratings          Type of protective
                                                       conductor connection                                                      device
      Socket
                                                       ____ fuse                   _______ A            Inc = _____ A
                                                       ____ MCB
                                                       ____ Circuit breaker and
                                                       residual current device
      Ohmic load, heater
                                                       ____ fuse                   _______ kW           Inc = _____ A
                                                       ____ MCB
                                                       ____ MCCB
      Inductive consumer,
                                                       ___ fuse                    _______ kW           Inc = _____ A
      motor, direct
                                                       ____ MCB                    _______ cos 
                                                       ___ MCCB
      Inductive consumer,
                                                       ____ fuse                   _______ kW           Inc = _____ A
      motor, controlled
                                                       ____ MCB                    _______ cos 
                                                       ____ manufacturer's
                                                       description
         Installation and
      3 environmental conditions
                                                          Operating and
                                                     4 servicing
     Mechanical conditions	                                                                                                   1
     Electrical conditions 		
     Thermal conditions 		
     Climatic conditions 	
     Stationary ASSEMBLIES
     … Are ASSEMBLIES which are permanently installed to their position, e.g. on
        the floor or a wall, and which permanently fixed and operated.
     Movable ASSEMBLIES
     … Are ASSEMBLIES which can easily be moved from one place of installation
        to another.
     	
     IP code
                                                                                                                                                                          1
     The IP code identifies the degree of protection of enclosures and covers:
     -	 ingress of solid foreign bodies
     -	 against contact with hazardous parts
     -	 ingress of water
           Element                           Numeral or letter    Effect on the protection of the equipment       Effect on the protection of people
           First digit                                            Against ingress of solid foreign bodies         Against contact with hazardous parts
                                             0                    (no protection)                                 (no protection)
                                             1                    ≥ 50 mm diameter                                Back of the hand
                                             2                    ≥ 12.5 mm diameter                              Finger
                                             3                    ≥ 2.5 mm diameter                               Tool
                                             4                    ≥ 1 mm diameter                                 Wire
                                             5                    dust-protected                                  Wire
                                             6                    dusttight                                       Wire
           Second digit                                           Against harmful effects due to the ingress of
                                                                  water
                                             0                    (no protection)
                                             1                    Vertical dripping
                                             2                    Drops (15° tilt)
                                             3                    Spray water
                                             4                    Splashing of water
                                             5                    Water jets
                                             6                    Powerful water jets
                                             7                    Temporary immersion
                                             8                    Permanent immersion (1)
           Additional letter                                                                                      Against contact with hazardous parts
           (option)
                                             A                                                                    Back of hand
                                             B                                                                    Finger
                                             C                                                                    Tool
                                             D                                                                    Wire
           Complementary letter                                   Complementary information about
           (option)
                                             H                    High voltage device
                                             M                    Tested for hazardous effects caused by the
                                                                  ingress of water when the movable device
                                                                  components are being operated
                                             S                    Tested for hazardous effects caused by the
                                                                  ingress of water when the movable device
                                                                  components stand still
                                             W                    Suited for a use under defined weather condi-
                                                                  tions and equipped with additional protective
                                                                  measures or processes
     (1)
           as agreed between user and manufacturer
     If one or two of the numeral(s) is/are not used, they are replaced by "X" and/or two "XX".
     If none of the letters is used, this is not shown.
                                                                                                                                   1
     IK code
     The IK code identifies the degree of protection of electric device enclosures against external mechanical
     impact. The IK code is defined in accordance with IEC 62262.
     The degree of protection is identified by the short sign IK and two numerals identifying the degree of
     protection and by two additional letters. The impact energy is stated in joules.
      IK code          IK00   IK01     IK02    IK03      IK04    IK05    IK06    IK07    IK08      IK09      IK10
      Weight                  200 g    200 g   200 g     200 g   200 g   500 g   500 g   1.7 kg    5 kg      5 kg
Conditions of use      Information provided by the        Measures/recommendations of the ASSEMBLY manufacturer                                        Selection
                       planner / customer
                                                          Definition pursuant to standard       This information is to be taken into account in the
                                                          IEC 61439-1                           planning of ASSEMBLIES
Indoor installation    Atmospheric conditions                                                   Comply with more severe requirements arising
                       Foreign bodies / dust              not less than IP2X                    from the product standard
                       Room air conditioned / tempera-    -5 to +35 °C                          Indicate the power loss of the ASSEMBLY for the
                       ture range                                                               dimensioning of the air-conditioning
                       Room ventilated / temperature      -5 to +35 °C                          Indicate the power loss of the ASSEMBLY for
                       range, relative humidity           90 % at 20 °C,                        ventilation dimensioning; and state the room size.
                                                                                                Higher ambient air temperatures are to be taken
                                                          up to 50 % at 40 °C                   into account in the planning of ASSEMBLIES
Outdoor installation   Protected installation /           -25 to +35 °C                         Possible measures against moderate condensation
                       temperature range, relative        90 % at 20 °C, up to 50 % at 40 °C,   due to temperature variations: Ventilating, heating,
                       humidity (against rain, sunshine   short term up to 100 % at 25 °C       air conditioning
                       and wind)
                       Foreign bodies / dust              not less than IP2X                    For increased dust production use a higher degree
                                                                                                of protection such as IP5X
                       Humidity / water                   not less than IPX1                    The manufacturer states the suitability of the
                                                                                                protected installation, if necessary by applying
                                                                                                additional measures
                       Unprotected installation /         -25 to +35 °C                         Higher ambient air temperatures which might result
                       temperature range rel. humidity    90 % at 20 °C, up to 50 % at 40 °C,   from direct sunlight are to be taken into account
                                                          short term up to 100 % at 25 °C       in the planning of ASSEMBLIES Possible measures
                                                                                                against moderate condensation due to temperature
                                                                                                variations: Ventilating, heating, air conditioning
                       Foreign bodies / dust              not less than IP2X	                   For increased dust production use a higher degree
                                                                                                of protection such as IP5X
                       Humidity / water                   not less than IPX1                    The manufacturer states the suitability of the
                                                                                                protected installation, if necessary by applying
                                                                                                additional measures
Conditions of use     Information provided by the           Measures/recommendations of the ASSEMBLY manufacturer                                           Selection
                      planner / customer
                                                            Definition pursuant to standard           This information is to be taken into account in the
                                                            IEC 61439-1                               planning of ASSEMBLIES
Dimensions for        Type of installation:                 None
                                                                                                                                                            _________
transport and         To the wall (recess), to the wall,
installation          free installation to base frame,                                                                                                      _________
                      double floor                                                                                                                          _________
                      Aisle widths / escape routes:         See IEC 60364-7-729                       Minimum aisle widths and the direction of the
                      Room dimensions and access            Requirements for special installations    escape routes are to be taken into account in the
                      doors                                 or locations – operating or maintenance   planning of ASSEMBLIES
                                                            gangways
         Installation and
      3 environmental conditions
                                                          Operating and
                                                     4 servicing
Form 1
Form 2b
Form 4b
      Form 2a   Separation of busbars from functional units The terminals for external conductors
                                                            do not need to be separated from the
                                                            busbars.
      Form 2b   Separation of busbars from functional units The terminals for external conductors
                                                            are separated from the busbars
      Form 3a   Separation of busbars from functional units The terminals for external conductors
                and separation of all functional units from do not need to be separated from the
                one another. Separation of the terminals    busbars.
                for external conductors from the units, but
                not from each other.
      Form 3b   Separation of busbars from functional units The terminals for external conductors are
                and separation of all functional units from separated from the busbars
                one another. Separation of the terminals
                for external conductors from the units, but
                not from each other.
      Form 4a   Separation of busbars from functional units The terminals for external conductors
                and separation of all functional units from are in the same compartment
                one another including the terminals for     as the associated functional unit
                external conductors which are an integral
                part of the functional unit.
      Form 4b   Separation of busbars from functional units   Terminals for external conductors
                and separation of all functional units from   are not in the same
                one another including the terminals for       compartment as the associated function
                external conductors which are an integral     unit, but in individual, separate, enclosed
                part of the functional unit.                  protected spaces or compartments.
     Instructed person
     … persons advised and/or instructed by skilled persons on the tasks assigned to them and the
     possible hazards involved in improper behaviours and also advised on required protection systems,
     personal protection equipment and devices.
     Ordinary person
     … a person who is neither a skilled person nor an instructed person.
    Accompanying standards:
    EN 50110-1 	 Operation of electrical installations – general requirements
    EN 50110-2 	 Operation of electrical installations / national annexes
    IEC 60050 	 International electrotechnical vocabulary
How can the original manufacturer or the manufacturer verify the safety of an ASSEMBLY?
     The new standard describes three design verification processes for an ASSEMBLY and requires a
     routine verification for each marketed product
                                                                                                                                     2
     These processes are essentially implemented          manufacturer will become original manufacturer
     by the original manufacturer. In case that the       for that alteration and will have to carry out the
     ASSEMBLY manufacturer does not install an            design verification in accordance with the
     ASSEMBLY in compliance with the instructions         described procedures.
     of the original manufacturer, the ASSEMBLY
     10.2.5 Lifting
     For ASSEMBLIES equipped with lifting appliances compliance is verified by the following tests.
     The highest number of sections allowed by the original manufacturer to be lifted in the same time
     is to be equipped thus to achieve a weight of 1.25-times the maximum transport weight. With
     the doors closed the ASSEMBLY shall be lifted using the lifting means specified by the original
     manufacturer.
     After this test, the ASSEMBLY must not show cracks or permanent deformation potentially
     affecting its characteristics.
     10.2.7 Marking
     Markings made by moulding, pressing, engraving or similar, including labels with laminated plastic
     surfaces, do not need to be tested separately. The test is described in this section and after the
     test, the markings must be legible without additional tools.
                                                                                                                                 2
     10.3 Degree of protection of enclosures
     The degree of protection is to be verified as provided for in IEC 60529.
     Where an empty enclosure in accordance with IEC 62208 is used, it must be verified by surveys
     that possible modifications which have been carried out do not impair the degree of protection.
     No further testing is required here.
     10.5.2 Continuity of the connection between parts of the ASSEMBLY and the protective
     circuit
     It is to be verified that the different parts of the ASSEMBLY are effectively connected to the
     terminal of the incoming external protective conductor and that the resistance of the circuit does
     not exceed 0.1 Ω.
     Verification is to be carried out using a resistance measurement device which is capable of
     supplying a current of not less than 10 A (AC or DC). The current is passed from each part to the
     terminal for the external protective conductor. The resistance must not exceed 0.1 Ω.
     Example I
     The operating currents are known and the rated current for the incoming supply is to be
     determined from the sum of the outgoing operating currents:
     with an assumed load factor n = 0.9 taken from table 101, EN 61439-2
     (Attention: Part 3 provides for another reduction of the load factors)
     As incoming equipment a fuse switch disconnector size III (630 A) would have to be
     selected, for example.
     *With an assumed load factor of n = 0,9 taken from table 101 of IEC 61439-2
       (Attention part 3 provides for an other reduction of the load factors)
Example II
     The operating current of the outgoing circuit is defined by the equipment selection so that
     the rated current of the outgoing circuit is calculated as follows:
                                                                                                                                     2
     Disconnector size 00, 160 A
     Reducing the rated current of each circuit leads also to another reduction of the power loss
     to be taken into account regarding the power losses occurring with the rated current.
Example III
Ith= 160 A at ambient air temperature, power loss of the equipment PVth=30 W
     Verified ASSEMBLIES are to be calculated so that the wiring sections are to be designed in
     accordance with the current rating of the associated circuit and all sections shall have not
     less than 1.25 times (125 %) of the current rating.
Example IV
with a derating factor of 0.8 to be taken into account for the calculation up to 630 A.
Single-core cables, touching free in air in accordance with Table H.1, Anne H, IEC 61439-1
Inc’ = 160 A Cross-sectional area of conductor: 70 mm² (max. operating current 171 A)
Number
                                                                                                                                        assumed
                                         Type
                                                                                                                                                      (IB/In)2          number
                                                                                                                                        load factor
     1) According to IEC 61439-2 Table 101 – Values of assumed loading – depending on the number of equipment used in the same time
     2) Manufacturer information for equipment under different conditions, but not less than 0.8 in line with section 10.10.4.2.1c
     3) The wiring power loss is assumed as percentage of the equipment power losses – proposal: 30 %
     If there is a positive difference between the dissipated power losses and the sum of the installed power losses, the
     temperature rise of the low voltage switchgear and controlgear ASSEMBLY is verified! In which case the ASSEMBLY
     manufacturer may indicate a RDF of 100 % for the complete installation since sufficient design reserves have been
     taken into account.
     If there is a negative difference between dissipated power losses and installed power losses, further action is
     required in the field:
     	
