Fire Detection &
Alarm System (FDAS)
P R ES EN T ED B Y :
DR. VICENTE Y. BUENCONSEJO JR., PECE
FACULTY, COLLEGE OF ENGINEERING
COLEGIO SAN AGUSTIN – BACOLOD
vicbuen76@gmail.com
Outline
2
1. Scope and Fundamentals
2. Design Requirements
3. Installation Requirements
4. Maintenance, Testing and Inspection
1. Scope and Fundamentals
3
Scope
This Code covers the design and application, installation,
maintenance, testing, and inspection of fire
detection and alarm system. It does not cover fire suppression
system
Purpose
The purpose of this Code is to define the means of signal
initiation, transmission, notification, annunciation,
emergency two-way communication, and emergency voice
evacuation in fire detection and alarm system. The Code
establishes the minimum required levels of performance and
quality of installation
1. Scope and Fundamentals
4
Application
All installations of automatic fire detection and alarm
system shall comply with the general design and
installation requirements.
1. Scope and Fundamentals
5
Definitions
Addressable Device -An FDAS component that can be
individually identified of its status or used to individually
control other functions.
Addressable System -A system consisting of an
addressable fire alarm control panel and addressable
devices that primarily give the exact location of a fire,
among other features.
1. Scope and Fundamentals
6
Definitions
Alarm -A notice or warning of danger
False Alarm -An alarm caused by a non-fire incident or activity
such as smoking, cooking, etc
Nuisance Alarm -An alarm caused by malfunction, equipment
defect, improper installation, or poor maintenance.
Alarm Zone -Location or part of the protected building or
premises. The detection of a firewill be indicated distinctly
and independently from an indication of fire in any other
location.
Authority Having Jurisdiction (AHJ) -The office of
Bureau of Fire Protection and the Office of Building Official.
1. Scope and Fundamentals
7
Definitions
Annunciator -An FDAS
component containing one or
more indicator lamps/LED’s or
alphanumeric displays in which
each indication provides status
information about an
addressable or conventional
device, a group of devices, a zone,
a circuit, or an LCD and Graphic
condition.
1. Scope and Fundamentals
8
Definitions
Annunciator
1. Scope and Fundamentals
9
Definitions
Central Station -An entity controlled and operated by a
person, firm, or corporation whose business is the monitoring,
recording, and maintaining of supervised alarms
automatically transmitted to it by the FDAS of a subscriber of
this service, and who upon receipt of such signals shall take
such actions as required by the AHJ and the subscriber.
Conventional Device -An FDAS component, such as a
smoke detector, heat detector, or manual fire alarm station,
that does not have an electromechanical or software address
that gives it a discrete identity.
1. Scope and Fundamentals
10
Definitions
Conventional System -A system with a conventional fire
alarm control panel and conventional devices that is wired in a
way that divides the protected building or premises
into parts or subdivisions which are called alarm zones.
1. Scope and Fundamentals
11
Definitions
Detector -A device or component that is used to sense the
products of fire, such as smoke, heat, flame, or carbon
monoxide.
Smoke Detector - A detector that detects particles of
combustion, whether visible or invisible. See Figure 1-2 and 1-3
1. Scope and Fundamentals
12
Definitions
Detector -A device or component that is used to sense the
products of fire, such as smoke, heat, flame, or carbon
monoxide.
