Quick Track Positioner
Quick Track Positioner
_____________________________________________________________________________________
        STI s.r.l. via pascoli 10 A/B 24020Gorle (Bg) – ITALY www.stistrumentazione.com
INDEX
1.         Description                                                             3
     1.1   System description                                                      3
     1.2   Specification and option                                                4
     1.3   Fail mode operation                                                     5
     1.4   Manufacturer’s identification                                           8
2.         General safety instruction                                             10
     2.1   Installation                                                           10
     2.2   Maintenance                                                            10
3.         Installation                                                           10
     3.1   Servovalve mounting                                                    10
     3.2   Controller mounting                                                    11
     3.3   Power board connections                                                12
     3.4   Display board connections                                              17
4.         Maintenance operation                                                  20
     4.1   Stepping motor                                                         20
     4.2   Spool valve manifold Cv 7                                              21
     4.3   Spool valve manifold Cv 22                                             22
     4.4   Controller                                                             23
     4.5   Position transmitter probe                                             23
ANNEX
I User Manual 24
_____________________________________________________________________________________
        STI s.r.l. via pascoli 10 A/B 24020Gorle (Bg) – ITALY www.stistrumentazione.com
1.0 DESCRIPTION
Cv 22 model Cv 7 model
_____________________________________________________________________________________
        STI s.r.l. via pascoli 10 A/B 24020Gorle (Bg) – ITALY www.stistrumentazione.com
        1.1.7   Fail-Mode pneumatic valves (2W, 4W for Cv 22 model and 3W or 2W for Cv 7 model)
                The fail mode is made by those pneumatic valves that are piloted by the solenoid valve (EV).
                The 4-way and 2-way pneumatic valve mounted on Cv 22 device are designed only as safety unit,
                not suitable for continuous service
_____________________________________________________________________________________
        STI s.r.l. via pascoli 10 A/B 24020Gorle (Bg) – ITALY www.stistrumentazione.com
        1.2.5   Specifications
                                                         Standard                              Option
                Input Signal / Position     4-20 mA; Hart protocol
                Feedback
                Maximum power               95W
                consumption
                Power Supply Module         120 Vac ±10% 50-60Hz ±5%
                                            240 Vac ±10% 50-60Hz ±5%
                                            110Vdc ±10% 1A
                                            48Vdc ±10% 3A
                                            24Vdc ±10% 5A
                Servo-Valve, Mounting       Actuator                               Remote
                Digital Controller,         Actuator                               Remote
                Mounting
                Digital Controller, Cable   6.0 ft (~ 1.8 m)                       100 ft ( ~ 30 m)
                Length
                Electrical Classification   EMC
                Certification for           IP66; UL ordinary location; NEMA4X
                Ordinary Location
                Certification for           Eexd IIC T5/T6 ATEX for motor
                Hazardous Location          enclosure
                                            Eexd IIB T5/T6 ATEX for controller
                                            enclosure
                Temperature Rating          -4 to 158 F (-20°C to 70 °C)               -40 to 212 F (-40°C to 100 °C)
                Air supply                  60 to 100 psig (4 to 7 barg)
        1.3     FAIL MODE OPERATION
                QuickTrak™ will fail on loss of power, loss of air supply or loss of signal.
                -    Loss of power: causes the Digital Controller to trip the Solenoid Valve for Fail Mode
                -    Loss of air supply: is detected by a pressure transducer in the Servo-Valve; the Digital
                     Controller trips the Solenoid Valve for Fail Mode when the air pressure drops below a set point
                     in the Controller software
                -    Loss of signal: causes the Digital Controller to position the valve at its fail position.
_____________________________________________________________________________________
        STI s.r.l. via pascoli 10 A/B 24020Gorle (Bg) – ITALY www.stistrumentazione.com
FAIL CLOSED
FAIL OPEN
FAIL IN PLACE
_____________________________________________________________________________________
        STI s.r.l. via pascoli 10 A/B 24020Gorle (Bg) – ITALY www.stistrumentazione.com
FAIL IN PLACE
FAIL OPEN
FAIL CLOSED
_____________________________________________________________________________________
        STI s.r.l. via pascoli 10 A/B 24020Gorle (Bg) – ITALY www.stistrumentazione.com
QTIII –
          Size
          1 – CV 7
          2 – CV 22
          Location
          O – Ordinary
          H – Hazardous
          Certification
          A – American (UL)
          E – European (CE – ATEX)
          Fail action
          O – Open
          C – Closed
          L – Lock in position
          Umbilical lengh
          1 – 6 ft
          2 – 12 ft
          3 – 100 ft
          9 – Special
          Supply
          1 – 120 Vac (50÷60 Hz)
          2 – 240 Vac (50÷60 Hz)
          3 – 24 Vdc
          4 – 48 Vdc
          5 – 110 Vdc
          9 – Special
_____________________________________________________________________________________
        STI s.r.l. via pascoli 10 A/B 24020Gorle (Bg) – ITALY www.stistrumentazione.com
               Every positioner mod. QUICK TRAK™III is provided with a name plate with its serial number. The
               year of manufacturing is indicated by the first two numbers of the serial number.
_____________________________________________________________________________________
        STI s.r.l. via pascoli 10 A/B 24020Gorle (Bg) – ITALY www.stistrumentazione.com
               The non-observation of the following safety instructions and of the instruction manuals can result in
               with serious injury.
        2.1    Installation
                - Must be done by qualified person trained to operate
                - A ground tap is necessary
                - The electrical and pneumatic connections must be done according to the diagram and label
                - The supply circuit must be protected in case of current exceeding the limit fixed
                - The equipment must be provided with cable entries and filler plugs certified according to the
                   required certification
                - The actuator must be installed and used according to the project design specification.
                - The fluid must be chemically compatible with the used gaskets and lubricant
                - The supply circuits must be protect in case of current exceeding the limits fixed The user has to
                   ensure prior to start up and during operation that the pressure transducers are correctly fixed
                   inside the enclosure all the time
                - The rated values for pressure transducer must be observed
        2.2    Maintenance
               - Must be done by qualified person
               - Cleaning must be done with a humid cloth
               - Greases and oils must be used according to the manufacturer’s instructions, however their
                  flammability point must be > 140°C
3. INSTALLATION
               The servovalve mounting and connection to the cylinder will be designed and provided by the
#              manufacturer. The servovalve motor enclosure has two electric conduit connections. One of these is
               for connection to the controller. The second is for connection to a solenoid valve for the safety
               shutdown system. The solenoid valve and wiring for this will be supplied and specified by the
               manufacturer.
               Refer to the project's documentation for the specific electrical diagram.
        CAUTION: Do not extend or re-wire the connections from the umbilical without consulting STI.
        Improper operation due to electrical interference may result.
_____________________________________________________________________________________
        STI s.r.l. via pascoli 10 A/B 24020Gorle (Bg) – ITALY www.stistrumentazione.com
               The controller enclosure is rated for NEMA4X / IP66 environment, which is watertight to “wash
               down”, such as a water hose. Outdoor mounting is acceptable, however, the controller should be
               protected from direct sunlight by a suitable sun shield (see temperature ratings).
               The controller should be mounted securely to a sturdy mechanical surface using four screws in the
               enclosure mounting flange holes, with washers. See the picture for hole size and position. The
               structure, at the controller mounting location, should not be subjected to temperatures higher than
               the maximum ambient temperature described above.
_____________________________________________________________________________________
        STI s.r.l. via pascoli 10 A/B 24020Gorle (Bg) – ITALY www.stistrumentazione.com
J4 (already wired by the manufacturer) is the stepper motor connection (terminals 1-2-3-4).
_____________________________________________________________________________________
        STI s.r.l. via pascoli 10 A/B 24020Gorle (Bg) – ITALY www.stistrumentazione.com
_____________________________________________________________________________________
        STI s.r.l. via pascoli 10 A/B 24020Gorle (Bg) – ITALY www.stistrumentazione.com
_____________________________________________________________________________________
        STI s.r.l. via pascoli 10 A/B 24020Gorle (Bg) – ITALY www.stistrumentazione.com
AC power : Standard available are 120 Vac and 240 Vac for alternate current power.
          J10
          1         AC
          2         AC
          3         EARTH
3.3.4.1 Fuses
                                     Supply / Fuse       F1          F2
                                        120 Vac       2A T        2A T
                                        240 Vac       1A T        1A T
                                         24Vdc        5A T        5A T
                                         48Vdc        2,5A T      2,5A T
                                        110Vdc        2A T        2A T
When the led LD17 is ON, it shows that the electronic board is powered.
_____________________________________________________________________________________
        STI s.r.l. via pascoli 10 A/B 24020Gorle (Bg) – ITALY www.stistrumentazione.com
         The led LD4, LD5, LD6 mounted on the power board show the status of the digital output 1, 2, 3
         respectively.
         The led LD1, LD2, LD3 mounted on the power board show the status of the EV1, EV2, EV3 respectively.
         The led LD7 shows that the presence of the 24VDC power.
_____________________________________________________________________________________
        STI s.r.l. via pascoli 10 A/B 24020Gorle (Bg) – ITALY www.stistrumentazione.com
_____________________________________________________________________________________
        STI s.r.l. via pascoli 10 A/B 24020Gorle (Bg) – ITALY www.stistrumentazione.com
               No maintenance operations are required on the stepping motor. In case of abnormal noise or
               malfunction contact STI.
               In case of complete motor and replacement in the field be careful at the following instructions to
               remove the spool valve from the manifold:
               -   unscrew the screws (pos. 18)
               -   lift the motor enclosure (pos. 16) slightly to insert a wrench onto the motor shaft slot
               -   de-couple the gear (pos. 21) from the split nut (pos. 7) with a counter clockwise rotation of the
                   wrench
               -   remove the anti-rotation device cover (pos. 1 and screws pos. 2) from the manifold side and
                   unscrew the anti-rotation pin (pos. 24)
               -   slip off the spool (pos. 2)
               -   push the sleeve to remove it from the manifold.
_____________________________________________________________________________________
        STI s.r.l. via pascoli 10 A/B 24020Gorle (Bg) – ITALY www.stistrumentazione.com
               No maintenance operations are required on the spool valve manifold. In case of abnormal noise or
               malfunction contact STI.
_____________________________________________________________________________________
        STI s.r.l. via pascoli 10 A/B 24020Gorle (Bg) – ITALY www.stistrumentazione.com
               No maintenance operations are required on the spool valve manifold. In case of abnormal noise or
               malfunction contact STI.
_____________________________________________________________________________________
        STI s.r.l. via pascoli 10 A/B 24020Gorle (Bg) – ITALY www.stistrumentazione.com
No maintenance operations are required on the controller. In case of malfunction contact STI.
                    If a complete replacement is required, disconnect all electrical wire and remove the fixing screw from
                    the back of the enclosure (see 3.2).
No maintenance operations are required on the probe. In case of malfunction contact STI.