     	          – Ventilation of the enclosure
     	          – Selecting a larger enclosure
     Or, as a third option, the manufacturer may also reduce the rated diversity factor:
     	
     	         – Determining of a smaller RDF (≤ 80 %)
     The RDF is the percent value of the rated current which the ASSEMBLY may carry continuously and simultaneously
     taking into account the mutual thermal influences.
     It may be specified by the ASSEMBLY manufacturer for the entire low voltage switchgear and controlgear ASSEMBLY
     combination or for groups of outgoing circuits.
     You will find the necessary information on the installed power losses for our enclosures in the technical specifications
     of our catalogues and in our design software.
1x Sace T5 20,35 W
6x XLP00 58,89 W
24 x F204A-40/0,03 46,45 W
                                                      Rated            Pvn        Derat-      Rated current      assumed            assumed            Power loss of      Sum of the
                                                      current of the              ing 1)      of a circuit Inc   load factor 2)     operating          a device at IB     power losses
                                                      equipment In                                                                  current IB
                  Manufacturer
                                                                                                                                    assumed load
                                 Type
                                                                                                                                                       (IB/In)2           number
Pos
factor
1) According to DIN EN 61439-2 Table 101 – Values of assumed loading – depending on the number of equipment used in the same time
2) Manufacturer information for equipment under different conditions, but not less than 0.8 in line with section 10.10.4.2.1c
3) The wiring power loss is assumed as percentage of the equipment power losses – proposal: 30 %
Scenario 1 Scenario 2
ΔPv = Pv diss - Pv total = 300 W – 271.23 W = 28.77 W ΔPv = Pv diss - Pv total = 150 W - 271.23 W = -121.23 W
Verified built-in power loss smaller than power loss to larger enclosure
be dissipated and or
                                                                                                                    150 W                 =0.74
                                                                                                                   271.23 W
Solution
                                                                                                                                                        Pv equipment 	 208.63 W
                                                  MK308                                                                             MK308
                                                                                                                                                                                                                 2
                                                                                                                                                        Pv wiring 	     62.59 W
      WRM381
WRM381
                                                                                                                                                        Pv total 	     271.23 W
                                                  MG304                                                                            MG304
                                                                                                                                                        Pv cabinet 	   354.50 W
               ZWM166
                   MB120                          MA292T                                                                           MG302
                           ZWM371
                           ZWM371
ABB T5
I on
0 off
MT336
ABB XLP00 ABB XLP00 ABB XLP00 ABB XLP00 ABB XLP00 ABB XLP00
MN274
MB316
      H: 1950 mm
      B: 1550 mm
      T: 350 mm
     Example 1
                                                       3/4A
                                              MK307
                                                                                                                                                                                                                                                                   2
MG434
                               MR202          MM112
                                                              Verlustleistung der Betriebsmittel
                                                              Pos       Type            Bezeichnung                                       Stück       PV (In)       AF      RDF       PV (eff.wirks.)
                                               M              1.1.3
                                                              1.3.1     S203-B16
                                                                                        60mm - SS-Einspeiseabdeckung 16-50mm²
                                                                                        S203-B16 Sicherungsautomat B-Char.,6kA
                                                                                                                                           1,00
                                                                                                                                           3,00
                                                                                                                                                      0,00
                                                                                                                                                      7,50
                                                                                                                                                                  0,00
                                                                                                                                                                  0,00
                                                                                                                                                                            0,81
                                                                                                                                                                            0,81
                                                                                                                                                                                           0,00
                                                                                                                                                                                           0,00
                                                              1.3.2     S201-B16        S201-B16 Sicherungsautomat                        21,00       2,50        0,00      0,81           0,00
                                                              1.3.3     F204A-40/0,3    F204A-40/0,3 FI-Schutzschalter 4P,Typ A,4          1,00       8,40        0,00      0,81           0,00
                                                              1.3.4     S201-B10        S201-B10 Sicherungsautomat B-Char.,6kA             6,00       2,10        0,00      0,81           0,00
                                                              1.3.5     E203/63R        E203/63R Trennschalter 3P,63A,Schaltgriff r        1,00       4,00        0,00      0,81           0,00
                                                              1.3.6     OVRT24L40-275   OVR T2 4L 40-275 P TS QS SPD Typ 2 für 2           1,00       0,00        0,00      0,81           0,00
                                                              1.3.7     F204A-40/0,03   F204A-40/0,03 FI-Schutzschalter 4P,Typ A           4,00       8,40        0,00      0,81           0,00
     Width: 	                   800 mm
                                                                                                                          Type                                                     3/4A
                                                                                                                          Abmessungen [mm]                                         Höhe:        1.250,00   Breite:   800,00      Tiefe:       215,00
                                                                                                                          Einbaubare
                                                                                                                                                                                           101,50
     Depth: 	                   215 mm
                                                                                                                          Verlustleistung [W]
Verlustleistung
(Ort und Datum der Ausstellung) (Prüfer: Name und Unterschrift od. gleichwertiges Kennzeichen des Befugten)
Seite 1 von 2
                           TG212G                       TG212G
                                                                                                        2
                           MK209                        MK209
Klemmen Klemmen
MG424 MG424
MG422 MG422
MR202 MR202
                                                                                                               white area
                                                                                                               Temperature rise verification to be made by
                                                                                                               the procedure specified in DIN EN 60890
                                                                                           MG424
ABB SACE X1
00
O I
                                                                                                      Zu berechnender Bereich
                                                                                                          (CombiLine Feld)
MG424
                          The peak short-circuit current Ip is used to assess mechanical strength. The thermal effects
                          of the short-circuit current can be assessed using the effective value Icp.
                                                                                                       Short-circuit
                                                                                     Icp [kAeff]       protective device
                                                                                         Icp [kAeff]                                                                                     ICC [kAeff]
                                                                                                       (SCPD)
            IIN                                                                                                                                                                          ICW [kAeff]
              N                                                                                                                 IIN
                                                                                                                                 N
                                                                                   t t[s]
                                                                                       [s]                                                                                       t [s]
                                      * The values match most use cases. At certain installation positions, e.g. in close proximity to transformers or genera-
                                         tors, there may be lower power factor values, which may effect that the peak value of the uninfluenced short-circuit
                                         current will be the limiting value instead of the effective value.
                                                                   Ip ≤ Ipk
                       t1
t2
                                                              Ip / Icp
                                                                               t1
t2
      In this case it must be made sure that the short-circuit current Ip and the
      uninfluenced short-circuit current Icp at the connection point are smaller
      and/or equal to the values specified by the manufacturer:
Ip ≤ Ipk
Icp ≤ Icw
t short circuit
                                                                                                                                    2
                                   Impedance of the
                                   cable run
                                    Impedance of the
                                    cable run
     The actual occurring short-circuit current might be determined using graphical calculation
     methods or software tools such as e-Design.
     In order to solve the question whether a verification of the Short-circuit withstand strength by test or
     derivation is required or not, the values of the prospective uninfluenced short-circuit current Icp or of the
     expected maximum peak current Ip at the connection point are to be determined.
     Example 1
     Always verify whether the system's short-circuit current to be expected at the
     specified place of use (supply position) does not exceed the short-circuit current                                                                                                  2
     values specified by the manufacturer for its components and/or the manufacturer
     for the planned ASSEMBLY. To do so, you may use the following examples
                                   Prescription of the planner for the        Technical Data given by the original manufacturer,
                                   connection point of the switchgear         for example, for short-circuit strength of a bus bar
                                   ASSEMBLY in the grid system                carrier: Icw (eff) = 30kA / Ipk = 50 kA at a specified
                                                                              distance between the bus bar carrier example 500 mm
                                   Icp (eff) = 15kA
Manufacter Kurzschlussfestigkeits-Diagramm
                                                                         no                                                  Sammelschienenhalterabstand (mm)
     a) Icp (eff) = 15kA ≤ Icw (eff) = 30kA
                                                            a and b
                                                             fulfill?
     b) Ip = Icp (eff) x n = 30kA ≤ Ipk = 50kA
                                                                                                           It is necessary to consider:
                                                                                                           if a bus bar carrier can be used with
                                                         yes                                               a higher short-circuit strength.
      Example 2
      If an ASSEMBLY for which the manufacturer specifies an Icw (eff) , is to be connected to
      a system in which the peak value of the short-circuit current from the system (peak                                                                                  2
      short-circuit current Ip) is higher than the rated peak short-circuit current specified by the
      manufacturer Ipk than a SCPD must be inserted upstream which is able to limit the peak
      value correspondingly.
                                   Prescription of the planner for the                 Details of the original manufacturer, for example,
                                   connection point of the switchgear                  for the short-circuit strength of bus bar carrier:
                                   assembly in the network                             Icw (rms) = 30kA / Ipk = 50 kA at a specified distance between
                                                                                       bus bar carrier example 500mm
                                   Icp (eff) = 28kA
Manufacter
yes
                                                                                                     It has to be checked:
                                                                                                     whether a short circuit protection device
                                                                                                     (SCPD) can be used whose short circuit
                                                                                                     current limiting characteristics are sufficient
           The direct connection of the bus bar system to the grid system,                           to prevent the peak short circuit current
           in compliance with the stated support distances is possible!                              Ipk from being exceeded.
ICOC ≈ 42 kA
     Example 3
     The ASSEMBLY manufacturer or the original manufacturer may specify a conditional
     rated short-circuit current Icc (eff) and a suitable protection device. An ASSEMBLY is only                                                        2
     suited for a use at the connecting point when the expected short-circuit current at the
     supply position Icp does not exceed the specified Icc .
Manufacter
yes no
              Example 4
              If the expected short-circuit current at the supply position, the cut-off current and the
              power-limiting properties of a protective device to be inserted upstream are known, these
                                                                                                                                                                                     2
              values may also be matched to find out whether an ASSEMBLY may be used in a given
              system.
                                               Default of the planner for the                    Details of the original manufacturer’s specifications
                                               connection point of the switchgear                for the switchgear assembly:
                                               assembly in the network
                                                                                                 Ipk = 63kA
                                               Icp = 50kA                                        Icw = 30kA
Manufacter
yes
                                                                                                           It has to be considered:
                                                                                                           whether a short-circuit protection device (SCPD)
                                                                                                           can be used whose pass energy is still dominated
                                                                                                           by the switchgear (I²t SCPD ≤ Icw (rms) ² t) and its
               The direct connection of the switchgear assembly without                                    Kurzschlussstrombegrenzende properties sufficient
               connecting device of a suitable SCPD is possible!                                           to peak short-circuit current limiting as far as that
                                                                                                           IPK does not exceed is (Ip SCPD ≤ Ipk).
          Kurzschluss	
  
