HTS
PBC6200
String 4 PBC6200
functions &
Parts
String 3
String 2
String 1
Prepared by Sahand Aras
I
HTS
Contents
PBC Introduction
PBC Features
Parts & Components
Item Specification
Disassemble
System Management
PBC 6200 by Sahand Aras II
HTS
PBC 6200
PBC 6200 series power system, consisting of compact rack enclosures, rectifier modules and related power
distribution units, is under the control of Supervisory Unit. User can operate the system through NRMS or
LCD interface.
Power and Battery Cabinet Rectifier produced by Delta Company
There are two types running in Suli Korek Network
PBC 6200 Normal Type
PBC 6200 Expansion board & High voltage protection board
PBC 6200 by Sahand Aras 1
HTS
System Features
Feature Specification
AC Input 220-240 VAC
Max 54A for 2.7kW
Max 36 for 2.0kW
System Capacity -54V/ 150A (1 to 4 Rect)
Rectifier Modules 2.7 kW BML161179/1
2.0 kW BML161179/2
LVDS LVBD + LVLD
Operation Temp 0 to 45 C
Storage Temp -40 to 75 C
Humidity 0 to 95%
PBC 6200 by Sahand Aras 2
HTS
Disassemble
Step 1 Step 2
Step 3
PBC 6200 by Sahand Aras 3
HTS
Disassemble
Controller Board
LCD display
Web Board
Step 1 Step 2 Step 3 Step 4
PBC 6200 by Sahand Aras 4
HTS
Components
Item Name PN
PS Nova CSU 3p of PCB (Control Unit) BMY 908 036/1
PS Nova Dummy Front Rectifier SDK 107 1707/1
Contactors
PS Nova LCD Display BMY 908 035/1 AC power
Rectifier -48 V/2.0 kW BML 161 179/1 Circuit Connection
Sealing Kit NTM 257 0038/1 Breaker
Service Outlet Fuse BMY 908 041/1
SPD-CU BMY 908 039/1
SSC-02 CCU Standard BGM 119 26/2
SSC-02 HEX Replacement BPD 901 47/5 Control
SSC-02 Lock System NTM 101 2481/1
Temperature Sensor Cable KET 109 42/3000
Board
Thermostat for SSC-02 NTM 101 2333/3
Web Interface Board BMY 908 034/1
Circuit breaker 2A 1 POS, LO, Black body NFS 815 1321/002
Circuit breaker 6A 1 POS, LO, Black body NFS 815 1321/006
Circuit breaker 10A 1 POS, LO, Black body NFS 815 1321/010
Circuit breaker 16A 1 POS, LO, Black body NFS 815 1321/016
Circuit breaker 20A 1 POS, LO, Black body NFS 815 1321/020 LCD Display High
Circuit breaker 25A 1 POS, LO, Black body NFS 815 1321/025 Supervision Unit
Circuit breaker 32A 1 POS, LO, Black body NFS 815 1321/032 Voltage
Circuit breaker 63A 1 POS, LO, Black body NFS 815 1331/063 Expansion Protection
Circuit breaker 200A 4 POS, LO, Black Body NFS 815 1329/200 Board unit
Gas ventilation kit NTB 101 215/2 Rectifier
Nova Controller Board BMY 908 060/1 Modules
PBC 6200 by Sahand Aras 5
HTS
Power System
Communication board
PBC 6200 by Sahand Aras 6
HTS
System Management
Power system controller Delta New Smart CSU Monitoring: AC input information
Display LCD 128 x 64 dots display DC information
Function System monitoring (remote/local) Rectifier information
Parameter setting Battery Information
Temperature compensation DC load information
Boost / Equalize charge Environment detection
Alarm relay definable Parameter Setting: System output parameter setting
Battery test Alarm threhold setting
Remote Interface RS-232 Alarm configuration setting
Rectifier Slot 1~4 rectifier System relay setting
