Manual LK
Manual LK
ii
                                                                          FIGURES
        Figure 1    Cabinet arrangement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
        Figure 2    Single module block diagram—dual input configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
        Figure 3    Input busbars . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
        Figure 4    Battery fuses and connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
        Figure 5    Ground and neutral busbar connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
        Figure 6    Monitor board U2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
        Figure 7    Auxiliary terminal block detail (Monitoring Board) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
        Figure 8    Input dry contacts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
        Figure 9    Jumper connection for BCB interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
        Figure 10   Output dry contacts and EPO wiring for firmware before M170 . . . . . . . . . . . . . . . . . . . . . . . . . . 17
        Figure 11   EPO wiring for firmware M200 or later . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
        Figure 12   Battery cabinet—details . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
        Figure 13   Narrow battery cabinet, 27 in. (690mm) - rear view. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
        Figure 14   Wide battery cabinet, 57 in. (1488mm) - front view . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
        Figure 15   Internal cable wiring from battery cabinet to Liebert NX . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
        Figure 16   Battery tray and supports . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
        Figure 17   Single UPS with external Maintenance Bypass Cabinet—typical configuration . . . . . . . . . . . . . 25
        Figure 18   Maintenance Bypass Cabinet—access plate removed . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
        Figure 19   Maintenance Bypass Cabinet wiring access panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
        Figure 20   Maintenance bypass control wire location. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
        Figure 21   Load Bus Synchronization cable connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
        Figure 22   1+N system block diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
        Figure 23   Connecting '1+N' system parallel control cables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
        Figure 24   Auxiliary dry contact cables for output breaker in multi-module system . . . . . . . . . . . . . . . . . . . 34
        Figure 25   Dry contacts, multiple UPS modules with distribution panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
        Figure 26   Connecting EPO push button . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
        Figure 27   Battery circuit breaker box connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
        Figure 28   Dimensional view- front and left side views . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
        Figure 29   Dimensions continued—top and bottom views . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
        Figure 30   Main components—typical unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
        Figure 31   Cable connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
        Figure 32   Location of internal batteries . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
        Figure 33   Battery connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
        Figure 34   Battery cabinet interconnection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
        Figure 35   Maintenance Bypass interconnection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
        Figure 36   NX 1+1 parallel cabinet interconnections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
        Figure 37   Lineup detail—SlimLine distribution cabinet to NX . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
        Figure 38   Lineup detail—1+N Type A connection to NX . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
        Figure 39   Lineup detail—1+N Type A1 connection to NX . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
        Figure 40   Lineup detail—1+N Type B connection to NX . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
        Figure 41   Lineup detail—1+N Type B1 connection to NX . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
        Figure 42   Lineup detail—1+N Type C connection to NX . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
        Figure 43   Lineup detail—1+N Type C1 connection to NX . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
        Figure 44   Lineup detail—1+N Type D connection to NX . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
        Figure 45   SlimLine locations. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
iii
iv
                 !   WARNING
                     Exercise extreme care when handling UPS cabinets to avoid equipment damage or injury to
                     personnel. The UPS module weight ranges from 850 to 1400 lb. (386 to 635kg).
                     Determine unit weight and locate center of gravity symbols
                     before handling the UPS. Test lift and balance the cabinet
                     before transporting. Never tilt equipment more than 15 degrees from vertical.
                     Battery manufacturers supply details of the necessary precautions to be observed when
                     working on, or in the vicinity of, a large bank of battery cells. These precautions should be
                     followed implicitly at all times.
                     Follow all battery safety precautions when installing, charging or servicing batteries. In
                     addition to the hazard of electric shock, gas produced by batteries can be explosive and
                     sulfuric acid can cause severe burns. When connected, the nominal battery voltage is 288VDC
                     and is potentially lethal.
                     In case of fire involving electrical equipment, use only carbon dioxide fire extinguishers or
                     those approved for use in fighting electrical fires.
                     Extreme caution is required when performing maintenance.
                     Be constantly aware that the UPS system contains high DC as well as AC voltages.
                     Check for voltage with both AC and DC voltmeters prior to making contact.
                 !   WARNING
                     As with other types of high power equipment, dangerous voltages are present within the UPS
                     and battery enclosure. The risk of contact with these voltages is minimized as the live
                     component parts are housed behind a hinged, lockable door. Further internal safety screens
                     make the equipment protected to IP20 standards.
                     No risk exists to any personnel when operating the equipment in the normal manner,
                     following the recommended operating procedures.
                     All equipment maintenance and servicing procedures involve internal access and should be
                     carried out only by trained personnel.
                 !   WARNING
                     High ground leakage current: Ground connection is essential before connecting the input
                     supply.
                     This equipment must be grounded in accordance with local electrical codes.
                     Maximum load must not exceed that shown on the UPS rating label.
                 !   WARNING
                     Under typical operation and with all UPS doors closed, only normal safety precautions are
                     necessary. The area around the UPS system should be kept free of puddles of water, excess
                     moisture and debris.
                     Special safety precautions are required for procedures involving handling, installation and
                     maintenance of the UPS system and the battery. Observe all safety precautions in this
                     manual before handling or installing the UPS system. Observe all precautions in the
                     Operation and Maintenance Manual, before as well as during performance of all maintenance
                     procedures. Observe all battery safety precautions before working on or near the battery.
                     This equipment contains several circuits that are energized with high voltage. Only
                     test equipment designed for troubleshooting should be used. This is particularly true for
                     oscilloscopes. Always check with an AC and DC voltmeter to ensure safety before making
                     contact or using tools. Even when the power is turned Off, dangerously high electric charges
                     may exist within the UPS.