          Kurzschlussstrom	
      am	
  
              ABB SACE T-max T5 400 A as E inspeisepunkt	
  
                                         upstream SCPD
             	
  
             ABB	
  SACE	
  T-‐max	
  T5	
  400A	
  als	
  vorgeschaltetes	
  SCPD	
                                                                                                                                                           2
             	
  
                                   Evaluation ofdthe
                                  Beurteilung	
         er	
  Dcut-off
                                                                  urchlassenergie	
      energy                      	
          	
               	
  	
  	
  	
  BEvaluation
                                                                                                                                                                    eurteilung	
  ofder	
  
                                                                                                                                                                                       theStrombegrenzung	
  
                                                                                                                                                                                                power limitation
             	
  
             	
  
             	
  
             	
  
             	
  
             	
  
             	
  
             	
  
             	
  
I²t LS ≈	
  3	
   ,2	
  x10 	
  A²s
                           6
                                                                                                                                      ID LS ≈	
  32	
  k A
             	
  
             	
  
             	
  
             	
  
             	
  
             	
  
             	
  
             	
  
             	
  
             	
  
             	
                                                                        Icp (eff) Netz = 50 kA                                                                                            Icp (eff) Netz = 50 kA
             	
  
             	
  
                                                                6                                            6
             	
                           I²t LS ≈	
  3,2	
  x10 	
  A²s	
  	
  <	
  Icw (eff) ²t = 900 x10 A²s	
                                                          Ip LS ≈	
  32	
  kA <	
  Ipk = 63 kA
             	
  
             	
  
             Durch	
  den	
        An EABB
                                       insatz	
  
                                              SACEeines	
  T-max
                                                               Leistungsschalters	
  
                                                                                  T5 400 used Aas            BB	
  upstream
                                                                                                                    SACE	
  T-‐max	
  
                                                                                                                                   SCPD T5	
  4would
                                                                                                                                                  00	
  als	
  sufficiently
                                                                                                                                                                      vorgeschaltetes	
  protect        SCPD	
  
                                                                                                                                                                                                           the w       äre	
  die	
  
                                                                                                                                                                                                                    ASSEMBLY!
             Anlage	
  ausreichend	
  geschützt!	
  	
  
             	
  
             	
  
             	
  
             	
  
             	
  
             	
  
             	
  
             	
  
             	
  
             	
  
             	
  
             	
  
             	
  
     For many cases it may be assumed that the short-circuit current will not
     exceed the limits* specified.
     For those parts which need to be verified (see 8.1.5), proper mechanical functioning
     has to be verified after their installation to an ASSEMBLY. The number of operating
     cycles shall be 200.
     At the same time, the function of the locking devices associated with these movements
     is to be tested. A test will be passed satisfactorily if the operation of the devices,
     interlocks, the defined degree of protection, etc. are not impaired and if the effort
     required to operate is practically the same before and after testing.
     In general, our low voltage switchgear and         This means that (subject to the positive outcome
     controlgear ASSEMBLIES and the system              of a mechanical test), products from other manu-
     components which we offer are tested with ABB      facturers might be incorporated.
                                                                                                                               2
     equipment.                                         This manufacturer, however, who offers this
     In case that devices from another manufacturer     product (and who thus becomes original manu-
     will be used as short-circuit protective devices   facturer due to the installation of the other prod-
     in low voltage switchgear and controlgear          uct as provided for in IEC 61439-1), should carry
     ASSEMBLIES, a new short-circuit test has           out a short-circuit test.
     necessarily to be carried out.
                                                                                                                              Company stamp
         Manufacturer of the ASSEMBLY
         Customer:
         Order number:
         Project:
                                                                                                                                Design verification part II
                                                                                                                                For low-voltage switchgear and controlgear ASSEMBLIES consisting of several parts and for separate observations to verify
                                                                                                                                the following characteristics: When 10.11 Short circuit withstand strength, 10.12 Electromagnetic Compatibility (EMC) have
        Low-voltage switchgear and controlgear ASSEMBLIES
                                                                                                                                been carried out, please enter the marking of the part of the low-voltage switchgear and controlgear ASSEMBLY here:
          ¨ 
            
            
           Power Switchgear Combination (PSC) Design verification pursuant to IEC 61439-2 / VDE
          ¨ 
            
            
           Sub-distribution board (DBO) Design verification pursuant to IEC 61439-3 / VDE                                        Sec.                       Characteristics to be verified                  Verification by                Remarks / annexes
                                                                                                                                 10.2.2                     Resistance to corrosion                         ABB
                                                                                                                                 10.2.3.2                   Strength against abnormal heat and fire         ABB
        ASSEMBLY rating data:
                                                                                                                                 10.2.4                     Resistance to UV radiation                      ABB
        (Required data from step 1: Collecting the requisite data)
                                                                                                                                 10.2.5                     Lifting                                         ABB
                                                                                                                            10.2.6                          Mechanical impact                               ABB
        Rated voltage:                                                 _________ V                    Short-circuit withstand strength
                                                                                                                            10.2.7                          Marking                                         ABB
        Rated frequency:                                               _________ Hz                   Icc: ___________ kA
                                                                                                                            10.3                            Degree of protection of enclosures              ABB
        Network system:                                                ¨TN ¨TT ¨IT                    Icw: ___________ kA        10.4                       Clearances and creepage distances               ABB
        Rated current of the ASSEMBLY InA:                             ___________ A                  Ipk: ___________ kA        10.5.2                     Continuity of the connection between            ABB
                                                                                                                                                            parts of the ASSEMBLY and the
        Rated impulse withstand voltage (Uimp):                        ___________ kV                                                                       protective circuit
                                                                                                                            10.5.3                          Short-circuit withstand strength of the         ABB
                                                                                                      (enter only applicable values)
                                                                                                                                                            protective circuit
                                                                                                                                 10.6                       Incorporation of equipment                      Manufacturer                   The ASSEMBLY manufacturer shall
        Verified for (see Annex – Part II):                                                                                                                                                                                                comply with the design requirements
                                                                                                                                                                                                                                           of the original manufacturer and of the
                                                                                                                                                                                                                                           equipment manufacturer (8.6)
                                                                                                                                 10.7                       Internal electric circuits and connections      Manufacturer                   The ASSEMBLY manufacturer shall
                                                                                                                                                                                                                                           comply with the design requirements of
                                                                                                                                                                                                                                           the original manufacturer (8.7)
                                                                                                                                 10.8                       Terminals for external conductors               Manufacturer                   Compliance with the requirements of
                                                                                                                                                                                                                                           the original manufacturer and of the
                                                                                                                                                                                                                                           device manufacturer (8.8)
        K-0318 Design verification Part I   •   PDF 05/2015 • 2CPC 000 318 L0201                           Copyright © 2015 STRIEBEL
                                                                                                                              Annexes   :
                                                                                                                                     & JOHN • All rights reserved
K-0319 Design verification Part II • PDF 05/2015 • 2CPC 000 319 L0201 Copyright © 2015 STRIEBEL & JOHN • All rights reserved
      The ASSEMBLY manufacturer carries out routine verifications. They are intended to detect defects
      in workmanship and or materials and are designed to guarantee proper functioning of ASSEMBLIES
      prior to being introduced to the market
                                                                                                                                                                                                                                                                                                                                                                                                                                                                      4
                                                                                                                                                                        Designation label                            Completed with all numer-            Visual inspection
                                                                                                                                                                                                                                                                                ¨	          ¨	            ¨
       ¨ 
         