                    In case of complete replacement disconnect all electrical wire and remove the probe from the top of
                    cylinder.
Le informazioni riportate sul seguente manuale sono coperte da copyright. Tutti i diritti sono riservati. Nessuna parte di questo
manuale e della relativa documentazione citata e/o allegata può essere riprodotta senza il preventivo consenso scritto della STI s.r.l.
STI s.r.l. non si assume alcuna responsabilità per eventuali danni a persone, apparecchiature o dati conseguenti all’uso improprio del
prodotto a cui il manuale si riferisce.
Le informazioni contenute in questo documento sono soggette a modifiche senza preavviso.
Information in this manual is protected by copyright. All rights are reserved. No part of this manual and relevant mentioned and/or
enclosed documentation may be reproduced without written authorization by STI s.r.l.
STI s.r.l. is not responsible for possible damage to people, equipment or data which might arise from incorrect use of the product to
which the manual is referred.
Information in this document may be modified at any time without notice.
_____________________________________________________________________________________
        STI s.r.l. via pascoli 10 A/B 24020Gorle (Bg) – ITALY www.stistrumentazione.com
                                User manual
                                             Referred to :
_____________________________________________________________________________________
        STI s.r.l. via pascoli 10 A/B 24020Gorle (Bg) – ITALY www.stistrumentazione.com
INDEX
1     DESCRIPTION ..........................................................................................................................................................28
1.1             CONTROLLER SWITCH ON / OFF ..............................................................................................................29
4 GRAPH....................................................................................................................................................................133
_____________________________________________________________________________________
        STI s.r.l. via pascoli 10 A/B 24020Gorle (Bg) – ITALY www.stistrumentazione.com
1   DESCRIPTION
        The Quick Trak III controller can be locally operated by:
• a local device monitor and 4-key keyboard located under the monitor
_____________________________________________________________________________________
        STI s.r.l. via pascoli 10 A/B 24020Gorle (Bg) – ITALY www.stistrumentazione.com
_____________________________________________________________________________________
        STI s.r.l. via pascoli 10 A/B 24020Gorle (Bg) – ITALY www.stistrumentazione.com
2     SOFTWARE INSTALLATION
2.1   REMOTE CONTROL SOFTWARE
      If a remote PC control via RS 232 is required, a management software should be installed on the laptop. The
      minimum system requirements are : MS-Windows-98, Windows-NT 4.0, Service Pack 5 or 6a, Windows 2000 or
      Windows XP.
      To install the software:
      -    make sure that the minimum hardware requirements are met
      -    start Windows
      -    shut down all running programs
      -    insert the provided CD
      -    install routine should start automatically otherwise activate the program “SETUP.exe”
      -    follow the instruction
      -    insert the password. The standard software manufacturer default password is: 1 2 3 4 5
      -    download the parameters to test the communication
The parameters download is available in the main command line (pull-down device menu).
_____________________________________________________________________________________
        STI s.r.l. via pascoli 10 A/B 24020Gorle (Bg) – ITALY www.stistrumentazione.com
At the end of the download phase the configuration parameters fields will be update.
      Or select it directly:
      C:\Program Files\STI s.r.l\Loader\Loader.exe
_____________________________________________________________________________________
        STI s.r.l. via pascoli 10 A/B 24020Gorle (Bg) – ITALY www.stistrumentazione.com
      Configure the PC COM port selecting: “Configuration” from EDIT menu for both Texas (DSP) and Motorola
      (HC12).
_____________________________________________________________________________________
        STI s.r.l. via pascoli 10 A/B 24020Gorle (Bg) – ITALY www.stistrumentazione.com
               Attach the RS 232 9 pin cable to the J9 connection block (Com DSP)
               Launch the loader program as in §2.2
               Select the down arrow next to the “OPEN” quick select button
_____________________________________________________________________________________
        STI s.r.l. via pascoli 10 A/B 24020Gorle (Bg) – ITALY www.stistrumentazione.com
_____________________________________________________________________________________
        STI s.r.l. via pascoli 10 A/B 24020Gorle (Bg) – ITALY www.stistrumentazione.com
_____________________________________________________________________________________
        STI s.r.l. via pascoli 10 A/B 24020Gorle (Bg) – ITALY www.stistrumentazione.com
I. MAIN
III.2 TUNING
III.4 INPUTS
III.5 OUTPUTS
IV. CALIBRATION
IV.2 CALIBRATION
V. COMMAND MODE
V.2 MANUAL
VII.2 LANGUAGE
VII.4 PASSWORD
VII.5 CONTRAST
VIII.1 TE
VIII.2 VI
IX. COMMUNICATION
X. DIAGNOSTIC
X.1 STROKE KM
X.5 AVER.TEMP.
X.6 PERM.TIME
X.7 dP UP-DOWN
_____________________________________________________________________________________
        STI s.r.l. via pascoli 10 A/B 24020Gorle (Bg) – ITALY www.stistrumentazione.com
XI. ADVANCED
XI.3 INTEGRAL
XI.7 PASSWORD
XI.13 PRESS.CALIB
XI.16 GEOMETRIC 0
The 4 keys provided ( ↑, ↓, OK, ESC) for the menus control, have the following function:
      Key ↑ allows to shift on the option immediately preceding the one currently selected, enabling the menu shift in
      the counterclockwise direction up to the reaching of the first option.
      Key ↓ allows to shift on the option immediately following the one currently selected, enabling the menu shift in
      the clockwise direction up to the reaching of the limit given by the last option.
      the OK key confirms the option currently selected and activates the correspondent operation.
      The ESC key (when enabled) allows to return to the previous menu.
      The enabled keys are showed in reverse to help the operator’s use of the interface, while the disabled keys are
      not pointed out.
3.1 MAIN
                         OK                     MAIN
                                ERR             To display the error page
                                ESC             To display the user access page
      The main page is displayed at the end of the device start up or by the operator’s request.
      It has the following format on the controller display :
Selecting the MAIN page, the following main system information is displayed on the LCD monitor :
      The active buttons in this page are ERR and ESC; ERR to enter the system error page and ESC to go to the
      user access page.
If a PC connection is active, on the screen this information is shown in the STATUS window.
_____________________________________________________________________________________
        STI s.r.l. via pascoli 10 A/B 24020Gorle (Bg) – ITALY www.stistrumentazione.com
      When ERR button is pushed from the main page the information referred to the present alarm (ERROR
      CONDITION) and the last detected alarm (LAST ERROR CONDITION) are showed.
      In normal operation condition (no error or fail conditions), the error description showed is NONE.
      The errors analyzed by the system are:
                                                          Nr.
                                                     CRIPTION
_____________________________________________________________________________________
        STI s.r.l. via pascoli 10 A/B 24020Gorle (Bg) – ITALY www.stistrumentazione.com
PASSWORD: *****
                    MAIN
                    SYSTEM INFO
                    SYSTEM SET UP
                    CALIBRATION
                    COMMAND MODE
                    FAIL & TRIP SETTING
                    GENERAL SETTING
                    SYSTEM DATA
                    COMMUNICATION
                    DIAGNOSTIC
                    ADVANCED
   On the PC, a sequence of alfa-numerical digits is required (default is 12345) to access the system
   in remote mode.
_____________________________________________________________________________________
        STI s.r.l. via pascoli 10 A/B 24020Gorle (Bg) – ITALY www.stistrumentazione.com
In this page the system part number and the software revisions are displayed.
     The part number is the instrument serial number and it corresponds in the HART Protocol to the Device ID.
     The HC12 µprocessor SW version is the number corresponding to the SW release currently loaded
      on the quick trak controller.
      The DSP µprocessor SW version is the number corresponding to the SW release currently loaded
      on the quick trak controller.
      The PLD SW version is the number corresponding to the SW release currently loaded on the quick
      trak controller.
     The HART Universal Revision Number is a whole number indicating the HART major revision level supported
     by the field device.
     The Device Revision Number defines the revision level of the command set supported by the field Device,
     including the device-specific commands.
By a sub-menu contained in this menu level, it’s possible to adjust the main positioner functions.
 A        ATTENTION: The system must be put into “out of service” in order to perform the “set up”.
          Please refer to chapter COMMAND MODE.
_____________________________________________________________________________________
        STI s.r.l. via pascoli 10 A/B 24020Gorle (Bg) – ITALY www.stistrumentazione.com
          CAUTION: When the system is “out of service” any parameters’ modifications can cause a
          movement of the actuator. Before making any changes, make sure that the plant and
          personnel are in a safe state to allow these movements.
                              TRAVEL CONTROL
                              TUNING
                              INPUT CHAR.
                              INPUTS
                              OUTPUTS
                              RESET COMMAND
On the PC screen, that information is shown under the SYSTEM SETUP window.
_____________________________________________________________________________________
        STI s.r.l. via pascoli 10 A/B 24020Gorle (Bg) – ITALY www.stistrumentazione.com
       With this set of commands, it is possible to configure the action of the actuator and special travel functions as
       limits or cut off functions.
       With the keys ↑ / ↓ , it is possible to shift on the demanded line, and pushing the OK button, it is possible to
       change the function. The active selection will come out in reverse. The possible options for the low and high
       travel control mode are: OFF, LIMIT, CUT OFF.
With the keys ↑ / ↓ , it is possible to shift on the demanded line and pushing the OK button it is possible to change the
function. The active selection will come out in reverse.
            CAUTION: Modifying this parameter, the actuator can move. Before changing, make sure
            that the plant and personnel are in a safe state to allow these movements.
3.3.1.2 0 POSITION
With this command, it is possible to select the position of the actuator stem corresponding to the 0 output signal (0%).
With the keys ↑ / ↓ , it is possible to shift on the demanded line and pushing the OK button it is possible to change the
function. The active selection will come out in reverse.
_____________________________________________________________________________________
        STI s.r.l. via pascoli 10 A/B 24020Gorle (Bg) – ITALY www.stistrumentazione.com
                               LTRAVEL POS.
                                  5.0 %
                               PRESS OK TO CONFIRM
      The second line value can be changed by pressing the key ↑/↓ and subsequently confirmed with OK. Press
      ESC to return to the previous menu.
          CAUTION: Modifying this parameter, the actuator can move. Before changing, make sure
          that the plant and personnel are in a safe state to allow these movements.
      On the PC, this function can be activated with the introduction of the value in the cell corresponding to the “low
      limit”.
          CAUTION: Modifying this parameter, the actuator can move. Before changing, make sure
          that the plant and personnel are in a safe state to allow these movements.
      On the PC, this function can be activated with the selection of the option corresponding to the low travel control
      mode.
_____________________________________________________________________________________
        STI s.r.l. via pascoli 10 A/B 24020Gorle (Bg) – ITALY www.stistrumentazione.com
                               HTRAVEL POS.
                                  95.0 %
                               PRESS OK TO CONFIRM
      The second line value can be changed by pressing the key ↑/↓ and subsequently confirmed with OK. Press
      ESC to return to the previous menu.