                     All power and control wiring should be installed by a qualified electrician. All power
                     and control wiring must comply with the NEC and applicable local codes.
                     ONLY qualified service personnel should perform maintenance on the UPS system.
                     When performing maintenance with any part of the equipment under power, service
                     personnel and test equipment should be standing on rubber mats. The service personnel
                     should wear insulating shoes for isolation from direct contact with the floor (earth ground).
                     Never work alone, even if all power is removed from the equipment. A second person should
                     be standing by to assist and summon help in case an accident should occur.
                 !   CAUTION
                     This unit complies with the limits for a Class A digital device, pursuant to Part 15 Subpart J
                     of the FCC rules. These limits provide reasonable protection against harmful interference in a
                     commercial environment. This unit generates, uses and radiates radio frequency energy and,
                     if not installed and used in accordance with this instruction manual, may cause harmful
                     interference to radio communications. This unit is not designed for use in a residential area.
                     Operation of this unit in a residential area may cause harmful interference that the user must
                     correct at his own expense.
              Battery Cabinet Precautions
              The following warning applies to all battery cabinets supplied with UPS systems. Additional warn-
              ings and cautions applicable to battery cabinets may be found in 3.0 - Battery Installation.
                 !   WARNING
                     Internal battery strapping must be verified by manufacturer prior to moving a battery cabinet
                     (after initial installation).
                     • Battery cabinets contain non-spillable batteries.
                     • Keep units upright.
                     • Do not stack.
                     • Do not tilt.
                     Failure to heed this warning could result in smoke, fire or electric hazard.
                     Call 1-800-LIEBERT before moving battery cabinets (after initial installation).
AC input
AC output
                       -       +
                                   Indicates the unit contains a valve-regulated lead acid battery
                       PbH2SO4
R Recycle
DC voltage
Bonded to ground
AC voltage
        1.0   INSTALLATION
              The Liebert NX™ UPS is designed primarily for telecommunications and data processing applica-
              tions. Liebert Corporation neither recommends nor knowingly sells this product for use with life sup-
              port and other designated “critical” devices.
              This section describes the NX’s environmental requirements and mechanical considerations that
              must be taken into account when planning the positioning and cabling of the UPS equipment.
              Because every site is unique, this section presents a guide to general procedures and practices that
              should be observed by the installing engineer, rather than step-by-step installation instructions.
                 !   WARNING
                     Do not apply electrical power to the UPS equipment before the arrival of the commissioning
                     engineer.
                 !   WARNING
                     The UPS equipment should be installed by a qualified engineer in accordance with the
                     information contained in this section.
                 !   WARNING
                     Special care should be taken when working with the batteries associated with this equipment.
                     When connected together, the nominal battery voltage is 288VDC and is potentially lethal.
                     • Eye protection should be worn to prevent injury from accidental electrical arcs.
                     • Remove rings, watches and all metal objects.
                     • Only use tools with insulated handles.
                     • Wear rubber gloves.
                     If a battery leaks electrolyte or is otherwise physically damaged, it must be replaced, stored in
                     a container resistant to sulfuric acid and disposed of in accordance with local regulations.
                     If electrolyte comes into contact with skin, the affected area should be washed immediately
                     with large amounts of water.
                     NOTE
                     The NX UPS can be used in TN utility system.
                  !      CAUTION
                         If the UPS must remain disconnected from power for more than six (6) months, the battery
                         must be recharged before use. To charge the batteries, the unit must be connected to utility
                         power and started up—the charger operates only while the NX is operating.
                  !      CAUTION
                         When batteries are installed in the UPS or are cabinet-mounted adjacent to the UPS unit, the
                         battery—not the UPS—dictates the designed maximum ambient temperature.
                  !    WARNING
                       Ensure that any equipment that will be used to move the NX has sufficient lifting capacity.
                       The NX weight ranges from 850 to 1400 lb. (386 to 635kg). See Table 9 for details. The UPS
                       presents a tipping hazard. Do not tilt the NX further than 15 degrees from vertical.
                       The UPS is fitted with casters—take care to prevent movement when unbolting the
                       equipment from its shipping pallet. Ensure adequate personnel and lifting equipment are
                       available when taking the NX off its shipping pallet. Do not tilt the unit more than 15 degrees
                       from center.
                  !    WARNING
                       The casters are strong enough for movement across even surfaces only. Casters may fail if
                       they are subjected to shock loading, such as being dropped or rolled over holes in the floor or
                       obstructions. Such failure may cause the unit to tip over, injuring personnel and damaging
                       the equipment.
                       Care must be taken when maneuvering units fitted with batteries. Keep such moves to a
                       minimum. For further information, see Battery Cabinet Precautions on page 2.
                Final Position
                When the equipment has been finally positioned, ensure that the adjustable stops are set so that the
                UPS will remain stationary and stable (see 7.0 - Installation Drawings).
        1.6     Mechanical Considerations
                The NX is constructed with a steel frame and removable panels. Top and side panels are secured to
                the chassis by screws. The doors may be opened for access to power connections bars, auxiliary termi-
                nals blocks and power switches.
                The UPS comes with an operator control panel, which provides basic operational status and alarm
                information. The cabinet houses both the power components and the internal batteries. Cooling is
                provided by internal fans. The unit sits on four casters. Adjustable stops are provided to prevent the
                UPS from moving once it has been moved to its final position.
        1.6.1   Clearances
                There are no ventilation grilles on the sides or rear of the UPS. The sides must be accessible during
                installation. After installation, the unit may be placed with the rear against a wall and optional cabi-
                nets on either side.