         
                                                                                                                                                                        - Name of the manufacturer or                als and values
        Power Switchgear Combinations pursuant to IEC 61439-2 (PSC)                                                                                                       trade mark
                                                                                                                                                                        - Type designation or identifier
       ¨ 
         
         
        Sub-distribution boards pursuant to IEC 61439-3 (DBO Type B)                                                                                                    - Date of manufacture
                                                                                                                                                                        - Applied standard
                                                                                                                                                                          IEC 61439-2/-3
                                                                                                                                                                        - Rated voltage (Un)
                                                                                                                                 Company stamp                          - Rated current (InA)
        Manufacturer of the ASSEMBLY:                                                                                                                                   - Rated frequency (fn)
                                                                                                                                                                                                          8. Dielectric properties IEC 61439-1, section 11.9
                                                                                                                                                                        - Degree of protection
                                                                                                                                                                        - Protection class                Criterion                                    Requirement                        Testing              Assessment                 Remark / Examiner
                                                                                                                                                                                                                                                                                                               [o.k. / n.o.k. / n.c.]
                                                                                                                                                                        - CE marking
                                                                                                                                                                                                           Insulation check (10.9.1 General / 10.9.2 Power-frequency withstand voltage)
                                                                                                                                                                                                (secure sample by barrier, only the examiner is allowed to the test area. test duration of not less than 1 s.)
                                                                                                                                                                        Recorded to the documentation:
                                                                                                                                                                                                           Rated insulation voltage Ui                 TestVisual
                                                                                                                                                                                                                                                            voltage                                            ¨	        ¨	        ¨
                                                                                                                                                                        Rated operational voltage                                                                 inspection
                                                                                                                                                                                                                                                       (AC effective value)     ¨	          ¨	            ¨
                                                                                                                                                                                                           __________________ V
                                                                                                                                                                        (Ue) of the outgoing circuits                                                     Visual inspection
                                                                                                                                                                                                                                                                                ¨	          ¨	            ¨
                                                                                                                                                                                                          Phase conductor to enclosure /               pursuant to Table 8                Measurement          ¨	        ¨	        ¨
                                                                                                                                                                        Rated    impulse withstand    voltage
                                                                                                                                                                                                          constructive parts
                                                                                                                                                                                                                              6. Terminals for external
                                                                                                                                                                                                                                                          Visual inspection
                                                                                                                                                                                                                                                        conductors
                                                                                                                                                                                                                                                _______________ V ¨	                       ¨	
                                                                                                                                                                                                                                                                                          _________ V¨                       IEC 61439-1, section 11.7
        Customer:                                                                                                                                                       (Uimp)                             Conductor to conductor
                                                                                                                                                                                                                              Criterion
                                                                                                                                                                                                                                                                                          Measurement
                                                                                                                                                                                                                                                                                Requirement                    ¨	        ¨	
                                                                                                                                                                                                                                                                                                                         Testing¨
                                                                                                                                                                                                                                                                                                                                               Assessment               Remark / Examiner
                                                                                                                                                                        Rated insulation voltage (Ui)                                                     Visual inspection
                                                                                                                                                                                                                                                                                ¨	 _________
                                                                                                                                                                                                                                                                                       ¨	    V¨
                                                                                                                                                                                                                                                                                                                                               [o.k. / n.o.k. / n.c.]
        Order number:                                                                                                                                                   Rated current (Inc) of
                                                                                                                                                                                                           N to PE
                                                                                                                                                                                                                              Outgoing terminals
                                                                                                                                                                                                                                                          Visual inspection
                                                                                                                                                                                                                                                                                ¨	
                                                                                                                                                                                                                                                                                          Measurement
                                                                                                                                                                                                                                                                                         ¨	 with¨manu-
                                                                                                                                                                                                                                                                                Compliance
                                                                                                                                                                                                                                                                                        _________ V
                                                                                                                                                                                                                                                                                                               ¨	        ¨	        ¨
                                                                                                                                                                                                                                                                                                                         Visual inspection
                                                                                                                                                                                                                                                                                                                                               ¨	           ¨	      ¨
                                                                                                                                                                        the outgoing circuits
                                                                                                                                                                                                                              (cross-section, clamping  capacity)               facturing  documentation
        Project:                                                                                                                                                        Rated Diversity Factor (RDF)
                                                                                                                                                                                                           Auxiliary circuit to main circuits
                                                                                                                                                                                                                         Material
                                                                                                                                                                                                                                                 pursuant to Table 9
                                                                                                                                                                                                                                                          Visual inspection
                                                                                                                                                                                                                                                   _______________ V        ¨	
                                                                                                                                                                                                                                                                            Compliance
                                                                                                                                                                                                                                                                                        Measurement
                                                                                                                                                                                                                                                                                       ¨	 with
                                                                                                                                                                                                                                                                                     _________  V¨manu-
                                                                                                                                                                                                                                                                                                               ¨	        ¨	
                                                                                                                                                                                                                                                                                                                 Visual inspection
                                                                                                                                                                                                                                                                                                                                   ¨
                                                                                                                                                                                                                                                                                                                                     ¨	         ¨	       ¨
                                                                                                                                                                                                     Auxiliary circuit to(copper,
                                                                                                                                                                                                                           enclosure aluminium)
                                                                                                                                                                                                                                      /                                     facturing   documentation
                                                                                                                                                                                                                                                                                     Measurement        ¨	       ¨	         ¨
                                                                                                                                                                        Rated peak withstand currentconstructive
                                                                                                                                                                                                       (Ipk)       parts                              Visual inspection
                                                                                                                                                                                                                                                                            ¨	 _________
                                                                                                                                                                                                                                                                                       ¨	       V¨
                                                                                                                                                                                                                         Type of contacting                                 Compliance with manu-                Visual inspection
                                                                                                                                                                                                                                                                                                                                     ¨	         ¨	       ¨
                                                                                                                                                                                                     As alternative to(plug-in,
                                                                                                                                                                                                                            the insulation   test for ASSEMBLIES withfacturing
                                                                                                                                                                                                                                      screw-in)                               an incoming   protective device rated up to 250 A:
                                                                                                                                                                                                                                                                                        documentation
        Type:                                                                                                                                                           (Icw)
                                                                                                                                                                                                     Insulation resistance verification (insulation
                                                                                                                                                                        Rated short-time withstand current
                                                                                                                                                                                                     Testing of the insulation
                                                                                                                                                                                                                         Conductor resistance
                                                                                                                                                                                                                                          type
                                                                                                                                                                                                                                                      Visual measurement
                                                                                                                                                                                                                                                              inspection
                                                                                                                                                                                                                                                                            ¨	
                                                                                                                                                                                                                                               (>1000 Ω/V per circuit referred
                                                                                                                                                                                                                                                                               device with not less than 500 V)
                                                                                                                                                                                                                                                                                       ¨	
                                                                                                                                                                                                                                                                                   to the supply
                                                                                                                                                                                                                                                                            Compliance      with
                                                                                                                                                                                                                                                                                                 ¨
                                                                                                                                                                                                                                                                                                  voltage
                                                                                                                                                                                                                                                                                                   manu-  of the Visual
                                                                                                                                                                                                                                                                                                                 circuits  to earth) ¨	
                                                                                                                                                                                                                                                                                                                        inspection
                                                                                                                                                                                                                                                                                                                                                ¨	       ¨
                                                                                                                                                                                                                         (flexible,
                                                                                                                                                                                                     Testing of the insulation        rigid)
                                                                                                                                                                                                                                 resistance        Compliance with          facturing   documentation
                                                                                                                                                                                                                                                                                     Visual             ¨	       ¨	         ¨
                                                                                                                                                                        Conditional rated short-time with-
                                                                                                                                                                                                     (>1000 Ω/V per circuit referred to the          3.Visual inspection
                                                                                                                                                                                                                                                         Protection
                                                                                                                                                                                                                                                   manufacturing            ¨	 electric
                                                                                                                                                                                                                                                                         against
                                                                                                                                                                                                                                                                    documentation      ¨	 shock
                                                                                                                                                                                                                                                                                     inspection  ¨ and continuity of the protective circuits                              IEC 61439-1, section 11.4
                                                                                                                                                                        stand current (Icc)          supply voltage of the circuits to earth)
                                                                                                                                                                                                                                                     Criterion                                     Requirement                       Testing           Assessment           Remark / Examiner
                                                                                                                                                                                                     Phase conductor 7.   to enclosure  /          1k Ω/V
                                                                                                                                                                                                                             Mechanical function (actuation*  U    _________V        Measurement
                                                                                                                                                                                                                                                                           elements, interlocks)¨	               ¨	 IEC 61439-1,
                                                                                                                                                                                                                                                                                                                            ¨         section 11.8 [o.k. / n.o.k. / n.c.]
                                                                                                                                                                        Included in the documentation                                                           e
                                                                                                                                                                                                     constructive parts
                                                                                                                                                                                                                                                   = _________kΩ                     ________ kΩ
                                                                                                                                                                                                                         Criterion                                          Requirement                          Testing             Assessment        ¨	 Remark       /¨Examiner
        Verifications:                                                                                                                                                  Wiring diagram
                                                                                                                                                                                                     Conductor to conductor
                                                                                                                                                                                                                                                     Protection     against¨	
                                                                                                                                                                                                                                                      Visual inspection
                                                                                                                                                                                                                                                     currents
                                                                                                                                                                                                                                                                             hazardous ¨	 body
                                                                                                                                                                                                                                                                                     Measurement
                                                                                                                                                                                                                                                                                                 ¨ • Protection
                                                                                                                                                                                                                                                                                                        ¨	
                                                                                                                                                                                                                                                                                                   disconnection
                                                                                                                                                                                                                                                                                                                  by
                                                                                                                                                                                                                                                                                                                 ¨	
                                                                                                                                                                                                                                                                                                                      automatic