          CAUTION: Modifying this parameter, the actuator can move. Before changing, make sure
          that the plant and personnel are in a safe state to allow these movements.
      On the PC this function can be activated with the introduction of the value in the cell corresponding to the “high
      limit”.
_____________________________________________________________________________________
        STI s.r.l. via pascoli 10 A/B 24020Gorle (Bg) – ITALY www.stistrumentazione.com
          CAUTION: Modifying this parameter, the actuator can move. Before changing, make sure
          that the plant and personnel are in a safe state to allow these movements.
      On the PC, this function can be activated with the selection of the option corresponding to the high travel control
      mode.
       3.3.2 Tuning
                                                MAIN
                                                SYSTEM INFO
                         OK                     SYSTEM SET UP
                                                TRAVEL CONTROL
                                 OK             TUNING
                                         ESC    To return to menu
      With this set of commands, it’s possible to configure the positioner response parameters such as gain, integral
      function and dead band.
                     PROPORTIONAL GAIN
                     SPEED CONTROL
                     DEAD BAND
          CAUTION: Modifying this parameter, the actuator can move. Before changing, make sure
          that the plant and personnel are in a safe state to allow these movements.
_____________________________________________________________________________________
        STI s.r.l. via pascoli 10 A/B 24020Gorle (Bg) – ITALY www.stistrumentazione.com
      Proportional gain is the multiplier of the error (difference between input signal and actuator actual position) and it
      is expressed in percent. It is active only for an error which is bigger than dead band value.
      A different gain for each stem direction can be imposed.
      With the OK command selection, it is possible to enter into the parameter change page for the selected line
      (actuator stem direction) and modify the displayed value:
      The second line value can be changed by pressing the key ↑/↓ and subsequently confirmed with OK. Press
      ESC to return to the previous menu.
      On the PC software, this parameter is called “Kp” and two cells are available (one for each direction) in “double”
      gain mode.
To set the value, double click on the selected cell and, the following window will appear :
_____________________________________________________________________________________
        STI s.r.l. via pascoli 10 A/B 24020Gorle (Bg) – ITALY www.stistrumentazione.com
                    STROKE TIME↓                  0
                    STROKE TIME↑                  0
                    APPROACH FACTOR↓              0
                    APPROACH FACTOR↑              0
      STROKE TIME is the value expressed in seconds of the stroking time for each direction.
      APPROACH FACTOR is a “damping” coefficient to be increased in order to avoid any overshooting
      when the actuator approaches the target position.
      It can be set in a range between 0÷1000 (0 = no control, 1000 = maximum control). With the OK
      command selection, it is possible to enter the parameter change page for the selected line (actuator stem
      direction) and modify the displayed value:
      The second line value can be changed by pressing the key ↑/↓ and subsequently confirmed with OK. Press
      ESC to return to the previous menu.
To set the value, double click on the selected cell and the following window will appear :
_____________________________________________________________________________________
        STI s.r.l. via pascoli 10 A/B 24020Gorle (Bg) – ITALY www.stistrumentazione.com
          CAUTION: Modifying this parameter, the actuator can move. Before changing, make sure
          that the plant and personnel are in a safe state to allow these movements.
                    DEAD BAND
                      0.50
                    PRESS OK TO CONFIRM
          CAUTION: Modifying this parameter, the actuator can move. Before changing, make sure
          that the plant and personnel are in a safe state to allow these movements.
On the PC software, a single cell is available to modify the dead band value.
_____________________________________________________________________________________
        STI s.r.l. via pascoli 10 A/B 24020Gorle (Bg) – ITALY www.stistrumentazione.com
To set the value, double click on the cell, the following window will appear :
With those commands, it is possible to configure the relationship between the input signal and valve position set.
      In the first line, it’s possible to move from linear to customer options (and vice versa) with the OK command. On
      the second line, with OK selection, it’s possible to enter the changing point values page of the customer curve.
_____________________________________________________________________________________
        STI s.r.l. via pascoli 10 A/B 24020Gorle (Bg) – ITALY www.stistrumentazione.com
                                 TABLE                    01/03
                                 SET POINT           TRAV.TARGET
                                  0.0                      0.0
                                  10.0                    10.0
                                  20.0                    20.0
                                  30.0                    30.0
      In the first line, the current page is indicated, in the second line there are the column titles. In the following lines,
      there are: the position and the corresponding parameter values.
      The active field will come out in reverse. With the OK selection, it’s possible to change the active data field. With
      the ↑/↓ commands, it’s possible to modify all the available parameters.
      Changing the page number, it’s possible to scroll the customer table.
                                 TABLE                    02/03
                                 SET POINT           TRAV.TARGET
                                 40.0                     40.0
                                 50.0                     50.0
                                 60.0                     60.0
                                 70.0                     70.0
                                 TABLE                    03/03
                                 SET POINT           TRAV.TARGET
                                 80.0                     80.0
                                 90.0                     90.0
                                100.0                    100.0
          CAUTION: Modifying this parameter, the actuator can move. Before changing, make sure
          that the plant and personnel are in a safe state to allow these movements.
On the PC software is possible to select the curve type form the “INPUT CHAR” window.
      In case of “Customer Curve” selection, pushing the “Table” button, it’s possible to display the entire curve. From
      this page, it’s possible to modify the point values inserting the value into the cell or trailing the point position on
      the graph with the mouse.
_____________________________________________________________________________________
        STI s.r.l. via pascoli 10 A/B 24020Gorle (Bg) – ITALY www.stistrumentazione.com
Press “SEND” to confirm the values or “CLOSE” to exit from this window.
       3.3.4 Inputs
                                                  MAIN
                                                  SYSTEM INFO
                         OK                       SYSTEM SET UP
                                                  TRAVEL CONTROL
                                                  TUNING
                                                  INPUT CHAR.
                                 OK               INPUTS
                                          ESC     To return to menu
With this set of commands, it’s possible to configure the zero inlet signal and span.
_____________________________________________________________________________________
        STI s.r.l. via pascoli 10 A/B 24020Gorle (Bg) – ITALY www.stistrumentazione.com
      The second line value can be changed by pressing the key ↑/↓ in a range between 0.0÷10.0 mA and
      subsequently confirmed with OK. Press ESC to return to the previous menu.
On the PC software, it’s possible to insert the required value into the “Input Range L” cell in the INPUTS window.
      To set the value, double click on the selected cell and press “SEND” to confirm or “ABORT” to exit from this
      window.
          CAUTION: Modifying this parameter, the actuator can move. Before changing, make sure
          that the plant and personnel are in a safe state to allow these movements.
      The second line value can be changed by pressing the key ↑/↓ in a range of between 10.0÷30.0 mA and
      subsequently confirmed with OK. Press ESC to return to the previous menu.
      On the PC software, it is possible to insert the required value into the “Input Range H” cell in the INPUTS
      window.
      To set the value, double click on the selected cell and press “SEND” to confirm or “ABORT” to exit from this
      window.
_____________________________________________________________________________________
        STI s.r.l. via pascoli 10 A/B 24020Gorle (Bg) – ITALY www.stistrumentazione.com
          CAUTION: Modifying this parameter, the actuator can move. Before changing, make sure
          that the plant and personnel are in a safe state to allow these movements.
3.3.4.3 CALIBRATE 4 mA or 20 mA
      With this command, it’s possible to calibrate the 4mA (or 20 mA) in order to set the input signal.
      A confirmation is required in order to start the 4ma/20mA calibration routine :
PRESS OK TO CONFIRM
      On the PC software, is possible calibrate the two points by pushing the “Calibrate 4mA” and “Calibrate 20mA”
      buttons.
          CAUTION: Modifying this parameter, the actuator can move. Before changing, make sure
          that the plant and personnel are in a safe state to allow these movements.
       3.3.5 Outputs
                                                 MAIN
                                                 SYSTEM INFO
                         OK                      SYSTEM SET UP
                                                 TRAVEL CONTROL
                                                 TUNING
_____________________________________________________________________________________
        STI s.r.l. via pascoli 10 A/B 24020Gorle (Bg) – ITALY www.stistrumentazione.com
                                                INPUT CHAR.
                                                INPUTS
                                OK              OUTPUTS
                                        ESC     To return to menu
With this set of commands, it’s possible to configure the available output channels.
                               ANALOG OUTPUT A
                               ANALOG OUTPUT B
                               DIGITAL OUTPUT1
                               DIGITAL OUTPUT2
                               DIGITAL OUTPUT3
      It’s possible to choose the required parameter, in order to associate it to the selected output channel for the
      reproduction of the indicated signal in a range from 4mA to 20 mA. Pressing OK to confirm the choice, the ON
      indication will be pointed out on the selected channel. Press ESC to return to the previous menu.
      On the PC software, it’s possible to impose the output parameter by its selection in correspondence of OUT A
      or OUT B.
      It’s possible to choose the required fail, warning or error activation, in order to associate it to the selected digital
      output channel. Pressing OK to confirm the choice, the ON indication will be pointed out on the selected
      channel. Press ESC to return to the previous menu.
      On the PC software, pushing the Dig. Out button located in the OUTPUTS window, it’s possible to impose the
      output parameter by its selection in correspondence of OUT 1, OUT 2 or OUT 3.
_____________________________________________________________________________________
        STI s.r.l. via pascoli 10 A/B 24020Gorle (Bg) – ITALY www.stistrumentazione.com
                                                  SYSTEM INFO
                         OK                       SYSTEM SET UP
                                                  TRAVEL CONTROL
                                                  TUNING
                                                  INPUT CHAR.
                                                  INPUTS
                                                  OUTPUTS
                                 OK               RESET COMMAND
                                         ESC      To return to menu
This option menu is only present on the local panel and it is not available on PC.
RESET TO DEFAULT
This function is available on PC software from the STI menu. See chapter ADVANCED for details.
_____________________________________________________________________________________
        STI s.r.l. via pascoli 10 A/B 24020Gorle (Bg) – ITALY www.stistrumentazione.com
RESET TO DEFAULT ?
PRESS OK TO CONFIRM
Press the OK key to confirm the reset operation or the ESC key to abort.
3.4 CALIBRATION
                                                  MAIN
                                                  SYSTEM INFO
                                                  SYSTEM SET UP
                          OK                      CALIBRATION
                                 ESC              To return to main menu
If the customer tries to make a calibration when the system is “in service”, the following message will be shown:
                     REFUSED REQUEST:
                     SVCSTATE MUST BE OUT!
                     PRESS ESC/OK TO EXIT
      First step of the calibration is the setting (by means of ↑ / ↓ buttons) of the probe constant. This value is
      printed on the probe label.
                    PROBE CONSTANT
                       2800
                    PRESS OK TO CONFIRM
          CAUTION: While the system is in calibration mode, the controller will move the cylinder
          (and process valve) automatically through various positions regardless of the state of the
          normal input command, including the fully open and fully close position. Before calibrating
          the system, make sure that the plant and personnel are in a safe state to allow these
_____________________________________________________________________________________
        STI s.r.l. via pascoli 10 A/B 24020Gorle (Bg) – ITALY www.stistrumentazione.com
automatic functions.