                To enable routine tightening of power terminations within the UPS, make sure there is sufficient
                clearance in front of the NX to permit free passage of personnel with the door fully opened.
                Leave a minimum of 2 ft. (610mm) between the top of the UPS and the ceiling to permit adequate air
                circulation above the unit. Liebert recommends against using air conditioning or other systems that
                blow air onto the top of the unit.
        1.6.2   Floor Installation
                The diagrams in 7.0 - Installation Drawings show the location of holes in the base plate for bolting
                the equipment to the floor. An optional anchoring kit is available. For information, see your local Lie-
                bert representative.
                If the equipment is to be placed on a raised floor, it should be mounted on a pedestal that will support
                the equipment point loading. Refer to the bottom view in Figure 28 to design this pedestal.
        1.6.3   Cable Entry
                Cables can enter the NX from the top or bottom. Cable entry is made possible by removing a metal
                plate attached to the UPS.
                These plates are designed to allow the personnel to punch holes for fitting and securing the conduit.
                Once the conduit holes are punched, these plates should be reattached to the UPS.
                Connecting cables to the NX may require that the UPS be accessible from the left side to allow per-
                sonnel to complete the connections and make necessary adjustments. After installation is complete,
                the NX may be serviced from the front.
                        NOTE
                        When installing the UPS, the customer must provide a disconnect with overcurrent protection
                        at the output of the UPS.
                10-30kVA UPS
                The 10-30kVA NX consists of a single cabinet housing the UPS components and the internal battery
                string.
                Optional battery cabinets are available to provide extended run time. Each cabinet houses additional
                strings of batteries that operate in parallel with the NX’s internal batteries. The cabinets are
                designed to be bolted to the right side of the UPS (see Figure 1). Refer to 3.4 - External Battery
                Cabinet Installation for details.
                Optional maintenance bypass/transformer cabinets (MBC-T) are available. These cabinets house the
                components necessary to:
                 • Provide an external wrap-around maintenance bypass switch for servicing the UPS
                 • Provide voltage transformation for site or application requirements
                 • Provide a means for neutral isolation and allow installations for site without a neutral conductor
                MBC-T cabinets are designed to be bolted to the left side of the UPS (see Figure 1). Refer to 4.5 -
                Locating the Cabinet, for further details.
                System Composition
                A UPS system can comprise a number of equipment cabinets, depending on the individual system
                design requirements—e.g., UPS cabinet and External Bypass cabinet. In general, all cabinets used
                will be the same height and are designed to be positioned side-by-side to form an aesthetically appeal-
                ing equipment suite.
                              Liebert                                        Liebert
            Maintenance         NX                          Maintenance        NX
              Bypass                                          Bypass                          Battery         Battery
              Cabinet                                         Cabinet                         Cabinet         Cabinet
            NX connected only to MBC                      NX connected to Maintenance Bypass Cabinet and Battery Cabinets
         (MBC must be on left side of the NX)                            (MBC must be on left side of the NX)
                                                              (Battery Cabinets must be on the right side of the NX in this
                                                                                    configuration)
                                                              Liebert
                                                                NX
                                                Battery                        Battery
                                                Cabinet                        Cabinet
                  !     WARNING
                        Before connecting input power to the NX, ensure that you are aware of the location and
                        operation of the overcurrent protection devices that connect the UPS input/bypass supply to
                        the power distribution panel.
                        De-energize and lockout or tagout all incoming high- and low-voltage power circuits before
                        installing cables or making any electrical connections.
                        NOTE
                        Table 10 gives nominal currents for determining the size of UPS power cables. Other
                        important factors to consider include cable route length and coordination with protective
                        devices.
The power cables can be sized to suit the UPS unit rating according to Table 10.
                                                                           Static Switch
                                               SW1/C    Contactor
          Bypass Input
CB1
                                                                                                      SW1/B
          Neutral Wire             Discharge
                                                               Battery
                                                               Charger
Battery
                         NOTE
                         Left-side access may be required when making power connections. Cable connections should be
                         made before a cabinet is attached to the left side of the NX or before the UPS is placed where
                         another obstruction, such as a wall, is against the NX’s the left side.
10
                        NOTE
                        External battery connection access requires removal of a protective panel on the lower front of
                        the UPS to the left of the bottom two battery shelves.
                                        C             B       A          C               B     A
                                                  OUTPUT                              BYPASS
                The internal batteries are connected with Anderson connectors inside the battery compartment. The
                batteries are connected to fuses to protect the NX and connected equipment (see Figure 4).
                                                B
                                            Bussmann
                                                                             B
                                                                       Bussmann                Battery fuses
                                             MADE IN USA                MADE IN USA
                                                                                               (fuses are behind
                                                                                               access plate on
                                                                                               front of UPS; see
                                                                                               Note on page 11)
11
                    !    WARNING
                         Failure to follow proper grounding procedures can result in electric shock hazard to personnel
                         or the risk of fire, should a ground fault occur.
                         NOTE
                         Proper grounding significantly reduces problems in systems caused by electromagnetic
                         interference.
                         NOTE
                         The ground and neutral busbars are easily accessible when the left protective cover plate is
                         removed. Cable connections should be made before a cabinet is attached to the left side of the
                         NX or before the UPS is placed where another obstruction, such as a wall, is against the NX’s
                         the left side.
                Output neutral
                busbar
                                                       OUTPUT                 INPUT
                                                       NEUTRAL               NEUTRAL
                                                                                                      Input neutral
                                                                                                      busbar
                    Ground
                    busbar
12
                  !    CAUTION
                       The operations described in this section must be performed by authorized electricians or
                       qualified technical personnel. If you have any difficulties, contact your local Liebert
                       representative or Liebert Global Services.