                                                                                                                                                                                                                                                                                                                            ¨¨
                                                                                                                                                                                                                                                                                                                                     Plan   = imple-
                                                                                                                                                                                                                                                                                                                                     [o.k. / n.o.k. / n.c.]
                                                                                                                                                                                                                                                                                                                                     mentation
                                                                                                                                                                                                                                                                                                                                                             ¨	
                                                                                                                                                                        Assembly plan                                                                 Visual inspection
                                                                                                                                                                                                                                                                            ¨	 ________¨	 kΩ¨                                        1+2, 3 = n.c.
        Serial Type of inspection                      Criterion                                                IEC 61439-1        Result          Examiner             Design verification          N to PE
                                                                                                                                                                                                                         Ventilation grid, assembled,
                                                                                                                                                                                                                         if necessary
                                                                                                                                                                                                                                                      Visual inspection     Compliance with manu-
                                                                                                                                                                                                                                                                            ¨	       Measurement
                                                                                                                                                                                                                                                                            facturing¨	          ¨• Protection
                                                                                                                                                                                                                                                                                        documentation   ¨	
                                                                                                                                                                                                                                                                                                                 Visual inspection
                                                                                                                                                                                                                                                                                                                  by double
                                                                                                                                                                                                                                                                                                                 ¨	         ¨
                                                                                                                                                                                                                                                                                                                                     ¨	         ¨	       ¨
                                                                                                                                                                                                                                                                                                                                     1+3,   2 = n.c.
        number V = visual inspection                                                                            Section                                                 Assembly, operating instructions                                              Visual inspection
                                                                                                                                                                                                                                                                            ¨	
                                                                                                                                                                                                                                                                                     ________ kΩ insulation
                                                                                                                                                                                                                                                                                       ¨	        ¨                               ¨
                                                                                                                                                                                                     Auxiliary circuit toActuation
                                                                                                                                                                                                                           main circuitselements 1. Verify basic protection Compliance      with manu-           Functional and
                                                                                                                                                                                                                                                                                     Measurement   Complete
                                                                                                                                                                                                                                                                                                        ¨	     covering     of
                                                                                                                                                                                                                                                                                                                 ¨	 inspection
                                                                                                                                                                                                                                                                                                                            ¨        ¨	inspection
                                                                                                                                                                                                                                                                                                                                     Visual     ¨	       ¨
               I = Inspection using                                                                                                                                     CE - Declaration of conformity                   (breakers / resetting devicesVisual inspection
                                                                                                                                                                                                                                                                  /         facturing¨	
                                                                                                                                                                                                                                                                            ¨	          documentation
                                                                                                                                                                                                                                                                                                 ¨               visual
                                                                                                                                                                                                                                                                                                   all conductive parts by
                                                                                                                                                                                                                                                                                          ________ kΩ
                                                                                                                                                                                                                                                                                                                                                       ¨	    ¨	        ¨
                                                                                                                                                                        Final testing                                         interlocks / selector switches)                                              double insulation
               mech. or electr. test                                                                                                                                                                       Auxiliary circuit to enclosure /
                                                                                                                                                                                                                       Interlocks / resi-                              Compliance
                                                                                                                                                                                                                                                                                          Measurement          ¨	        ¨	        ¨
                                                                                                                                                                                                                                                                                 ¨	 with    ¨manu-
                                                                                                                                                                                                                                                                                                            Functional   and
                                                                                                                                                                        Cleanliness of the installationconstructive
                                                                                                                                                                                                                 Noparts
                                                                                                                                                                                                                    shavings,  cable                      Visual inspection
                                                                                                                                                                                                                                                                       ¨	       ________  kΩ Enclosures and       covers         Visual
                                                                                                                                                                                                                                                                                                                                 ¨	inspection ¨	                    ¨
                                                                                                                                                                                                                                                                                                                                                                   ¨	     ¨	       ¨
               devices                                                                                                                                                                                                 locks
                                                                                                                                                                                                                 dues, pollution                                       facturing documentation
                                                                                                                                                                                                                                                                                                            visual inspection
                                                                                                                                                                                                                                                                                             have completely and as a
                                                                                                                                                                                                                                                                                       Routine verification checklist (routine check protocol)
                                                                                                                                                                                                                                                                                             minimum IPXXB (>1.6 m
                                                                                                                                                                        Documentation attached                                                 Visual
                                                                                                                                                                                                          9. Wiring, operational performance and      inspection
                                                                                                                                                                                                                                                 function              ¨	 IEC               ¨above
                                                                                                                                                                                                                                                                                     61439-1,  sectionthe11.10
                                                                                                                                                                                                                                                                                                           base, minimum
        1             S                                Degree of protection of cabinets / enclosures            11.2                                                    Enclosure surface
                                                                                                                                                                                                                          Door couplings / switch
                                                                                                                                                                                                          CriterionFree from  scratches,
                                                                                                                                                                                                                                                   actuators
                                                                                                                                                                                                                                            Requirement
                                                                                                                                                                                                                                               Visual inspection
                                                                                                                                                                                                                                                                       Compliance
                                                                                                                                                                                                                                                                                 ¨	
                                                                                                                                                                                                                                                                               Testingwith manu-
                                                                                                                                                                                                                                                                                             IPXXD)
                                                                                                                                                                                                                                                                                                 Assessment
                                                                                                                                                                                                                                                                                                            Functional and
                                                                                                                                                                                                                                                                                                            visual inspection
                                                                                                                                                                                                                                                                                                                                 ¨	
                                                                                                                                                                                                                                                                                                                             Remark           ¨	
                                                                                                                                                                                                                                                                                                                                     / Examiner                     ¨
                                                                                                                                                                                                                                                                       ¨	
                                                                                                                                                                                                                                                                       facturing¨	          ¨
                                                                                                                                                                                                                                                                                    documentation                                                                                                                          Company stamp
                                                                                                                                                                                                                                                                                                 [o.k.and/or
                                                                                                                                                                                                                                                                                             If PCII   / n.o.k.use
                                                                                                                                                                                                                                                                                                                / n.c.]
                                                                                                                                                                                                                                                                                                                      by         Visual inspection
                                                                                                                                                                                                                 pollution, pockets                                            Manufacturer        of the ASSEMBLY:                                                ¨	     ¨	       ¨
        2             V/I                              Clearances and creepage distances                        11.3                                                                                   Cable colours and                     IEC 60446                         Visual        ordinary
                                                                                                                                                                                                                                                                                                 ¨	 persons:¨	         ¨
                                                                                                                                                                        Installation suited for transport        Fixed
                                                                                                                                                                                                       marking main      to
                                                                                                                                                                                                                     circuitstransport
                                                                                                                                                                                                                         Screw         means,AC/DC:
                                                                                                                                                                                                                                   connections /
                                                                                                                                                                                                                                                  Visualblack (brown, grey)
                                                                                                                                                                                                                                                         inspection
                                                                                                                                                                                                                                                                       ¨	      inspection
                                                                                                                                                                                                                                                                       According ¨	         ¨Enclosures and
                                                                                                                                                                                                                                                                                      to data                     covers
                                                                                                                                                                                                                                                                                                            Functional   and
                                                                                                                                                                                                                                                                                             have   completely      and          ¨	           ¨	                    ¨
                                                                                                                                                                                                                 no loose
                                                                                                                                                                                                       Cable colours and parts, labels       IEC 60204                         Visual                                  ¨ as a
                                                                                                                                                                                                                                                                                                            visual inspection
        3             V/I                              Protection against electric shock and continuity         11.4
                                                                                                                                                                                                                                                                                                 ¨	         ¨	
                                                                                                                                                                                                                         device installation AC:
                                                                                                                                                                                                       marking control circuits              / fastening
                                                                                                                                                                                                                                                  red, DC: blue        provided     by original
                                                                                                                                                                                                                                                                               inspection        man-
                                                                                                                                                                                                                                                                                             minimum      IP2XC
                                                                                                                                                                                                                                             Exceptions: orange        ufacturer
                                                       of the protective circuits                                                                                      Routine verification performed: Cable colours and marking PE- and
                                                                                                                                                                                                       N-conductor
                                                                                                                                                                                                                                                2.  Fault
                                                                                                                                                                                                                                             IEC 60446
                                                                                                                                                                                                                         Cabling / fastening(green/yellow
                                                                                                                                                                                                                                                            protection
                                                                                                                                                                                                                                               / type of for PE, blue
                                                                                                                                                                                                                                                                               Visual
                                                                                                                                                                                                                                                                       According
                                                                                                                                                                                                                                                                          for inspection
                                                                                                                                                                                                                                                                                             Full integration
                                                                                                                                                                                                                                                                                                 ¨	
                                                                                                                                                                                                                                                                                      to datacomponents     ¨	  of
                                                                                                                                                                                                                                                                                                            Visual
                                                                                                                                                                                                                                                                                                                     all
                                                                                                                                                                                                                                                                                                                       ¨
                                                                                                                                                                                                                                                                                                              intoinspection
                                                                                                                                                                                                                                                                                                                     the
                                                                                                                                                                                                                                                                                                                                 Visual inspection
                                                                                                                                                                                                                                                                                                                                 ¨	           ¨	
                                                                                                                                                                                                                                                                                                                                                                   ¨	