CALIBRATION ?
PRESS OK TO CONFIRM
Once the calibration operation is confirmed with OK, the following page will be displayed on video:
SYSTEM CALIBRATION………..
PLEASE WAIT
                    SYSTEM CALIBRATED
                    PRESS ESC TO MENU
                    PRESS OK TO GO IN SVC
      On the PC software, it is possible to start calibration, selecting the “start calibration” button, on the calibration
      window.
Calibration status is shown on the upper side on the right of the panel :
_____________________________________________________________________________________
        STI s.r.l. via pascoli 10 A/B 24020Gorle (Bg) – ITALY www.stistrumentazione.com
                    SERVICE OUT / IN
                    MANUAL
When a different option is selected, a confirmation is required in order to change the system service status.
      If the system is out of service, the OUT option is displayed in reverse and the IN selection is made pressing OK.
      The following message appears:
                                 SERVICE STATE:
                                 OUT SVC -> IN SVC
              PRESS              PRESS OK TO CONFIRM
_____________________________________________________________________________________
        STI s.r.l. via pascoli 10 A/B 24020Gorle (Bg) – ITALY www.stistrumentazione.com
                                SERVICE STATE:
                                IN SVC -> OUT SVC
             PRESS              PRESS OK TO CONFIRM
      In order to go in service state, the system must be calibrated, if this condition is not satisfied, the error message
      is displayed:
                                REFUSED REQUEST:
                                INVALID SYSTEM STATE!
                                PRESS ESC/OK TO EXIT
      On the PC, it is possible to choose the service state, selecting the service status on the pull-down menu in the
      command mode cell.
          CAUTION The plant operator has the responsibility to make sure that automatic cycling of
          the process valve, will not cause any damage to property or personnel before issuing the
          “in service” command. This includes making sure that personnel and equipment are clear
          of moving parts of the cylinder and process valve and that the plant process has been
          made safe by bypassing the process valve.
       3.5.2 Manual
                                                 MAIN
                                                 SYSTEM INFO
                                                 SYSTEM SET UP
                                                 CALIBRATION
                         OK                      COMMAND MODE
                                                 SERVICE OUT/IN
                                 OK              MANUAL
                                         ESC     To return to menu
Selecting this option, the system changes from the automatic control mode to the manual mode (Direct Mode).
      To activate “Manual mode”, the system must be calibrated and “out of service”, in case of one or both
      conditions are not satisfied, the error message is displayed:
                                REFUSED REQUEST:
                                INVALID SYSTEM STATE!
                                PRESS ESC/OK TO EXIT
In manual mode, the required (variable value with ↑ / ↓ buttons) and current position are displayed.
_____________________________________________________________________________________
        STI s.r.l. via pascoli 10 A/B 24020Gorle (Bg) – ITALY www.stistrumentazione.com
      Operating with PC selecting the “Manual” option in the service pull-down menu, it’s possible to insert the
      required position cell and confirm it, pushing the X% button.
      With this selection, it’s possible to define the system behaviour in case of pressure, power or signal failure
      and/or activation of a trip signal.
                              SOV CONFIGURATION
                              POS.EXCESS FAIL MODE
                              POWER FAIL MODE
                              SIGNAL FAIL MODE
                              PRESSURE FAIL MODE
                              MODE FOR TRIP1
                              MODE FOR TRIP2
                              MODE FOR TRIP3
                              MODE FOR TRIP4
On the PC this options are displayed and can be customized in the “FAIL / TRIP SETTINGS” window.
_____________________________________________________________________________________
        STI s.r.l. via pascoli 10 A/B 24020Gorle (Bg) – ITALY www.stistrumentazione.com
      Selecting this option, it’s possible to display and modify the system configuration provided for the solenoid
      valves (SOV).
      In the first line, it’s possible to configure the system SOV number (1, 2 or 3), in the second line the SOV
      configuration provided for running mode (normal operation mode); in next lines the SOV configuration provided
      for three specific cases : SAFETY SHUT DOWN 1, 2 and 3.
      The active field will come out in reverse. With the OK selection, it’s possible to change the active data field. With
      the ↑/↓ keys, it’s possible to change the parameter option.
      On the PC software, it’s possible to display the SOV configuration, pressing the corresponding button in the
      “SOV Configuration” window.
_____________________________________________________________________________________
        STI s.r.l. via pascoli 10 A/B 24020Gorle (Bg) – ITALY www.stistrumentazione.com
      To set the SOV number, double click on the corresponding cell, and press “SEND” to confirm the value or
      “ABORT” to exit from this window.
      To set the SOV configuration in case of running, safety shut down 1, 2, 3 modes, check the selected options
      and press “SEND” to confirm the entire selection or “ABORT” to exit from this window.
      Selecting this command, it’s possible to configure the max admissible position error and warning (difference
      between the required and the actual position) and the actions to be executed, if these limits are exceeded.
_____________________________________________________________________________________
        STI s.r.l. via pascoli 10 A/B 24020Gorle (Bg) – ITALY www.stistrumentazione.com
On the PC, it’s possible to configure all the selections and values in the “Position excess fail” panel.
_____________________________________________________________________________________
        STI s.r.l. via pascoli 10 A/B 24020Gorle (Bg) – ITALY www.stistrumentazione.com
                                EXCESS ERROR
                                  3.0 %
                                PRESS OK TO CONFIRM
      The value can be changed by pressing the ↑ and ↓ keys in a range between 0÷100% and subsequently
      confirmed with OK. Press ESC to return to the previous menu.
On the PC, it’s possible to configure the parameter in the “Position excess fail” panel.
      To set the value, double click on the corresponding cell, input the value and press “SEND” to confirm it or
      “ABORT” to exit.
_____________________________________________________________________________________
        STI s.r.l. via pascoli 10 A/B 24020Gorle (Bg) – ITALY www.stistrumentazione.com
                                ERROR SECONDS
                                  10 SEC
                                PRESS OK TO CONFIRM
      The value can be changed by pressing the ↑ and ↓ keys in a range between 0÷1000 seconds and subsequently
      confirmed with OK. Press ESC to return to the previous menu.
On the PC, it’s possible to configure the parameter in the “Position excess fail” panel.
      To set the value, double click on the corresponding cell, input the value and press “SEND” to confirm it or
      “ABORT” to exit.
_____________________________________________________________________________________
        STI s.r.l. via pascoli 10 A/B 24020Gorle (Bg) – ITALY www.stistrumentazione.com
                                EXCESS WARN.
                                  3.0 %
                                PRESS OK TO CONFIRM
      The value can be changed by pressing the ↑ and ↓ keys and subsequently confirmed with OK. Press ESC to
      return to the previous menu.
On the PC, it’s possible to configure the parameter in the “Position excess fail” panel.
      To set the value, double click on the corresponding cell, input the value and press “SEND” to confirm it or
      “ABORT” to exit.
                                WARN. SECONDS
                                  10 SEC
                                PRESS OK TO CONFIRM
      The value can be changed by pressing the ↑ and ↓ keys and confirmed with OK. Press ESC to return to the
      previous menu.
On the PC, it’s possible to configure the parameter in the “Position excess fail” panel.
_____________________________________________________________________________________
        STI s.r.l. via pascoli 10 A/B 24020Gorle (Bg) – ITALY www.stistrumentazione.com
      To set the value, double click on the corresponding cell, input the value and press “SEND” to confirm it or
      “ABORT” to exit.
      Selection of this command, allows to define the minimum and maximum admissible power to the main PCB, and
      to configure the power fail condition.
On the PC, is possible to configure all the selections and values in the “Power fail” panel.
_____________________________________________________________________________________
        STI s.r.l. via pascoli 10 A/B 24020Gorle (Bg) – ITALY www.stistrumentazione.com
      On the PC, it is possible to choose the power end mode, selecting the option on the corresponding pull-down
      menu.
_____________________________________________________________________________________
        STI s.r.l. via pascoli 10 A/B 24020Gorle (Bg) – ITALY www.stistrumentazione.com
Selecting the first line, it is possible to modify the low voltage supply limit value.
Selecting the second line, it is possible to modify the high voltage supply limit value.
      On the PC, it is possible to modify the low and high power limits.
      To set the parameters, double click on the selected cell, input the value and press “SEND” to confirm it or
      “ABORT” to exit from the input window.
_____________________________________________________________________________________
        STI s.r.l. via pascoli 10 A/B 24020Gorle (Bg) – ITALY www.stistrumentazione.com
      This command allows to configure the minimum and maximum admissible inlet signal (mA), the actions to be
      executed if these limits are reached and the error clearing condition.
On the PC, it’s possible to configure all the selections and values in the “Signal fail” panel.
_____________________________________________________________________________________
        STI s.r.l. via pascoli 10 A/B 24020Gorle (Bg) – ITALY www.stistrumentazione.com
      be made by selecting the line with the up / down buttons and scrolling the options by pushing the OK key. The
      available options are:
      On the PC, it is possible to choose the power end mode selecting the option on the corresponding pull-down
      menu.
Selecting the first line, it is possible to modify the low limit, using the ↑ and ↓ keys and the OK button to confirm.
      On the PC, it is possible to configure all the values in the “Signal fail” panel.
      To set the value, double click on the selected cell, input the value and press “SEND” to confirm it or “ABORT” to
      exit from the input window.
_____________________________________________________________________________________
        STI s.r.l. via pascoli 10 A/B 24020Gorle (Bg) – ITALY www.stistrumentazione.com
                               ACTUATOR POSITION
                                   1.0 %
                               PRESS OK TO CONFIRM
      The value of the position (expressed in percentage of the stroke) can be adjusted between -10 and 110% of the
      stroke, by pressing the ↑ and ↓ keys and subsequently confirmed with the OK key.
      To set the value, on the PC, double click on the corresponding cell, input the value and press “SEND” to confirm
      it or “ABORT” to exit from the input window.
_____________________________________________________________________________________
        STI s.r.l. via pascoli 10 A/B 24020Gorle (Bg) – ITALY www.stistrumentazione.com
This command allows to configure the minimum admissible supply pressure value.
On the PC, it is possible to configure all the selections and values in the “Pressure fail” panel.
_____________________________________________________________________________________
        STI s.r.l. via pascoli 10 A/B 24020Gorle (Bg) – ITALY www.stistrumentazione.com
_____________________________________________________________________________________
        STI s.r.l. via pascoli 10 A/B 24020Gorle (Bg) – ITALY www.stistrumentazione.com
                                PRESS. LIMIT
                                 5.00 Bar
                                PRESS OK TO CONFIRM
      The input pressure value can be selected in a range of 0÷150 Psi or 0÷10 bar, using the ↑ and ↓ keys. OK
      button confirmation is required.