Others: Remote management
Event log
Efficiency management
Battery discharge test function
PBC 6200 by Sahand Aras 7
HTS
Default Parameters & Alarms
Relay Event Alarm Event Description
1 AC Off AC Fail Alarm
2 RFA Rectifiers Fail Alarm
3 CSU Fail CSU Fail Alarm
4 DCL DC Low Voltage Alarm
5 Batt. Switch Battery Breaker or Fuse Fail Alarm
6 Major DCH, HVDS, LVDS Trip, TAH, TA Sensor Fail, AC Fail, TB Sensor Fail, TBH,
One Rectifier, Rect Over Percent of Capacity, Load Priority Hi, Load Priority Lo,
7 Minor DCL, TAL, HTSD, CL, Battery Switch, Battery Discharge, Battery Test
Fail, More Rectifier Fail
PBC 6200 by Sahand Aras 8
HTS
Parameter Descriptions Setting Setting Range
HVSD Shutdown 59.5 V 58.0~60.0 V
HV Alarm 57.5 V 56.0~58 V
LV Alarm 45.0 V 44.0~50.0 V
LVDS1 42.0 V 40.0~48.0 V
LVDS2 45.2V 40.0~48.0V
LVDS3 47.2V 40.0~48.0V
Set FL Voltage 54.0 V 50.0~56 V
Set EQU Voltage 56.0 V 50~57 V
HTSD Shutdown 60 ℃ 45~75 ℃
LTSD Shutdown -15 ℃ -40~10℃
Single Phase 220 ACV High Alarm 264V 230~276V
Single Phase 220 ACV Low Alarm 176 V 90~184 V
SMR CL (2700W) 50A 5A~50A
Battery Test Voltage 45.0 V 42.0~52.0 V
Battery test current 0.1C 0.05~0.5 C
PBC 6200 by Sahand Aras 9
HTS
Rectifier Modules
2.0 kW 2.7 kW
Input Voltage 230 VAC Single phase 230 VAC Single phase
176-276 VAC 176-276 VAC
PF 0.99 at full load 0.99 at full load
Protection Fuse Fuse
Output Voltage -40V to -59V -40V to -59V
Output Power 2000W 2700W
Max Current 37A 50A
PBC 6200 by Sahand Aras 10
HTS
Input Signal Output
Status/Alarm Indicators
AC OK: AC input Voltage Green LED
RFA: Rectifier Fail Alarm Red LED
C.L.: Current Limit Yellow LED
PBC 6200 by Sahand Aras 11
HTS
Software Interface
Main Controller Board Connector Board
Power system controller Delta New Smart CSU
Display LCD 128 x 64 dots display
LED (Major, Minor, EQU)
4 push buttons on the CSU LCD display. Expand Board
They are use to control the power system.
PBC 6200 by Sahand Aras 12
HTS
Real Time Operation Status
The shelf status is displayed on the front of the CSU. The Main page is always
displayed during normal operation.
DCV: System output DC Voltage
DCI: Total system output current
Sys Sta: System status
Alarm Existing: “Alarm Existing” will display if alarm had occurred
PBC 6200 by Sahand Aras 13
HTS
PBC 6200 by Sahand Aras 14
HTS
PBC 6200 by Sahand Aras 15
HTS
DC O/P V
Temp
Load Current
Load + Battery
Equalization
Phase 1
Manual Battery test
Phase 2
Phase 3
PBC 6200 by Sahand Aras 16
HTS
Available slots
Failed slot Number
Working slot Number
Turned off slot Number
Modules status
PBC 6200 by Sahand Aras 17
HTS
+ Charging
- Discharging
Batt Capacity
PBC 6200 by Sahand Aras 18
HTS
PBC 6200 by Sahand Aras 19
HTS
PBC 6200 by Sahand Aras 20
HTS
Enable/Disable
Temp Alarm
High Temp
Battery test
Disconnecting
Enable/Disable
High Temp
Battery
Disconnecting
PBC 6200 by Sahand Aras 21
HTS
System V
PBC 6200 by Sahand Aras 22
HTS
PBC 6200 by Sahand Aras 23
HTS
PBC 6200 by Sahand Aras 24
HTS
PBC 6200 by Sahand Aras 25
HTS
Thank You
PBC 6200 by Sahand Aras 26