                                                                                                                                                                                                                                                                                                                                                                    ¨
                                                                                                                                                                                                                                                                                                                                                                          ¨	       ¨
                                                                                                                                                                                                                         installation        N, PEN green/yellow with     blue Customer:
                                                                                                                                                                                                                                                                       provided     by original  man- circuit
                                                                                                                                                                                                                                                                                             protective
        4             S                                Incorporation of equipment                               11.5                                                                                   Wiring /cables /
                                                                                                                                                                                                                                             marking at the end)
                                                                                                                                                                                                                                             No installation
                                                                                                                                                                                                                                                                       ufacturer
                                                                                                                                                                                                                                                               to and signatureOrder
                                                                                                                                                                                                                                                                               Visual   number:
                                                                                                                                                                                                                                                                                             Complete      marking     of  the   Visual inspection
                                                                                                                                                                                                                                                                                                                                                                   ¨	     ¨	       ¨
                                                                                                                                                                       Place / Date                                                                        Name                 of the performer ¨	         ¨	         ¨
                                                                                                                                                                                                                         Door
                                                                                                                                                                                                       cable and fastening  type requirementssharp-edged corners and   Compliance            protective conductors
                                                                                                                                                                                                                                                                                        with manu-
                                                                                                                                                                                                                                                                               inspection                   Functional andPE/
                                                                                                                                                                                                                                                                                                                                 ¨	           ¨	                    ¨
                                                                                                                                                                                                                                                                               Project:
        5             V/I                              Internal electric circuits and connections               11.6                                                                                                     (door hinge l./r.) edges                                            PEN
                                                                                                                                                                                                                                                                       facturing documentation
                                                                                                                                                                                                                                                                                                            visual inspection
        For test values at other rated insulation voltages, see Table 8 of the IEC 61439-1.                                                                                                                                   Colour
                                                                                                                                                                                                                                                         Use of equipment          protection, dew
                                                                                                                                                                                                                                                                             Compliance with manu-
                                                                                                                                                                                                                                                                                                      condensation)
                                                                                                                                                                                                                                                                                                 Complies    with wiring
                                                                                                                                                                                                                                                                                                              Visual inspection
                                                                                                                                                                                                                                                                                                                                manufacturer
                                                                                                                                                                                                                                                                                                                                 Visual inspection
                                                                                                                                                                                                                                                                                                                                  ¨	          ¨	
                                                                                                                                                                                                                                                                                                                                                      ¨	
                                                                                                                                                                                                                                                                                                                                                       ¨
                                                                                                                                                                                                                                                                                                                                                                          ¨	       ¨
                                                                                                                                                                                                                                                         (auxiliary contacts, fuse links)        diagram
                                                                                                                                                                                                                              (RAL)                                                   Mechanical
                                                                                                                                                                                                                                                                                facturing        impact strength of
                                                                                                                                                                                                                                                                                          documentation                                      IK07                            see contract         ¨	        ¨	       ¨
                                                                                                                                                                                                                                                         Equipment arrangement outdoor installations (use
                                                                                                                                                                                                                                                                                           complies with    by plan
                                                                                                                                                                                                                                                                                                         assembly                              Visual inspection
                                                                                                                                                                                                                                                                                                                                                                   ¨	     ¨	       ¨
                                                                                                                                                                                                                              Cable inlet flanges                               Compliance with manu-                    Visual inspection
                                                                                                                                                                                                                                                                                                                                               ¨	           ¨	      ¨
                                                                                                                                                                                                                                                         Installation position of: ordinary
                                                                                                                                                                                                                                                                             facturing
                                                                                                                                                                                                                                                                                            persons)
                                                                                                                                                                                                                                                                                       documentation
        For ASSEMBLIES up to 250 A with an incoming protective device the insulation resistance may be                                                                                                                                                   Breaker actuators (directVerification
                                                                                                                                                                                                                                                                                   drive,      of the measures
                                                                                                                                                                                                                                                                                               Complies  with wiring     Cable
                                                                                                                                                                                                                                                                                                                           Visual entries,
                                                                                                                                                                                                                                                                                                                                  inspection flanges
                                                                                                                                                                                                                                                                                                                                                ¨	                        ¨	
                                                                                                                                                                                                                                                                                                                                                                             Visual
                                                                                                                                                                                                                                                                                                                                                                                  ¨               ¨	        ¨	       ¨
                                                                                                                                                                                                                                                         rotary drive, motor)     taken to achieve   the/degree
                                                                                                                                                                                                                                                                                               diagram   assemblyof plan fastened correctly and                              inspection
        measured using an insulation measurement device at a voltage of not less than 500 V DC. This test                                                                                                                                                                                protection
                                                                                                                                                                                                                                                         Measurement devices (in door, behind the door)    Complies with assembly plan
                                                                                                                                                                                                                                                                                                                                             closed
                                                                                                                                                                                                                                                                                                                                               Visual inspection
                                                                                                                                                                                                                                                                                                                                                                   ¨	     ¨	       ¨
        will be passed successfully when the insulation resistance is at least 1000 Ω/V.                                                                                                                                                                 Control and signalling devices                    Complies with assembly plan         Visual inspection
                                                                                                                                                                                                                                                                                                                                                                   ¨	     ¨	       ¨
                                                                                                                                                                                                                                                                                         2. Clearances and creepage distances                                                   IEC 61439-1, section 11.3
                                                                                                                                                                                                                                                                                   Criterion
                                                                                                                                                                                                                                                         5. Internal electrical circuits and connections                                     Requirement
                                                                                                                                                                                                                                                                                                                                        IEC 61439-1, section 11.6            Testing              Assessment                Remark / Examiner
                                                                                                                                                                                                                                                                                                                                                                                                          Page 3/ n.c.]
                                                                                                                                                                                                                                                                                                                                                                                                  [o.k. / n.o.k.
                                                                                                                                                                                                                                                         Criterion                                         Requirement                         Testing             Assessment           Remark / Examiner
                                                                                                                                                                                                                            K-0320 Routine verification checklist      •   PDF 05/2015Clearance
                                                                                                                                                                                                                                                                                      • 2CPC 000 verification
                                                                                                                                                                                                                                                                                                 320 L0201                                   Rated impulse       withstand
                                                                                                                                                                                                                                                                                                                                                          Copyright[o.k.
                                                                                                                                                                                                                                                                                                                                                                    © 2015      Visual
                                                                                                                                                                                                                                                                                                                                                                         / n.o.k. / n.c.]& JOHN • All rights
                                                                                                                                                                                                                                                                                                                                                                             STRIEBEL                 ¨	 reserved
                                                                                                                                                                                                                                                                                                                                                                                                             ¨	      ¨
                                                                                                                                                                                                                                                                                         (see Table 1)                                       voltage    U and                   inspection1)
                                                                                                                                                                                                                                                         Electrical connections / devices                  According to data                   Spot checkimp
                                                                                                                                                                                                                                                                                                                                                                   ¨	        ¨	         ¨ then
                                                                                                                                                                                                                                                         and busbar system (spot checks                    provided by original                visual inspection                1)
                                                                                                                                                                                                                                                                                                                                                                                   if n.o.k.,
       Check performed by:                                                                                                                                                                                                                               of the cross-sections and torques)                manufacturer
                                                                                                                                                                                                                                                                                                           (spot check matrix)
                                                                                                                                                                                                                                                                                                                                             =_____________V                    Testing for
                                                                                                                                                                                                                                                                                                                                                                                rated peak
                                                                                                                                                                                                                                                                                                                                             Minimum clearances in air withstand
                                                                                                                                                                                                                                                                                                                                                                                current
                                                                                                                                                                                                                                                                                                                                             =_____________ mm                  Uimp pursuant                          Page 2
                                                                                                                                                                                                                                                                                                                                                                                to 10.9.3
                                                                                                                                                                                                                                                        K-0320 Routine verification checklist     •   PDF 05/2015 • 2CPC 000 320 L0201                                  Copyright © 2015 STRIEBEL & JOHN • All rights reserved
                                                                                                                                                                                                                                                                                         Verification of the creepage                        Rated insulation voltage        Visual               ¨	        ¨	       ¨
                                                                                                                                                                                                                                                                                         distances                                           Ui                              inspection2)
       Place / Date                                                                        Name and signature of the performer                                                                                                                                                           (see Table 2)                                       =_____________ V                2)
                                                                                                                                                                                                                                                                                                                                                                                if
                                                                                                                                                                                                                                                                                                                                             (Attention: Ui ≥ Ue)            not obviously
                                                                                                                                                                                                                                                                                                                                             Minimum creepage                o.k., then
                                                                                                                                                                                                                                                                                                                                             distance in                     verification
                                                                                                                                                                                                                                                                                                                                                                             by physical
                                                                                                                                                                                                                                                                                                                                             =_____________ mm               measurement
       Place / Date                                                                        Name and signature of the tester                                                                                                                                                                                                                  (Attention: Minimum
                                                                                                                                                                                                                                                                                                                                             creepage distance ≥ Mi-
                                                                                                                                                                                                                                                                                                                                             nimum clearance in air)
K-0321 Routine verification protocol • PDF 05/2015 • 2CPC 000 321 L0201 Copyright © 2015 STRIEBEL & JOHN • All rights reserved Page 1
K-0320 Routine verification checklist • PDF 05/2015 • 2CPC 000 320 L0201 Copyright © 2015 STRIEBEL & JOHN • All rights reserved
      Also the correct documents for the design verification should be available
      (see Step 2: Distribution board design and design verification).
    The low voltage directive (2006/95/EC) stipulates that every marketed product falling within the
    scope of this directive has to bear the CE mark and that there has to be an associated declaration
    of conformity. This EU Directive is implemented as the Product Safety Act in German law.
    As manufacturer we assist you by our declaration of conformity (to the extent that we market
    products falling within the scope of the low voltage directive and/or the Product Safety Act) and
    by our form sheets:
    -	 Routine verification protocol (see explanations under Step 4: Implementing routine verifications)
    -	 Checklist on the conformity assessment procedure
    -	 Declaration of conformity
    In addition, you are free to use all shown tables as additional tools and may save them from our
    download area.
       Customer:
       Order number:
       Project:
Type:
Low-voltage switchgear and controlgear ASSEMBLIES We declare under our sole responsibility that the product
¨ Power Switchgear Combination (PSC) Design verification pursuant to IEC 61439-2 / VDE ¨ Sub-distribution board,
¨ Sub-distribution board (DBO) Design verification pursuant to IEC 61439-3 / VDE ¨ Power Switchgear Combination (PSC)
       	