      This option allows to configure the position of the actuator when the trip 1 (or 2, 3, 4) is fired, the actions to be
      executed and the trip clearing condition.
With the selection of one of the available trips, the displayed menu is:
_____________________________________________________________________________________
        STI s.r.l. via pascoli 10 A/B 24020Gorle (Bg) – ITALY www.stistrumentazione.com
On the PC, all these options could be configured from the “Trips” panel.
_____________________________________________________________________________________
        STI s.r.l. via pascoli 10 A/B 24020Gorle (Bg) – ITALY www.stistrumentazione.com
      On the PC, it is possible to choose the trip end mode, selecting the option on the corresponding pull-down
      menu.
_____________________________________________________________________________________
        STI s.r.l. via pascoli 10 A/B 24020Gorle (Bg) – ITALY www.stistrumentazione.com
                               ACTUATOR POSITION
                                 1.0 %
                               PRESS OK TO CONFIRM
      The value of the position (expressed in percentage of the stroke) can be adjusted between -10 and 110% of the
      stroke, by pressing the ↑ and ↓ keys and subsequently confirmed with the OK key.
      To set the value, on the PC, double click on the corresponding cell, input the value and press “SEND” to confirm
      it or “ABORT” to exit from the input window.
3.6.6.4 ON STATUS
      This option allows to configure the ON status for the selected trip; the changing can be made by selecting the
      line with the up / down buttons and scrolling the options by pushing the OK key. The available options are:
                       OPTION                              DESCRIPTION
                      ENERGIZED        ON Status = Energized. Corresponds to “1” state.
                      NOT ENERG.       ON Status = NOT Energized. Corresponds to “0” state.
                                                    OPTION
      On the PC, it is possible to choose the trip ON status, selecting the option on the corresponding pull-down
      menu.
_____________________________________________________________________________________
        STI s.r.l. via pascoli 10 A/B 24020Gorle (Bg) – ITALY www.stistrumentazione.com
On the PC, only some of these data are available into the “General setting” panel.
The password login and changing are available in the main command line (pull-down password menu).
This command allows to configure the measurement units system used to display the variables.
      The configuration can be made by selecting the line with the up / down buttons, scrolling the options by pushing
      the OK key and choosing between ISO metrical system (MET) and imperial system (IMP).
      On the PC, it is possible to choose the measurement units system, selecting the option on the corresponding
      pull-down menu.
_____________________________________________________________________________________
        STI s.r.l. via pascoli 10 A/B 24020Gorle (Bg) – ITALY www.stistrumentazione.com
       3.7.2 Language
                                                MAIN
                                                SYSTEM INFO
                                                SYSTEM SET UP
                                                CALIBRATION
                                                COMMAND MODE
                                                FAIL & TRIP SETTING
                         OK                     GENERAL SETTING
                                                MEASUR UNITS
                                OK              LANGUAGE
                                        ESC     To return to menu
                               [mm/dd/yyyy]
                               10 / 03 / 2007
                               12 : 25 : 41
Every value can be modified using the up / down buttons and the OK key to confirm it.
_____________________________________________________________________________________
        STI s.r.l. via pascoli 10 A/B 24020Gorle (Bg) – ITALY www.stistrumentazione.com
       3.7.4 Password
                                                 MAIN
                                                 SYSTEM INFO
                                                 SYSTEM SET UP
                                                 CALIBRATION
                                                 COMMAND MODE
                                                 FAIL & TRIP SETTING
                         OK                      GENERAL SETTING
                                                 MEASUR UNITS
                                                 LANGUAGE
                                                 DATE & TIME
                                 OK              PASSWORD
                                         ESC     To return to menu
                              PASSWORD: _ _ _ _ _
                              CONFIRM: _____
      A sequence of 5 push buttons is required to define the user password, used to enter the system from the local
      panel (the device is supplied by the manufacturer with the default user password [ OK ↑ ↓ ↑ ↓ ]).
      On the PC, a sequence of alfa-numerical digits is required (default is 12345).
_____________________________________________________________________________________
        STI s.r.l. via pascoli 10 A/B 24020Gorle (Bg) – ITALY www.stistrumentazione.com
       3.7.5 Contrast
                                                  MAIN
                                                  SYSTEM INFO
                                                  SYSTEM SET UP
                                                  CALIBRATION
                                                  COMMAND MODE
                                                  FAIL & TRIP SETTING
                          OK                      GENERAL SETTING
                                                  MEASUR UNITS
                                                  LANGUAGE
                                                  DATE & TIME
                                                  PASSWORD
                                  OK              CONTRAST
                                          ESC     To return to menu
Selecting this option, it’s possible to adjust the contrast of the local control device monitor.
                                CONTRAST
                                  070
      The value can be changed in a range between 1 and 100 using the up / down buttons and can be confirmed by
      the OK key.
On the PC, it is possible to adjust the contrast from the “General setting” panel.
      To set the value, double click on the corresponding cell, input the value and press “SEND” to confirm it or
      “ABORT” to exit from the input window.
      This option shows on the local control panel display the values of the electronic board temperature (TE) and the
      supply power voltage (VI) on the main PCB.
_____________________________________________________________________________________
        STI s.r.l. via pascoli 10 A/B 24020Gorle (Bg) – ITALY www.stistrumentazione.com
                              SYSTEM DATA
                              ------------------------------------------
                              TE        XXX.X C
                              VI        X :XX V
3.9 COMMUNICATION
                                                 MAIN
                                                 SYSTEM INFO
                                                 SYSTEM SET UP
                                                 CALIBRATION
                                                 COMMAND MODE
                                                 FAIL & TRIP SETTING
                                                 GENERAL SETTING
                                                 SYSTEM DATA
                        OK                       COMMUNICATION
                               ESC               To return to main menu
      Selecting the only (at the present time) available option in the menu COMMUNICATION, it’s possible to enter
      the HART PROTOCOL 6.0 parameters list.
                              HART TAG
                              MESSAGE
                              DESCRIPTOR
                              DATE
                              POLLING ADDRESS                 0
                              DEVICE ID                       1
On the PC, these data are available into the “Communication” panel.
_____________________________________________________________________________________
        STI s.r.l. via pascoli 10 A/B 24020Gorle (Bg) – ITALY www.stistrumentazione.com
                                                COMMAND MODE
                                                FAIL & TRIP SETTING
                                                GENERAL SETTING
                                                SYSTEM DATA
                         OK                     COMMUNICATION
                                OK              HART TAG
                                        ESC     To return to menu
                               HART TAG
                                  STID881
                               PRESS ESC/OK TO EXIT
      The Tag is a 8 character label assigned by the end user based on the location and use of the field device. It’s a
      8 character (6 byte) Packed ASCII string used to identify the field device. The term originated when physical
      tags were attached to instruments for this purpose.
      It’s not possible to modify the Tag parameter by the local user interface.
      To set the value, double click on the corresponding cell, input the value and press “SEND” to confirm it or
      “ABORT” to exit from the input window.
       3.9.2 Message
                                                MAIN
                                                SYSTEM INFO
                                                SYSTEM SET UP
                                                CALIBRATION
                                                COMMAND MODE
                                                FAIL & TRIP SETTING
                                                GENERAL SETTING
                                                SYSTEM DATA
                         OK                     COMMUNICATION
                                                HART TAG
                                OK              MESSAGE
                                        ESC     To return to menu
                               MESSAGE
                                …first 16 chars
                                …second 16 chars
                               PRESS ESC/OK TO EXIT
_____________________________________________________________________________________
        STI s.r.l. via pascoli 10 A/B 24020Gorle (Bg) – ITALY www.stistrumentazione.com
      The Message is a 32 character (24 byte) Packed ASCII string used by the Master for record keeping.
      The default value is a blanked string, 32 bytes long.
      It’s not possible to modify the Message parameter by the local user interface.
      To set the value, double click on the corresponding cell, input the value and press “SEND” to confirm it or
      “ABORT” to exit from the input window.
       3.9.3 Descriptor
                                               MAIN
                                               SYSTEM INFO
                                               SYSTEM SET UP
                                               CALIBRATION
                                               COMMAND MODE
                                               FAIL & TRIP SETTING
                                               GENERAL SETTING
                                               SYSTEM DATA
                        OK                     COMMUNICATION
                                               HART TAG
                                               MESSAGE
                                OK             DESCRIPTOR
                                       ESC     To return to menu
                              DESCRIPTOR
                               …….16 chars
                              PRESS ESC/OK TO EXIT
      The Descriptor is a 16 character (12 byte) Packed ASCII string used by the Master for record keeping.
      The default value is a blanked string, 16 bytes long.
      It’s not possible to modify the Descriptor parameter by the local user interface.
_____________________________________________________________________________________
        STI s.r.l. via pascoli 10 A/B 24020Gorle (Bg) – ITALY www.stistrumentazione.com
      To set the value, double click on the corresponding cell, input the value and press “SEND” to confirm it or
      “ABORT” to exit from the input window.
       3.9.4 Date
                                                 MAIN
                                                 SYSTEM INFO
                                                 SYSTEM SET UP
                                                 CALIBRATION
                                                 COMMAND MODE
                                                 FAIL & TRIP SETTING
                                                 GENERAL SETTING
                                                 SYSTEM DATA
                         OK                      COMMUNICATION
                                                 HART TAG
                                                 MESSAGE
                                                 DESCRIPTOR
                                 OK              DATE
                                         ESC     To return to menu
This option allows to display and/or modify the HART parameter named Date.
                     DATE [mm/dd/yyyy]
                     05/29/2006
                     PRESS ESC TO EXIT
      The date is represented by three 8-bit binary unsigned integers representing, respectively, the day, month and
      year (minus 1900). It’s a date code, used by the Master for record keeping (e.g. last or next calibration date).
      In this page, the 4 provided keys are OK, ↑, ↓ and ESC and they have the following function:
      OK key allows to shift from a field to an other one of the page or in clockwise direction from day to month and to
      year.
      Key ↑ once pointed out the interest field, the current value is allowed to increase according to the field standards
      (ex.: day field including between 1 and 31);
      Key ↓ once pointed out the concern field, the current value is allowed to decrease according to the field
      standards (ex.: month field including between 1 and 12);
      The ESC key allows to return to the Hart Protocol submenu.
On the PC, it is possible to modify the Date parameter from the “Communication” panel.
_____________________________________________________________________________________
        STI s.r.l. via pascoli 10 A/B 24020Gorle (Bg) – ITALY www.stistrumentazione.com
      To set the value, double click on the corresponding cell, input the value and press “SEND” to confirm it or
      “ABORT” to exit from the input window.
This option allows to display and/or modify the HART parameter named Polling Address.
                    POLLING ADDRESS
                     00
                    PRESS OK TO CONFIRM
      In the HART Protocol, the polling address is an integer used to identify the field device. It is used to construct
      the Short Frame Address. The Polling Address is set to 0 in point to point installations.