                       NOTE
                       Hydraulic pressure pliers, combinative tools and piston ring pliers should be used to connect
                       AC wiring.
                Once the equipment has been positioned and secured for operation, and the battery and ground col-
                lars have been connected (see 2.1.4 - Cable Connections), connect the power cables as described
                below. (Study the reference drawing in 7.0 - Installation Drawings.)
                1. Verify that all incoming high and low voltage power circuits are de-energized and locked out or
                   tagged out before installing cables or making any electrical connections.
                2. Remove the left side panel to gain easier access to the connections busbars.
                3. Connect the safety ground and any easier bonding ground bus cables to the copper ground busbar
                   located on the bottom of the equipment below the power connections. All cabinets in the UPS
                   system must be connected to the user’s ground connection.
                       NOTE
                       The grounding and neutral bonding arrangement must comply with the National Electrical
                       Code and all applicable local codes.
                4. Identify and make power connections with incoming cables according to Steps 5 through 11.
                       NOTE
                       Both the rectifier and bypass feeds MUST come from the same utility source, except if the UPS
                       system includes either a configuration F or P external maintenance bypass cabinet.
                  !    WARNING
                       If the load equipment will not be ready to accept power on the arrival of the commissioning
                       engineer, then ensure that the system output cables are safely isolated.
13
                   !   WARNING
                       The DC bus is live when this internal battery connection is made. This connection is to be
                       performed ONLY by Liebert Global Services at startup.
                    Observe the battery cable polarity. Be sure that the battery connector is made with the cor-
                    rect polarity.
                11. Refit all protective covers removed for cable installation
                                              U1                            K1
                                          DSP Control                Key & LED Board
                                                                                      M3
                                   M5                        U2
                                                                                 Parallel Logic
                            Auxiliary Power             Monitor Board
                                                                                    Board
                                                             X1
                                                        User Interface
                                                           Board
14
                                J8
                                                                            J3                J1
                   LCD                                                                                  J22                X7
J23 X6
J12
                                                                                                        J9
                   J2
                                                                                                                   PWR
                                                                                                        J15        MODEM
                                                                                                                   SNMP CARD      X5
                                                                                                        J16
J17
                                                                                     Intellislot 2
                                                                                                         X4
                                                                                                                      X4
                J13 J21 J25            J28           J4     J26 J30 J10              Intellislot 1
                                                                                                             J24
                                                                                     Intellislot 3
                BFP INV ACF           EPO          Dry in     MBC       BCB
                                                                                                                    NOTE: The black square ()
                         X1             X2                    X3                                                    on each slot indicates Pin 1.
15
                           NOTE
                           All auxiliary cables of terminal must be double-insulated. Wire should be 20-16AWG stranded
                           for maximum runs between 82 and 164 feet (25-50m), respectively.
        2.3.3   BCB Box Interface
                J10 is the BCB box interface.
                Table 3         BCB box interface
                   Position     Name       Description
                   J10.1         DRV       BCB Driver Signal - Reserved
                   J10.2          FB       BCB Contact State
                   J10.3         GND       Power Ground
                                           BCB On-Line - Input - This pin will become active when
                   J10.4          OL
                                           BCB interface is connected. (N.O.)
                           NOTE
                           All auxiliary cables of terminal must be double-insulated. Wire should be 20-16AWG stranded
                           for maximum runs between 82 and 164 feet (25-50m), respectively.
                           NOTE
                           If BCB interface is connected, a jumper needs to added between Pin 3 and Pin 4.
        Figure 9     Jumper connection for BCB interface
                                                     J10
                                                     DRV
                                                     GND
                                                      FB
                                                OL
                                                                    Aux – N.O.
                                                                    Aux – N.O.
16
+12V
           X1                                                                                                                          X2
                        J13                               J21                            J25                      J28
EPO-H
                                                                                                       ACF_O
                                      BFP_O
                                                                                 ACF_C
                                                                                                                            EPO-L
                BFP_C
                                                                                               ACF_S
                              BFP_S
                                                                        INV_O
                                                  INV_C
                                                                INV_S
                Table 4               Output dry contact relays
                 Position              Name    Description
                        J13.2         BFP_O    Bypass feedback protection relay. Normally open. Closed when bypass SCR is shorted.
                        J13.3         BFP_S    Bypass feedback protection relay center
                        J13.4         BFP_C    Bypass feedback protection relay. Normally closed. Open when bypass SCR is shorted.
                        J21.2         INV_O    Inverter mode relay. Normally open. Closed when UPS is in inverter mode.
                        J21.3         INV_S    Inverter mode relay center
                        J21.4         INV_C    Inverter mode relay. Normally closed. Open when UPS is in inverter mode.
                        J25.2         ACF_O    Main input fault relay. Normally open. Closed when main input is in fault.
                        J25.3         ACF_S    Main input fault relay center
                        J25.4         ACF_C    Main input fault relay. Normally closed. Open when main input is in fault.
                                 NOTE
                                 All auxiliary cables of terminal must be double-insulated. Wire should be 20-16AWG stranded
                                 for maximum runs between 82 and 164 feet (25-50m), respectively.
        2.3.5   EPO Input—Optional
                Firmware Before M200
                The UPS has an Emergency Power Off (EPO) function that operates by a button on the control panel
                or by a remote contact provided by the user. The EPO button is under a hinged, clear plastic shield.
                The X2 slot, shown in Figure 10, is the remote EPO input interface. It is active when shorted from
                EPO-L to EPO-H.