Smoke Detector - A detector that detects particles of
combustion, whether visible or invisible. See Figure 1-2 and 1-3
1. Scope and Fundamentals
13
Definitions
Heat Detector - A detector that
detects abnormally high temperature,
abnormally fast rate of temperature
rise, or both. See Figure 1-4
Figure 1-4 Fixed Temperature
and Rate of Rise Heat Detector
1. Scope and Fundamentals
14
Definitions
Multi-criteria Detector - A detector that
contains two or more sensors that tracks
the corresponding products of fire, such as
smoke, heat, flame, or carbon monoxide,
and transmits signals to the fire alarm
control panel, which shall mathematically
evaluate them with pre-programmed
algorithms to determine when an alarm
signal is warranted. The evaluation may
Figure 1-6 Miiltisensor
also be performed at the detector. The
Detector Optical /
objective of using this type of detector is to Thermal/Chemical
reduce false alarms. See Figure 1-6
1. Scope and Fundamentals
15
Definitions
Duct Detector - A smoke detector,
using sampling tubes, that senses
smoke in the air circulating within
air-conditioning or ventilating
ducts. See Figure 1-7 Figure 1-7
Duct Detector
1. Scope and Fundamentals
16
Definitions
Beam Detector - A smoke
detector that senses smoke along
a continuous path, usually
installed in high-ceiling areas. It
is alternately called a projected
beam smoke detector. See Figure
1-8 and 1-9
Figure 1-8 Reflective
Beam Detector
1. Scope and Fundamentals
17
Definitions
Beam
Detector
Figure 1-9 Beam
Detector details
1. Scope and Fundamentals
18
Definitions
Flame Detector - A detector
that senses and detects the
radiant energy emitted by a
flame. See Figure 1-10
Figure 1-10 Ultraviolet
Flame Detector
1. Scope and Fundamentals
19
Definitions
Air Sampling-type Detector -A
detector that consists of a piping
layout network that runs from the
detector to the protected area or
areas. A fan inside the detector
housing draws air from the
protected area or areas through air
sampling holes or ports on the
piping network. The air is then
evaluated and analyzed at the
detector to determine if an alarm
Figure 1-11 Air Sampling
signal is warranted. See Figure 1-11 Type Detector
1. Scope and Fundamentals
20
Definitions
Carbon Monoxide Detector -
A detector that senses and
detects abnormally high
levels of carbon monoxide. See
Figure 1-12
Figure 1-12 Carbon
Monoxide Detector
1. Scope and Fundamentals
21
Definitions
Emergency Communications System - A sub-system of
an FDAS that broad casts the existence of a fire or an
emergency situation, or communicates information necessary
to facilitate an appropriate action.
Emergency Voice Alarm Communication (EVAC) - It is a
sub-system that broadcasts information during an emergency to
the occupants of a building or facility and instructs appropriate
actions to them, such as evacuating. It is conveyed by audible or
visible means, or both.
1. Scope and Fundamentals
22
Definitions
Two-Way Emergency Communications System - It is a sub-
system intended for use by the building fire safety personnel or by
fire fighters and first responders to both exchange information and
to communicate information, such as condition of local
environment, condition of persons, to give assurance that help is on
the way, or other instructions. See Figure 1-13, 1-14 and 1-15
Figure 1-13 Figure 1-14 Figure 1-15 Telephone
Telephone Jack Telephone Jack Mobile Handset
1. Scope and Fundamentals
23
Definitions
Fire Alarm Control Panel (FACP) - An FDAS component, provided
with primary and secondary power supplies that receives signals from
initiating devices, such as detectors and manual fire alarm stations and
processes these signals to determine the required output functions, such
as activation of notification appliances, annunciators, and the one-way
emergency communications system. See Figure 1-16
1. Scope and Fundamentals
24
Definitions
Figure 1-16 FDAS Process
1. Scope and Fundamentals
25
Definitions
Conventional Fire Alarm Control Panel - An FACP that
comes with one or more alarm zones. It can only connect
conventional devices. See Figure 1-17
Figure 1-17 Conventional
Fire Alarm Control panel
1. Scope and Fundamentals
26
Definitions
Addressable Fire Alarm Control
Panel - An FACP that comes with one
or more signaling line circuits, called
addressable loops, to which
addressable devices are connected.
Conventional devices may also be
connected to these loops through input
addressable modules. Also known as
Intelligent FACP. See Figure 1-18
Figure 1-18
Conventional/Intelligent
Fire Alarm Control panel
1. Scope and Fundamentals
27
Definitions
Fire Command Center - The room or
principal location wherein the FACP and
other life safety system are located to
display and monitor all fire alarms and
system troubles, and from which all
output functions are automatically and
manually controlled. Requirements for
Fire Command Center shall follow the
provisions stipulated in the Implementing
Rules and Regulation of Republic Act
9514, the revised fire code of the
Figure 1-19
Philippines 2008, Division 19, Chapter
Graphic Monitor Center
10.2.19.5, see Annex D. See Figure 1-19
1. Scope and Fundamentals
28
Definitions
Manual Fire Alarm Station -An FDAS component that is
manually operated to initiate a fire alarm signal. See Figure 1-20
Figure 1-20
Manual Call Point
1. Scope and Fundamentals
29
Definitions
Notification Appliance -
An FDAS component such
as a bell, horn, speaker,
strobe, or text display that
provides audible or visible
outputs, or both.
See Figure 1-21, 1-22, 1-23,
1-24, 1-25, 1-26, 1-27, 1-28,
1-29,1-30,1-31,1-32,1-33
and 1-34.