On the PC, it is possible to modify the Polling Address from the “Communication” panel.
_____________________________________________________________________________________
        STI s.r.l. via pascoli 10 A/B 24020Gorle (Bg) – ITALY www.stistrumentazione.com
      To set the value, double click on the corresponding cell, input the value and press “SEND” to confirm it or
      “ABORT” to exit from the input window.
      The master usually reaches the devices, starting from polling address equal to 0.
      In multi-drop installations all the field devices are generally configured to a different polling address to allow
      automatic identification by the master.
      Using the “Poll” command button, it’s possible to identify a device having the polling address not equal to 0.
       3.9.6 Device ID
                                                MAIN
                                                SYSTEM INFO
                                                SYSTEM SET UP
                                                CALIBRATION
                                                COMMAND MODE
                                                FAIL & TRIP SETTING
                                                GENERAL SETTING
                                                SYSTEM DATA
                         OK                     COMMUNICATION
                                                HART TAG
                                                MESSAGE
                                                DESCRIPTOR
                                                DATE
                                                POLLING ADDRESS
                                OK              DEVICE ID
                                        ESC     To return to menu
This option allows to display the HART parameter named Device ID (integer number).
_____________________________________________________________________________________
        STI s.r.l. via pascoli 10 A/B 24020Gorle (Bg) – ITALY www.stistrumentazione.com
      This number is different for every device manufactured with a given Manufacturer ID and Device
      Type. It returned in bytes 9-11 of Identity Commands and for the Quick Trak III it coincides with the
      system serial number (Part Number).
      It’s not possible to modify the Device ID parameter by the local user interface or by remote; this value changes if
      the Part Number parameter is modified. See chapter ADVANCED for details.
_____________________________________________________________________________________
        STI s.r.l. via pascoli 10 A/B 24020Gorle (Bg) – ITALY www.stistrumentazione.com
3.10 DIAGNOSTIC
                                               MAIN
                                               SYSTEM INFO
                                               SYSTEM SET UP
                                               CALIBRATION
                                               COMMAND MODE
                                               FAIL & TRIP SETTING
                                               GENERAL SETTING
                                               SYSTEM DATA
                                               COMMUNICATION
                         OK                    DIAGNOSTIC
                                ESC            To return to main menu
                               STROKE KM    XXXXXX.XX
                               IN SVC HOURS XXXXXX.XX
                               MIN TEMP.    XXX.XC
                               MAX TEMP.    XXX.XC
                               AVER.TEMP.   XXX.XC
                               PERM. TIME
                               dP UP-DOWN
                               ERROR STAT
                               CALIB STAT
                               OUT SVC STAT
                               IN SVC STAT
                               STAT FREQ
                STROKE KM    XXXXXX.XX
                IN SVC HOURS XXXXXX.XX
                MIN TEMP.    XXX.XC
                MAX TEMP.    XXX.XC
                AVER.TEMP.   XXX.XC
      where :
      -  STROKE KM is the total distance covered by the stem (piston) expressed in [km]
      -  IN SVC HOURS the total time of working [h]
      -  MIN TEMP. is the minimum temperature reached during the use
      -  MAX TEMP. is the maximum temperature reached during the use
      -  AVER.TEMP is the average temperature during the use
_____________________________________________________________________________________
        STI s.r.l. via pascoli 10 A/B 24020Gorle (Bg) – ITALY www.stistrumentazione.com
      From this page, press the “Download” command button to read or refresh the system diagnostic data.
      Press the “Report” command button to save the data in RTF format.
                  Diagnostic Report
             Report Date : 14/02/2007 10.22
           Pressure             :                  0
           Signal <min          :                  0
           Signal >max          :                  0
           Pos.Exc.Error        :                  0
           Pos.Exc.Warn.        :                  0
           Probe                :                  0
           Power <min           :                  0
           Hard Limits          :                  0
           DSP Timeout          :                  0
           Watch Dog            :                  0
           Power >max           :                  0
           Error On SOV 1       :                  0
           Error On SOV 2       :                  0
           Error On SOV 3       :                  0
           DSP Restart          :                  0
           Calib. Erased        :                  0
           Encoder              :                  0
           Friction             :                  0
           Index1               :                  0
           Index2               :                  0
           TEMPERATURE (C)
           Min     : 26.0
           Max     : 26.0
           Average :
_____________________________________________________________________________________
        STI s.r.l. via pascoli 10 A/B 24020Gorle (Bg) – ITALY www.stistrumentazione.com
                                                GENERAL SETTING
                                                SYSTEM DATA
                                                COMMUNICATION
                         OK                     DIAGNOSTIC
                                                STROKE KM
                                                IN SVC HOURS
                                                MIN TEMP.
                                                MAX TEMP.
                                                AVER.TEMP.
                                OK              PERM. TIME
                                        ESC     To return to menu
      With this selection, it is possible to know the permanence time in defined range of the stroke. The stroke range
      expressed in percent of the stroke are the following:
      0÷1
      1 ÷ 25
      25 ÷ 50
      50 ÷ 75
      75 ÷ 99
      99 ÷ 100
On the local control panel display the values expressed in hours are shown as it follows:
                                 0-1  XXXXXXX.XXh
                                1-25  XXXXXXX.XXh
                               25-50 XXXXXXX.XXh
                               50-75 XXXXXXX.XXh
                               75-99 XXXXXXX.XXh
                               99-100 XXXXXXX.XXh
       3.10.2             dP UP-DOWN
                                                MAIN
                                                SYSTEM INFO
                                                SYSTEM SET UP
                                                CALIBRATION
                                                COMMAND MODE
                                                FAIL & TRIP SETTING
_____________________________________________________________________________________
        STI s.r.l. via pascoli 10 A/B 24020Gorle (Bg) – ITALY www.stistrumentazione.com
                                                    GENERAL SETTING
                                                    SYSTEM DATA
                                                    COMMUNICATION
                        OK                          DIAGNOSTIC
                                                    STROKE KM
                                                    IN SVC HOURS
                                                    MIN TEMP.
                                                    MAX TEMP.
                                                    AVER.TEMP.
                                                    PERM. TIME
                                OK                  dP UP-DOWN
                                          ESC       To return to menu
      This selection shows the difference of actuator chamber pressure in each sector of the stroke for extending and
      retracting stem stroke.
_____________________________________________________________________________________
        STI s.r.l. via pascoli 10 A/B 24020Gorle (Bg) – ITALY www.stistrumentazione.com
In this menu the error quantity, the date and time of the last error occurred are stored for each event.
                                    TRIP1
                                    TRIP2
                                    TRIP3
                                    TRIP4
                                    PRESSURE FAIL
                                    LOW SIGNAL FAIL
                                    HIGH SIGNAL FAIL
                                    POS. EXCESS ERROR
                                    POS. EXCESS WARNING
                                    PROBE ERROR
                                    LOW POWER FAIL
                                    HARD LIMITS ERROR
                                    DSP TIMEOUT
                                    WATCH DOG ERROR
                                    HIGH POWER FAIL
                                    ERROR ON SOV1
                                    ERROR ON SOV2
                                    ERROR ON SOV3
                                    DSP RESTART
                                    CALIBRATION ERASED
                                    FREE 1
                                    FREE 2
                                    FREE 3
                                    FREE 4
                                   FREE 5
                                   ENCODER ERROR
                                   EXC. FRICTION ERROR
                                   INDEX1 NOT FOUND ERR
                                   INDEX2 NOT FOUND ERR
      The selection can be made by selecting the line with the up / down buttons and pushing the OK key.
      Once selected the event, the error counter and the last error date are shown :
_____________________________________________________________________________________
        STI s.r.l. via pascoli 10 A/B 24020Gorle (Bg) – ITALY www.stistrumentazione.com
                                                    ERROR STAT
                                 OK                 CALIB STAT
                                          ESC       To return to menu
      This selection shows the operator the statistical information about the instrument calibration routine (calibration
      number and last date).
                               CALIBRATION
                               ----------------------------------------
                               COUNTER: XXXXXXXXXX
                               LAST DATE: mm/dd/yyyy
                                                  hh:mm:ss
      This selection shows the operator the statistical information about the “out of service” system state (counter and
      last date).
_____________________________________________________________________________________
        STI s.r.l. via pascoli 10 A/B 24020Gorle (Bg) – ITALY www.stistrumentazione.com
                               OUT SVC
                               ----------------------------------------
                               COUNTER: XXXXXXXXXX
                               LAST DATE: mm/dd/yyyy
                                                   hh:mm:ss
      This selection shows the operator the statistical information about the “in service” system state (counter and last
      date).
                               IN SVC
                               ----------------------------------------
                               COUNTER: XXXXXXXXXX
                               LAST DATE: mm/dd/yyyy
                                                  hh:mm:ss
_____________________________________________________________________________________
        STI s.r.l. via pascoli 10 A/B 24020Gorle (Bg) – ITALY www.stistrumentazione.com
This selection allows to modify the storage frequency of the diagnostic data.
                         STAT FREQ     ON
                               01:00
                         PRESS OK TO CONFIRM
      From this page, it’s possible to change the storage frequency, using the ↑ / ↓ buttons, to confirm the value with
      the OK key or to cancel the selection pressing the ESC key.
      Setting 00:00, the storage frequency is disabled.
      It’s not possible to change this parameter by remote, on the PC.
3.11 ADVANCED
                                                MAIN
                                                SYSTEM INFO
                                                SYSTEM SET UP
                                                CALIBRATION
                                                COMMAND MODE
                                                FAIL & TRIP SETTING
                                                GENERAL SETTING
                                                SYSTEM DATA
                                                COMMUNICATION
                                                DIAGNOSTIC
_____________________________________________________________________________________
        STI s.r.l. via pascoli 10 A/B 24020Gorle (Bg) – ITALY www.stistrumentazione.com
                          OK                      ADVANCED
                                 ESC              To return to main menu
In order to enter into this menu from the local panel, the advanced level password is required.
PASSWORD: *****
   The device is supplied by the manufacturer with the default advanced level password :
   [ OK ↑ ↓ ↑ OK ].
   At the end of the login phase, the advanced menu will appear on the screen :
                                DIAGNOSTIC DATA
                                PROBE TYPE MICROPULSE
                                INTEGRAL            0
                                PROP.GAIN MODE DOUBLE
                                PROP.BAND GAIN
                                PART NUMBER         1
                                PASSWORD
                                SET AS DEFAULT
                                RESET STAT
                                ERASE CALIB
                                STAT DEBUG
                                HART DEBUG
                                PRESS.CALIB
                                MOTOR TEST
                                STEP MOTOR
                                GEOMETRIC 0         1
                                SPOOL LIMIT
 With the keys ↑ / ↓ , it ‘s possible to shift on the demanded line, and pushing the OK button, it’s possible
 to activate or change the selected option.
 On the PC, in order to access the Sti page, the user must login as “advanced user”, inserting
 the advanced level password in login phase. The default advanced level password is 23456.