                If an external Emergency Stop facility is required, it is connected terminals EPO-L to EPO-H of the
                auxiliary terminal block (X2). It also is connected to the Normally Open remote stop switch between
                these two terminals using shielded cable (see Figure 10 and Table 5). If this function is not used,
                terminals EPO-L to EPO-H must be opened.
                Table 5     EPO input contact relays
                 Position               Name   Description
                        J28.2         EPO_L    Emergency Power Off Low
                        J28.4         EPO_H    Emergency Power Off High
                                 NOTE
                                 The Emergency Stop action within the UPS shuts down the rectifier, inverter and static
                                 bypass. It does not internally disconnect the input power supply.
                                 To disconnect ALL power to the UPS, open the upstream feeder breaker(s) when the remote
                                 EPO is activated.
17
                                                                             X2
                                                       J28
                                                     EPO - NO    EPO - NC
               Table 6      EPO input contact relays
                Position     Name      Description
                J28.1        EPO_NC    EPO Activated when opened to J28.2
                J28.2        EPO_NC    EPO Activated when opened to J28.1
                J28.3        EPO_NO    EPO Activated when shorted to J28.4
                J28.4        EPO_NO    EPO Activated when shorted to J28.3
                         NOTE
                         The Emergency Stop action within the UPS shuts down the rectifier, inverter and static
                         bypass. It does not internally disconnect the input power supply. To disconnect ALL power to
                         the UPS, open the upstream feeder breaker(s) when the remote EPO is activated.
                         NOTE
                         Normally Closed EPO – X2: 1,2, these terminals are supplied factory-linked on the monitor
                         board and must remain installed if using NC contacts.
                         NOTE
                         All auxiliary cables of terminal must be double-insulated. Wire should be 20-16AWG stranded
                         for maximum runs between 82 and 164 feet (25-50m), respectively.
18
        3.1   Introduction
              Liebert recommends that the batteries in external cabinets match the internal batteries in the NX in
              manufacturer and type.
              If using multiple sets of batteries connected in parallel to provide the required battery backup run
              times, fit each set with an isolating device to permit working on one of the battery sets while leaving
              the others in service and providing backup protection.
              When replacing batteries, replace with the same manufacturer and type, or equivalent. See your Lie-
              bert representative for a list approve batteries.
                     NOTE
                     The NX, as shipped, has 24 12-volt batteries installed internally in each unit.
        3.2   Safety
              Special care should be taken when working with the batteries associated with the NX system equip-
              ment. When all batteries are connected together, the battery terminal voltage may exceed 324V and is
              POTENTIALLY LETHAL.
                 !   WARNING
                     The NX's internal batteries are connected and energized even if the UPS is turned Off. To
                     minimize the risk of injury, a qualified service person should disconnect internal batteries
                     before any maintenance is performed on the unit.
                     The center of the battery is connected to the neutral of the UPS and is grounded.
                     A battery can present a risk of electrical shock and high short circuit current. The following
                     precautions should be observed when working on batteries:
                     • Remove watches, rings and other metal objects.
                     • Use tools with insulated handles.
                     • Wear rubber gloves and boots.
                     • Do not lay tools or metal parts on top of batteries.
                     • Disconnect charging source prior to connecting or disconnecting battery terminals.
                     NOTE
                     Full safety instructions concerning the use and maintenance of UPS batteries are provided in
                     the appropriate battery manufacturer's manuals, available on the manufacturer's Web site.
                     The battery safety information contained in this section relates to key considerations that must
                     be taken into account during the installation design process and might affect the design
                     outcome, depending on your installation.
19
                  !     CAUTION
                        Any battery system should be installed by qualified personnel.
                When installing an external battery cabinet that is NOT a Liebert NX battery cabinet, the customer
                must provide overcurrent protection. See Table 10 for sizing of protection devices.
                        NOTE
                        When using an external battery supply that is not provided with the UPS, please make
                        reference to the battery manufacturer’s installation manual for battery installation and
                        maintenance instructions, available on the manufacturer’s Web site. When replacing batteries,
                        Liebert recommends that the batteries in external cabinets be the same type used internally in
                        the NX. See Table 11 for a list of batteries that are approved for use with this product.
Removable retainer
Tray handle
                                                                              Insulated post
                                                                              for cabling
20
                          Battery
                          trays
          Battery tray
          support
                                                                                               Service
                                                                                               shelf
           Battery tray
21
22
           Power cables
           from batteries                                                                   Power cables exit battery
                                                                                            cabinet, enter Liebert NX
        Power cables
        (black) enter                                                                             RIGHT SIDE CABLE
        channel down side                                                                         ENTRY SHOWN;
        of NX to power                                                                            CUTOUTS ON LEFT
        input connections                                                                         SIDE PERMIT
                                                                                                  CONNECTION
                                                                                                  FROM THAT SIDE.
23
24
Sys In CB1
Qin UPS
                                      Input Mains
                                     Supply A B C
                                                     CB 1
                                           UPS 1
                                                     Rectifier
                                                    CB 1
                                 Charger
                                                                       SW1-C
                                                                                        Rotary
                                                                                        Switch
                                                        Static                          SW
                                                        Switch
Fuse
                                                            Inverter
                                                                       SW1-D
                                Battery 1
                                                                          N                      Ext Byp
                                                      ABC
                                Y
                                                                                 QoutUPS
To Load
25
                  !     WARNING
                        Please read this section thoroughly before attempting to install wiring to this unit.
                Extract screws
                from corners to
                remove the
                access plate
26
                       NOTE
                       Transient and steady state earth leakage currents may occur when starting the equipment.