1. Scope and Fundamentals
30
Definitions
1. Scope and Fundamentals
31
Definitions
1. Scope and Fundamentals
32
Definitions
1. Scope and Fundamentals
33
Definitions
Audible Notification Appliance - A notification appliance that
warns by the sense of hearing
Exit Marking Audible Notification Appliance - An audible
notification appliance that arks building exits, floor exits, stairwells,
or paths to exits for the purpose of evacuation.
1. Scope and Fundamentals
34
Definitions
Visible Notification
Appliance - A
notification appliance
that warns by the sense
of sight.
Tactile Notification
Appliance - A
notification appliance
that warns by the sense
of touch or vibration.
1. Scope and Fundamentals
35
Definitions
Personnel - People, who install, maintain, service, test, and/or
inspect fire detection and alarm system.
Maintenance and Service Personnel - Individuals who
perform cleaning, adjustments, replacements of equipment &
components, system programming, and other maintenance
work according to the manufacturer’s recommendations for the
system to perform as required.
Testing Personnel -Individuals who perform physical checks,
tests, and procedures to determine whether a system performs as
required for acceptance or reacceptance.
1. Scope and Fundamentals
36
Definitions
Personnel - People, who install, maintain, service, test, and/or
inspect fire detection and alarm system.
Inspection Personnel - Individuals representing the AHJ who
perform physical checks, tests, and procedures to determine
whether a system functions and performs as required, as
partial compliance for issuance of a Fire Safety Inspection
Certificate (FSIC).
1. Scope and Fundamentals
37
Definitions
Power Supply - It is the source of electricity that provides the
power needed to operate the FACP, and consequently all devices
connected to it. See Figure 1-35
Primary Power Supply - It is the 220VAC power voltage from
the electrical utility company. Within the FACP it is converted to
the system voltage of 24VDC.
Secondary Power Supply - When there is a failure of the
primary power supply, the batteries (serving as the secondary
power supply) automatically switch over to provide uninterrupted
power to the system
1. Scope and Fundamentals
38
Definitions
Power Supply - It is the source
of electricity that provides the
power needed to operate the
FACP, and consequently all
devices connected to it. See
Figure 1-35
1. Scope and Fundamentals
39
Definitions
Semi-addressable System - A system consisting of an addressable
fire alarm control panel and conventional devices connected to it
through input addressable modules.
Shall - Indicates a mandatory requirement.
Should - Indicates a recommendation, but not required.
1. Scope and Fundamentals
40
General Requirements
All buildings, facilities, houses, structures, and premises, except those
specified in Clause 1.6.1, shall have fire detection and alarm system
that complies with the requirements of this Code.
The fire detection and alarm system shall be for the protection of life
or property, or both, by detecting and notifying the existence of fire,
smoke, heat, or other emergencies that impact and affect the
protected premises.
1. Scope and Fundamentals
41
General Requirements
The fire detection and alarm system shall have one or more of the
following functions:
1. Automatic detection of smoke and/or heat, and manual fire alarm
signal initiation
2. Activation of fire alarm notification appliances
3. Emergency communications system
4. Activation of annunciators
5. Monitoring of abnormal conditions in fire suppression system
6. Activation of fire safety functions
7. Transmission of alarm signal to an off-premise Central Station
1. Scope and Fundamentals
42
General Requirements
The fire detection and alarm system shall, at the very least, consist of
a fire alarm control panel, the appropriate automatic detectors,
manual fire alarm station(s), and notification appliance(s)
The type or kind of equipment, location, mounting, spacing, and
other engineering considerations in the design of the fire detection
and alarm system shall comply with the requirements of Chapter 2
The installation of the fire detection and alarm system shall comply
with the requirements of Chapter 3.
1. Scope and Fundamentals
43
General Requirements
The properly designed, installed, and accepted fire detection and
alarm system shall undergo annual testing and inspection by the AHJ
for reacceptance, as specified in Chapter 4.
The primary power supplied to the fire alarm control panel, and
hence to the entire system, shall be from a dedicated and exclusive
branch circuit. The secondary power supply shall ave sufficient
capacity to operate the system under normal non-alarm condition for
a minimum of 24 hours, and at the end of that period, capable of
operating all alarm notification appliances and emergency
communications system for a period of 30 minutes.