      ¨ 1. Technical documentation                                                                                                                                     ¨        Sub-distribution board (DBO) for a use by ordinary people,
                                                                                                                                                                 Designation, type, catalogue or order number:
             Scope of the low-voltage directive 2006/95/EC
        		
         ¨	Technical documentation of the original manufacturer of the low-voltage switchgear and controlgear ASSEMBLY                                           to which this declaration refers, complies with the following standard(s).
                     (Important: Name and address of the original manufacturer as well as the type designation, applicable standard,
                     product description must be stated)
                                                                                                                                                                 Low-voltage switchgear and controlgear ASSEMBLIES
         ¨	Assembly and installation instructions of the original manufacturer
        	¨	Wiring diagram, assembly drawing and parts list                                                                                                       ¨     Power Switchgear Combination (PSC) Design verification pursuant to IEC 61439-2 / VDE
¨ Routine verification protocol ¨ Sub-distribution board (DBO) Design verification pursuant to IEC 61439-3 / VDE
                                                                                                                                                                 The product named complies with the provisions of the following European directives:
             Scope of the EMC directive 2004/108/EC
        	¨	Completion of the technical documentation by manufacturer‘s documentation for all electronic installation
                     equipment and devices, including electronic parts (assembly and installation instructions)	                                                 ¨     Low-voltage directive 2006/95/EC
        	¨	Declaration of conformity by the device manufacturer certifying the compliance of the products with the provisions                                    ¨     EMC directive 2004/108/EC (e.g. for electronic equipment installed
                     of the EMC directive. A note in the supporting documents is of similar importance and has to be kept.                                             to ASSEMBLIES or distribution boards pursuant to IEC 61439-1/-2)
Conformity assessment procedure carried out by: Conformity assessment procedure carried out by:
K-0322 Conformity assessment checklist • PDF 05/2015 • 2CPC 000 322 L0201 Copyright © 2015 STRIEBEL & JOHN • All rights reserved K-0323 Declaration of conformity • PDF 05/2015 • 2CPC 323 045 L0201 Copyright © 2015 STRIEBEL & JOHN • All rights reserved
         Ir                                                                                        In
                                                                             InA / Inc
         Rated current of anelectrical equipment                                                   Rated current
                                                                                                   Icu
                                                                                  Icp              Rated ultimate short-circuit breaking capacity
         Ik                                                                                        Ics
         Sustained short-circuit current                                                           Rated service short-circuit breaking capacity
         Ip                                                                                        Icm
                                                                                  Ipk
         Peak short-circuit current                                                                Rated short-circuit making capacity
         Ith                                                                                       Icw
                                                                                  Icw
         Thermally effective short-circuit current                                                 Rated short-time withstand current
IEC 61439-2
Projekt Example
     Minimum requirements:
     a. Name of the Manufactor of the ASSEMBLY
     b. IEC 61439-X
     c. Type or code number
     d. production date
Select 'Tools' then 'Data import or export' to import or export the user data.
                                                   Rated            Pvn      Derat-   Rated current      assumed            assumed            Power loss of      Sum of the
                                                   current of the            ing 1)   of a circuit Inc   load factor 2)     operating          a device at IB     power losses
                                                   equipment In                                                             current IB
               Manufacturer
                                                                                                                            assumed load
                              Type
                                                                                                                                               (IB/In)2           number
Pos
factor
                                       F204A-
3      40        ABB          FI                   40A              8,4 W    0,6      24 A               0,8                19,2 A             1,94 W             46,45 W
                                       40/0,03	
4 144 ABB S201-B16 16 A 2,5 W 0,6 9,6 A 0,8 7,68 A 0,58 W 82,94 W
    Characteristics                          Information provided by the planner / customer                        Information provided by the manufacturer
    Nominal voltage of the incoming
                                             AC _______ V _____ Hz                                                 Ue = ____________ V
    supply
                                             DC _______ V                                                          fn = ____________ Hz
    System                                   __________ TN-C                                                       __________ Protection by automatic disconnection
                                             __________ TN-C-S                                                                     of the power supply (PC I)
                                             __________ TN-S
                                             __________ TT                                                         __________ protection by protective insulation (PC II)
                                             __________ IT
    Rated current                            Supply current (nominal current transformer / upstream
                                                                                                                   InA = ___________ A
                                             protective device)
    Short-circuit withstand strength
                                             Icp = _______ kA                                                      Ipk = ___________ kA
    (please see notes on pages 9 - -12)
                                             (uninfluenced short-circuit current at the supply terminals)          Icw = ___________ kA
                                                                                                                   Icc = ___________ kA
    Overvoltage                              Overvoltage category                                                  Rated impulse withstand voltage
                                             __________ III                                                        Uimp = ___________ kV
                                             __________ IV
    Incoming line connection
                                             __________ from below                                                 __________ single-core cable
                                             __________ from above                                                 __________ multi-core cable
                                             __________ copper conductor                                           __________ number
                                             __________ aluminium conductor                                        __________ mm² section
                                             __________ connection using terminal blocks                           __________ copper conductor
                                                                                                                   __________ aluminium conductor
                                                                                                                   __________ connection to equipment
                                                                                                                   __________ connection using terminal blocks
    Consumer /                   Information provided by the planner / customer                                                          Data to be derived from step 2 by
    circuit types                                                                                                                        manufacturer
                                 Number of         Type of protective device                                Distribution board ratings   Circuit ratings         Type of protective device
                                 circuits
    Distribution circuits for
                                                   ___ fuse
    downstream subdistri-
    bution boards                                  ___ MCB
                                                   ___ MCCB
    Final circuits
                                 Number of         Type of the protective conductor                         Consumer ratings             Circuit ratings         Type of protective device
                                                   connection
                                 circuits
    Socket
                                                   ____ fuse                                                _______ A                    Inc = _____ A
                                                   ___ MCB
                                                   ____ Circuit breaker and residual current device
    Ohmic load, heater
                                                   ____ fuse                                                _______ kW                   Inc = _____ A
                                                   ___ MCB
                                                   ____ MCCB
    Inductive consumer,
                                                   ___ fuse                                                 _______ kW                   Inc = _____ A
    motor, direct
                                                   ___ MCB                                                  _______ cos 
                                                   ___ MCCB
    Inductive consumer,
                                                   ____ fuse                                                _______ kW                   Inc = _____ A
    motor, controlled
                                                   ___ MCB                                                  _______ cos 
                                                   ____ manufacturer's description
    Capacitive consumers
                                                   ____ fuse                                                _______ kW                   Inc = _____ A
                                                   ___ MCB                                                  _______ cos 
                                                   ____ manufacturer's description
Conditions of use      Information provided by the        Measures/recommendations of the ASSEMBLY manufacturer                                                   Selection
                       planner / customer
                                                          Definition pursuant to standard IEC   This information is to be taken into account in designing
                                                          61439-1                               ASSEMBLIES
Indoor installation    Atmospheric conditions                                                   Comply with more severe requirements arising from the
                                                          not less than IP2X
                       Foreign bodies / dust                                                    product standard
                       Dust
                                                          dust-protected                        IP5X
                       Increased presence of dust
Humidity / water
                       Room air conditioned / tempera-    -5 to +35 °C                          Indicate the power loss of the ASSEMBLY for the
                       ture range                                                               dimensioning of the air-conditioning
                       Room ventilated / temperature      -5 to +35 °C                          Indicate the power loss of the ASSEMBLY in order for venti-
                       range, relative humidity           90 % at 20 °C,                        lation dimensioning; and state the room size. Higher ambient
                                                                                                air temperatures are to be taken into account in the planning
                                                          up to 50 % at 40 °C                   of ASSEMBLIES
Outdoor installation   Protected installation /           -25 to +35 °C                         Possible measures against moderate condensation due to
                       temperature range, relative        90 % at 20 °C, up to 50 % at 40 °C,   temperature variations: Ventilating, heating, air conditioning
                       humidity (against rain, sunshine   short term up to 100 % at 25 °C
                       and wind)
                       Foreign bodies / dust              not less than IP2X                    For increased dust production use a higher degree of
                                                                                                protection such as IP5X
                       Humidity / water                   not less than IPX1                    The manufacturer states the suitability of the protected
                                                                                                installation, if necessary by applying additional measures
                       Unprotected installation /         -25 to +35 °C                         Higher ambient air temperatures which might result from
                       temperature range rel. humidity    90 % at 20 °C, up to 50 % at 40 °C,   direct sunlight are to be taken into account in the planning of
                                                          short term up to 100 % at 25 °C       ASSEMBLIES Possible measures against moderate conden-
                                                                                                sation due to temperature variations: Ventilating, heating, air
                                                                                                conditioning
                       Direct sunlight                    UV resistance                         Follow manufacturer's instructions
                       Foreign bodies / dust              not less than IP2X	                   For increased dust production use a higher degree of
                                                                                                protection such as IP5X
                       Humidity / water                   not less than IPX1                    The manufacturer states the suitability of the protected
                                                                                                installation, if necessary by applying additional measures
Conditions of use       Information provided by the             Measures/recommendations of the ASSEMBLY manufacturer                                                Selection
                        planner / customer
                                                                Definition pursuant to standard               This information is to be taken into account in the
                                                                IEC 61439-1                                   planning of ASSEMBLIES
Dimensions for trans-   Type of installation:                   None
                                                                                                                                                                     _________
port and installation   To the wall (recess), to the wall,
                        free installation to base frame,                                                                                                             _________
                        double floor                                                                                                                                 _________
                        Aisle widths / escape routes:           See IEC 60364-7-729                           Minimum aisle widths and the direction of the
                        Room dimensions and access              Requirements for special installations        escape routes are to be taken into account in the
                        doors                                   or locations – operating or maintenance       planning of ASSEMBLIES
                                                                gangways
                        Distribution board:                     None                                          Possible restrictions are to be stated
                                                                                                                                                                     W ______
                        max. dimensions: W x H x D
                        max. weight                                                                                                                                  H ______
                                                                                                                                                                     D ______
                                                                                                                                                                     kg ______                5
                        Transport: max. transport dimen-        None                                          Possible restrictions are to be stated, such as only
                                                                                                                                                                     W ______
                        sions W x H x D, max. transport                                                       standing transport, max. acceleration values
                        weight                                                                                                                                       H ______
                        Transport type, e.g. crane                                                                                                                   D ______
                        Accessibility at the construction
                                                                                                                                                                     kg ______
                        site
Chemical influences                                             None                                          Type of the enclosure material
                                                                                                              Chemical device version
                                                                                                              Special installation / ventilation
Mechanical impact                                               Sub-distribution board                                                                               IK05
                                                                Indoor installation                                                                                  IK07
                                                                Outdoor installation
                                                     Rated            Pvn   Derating 1)   Rated current      Assumed             Assumed            Power loss of         Sum of the
                                                     current of the                       of a circuit Inc   load factor 2)      operating          a device at IB        power losses
                                                     equipment In                                                                current IB
                 Manufacturer
                                                                                                                                 assumed load
                                Type
                                                                                                                                                                          number
Pos
factor
Difference = power loss dissipation – sum of the installed power loss= Pvzul – ∑PvB
1) According to IEC 61439-2 Table 101 – Values of assumed loading – depending on the number of equipment used in the same time
2) Manufacturer information for equipment under different conditions, but not less than 0.8 in line with section 10.10.4.2.1c
3) The wiring power loss is assumed as percentage of the equipment power losses – proposal: 30 %
                                                                                                                                Company stamp
           Manufacturer of the ASSEMBLY
           Customer:
           Order number:
           Project:
Type:
            ¨ 
               