                       This should be taken into account when selecting ground current detection devices because
                       these will carry the earth leakage currents of both the UPS equipment and the load.
                       NOTE
                       Input wiring must be installed using conduit if cabinet is not mounted to the immediate left of
                       the UPS.
                1. Locate the input wiring access (top or bottom access), remove the conduit landing plate and punch
                   the appropriate size hole for the size conduit being used. Pull the three/four input wires through
                   it, allowing some slack for installation. For cabinets that are located to the immediate left of the
                   UPS, the access plate is on the lower right of the cabinet. Remove the access plate and verify that
                   the edge guarding is installed and intact.See Figure 19.
                       Wiring access is on
                       lower right side of
                       Maintenance
                       Bypass Cabinet
Edge Guard
                2. Secure the conduit to the access plate of the Maintenance Bypass Cabinet.
                3. Input power cables connect to the system input circuit breaker. Refer to Figure 35 -
                   Maintenance Bypass interconnection
                4. Connect the ground (earth) wire to the earth busbar and tighten it to 44 lb-in. (5 N-m) (M6 bolt).
                5. Locate UPS input and output cables and access panel to UPS on lower right side. See Figure 19.
                       NOTE
                       If the maintenance bypass cabinet is not to be bolted to the UPS, use either top or
                       bottom access plate.
                6. Connect the system ground cable between the Maintenance Bypass Cabinet and UPS and tighten
                   the connections to 44 lb-in. (5 N-m) (M6 bolt).
27
               7. Connect the system input cables between the Maintenance Bypass Cabinet 'UPS Input' Busbars
                  (A-B-C N terminals) and UPS input busbars (A-B-C N terminals) and tighten the connections to
                  44 lb-in. (5 N-m) (M6 bolt).
               8. Connect the system outnput cables between the Maintenance Bypass Cabinet 'UPS Output'
                  Busbars (A-B-C N terminals) and UPS output busbars (A-B-C N terminals) and tighten the
                  connections to 44 lb-in. (5 N-m) (M6 bolt).
               9. Connect supplied control wire to X3 on the Parallel (M3) board (see Figure 20).
                 !    WARNING
                      The control wire must be installed to ensure proper operation of the system and fully protect
                      the load when switching between bypass cabinet and UPS.
:X T M IAN T
                                                                                                     485+
                                                                                                     485-
                                                             X2 2   P2
                 Terminal Block Location
                                                                                X3
                                                                               DBS
                                                             X2 1   P1
                      NOTE
                      For startup procedure, see the UPS operations and maintenance manual, SL-25210.
28
29
5.0 OPTIONS
LBS Cable
                The LBS function is activated with configuration software; when the LBS takes effect, the graphic
                LCD will display “LBS active.”
30
                                Supplied             N                                                           N
                                by Others
                                 UPS 1       CB 1                                             UPS 2       CB 1
                                              Rectifier                                                   Rectifier
                                                              SW1-C
SW1-C
                Fuse                                                          Fuse
                                              Static                                                       Static
                                              Switch                                                       Switch
                  Battery 1
Battery 2
                               Charger                                                      Charger
                                                                      SW1-D
SW1-D
Inverter Inverter
SW1-A SW1-A
ABC ABC
Q1Ext Q2Ext
To Load
31
32
                               1                  2
                                                            UPS             3                 4
                                                                                                          Interconnecting
                                                                                                               Cables
                          P2
P1
P2
P1
P2
P1
P2
P1
P4
P4
                                                                                                  P4
                          P3
P3
P3
P3
33
Figure 24 Auxiliary dry contact cables for output breaker in multi-module system
:X T M IAN T
                                                                                     485+
                                                                                     485-
                                           X2 2   P2
                                                                      X3
                                                                     DBS
                                           X2 1   P1
                  !      CAUTION
                         The auxiliary control wire must be installed to ensure proper operation of the system.
                         NOTE
                         For startup procedure, see the UPS operations and maintenance manual, SL-25210.
Input Distribution
QUPS QByp
To Load
34
UPS2
                                                                                      X2:3
                                                                                      X2:4    Monitor Board
                                                                   X2:3
                                                                           Monitor Board
                                                                   X2:4
UPS1
                    Normally
                    Open EPO
                                                                                        UPS2
                                                                                    X2:1
                                                                                             Monitor Board
                                                                                    X2:2
                                                                   X2:1
                                                                          Monitor Board
                                                                   X2:2
UPS1
                    Normally
                   Closed EPO
35
36
                                                                                                                   Midpoint
                                                                              8.3"
                                                                                                                    (GND)
        for control wiring
                                                                                                                    J10.2
                                                                                                                    J10.3
                                                                                                                      (+)
                                                                           (211.7mm)
                                                                                                                      (-)
        conduit entry                   Top View                                                       1
                                                                                                       2
                                            20.0"                                                      3
                                          (508mm)                                                      4
                     2.5"                   15.0"                                                      5
                                                                                                       6                                            Midpoint
                  (63.5mm)                (381mm)
                                                                                                      TB1                       (-)   (+)                CB
                                                                                                                                                         Load
           TB1                                                                                     COM Black                                             Side
                                                                                                      N.O. Red             Circuit Breaker
                                                                                                     N.C. Blue                                           CB
                                                                                                                                                         Line
                                                                                                                    (-) (+)            (-) (+)
                                                                                                                                                         Side
(+)
                                                                                                                                              (+)
                                                                                                                    (-)
                                                                                                                                        (-)
                32.3"                                               31.5"
              (819.2mm)                                           (800.1mm)