At the end of the login phase, the STI button will appear on the screen :
_____________________________________________________________________________________
        STI s.r.l. via pascoli 10 A/B 24020Gorle (Bg) – ITALY www.stistrumentazione.com
On the PC, pushing the STI button, the following page is displayed :
      It contains the advanced configuration parameters, the calibration data, some run-time information and the
      advanced function buttons.
      This option shows on the local control panel display the values of the system diagnostic data (Motor Steps,
      Aligned Steps, Spool Position, Encoder Position and P0-P3 DSP params).
where :
      -    MOTOR STEPS that is the total number of motor steps performed by the system;
      -    ALIGN. STEPS that is the total number of aligned motor steps;
      -    SPOOL POS. that corresponds to the spool valve position (Step motor);
      -    ENCOD. POS. that corresponds to the encoder position (Encoder);
      -    P0-P3 DSP parameters are 4 short parameters provided for future use.
_____________________________________________________________________________________
        STI s.r.l. via pascoli 10 A/B 24020Gorle (Bg) – ITALY www.stistrumentazione.com
      The selection can be made by selecting the line with the up / down buttons and scrolling the options by pushing
      the OK key. The available options are: MICROPULSE,4-20 mA, LVDT.
      The active selection will come out in reverse.
On the PC, it is possible to choose the probe type, selecting the option on the corresponding pull-down menu.
       3.11.3             INTEGRAL
                                                MAIN
                                                SYSTEM INFO
                                                SYSTEM SET UP
                                                CALIBRATION
                                                COMMAND MODE
_____________________________________________________________________________________
        STI s.r.l. via pascoli 10 A/B 24020Gorle (Bg) – ITALY www.stistrumentazione.com
                                 INTEGRAL
                                     0
                                 PRESS OK TO CONFIRM
      This parameter defines the integral value of the PID tuning process.
      With the 4 keys enabled, it is possible :
       -     to change the proposed integral setting increasing it with the STEM ↑ and decreasing it with the STEM ↓;
       -     to cancel the possible changes and return to the advanced submenu with the ESC key;
       -     to confirm the set value by pressing OK.
       To set the value, double click on the corresponding cell, input the value and press “SEND” to confirm it or
       “ABORT” to exit from the input window.
_____________________________________________________________________________________
        STI s.r.l. via pascoli 10 A/B 24020Gorle (Bg) – ITALY www.stistrumentazione.com
                                                  DIAGNOSTIC DATA
                                                  PROBE TYPE
                                                  INTEGRAL
                                  OK              PROP.GAIN MODE
                                          ESC     To return to menu
      With this command, it is possible to change the proportional gain modality, choosing between two possible
      options : DOUBLE and BAND.
Pushing the OK button, it is possible to change the gain modality. The active selection will come out in reverse.
      On the PC, it is possible to choose the proportional gain mode, selecting the option on the corresponding
      pull-down menu.
where :
           •    the PROP. BAND GAIN↓ represents the proportional gain to be applied to the actuator movement
                in the stem ↓ direction, when the error is smaller than the expected band;
           •    the PROP. BAND GAIN↑ represents the proportional gain to be applied to the actuator movement in
                the stem ↑ direction, when the error is smaller than the expected band.
 With the keys ↑ / ↓ , it ‘s possible to shift on the demanded line, pushing the OK button, it’s possible
 to enter the parameter change page for the selected line and modify the displayed value:
_____________________________________________________________________________________
        STI s.r.l. via pascoli 10 A/B 24020Gorle (Bg) – ITALY www.stistrumentazione.com
Or
In the parameter change page with the 4 keys enabled, it’s possible :
      -    to change the proposed value increasing it with the STEM ↑ and decreasing it with the STEM ↓;
      -    to cancel the possible changes and return to the Proportional Band Gain submenu with the ESC
           key;
      -    to confirm the set value by pressing OK.
_____________________________________________________________________________________
        STI s.r.l. via pascoli 10 A/B 24020Gorle (Bg) – ITALY www.stistrumentazione.com
      To set the value, double click on the corresponding cell, input the value and press “SEND” to confirm it or
      “ABORT” to exit from the input window.
     With this command, it is possible to modify the QUICK TRAK III part number, in a range of 1÷32767.
     In the HART Protocol this number corresponds to the Device ID.
                    PART NUMBER
                      1
                    PRESS OK TO CONFIRM
      -     to change the proposed value increasing it with the STEM ↑ and decreasing it with the STEM ↓;
      -     to cancel the possible changes and return to the Advanced submenu with the ESC key;
      -     to confirm the inputted value by pressing OK.
_____________________________________________________________________________________
        STI s.r.l. via pascoli 10 A/B 24020Gorle (Bg) – ITALY www.stistrumentazione.com
      To set the value, double click on the corresponding cell, input the value and press “SEND” to confirm it or
      “ABORT” to exit from the input window.
       3.11.7             PASSWORD
                                                MAIN
                                                SYSTEM INFO
                                                SYSTEM SET UP
                                                CALIBRATION
                                                COMMAND MODE
                                                FAIL & TRIP SETTING
                                                GENERAL SETTING
                                                SYSTEM DATA
                                                COMMUNICATION
                                                DIAGNOSTIC
                         OK                     ADVANCED
                                                DIAGNOSTIC DATA
                                                PROBE TYPE
                                                INTEGRAL
                                                PROP.GAIN MODE
                                                PROP.BAND MODE
                                                PART NUMBER
                                OK              PASSWORD
                                         ESC    To return to menu
With this selection, it’s possible to change the advanced level password.
                               PASSWORD: _ _ _ _ _
                               CONFIRM:  _____
      A sequence of 5 push buttons is required to define this password, used to enter the advanced
      menu from the local panel (the device is supplied by the manufacturer with the default advanced
      password [ OK ↑ ↓ ↑ OK ]).
_____________________________________________________________________________________
        STI s.r.l. via pascoli 10 A/B 24020Gorle (Bg) – ITALY www.stistrumentazione.com
      To set the value, double click on the corresponding cell, input the value and press “SEND” to confirm it or
      “ABORT” to exit from the input window.
This command sets the actual configuration parameters as system default values.
SET AS DEFAULT ?
PRESS OK TO CONFIRM
Press the OK key to confirm the operation or the ESC key to abort.
_____________________________________________________________________________________
        STI s.r.l. via pascoli 10 A/B 24020Gorle (Bg) – ITALY www.stistrumentazione.com
This command globally resets the statistical data and the diagnostic information, computed by the sytem.
RESET STAT ?
PRESS OK TO CONFIRM
      Press the OK key to confirm the operation or the ESC key to abort.
      This function is not available on PC software.
_____________________________________________________________________________________
        STI s.r.l. via pascoli 10 A/B 24020Gorle (Bg) – ITALY www.stistrumentazione.com
                                                COMMUNICATION
                                                DIAGNOSTIC
                         OK                     ADVANCED
                                                DIAGNOSTIC DATA
                                                PROBE TYPE
                                                INTEGRAL
                                                PROP.GAIN MODE
                                                PROP.BAND MODE
                                                PART NUMBER
                                                PASSWORD
                                                SET AS DEFAULT
                                                RESET STAT
                                OK              ERASE CALIB
                                        ESC     To return to menu
This command erases the calibration data and resets the system calibration state (NO CAL = Not Calibrated).
ERASE CALIB ?
PRESS OK TO CONFIRM
Press the OK key to confirm the operation or the ESC key to abort.
_____________________________________________________________________________________
        STI s.r.l. via pascoli 10 A/B 24020Gorle (Bg) – ITALY www.stistrumentazione.com
     Reserved debug page containing information about the statistical calculation and the recording time
     in External EEPROM.
     This function is not available on PC software.
     Reserved debug page containing information about the input/output HART frames.
     This function is not available on PC software.
_____________________________________________________________________________________
        STI s.r.l. via pascoli 10 A/B 24020Gorle (Bg) – ITALY www.stistrumentazione.com
                                                PROP.GAIN MODE
                                                PROP.BAND MODE
                                                PART NUMBER
                                                PASSWORD
                                                SET AS DEFAULT
                                                RESET STAT
                                                ERASE CALIB
                                                STAT DEBUG
                                                HART DEBUG
                                OK              PRESS.CALIB
                                        ESC     To return to menu
With this set of commands, it’s possible to calibrate the pressure values (SUPPLY, OUT1, OUT2).
                               SUPPLY CALIB.
                               OUT1 CALIB.
                               OUT2 CALIB.
 A        ATTENTION: The system must be put into “out of service” in order to calibrate pressures.
          Please refer to chapter COMMAND MODE.
                          SUPPLY-P1 CALIB.
                          SUPPLY-P2 CALIB.
                          SUPPLY-P3 CALIB.
With this command, selecting the required point, it’s possible to calibrate the SUPPLY-PI pressure signal.
                    SUPPLY-P1
                       0.00 Bar
                    PRESS OK TO CONFIRM
      The second line value can be changed by pressing the key ↑/↓ in a range between 0÷150 Psi or 0÷10 bar and
      subsequently confirmed with OK. Press ESC to return to the previous menu.
This function is available on PC software from the STI menu, pushing the Press. Calib. Button.
_____________________________________________________________________________________
        STI s.r.l. via pascoli 10 A/B 24020Gorle (Bg) – ITALY www.stistrumentazione.com
_____________________________________________________________________________________
        STI s.r.l. via pascoli 10 A/B 24020Gorle (Bg) – ITALY www.stistrumentazione.com
      To calibrate the pressure signal, select the pressure transducer type (PI/PA/PB), input the value in the required
      empty cell and press the corresponding Calib. button.
                          OUT1-P1 CALIB.
                          OUT1-P2 CALIB.
                          OUT1-P3 CALIB.
With this command, selecting the required point, it’s possible to calibrate the OUT1-PA pressure signal.
                    OUT1-P1
                       0.00 Bar
                    PRESS OK TO CONFIRM
      The second line value can be changed by pressing the key ↑/↓ in a range between 0÷150 Psi or 0÷10 bar and
      subsequently confirmed with OK. Press ESC to return to the previous menu.
This function is available on PC software from the STI menu, pushing the Press. Calib. Button.
_____________________________________________________________________________________
        STI s.r.l. via pascoli 10 A/B 24020Gorle (Bg) – ITALY www.stistrumentazione.com
_____________________________________________________________________________________
        STI s.r.l. via pascoli 10 A/B 24020Gorle (Bg) – ITALY www.stistrumentazione.com
      To calibrate the pressure signal, select the pressure transducer type (PI/PA/PB), input the value in the required
      empty cell and press the corresponding Calib. button.
                          OUT2-P1 CALIB.
                          OUT2-P2 CALIB.
                          OUT2-P3 CALIB.
With this command, selecting the required point, it’s possible to calibrate the OUT1-PA pressure signal.