              Power Switchgear Combination (PSC) Design verification pursuant to IEC 61439-2 / VDE
              
               
            ¨ Sub-distribution board (DBO) Design verification pursuant to IEC 61439-3 / VDE
K-0318 Design verification Part I • PDF 05/2015 • 2CPC 000 318 L0201 Copyright © 2015 STRIEBEL & JOHN • All rights reserved
          For low-voltage switchgear and controlgear ASSEMBLIES consisting of several parts and for separate observations to verify
          the following characteristics: When 10.11 Short circuit withstand strength, 10.12 Electromagnetic Compatibility (EMC) have
          been carried out, please enter the marking of the part of the low-voltage switchgear and controlgear ASSEMBLY here:
Annexes:
K-0319 Design verification Part II • PDF 05/2015 • 2CPC 000 319 L0201 Copyright © 2015 STRIEBEL & JOHN • All rights reserved
           
            
         ¨ Sub-distribution boards pursuant to IEC 61439-3 (DBO Type B)
                                                                                                                                   Company stamp
          Manufacturer of the ASSEMBLY:
          Customer:
          Order number:
          Project:
Type:
          Verifications:
          Serial Type of inspection                      Criterion                                                IEC 61439-1        Result          Examiner
          number V = visual inspection                                                                            Section
                 I = Inspection using
                 mech. or electr. test
                 devices
          1             S                                Degree of protection of cabinets / enclosures            11.2
          2             V/I                              Clearances and creepage distances                        11.3
          3             V/I                              Protection against electric shock and continuity         11.4
                                                         of the protective circuits
          4             S                                Incorporation of equipment                               11.5
          5             V/I                              Internal electric circuits and connections               11.6
          6             S                                Terminals for external conductors                        11.7
          7             V                                mech. Function (actuation elements, interlocks)          11.8
          8             V                                Dielectric properties                                    11.9
          9             V                                Wiring, operating behaviour and function                 11.10
          Test voltage value
          The power-frequency withstand voltage is to be tested on all circuits for a duration of 1 s.                               V AC
          in accordance with 10.9.2. Test voltage = 1890 V AC at a rated insulation voltage between 300 V-690 V AC.
          For test values at other rated insulation voltages, see Table 8 of the IEC 61439-1.
          For ASSEMBLIES up to 250 A with an incoming protective device the insulation resistance may be
          measured using an insulation measurement device at a voltage of not less than 500 V DC. This test
          will be passed successfully when the insulation resistance is at least 1000 Ω/V.
K-0321 Routine verification protocol • PDF 05/2015 • 2CPC 000 321 L0201 Copyright © 2015 STRIEBEL & JOHN • All rights reserved
          Customer:
          Order number:
          Project:
Type:
Page 1
K-0320 Routine verification checklist • PDF 05/2015 • 2CPC 000 320 L0201 Copyright © 2015 STRIEBEL & JOHN • All rights reserved
          3. Protection against electric shock and continuity of the protective circuits                                                  IEC 61439-1, section 11.4
          Criterion                                        Requirement                       Testing             Assessment                 Remark / Examiner
                                                                                                                 [o.k. / n.o.k. / n.c.]
          Protection against hazardous body • Protection by automatic                        Plan = imple-       ¨	        ¨	        ¨
          currents                          disconnection       ¨                            mentation
                                                                                             1+2, 3 = n.c.
                                                           • Protection by double
                                                                                             1+3, 2 = n.c.
                                                           insulation                    ¨
          1. Verify basic protection                       Complete covering of              Visual inspection
                                                                                                                 ¨	        ¨	        ¨
                                                           all conductive parts by
                                                           double insulation
                                                           Enclosures and covers             Visual inspection
                                                                                                                 ¨	        ¨	        ¨
                                                           have completely and as a
                                                           minimum IPXXB (>1.6 m
                                                           above the base, minimum
                                                           IPXXD)
                                                           If PCII and/or use by             Visual inspection
                                                                                                                 ¨	        ¨	        ¨
                                                           ordinary persons:
                                                           Enclosures and covers
                                                           have completely and as a
                                                           minimum IP2XC
          2. Fault protection                              Full integration of all           Visual inspection
                                                                                                                 ¨	        ¨	        ¨
                                                           components into the
                                                           protective circuit
                                                           Complete marking of the           Visual inspection
                                                                                                                 ¨	        ¨	        ¨
                                                           protective conductors PE/
                                                           PEN
                                                           Continuous connection of          Resistance  ¨	                ¨	        ¨
                                                           the protective circuit            measurement
                                                                                             < 0.1Ω
                                                           Spot checks screw                 Torque check
                                                                                                                 ¨	        ¨	        ¨
                                                           connections
          3. Fault protection                              No connection of the              Visual inspection
                                                                                                                 ¨	        ¨	        ¨
                                                           components to the
                                                           protective circuit
                                                           Graphic symbol attached           Visual inspection
                                                                                                                 ¨	        ¨	        ¨
Page 2
         K-0320 Routine verification checklist     •   PDF 05/2015 2CPC 000 320 L0201
                                                                   •                                                    Copyright © 2015 STRIEBEL & JOHN All rights reserved
                                                                                                                                                            •
Page 3
K-0320 Routine verification checklist • PDF 05/2015 • 2CPC 000 320 L0201 Copyright © 2015 STRIEBEL & JOHN • All rights reserved
Page 4
K-0320 Routine verification checklist • PDF 05/2015 • 2CPC 000 320 L0201 Copyright © 2015 STRIEBEL & JOHN • All rights reserved
          - Date of manufacture
          - Applied standard
            IEC 61439-2/-3
          - Rated voltage (Un)
          - Rated current (InA)
          - Rated frequency (fn)
          - Degree of protection
          - Protection class
          - CE marking
Page 5
K-0320 Routine verification checklist • PDF 05/2015 • 2CPC 000 320 L0201 Copyright © 2015 STRIEBEL & JOHN • All rights reserved
         Table 8 – Power-frequency withstand voltage for main circuits IEC 61439-1, section 10.9.2
                      Rated insulation voltage Ui                                       Test voltage                      Test voltage b
                  (conductor to conductor, AC or DC)                                 (AC effective value)                      (DC)
                                        P                                                     P                                    P
                                      Ui                   ≤   60                           1000                              1415
             60 <                     Ui                   ≤   300                          1500                              2120
             300 <                    Ui                   ≤   690                          1890                              2670
             690 <                    Ui                   ≤   800                          2000                              2830
             800 <                    Ui                   ≤   1000                         2000                              3110
             1000 <                   Ui                   ≤   1500a                                                          3820
             a
                 for DC only
             b
                 Test voltages based on 6.1.3.4.1, fifth paragraph of IEC 60664-1.
         Table 9 – Power-frequency withstand voltage for auxiliary and control circuits IEC 61439-1, section 10.9.2
                                      Rated insulation voltage Ui                                              Test voltage
                                      (Conductor to conductor)                                              (AC effective value)
                                                 P                                                                   P
                                                      Ui                   ≤ 12                                     250
                         12 <                         Ui                   ≤ 60                                     500
                         60 <                         Ui                                                        see Table 8
         a
             assumption numeral 0 means:
No erroneous screw connections are accepted for spot checks ➜ immediate reworking / 100% check!
         Customer:
         Order number:
         Project:
Type:
        ¨	
         Sub-distribution board (DBO) Design verification pursuant to IEC 61439-3 / VDE
        ¨	
         1. Technical documentation
          	¨	Declaration of conformity by the device manufacturer certifying the compliance of the products with the provisions
                       of the EMC directive. A note in the supporting documents is of similar importance and has to be kept.
        ¨	
         2. Preparing a declaration of conformity
        ¨	
         3. Affixing of the CE – marking
K-0322 Conformity assessment checklist • PDF 05/2015 • 2CPC 000 322 L0201 Copyright © 2015 STRIEBEL & JOHN • All rights reserved
         Declaration of conformity
                                  Company stamp
¨ Sub-distribution board,
¨ Power Switchgear Combination (PSC) Design verification pursuant to IEC 61439-2 / VDE
The product named complies with the provisions of the following European directives:
               With this declaration of conformity the manufacturer certifies compliance with the specified directives and standards.
               This declaration of conformity meets the provisions of IEC 45014 - General criteria for supplier's declaration of conformity.
K-0323 Declaration of conformity • PDF 05/2015 • 2CPC 323 045 L0201 Copyright © 2015 STRIEBEL & JOHN • All rights reserved
STRIEBEL & JOHN GmbH & Co. KG We reserve the right to make technical changes or modify