72 Cells 72 Cells
                              NOTE
                              1. The signal cables in this figure must be shielded and double-insulated.
                              2. Connect the Pes (Protection Earth) of the UPS cabinet and BCB box to the same point.
37
38
         Output
                                                                                            Maximum Recommended Lug
                              Nominal                             OCP
           Unit               Output                   OCP       Device                     Lug T&B           Lug T&B
          Rating              Current                 Current    Rating       Bolt Size   One Hole 54000   One Hole REDDY
              10                28                      35         35         6M (1/4”)       54130            62204
              15                42                      53         60         6M (1/4”)       54106            62204
              20                56                      70         70         6M (1/4”)       54106            62204
              30                84                     105        110         6M (1/4”)       54108            62205
         Battery
                                                                                            Maximum Recommended Lug
                                                                  OCP
           Unit               Battery                  OCP       Device                     Lug T&B           Lug T&B
          Rating              Current                 Current    Rating       Bolt Size   One Hole 54000   One Hole REDDY
           10/15                 55                     55         70         6M (1/4”)       54106            62204
           20/30                110                    110        125        8M (5/16”)       54153            62212
39
40
41
                                                                                                               Leveler
              1600
                                               90
                                                                                            Adjustable Stops
                      FRONT VIEW                              LEFT SIDE VIEW
                                                                                            (see Note 11)
         1. All dimensions are in millimeters.
         2. A minimum of 24 inches clearance above the unit is required for air exhaust.
         3. Installation and service access required. Left-side access recommended for maximum ease of
             installation.
         4. Keep cabinet within 15 degrees of vertical while handling.
         5. Top and bottom cable entry available through removal access plates. Remove punch to suit conduit size
             and replace.
         6. Unit bottom is structurally adequate for forklift handling.
         7. Open door to replace air filter, washable type, size 354x314.
         8. Threaded mounting holes used for seismic anchoring or floor stand. Note: If a floor stand is used, the
             weight of the unit must be supported under all casters.
         9. Each mounting location is supported by two 10 GA. (.135”) galvanized steel. The threaded 12mm insert
             is approximately 3/4” deep. Mounting bolts must be threaded into unit.
         10. Includes side panel. Refer to Detail A for dimension to frame with side panel removed. Side panels are
             removed between adjacent units that are bolted together.
         11. Adjustable stops are not designed to carry the full weight of the cabinet. Finger-tighten stop against the
             floor, then tighten with a wrench less than two turns for friction against the floor.
42
                                          Rear stabiliz-
                                          ing foot
Air
Air Exhaust
                                          Power Cable
                                          Entry Area
                                           Top and
                                           Bottom
                            Monitor
                            Board
                            (U2)
                     IntelliSlot                                                     Power
                     Communication                                                   Electronics
                     Ports
                             Input
                             Breaker
                           Rotary
                           System                                                    Battery
                           Switch                                                    Trays
                     Input Breaker
                     Access Plate
                       Internal and
                       External Battery
                       Terminal Block
                       Access Plate            Front View
                                                                                DPN U3812048
                                            (with door open)                    Rev. 1
43
                                                                                     AC output cable
                                                                                     connections
                                                                  Battery connections (+ N -)
                                                                    4.1 to battery
                                                                    4.2 to external battery cabinet
         NOTES
         1. All dimensions are millimeters.
         2. Top and bottom cable entry available through removable access plates. Remove, punch to
            accommodate conduit size and replace.
         3. Control wiring and power wiring must be run in separate conduit. Output and input cables must be
            run in separate conduit.
         4. Aluminum and copper-clad aluminum cables are not recommended,
         5. All wiring is to be in accordance with national and local electrical codes.
44
                                                                Battery
                                                                              186mm
417mm
687mm
45
DYNASTY BATTERY
                                                                       W506 to W507
                           +        -      +      -                                   +   -   +      -
W500 18pcs
+ - + - + - + -
+ - + - + - + -
+ - + - + - + -
                           W511 to W510
                                                                                      BOTTOM LAYER
W507 to W506
W509 to W508 + - + -
+ - + -
                                                                                      +   -   +      -
                       +        N          -
                                                CON4
+ - + -
46
                                                                                                        Midpoint (N)
                                                                                                                       Negative (-)
                                                                                         Positive (+)
                                             Positive (+)
                                                 Midpoint (N)
                                             Negative (-)
                                                         Breaker
                     Connection                           Detail                         Breaker
                       Detail                                                             Detail
                                                     A                                                                                A
           B                                                                                                                                               B
OR
          NOTES:
          1. All Liebert-supplied cable must be repositioned prior to and while the cabinets are being placed in
             their final installed location.
          2. All interconnection hardware supplied by Liebert
          3. All interconnection cables supplied by Liebert when bolted together.
          4. Interconnection cables field-supplied when battery cabinets are stand-alone.
          5. Refer to the individual drawing of each piece of equipment for additional details.
47
48
J J J
                                                      D1                                       D1                            K1                     H
         E1,E2
                                                      D2                          H           D2                  H          K2
                                                                                                                                                    B
         F1,F2                                                                                  B
                                             C       F1, F2                       I        F1,F2                   I          D1
                                             K1,K2      G                                      G                              D2
                                                                                                                              G
                                             D1,D2                                                                                                  I
                                                                                                                   A       F1,F2
                                          I                                                                                                         E1,E2
                 UPS Module Left Side View                       Type A00                           Type BR0                       Type DR1 & CR1
                   (Without Side Panel)
        NOTES:
        1. All Liebert-supplied cable will need to be repositioned prior to and while setting the cabinets in their
           installed location.