1. Scope and Fundamentals
44
General Requirements
Detectors, manual fire alarm stations, notifications appliances,
emergency communications devices, and annunciators shall be
installed throughout all parts of the building, facility, structure, or
house as required under Chapter 2.
An alarm zone shall have a maximum floor area of 800 sq. m. A
separate alarm zone shall be provided for each 800 sq.m, of protected
floor area.
The color of the manual fire alarm station must be red.
1. Scope and Fundamentals
45
General Requirements
Audible notification signal shall have a sound level of at least 15 dB
above the average ambient sound level, or 5 dB above the maximum
sound level having a duration of at least 30 seconds or 75 dBA,
whichever is greater, measured 1.40 meters above the floor in the
area required to be served.
Emergency communications system shall be installed in buildings,
facilities, or structures are required to have such sub-system under
Chapter 2.
1. Scope and Fundamentals
46
USE OF BATTERY-OPERATED SMOKE/HEAT DETECTORS
Buildings, structures, facilities, houses, or premises that are not record
and refer of protection code, more than 400 sq.m, in total floor area,
not more than two floors or less and with a height of not more than 10
meters may choose not to install a fire detection alarm system.
However, in its place, battery-operated, stand-alone detectors shall be
installed. Each battery-operated, stand-alone detector shall cover a
floor area of not more than 50 sq m Each room shall be separately
protected.
In buildings, structures, facilities, houses, or premises that are over
and above the specified in Clause 1.6.1, battery-operated detectors
shall not substitute or take the place wired detectors in the fire
detection and alarm system
1. Scope and Fundamentals
47
AREAS WHERE DETECTION IS REQUIRED
Further to Clause 1.5.9, the following are areas or spaces where
detection is required. Refer to Division 8 to 19 of the Fire Code of the
Philippines in Annex E.
1. The spaces under raised floor more than 600 mm in height. If
conventional detectors are used they should be wired as a separate
alarm zone.
2. The spaces above drop ceiling more than 1 meter in height. If
conventional detectors are used they should be wired as a separate
alarm zone.
3. Concealed spaces under the roof more than 1 meter in height. If
conventional detectors used, they should be wired as a separate
alarm zone
1. Scope and Fundamentals
48
AREAS WHERE DETECTION IS REQUIRED
Further to Clause 1.5.9, the following are areas or spaces where
detection is required. Refer to Division 8 to 19 of the Fire Code of the
Philippines in Annex E.
4. Stairwells, with detection at each floor level
5. Return air ducts of air conditioning system using sampling tubes
6. Tunnels linking two or more buildings
7. Vaults or the like
8. Vertical shafts
1. Scope and Fundamentals
49
AREAS WHERE DETECTION IS NOT REQUIRED
Detectors are not required in the following locations:
1. Toilet and/or bathroom with a floor area of less than 4 sq.m
2. Exhaust ducts exhausting from toilets and/or bathrooms
3. Any walk-in type enclosure with a floor area not more than 1 sq. m.
provided its content is minimal fire risk, or one with floor area not
more than 0.5 sq.m, if it contains electrical communication
equipment.
4. The spaces under raised floor with a height of 250 mm or less.
5. The spaces above drop ceiling with a height of 1 meter or less without
combustible materials.
1. Scope and Fundamentals
50
AREAS WHERE DETECTION IS NOT REQUIRED
Detectors are not required in the following locations:
6. Concealed spaces under the roof with a height of 1 meter or less
without combustible materials.
7. Covered paths: balconies, open-sided covered walkways & staircases,
overhanging roof art verandas, provided they are not used for storage
of goods.
8. The area under structures such as platforms, ducts, and the like,
within a protected room areas, which are less than 3 meters in width,
provided the free flow of air reaching the detection mounted above is
not obstructed.
1. Scope and Fundamentals
51
CENTRAL STATION ALARM MONITORING
All installed FDAS should subscribe to the alarm monitoring s services
of a central station. All alarm signals received by the monitoring central
station shall be forwarded or redirected to fire fighting authorities
The competence of the operators of the central station shall be certified
by the manufacturer of the receiving system or equipment, or by an
organization acceptable to the AHJ.
1. Scope and Fundamentals
52
CENTRAL STATION ALARM MONITORING
REFERENCES
53
1. The Philippine Electronics Code (2016). Fire
Detection and Alarm System. Institute of the
Electronics Engineers of the Philippines, Inc.
Manila
2. RA 9154 (2008). Fire Code of the Philippines.
3. RA 9292 (2004). Electronics Engineering Law of
2004.
54