        2. All interconnection cable and hardware supplied by others.
        3. AC connections must be made to the UPS modules before attaching paralleling cabinet to UPS modules.
        4. Utility AC source neutral not required for maintenance bypass/transformer cabinet type CR1.
        5. Paralleling cabinets must between both UPS modules.
        6. Refer to the individual drawing of each piece of equipment for additional details
49
                            E                              H
                            H                              A
                            G                              C
                        B
                                                          D
                            D
                                                                                                       E
                                                                                                       H
        NOTES:
        1. All Liebert-supplied cable will need to be repositioned prior to and while setting the cabinets in their
           installed location.
        2. All interconnection cables and hardware supplied by Liebert.
        3. AC connections must be made to the UPS module before attaching.
        4. See Figure 45 for placement of distribution cabinet.
        5. Refer to the individual drawing of each piece of equipment for additional details.
50
                                                                               1 + N Parallel Cabinet
                                                                     (front view without front door and panel)
          1. All Liebert-supplied cable must be repositioned prior to and while setting the cabinets in their installed
             location.
          2. All interconnection cables and hardware supplied by others.
          3. AC connections must be made to the UPS modules before attaching paralleling cabinet to UPS modules
          4. The interconnecting output cables between the paralleling cabinet and the UPSes must be the same size
             and the same length.
          5. The location of the system output neutral busbar (connection K) and the ground busbar (connections H, I
             and J) are shown for a left-access style. For right-access version, these busbars are at opposite locations
          6. Refer to the individual drawing of each piece of equipment for additional details.
51
52
53
54
55
56
57
SlimLine
                                                          SlimLine
                               UPS                                        UPS        Battery
                                                          SlimLine
                                                                          MBC         UPS
                              SlimLine
SlimLine
SlimLine
                                                                 1+N              1+N
                  UPS                                          Paralleling      Paralleling
                                                                Cabinet          Cabinet
58
59
60
61
62
63
64
65
66
67
68
         Output
                                                                Maximum Recommended Lug
          Unit       Nominal System                         Lug T&B               Lug T&B
         Rating      Output Voltage       Bolt Size       One Hole 54000       One Hole REDDY
           30              600             6M (1/4”)            54130                62204
           30              480             6M (1/4”)            54106                62204
           30              240             6M (1/4”)            54108                62205
           30              220             6M (1/4”)            54108                62205
           30              208             6M (1/4”)            54108                62205
           20              600             6M (1/4”)              NA                 62204
           20              480             6M (1/4”)            54130                62204
           20              240             6M (1/4”)            54106                62204
           20              220             6M (1/4”)            54106                62204
           20              208             6M (1/4”)            54106                62204
           15              600             6M (1/4”)              NA                 62204
           15              480             6M (1/4”)              NA                 62204
           15              240             6M (1/4”)            54106                62204
           15              220             6M (1/4”)            54106                62204
           15              208             6M (1/4”)            54106                62204
           10              600             6M (1/4”)              NA                 62204
           10              480             6M (1/4”)              NA                 62204
           10              240             6M (1/4”)            54130                62204
           10              220             6M (1/4”)            54130                62204
           10              208             6M (1/4”)            54130                62204
69
70
NOTES
71
72
Emerson Network Power, the global leader in enabling business-critical                                         Technical Support / Service
continuity, ensures network resiliency and adaptability through                                                                  Web Site
a family of technologies—including Liebert power and cooling                                                              www.liebert.com
technologies—that protect and support business-critical systems.                                                               Monitoring
                                                                                                                             800-222-5877
Liebert solutions employ an adaptive architecture that responds
                                                                                                   monitoring@emersonnetworkpower.com
to changes in criticality, density and capacity. Enterprises benefit                                         Outside the US: 614-841-6755
from greater IT system availability, operational flexibility and                                                         Single-Phase UPS
reduced capital equipment and operating costs.                                                                               800-222-5877
                                                                                                     upstech@emersonnetworkpower.com
                                                                                                             Outside the US: 614-841-6755
                                                                                                                         Three-Phase UPS
                                                                                                                             800-543-2378
                                                                                                   powertech@emersonnetworkpower.com
                                                                                                                  Environmental Systems
                                                                                                                             800-543-2778
                                                                                                                 Outside the United States
                                                                                                                             614-888-0246
                                                                                                                                        Locations
                                                                                                                                 United States
                                                                                                                         1050 Dearborn Drive
                                                                                                                               P.O. Box 29186
                                                                                                                        Columbus, OH 43229
                                                                                                                                       Europe
                                                                                                                      Via Leonardo Da Vinci 8
                                                                                                                     Zona Industriale Tognana
                                                                                                               35028 Piove Di Sacco (PD) Italy
                                                                                                                            +39 049 9719 111
While every precaution has been taken to ensure the accuracy
and completeness of this literature, Liebert Corporation assumes no
                                                                                                                       Fax: +39 049 5841 257
responsibility and disclaims all liability for damages resulting from use of                                                              Asia
this information or for any errors or omissions.                                                                7/F, Dah Sing Financial Centre
© 2006 Liebert Corporation                                                                                     108 Gloucester Road, Wanchai
All rights reserved throughout the world. Specifications subject to change
without notice.                                                                                                                    Hong Kong
® Liebert and the Liebert logo are registered trademarks of Liebert                                                              852 2572220
Corporation. All names referred to are trademarks                                                                          Fax: 852 28029250
or registered trademarks of their respective owners.
SL-25215_REV6_11-06
Business-Critical Continuity, Emerson Network Power and the Emerson Network Power logo are trademarks and service marks of Emerson Electric Co.
©2006 Emerson Electric Co.