                    OUT2-P1
                       0.00 Bar
                    PRESS OK TO CONFIRM
      The second line value can be changed by pressing the key ↑/↓ in a range between 0÷150 Psi or 0÷10 bar and
      subsequently confirmed with OK. Press ESC to return to the previous menu.
This function is available on PC software from the STI menu, pushing the Press. Calib. Button.
_____________________________________________________________________________________
        STI s.r.l. via pascoli 10 A/B 24020Gorle (Bg) – ITALY www.stistrumentazione.com
_____________________________________________________________________________________
        STI s.r.l. via pascoli 10 A/B 24020Gorle (Bg) – ITALY www.stistrumentazione.com
      To calibrate the pressure signal, select the pressure transducer type (PI/PA/PB), input the value in the required
      empty cell and press the corresponding Calib. button.
_____________________________________________________________________________________
        STI s.r.l. via pascoli 10 A/B 24020Gorle (Bg) – ITALY www.stistrumentazione.com
      With the keys ↑ / ↓ , it is possible to select the hard limit search direction and, pushing the OK button, it is
      possible to activate the selected function.
PRESS OK TO START
INDEX SEARCH
PRESS OK TO START
_____________________________________________________________________________________
        STI s.r.l. via pascoli 10 A/B 24020Gorle (Bg) – ITALY www.stistrumentazione.com
INDEX SEARCH
At the end of the index search, the last found index position will be displayed on the screen :
INDEX FOUND
                        CYCLES               XXXXXX
                        DELAY                XXXXXX MSEC
                        STEPS                XXXXXX
                        START TEST
     With the keys ↑ / ↓ , it ‘s possible to shift on the demanded line, and pushing the OK button, it’s
     possible to activate the selected option.
3.11.14.3.1              CYCLES
      With this command, it is possible to set up the number of repetitions of the ahead/behind sequence,
      to use for the motor test.
                    CYCLES
                       1
                    PRESS OK TO CONFIRM
      The second line value can be changed by pressing the key ↑/↓ in a range between 1÷ 32767 and
      subsequently confirmed with OK. Press ESC to return to the previous menu.
3.11.14.3.2               DELAY
      With this command, it is possible to set up the delay, expressed in msec, between the start of one
     sequence, ahead or behind, and the successive one, to use for the motor test.
                    DELAY
                      500 MSEC
                    PRESS OK TO CONFIRM
_____________________________________________________________________________________
        STI s.r.l. via pascoli 10 A/B 24020Gorle (Bg) – ITALY www.stistrumentazione.com
      The second line value can be changed by pressing the key ↑/↓ in a range between 0÷ 32767 and
      subsequently confirmed with OK. Press ESC to return to the previous menu.
3.11.14.3.3                  STEPS
      With this command, it is possible to set up the number of steps for the ahead/behind sequence, to
      use for the motor test.
                   STEPS
                     1000
                   PRESS OK TO CONFIRM
      The second line value can be changed by pressing the key ↑/↓ in a range between -32768÷32767
      and subsequently confirmed with OK. Press ESC to return to the previous menu.
START TEST
PRESS OK TO START
_____________________________________________________________________________________
        STI s.r.l. via pascoli 10 A/B 24020Gorle (Bg) – ITALY www.stistrumentazione.com
                                                HART DEBUG
                                                PRESS.CALIB
                                                MOTOR TEST
                                OK              STEP MOTOR
                                        ESC     To return to menu
                    SPEED INI
                       50
                    PRESS OK TO CONFIRM
      The second line value can be changed by pressing the key ↑/↓ in a range between 10÷200 and subsequently
      confirmed with OK. Press ESC to return to the previous menu.
                    SPEED MAX
                       14
                    PRESS OK TO CONFIRM
      The second line value can be changed by pressing the key ↑/↓ in a range between 10÷200 and subsequently
      confirmed with OK. Press ESC to return to the previous menu.
                    ACC. TIME
                       100
                    PRESS OK TO CONFIRM
_____________________________________________________________________________________
        STI s.r.l. via pascoli 10 A/B 24020Gorle (Bg) – ITALY www.stistrumentazione.com
      The second line value can be changed by pressing the key ↑/↓ in a range between 0÷500 and subsequently
      confirmed with OK. Press ESC to return to the previous menu.
3.11.16         GEOMETRIC 0
                                               MAIN
                                               SYSTEM INFO
                                               SYSTEM SET UP
                                               CALIBRATION
                                               COMMAND MODE
                                               FAIL & TRIP SETTING
                                               GENERAL SETTING
                                               SYSTEM DATA
                                               COMMUNICATION
                                               DIAGNOSTIC
                        OK                     ADVANCED
                                               DIAGNOSTIC DATA
                                               PROBE TYPE
                                               INTEGRAL
                                               PROP.GAIN MODE
                                               PROP.BAND MODE
                                               PART NUMBER
                                               PASSWORD
                                               SET AS DEFAULT
                                               RESET STAT
                                               ERASE CALIB
                                               STAT DEBUG
                                               HART DEBUG
                                               PRESS.CALIB
                                               MOTOR TEST
                                               STEP MOTOR
                                OK             GEOMETRIC 0
                                       ESC     To return to menu
With this command, it is possible to modify the geometric zero (Th. 0 Spool), in a range of 0÷6000.
                    GEOMETRIC 0
                      3500
                    PRESS OK TO CONFIRM
      -   to change the proposed value increasing it with the STEM ↑ and decreasing it with the STEM ↓;
      -   to cancel the possible changes and return to the Advanced submenu with the ESC key;
      -   to confirm the inputted value by pressing OK.
_____________________________________________________________________________________
        STI s.r.l. via pascoli 10 A/B 24020Gorle (Bg) – ITALY www.stistrumentazione.com
      To set the value, double click on the corresponding cell, input the value and press “SEND” to confirm it or
      “ABORT” to exit from the input window.
With this set of commands, it’s possible to configure the Min and Max spool limits.
_____________________________________________________________________________________
        STI s.r.l. via pascoli 10 A/B 24020Gorle (Bg) – ITALY www.stistrumentazione.com
      The second line value can be changed by pressing the key ↑/↓ in a range between -3500÷0 and subsequently
      confirmed with OK. Press ESC to return to the previous menu.
      To set the value, double click on the selected cell and press “SEND” to confirm or “ABORT” to exit from this
      window.
      The second line value can be changed by pressing the key ↑/↓ in a range of between 0÷3500 and subsequently
      confirmed with OK. Press ESC to return to the previous menu.
_____________________________________________________________________________________
        STI s.r.l. via pascoli 10 A/B 24020Gorle (Bg) – ITALY www.stistrumentazione.com
       To set the value, double click on the selected cell and press “SEND” to confirm or “ABORT” to exit from this
       window.
4    GRAPH
       This feature allows user to record set point and position signal waveforms for 10 seconds. Moreover, it comes
       with some tools to analyze the acquired waveforms. This feature is available just on the “Remotectrl” program.
       To enable this feature, user must put the system into MANUAL mode. Open the Graph window clicking the
       GRAPH button on the remote control panel.
Using the up/down and right/left arrows on the laptop keyboard is possible to move on the graph’s window.
It’s also possible to make a “zoom in”: right click , define the window to be zoomed in, release the right click.
Pressing the “Graph Cfg” button, the operator can choose the following signals on the graph :
_____________________________________________________________________________________
        STI s.r.l. via pascoli 10 A/B 24020Gorle (Bg) – ITALY www.stistrumentazione.com
Pressing the “Test” button, it’s possible to perform the actuator test and draw the selected signals :
_____________________________________________________________________________________
        STI s.r.l. via pascoli 10 A/B 24020Gorle (Bg) – ITALY www.stistrumentazione.com
5    TROUBLE SHOOTING
  Problem description                             Cause                                                Solution
1. The controller doesn’t    1.1 The power is not connected                            1.1 Connect the power
switch on                    1.2 the power supply voltage is out of the                1.2 check the power supply voltage
                             admissible range (+/-10%)                                 value with a multimeter
                             1.3 the main power switch inside the controller is        1.3 switch on the main power switch
                             OFF
                             1.4 the fuses are blown                                   1.4 replace the fuses
                             1.5 some wiring is not properly done either               1.5 check the wiring using the electrical
                             inside the controller or in the step motor                diagram and that the connector to step
                             enclosure                                                 motor,     encoder      and     pressure
                                                                                       transducers is properly plugged.
                                                                                       1.6 disconnect all the terminal boards
                             1.6 there is a short circuit on some of the               connected to these device and check
                             devices connected to the controller                       whether the controller switches on.
2. Probe error E10           2.1 some wiring is not properly done                      2.1 check the wiring
                             2.2 the software selection in STI menu of the             2.2 check that the software setting
                             used probe is not correct                                 corresponds to the used probe
                             2.3 the probe has been calibrated with a shorter          2.3 erase the previous calibration and
                             stroke process valve                                      perform a new calibration
                             2.4 the probe is damaged                                  2.4 replace the probe
3. Red light flashing on     3.1 the step motor connector is not properly              3.1 check the connector plug
motor-driver    electronic   plugged
board                        3.2 the wiring is not properly done                       3.2 check the wiring
                             3.3 there is an excessive friction on the spool           3.2 check that the spool valve can slide
                             valve driven by the step motor                            smoothly and in STI menu the
                                                                                       difference between step motor and
                                                                                       encoder steps is not too big
4. A change in the valve     4.1 the air supply pressure value is too low              4.1 check the air supply pressure value
position set point doesn’t   4.2 the spool valve is sticking                           4.2 check that the spool valve can slide
affect   the    actuator’s                                                             smoothly and in STI menu the
position                                                                               difference between step motor and
                                                                                       encoder steps is not too big
                             4.3 the parameters configuration is not correct           4.3 check gain and dead band values
                             4.4 actuator and/or jammed valve                          4.3 check that the actuator can move in
                                                                                       a continuous way and not in steps
                             4.5 signal wires are not properly connected               4.5 check signal wires
                             4.6 circuit boards are defective                          4.6 replace circuit boards
                             4.7 calibration and tuning have not been carried          4.7 perform a calibration and make the
                             out                                                       proper tuning
                             4.8 device is in “manual” or “out of service”             4.8 set the system in “in service” mode
                             mode
                             4.9 device is in fail safe status                         4.9 check whether the solenoid valve
                                                                                       making the fail safe mode is energized
5.     Overshooting    or    5.1 incorrect tuning in terms of dead band and            5.1 change the dead band and gain
positioning too slow         gain                                                      values
                             5.2 the spool valve is sticking                           5.2 check that the spool valve can slide
                                                                                       smoothly and in STI menu the
                                                                                       difference between step motor and
                                                                                       encoder steps is not too big
                             5.3 too small air tubing or dirty air filter              5.3 check air tubing size with the factory
                                                                                       and inspect air filter
                             5.4 leakages in air tubing             and     manifold   5.4 check leakages in air tubing and
                             connections                                               manifold connections
                             5.5 process valve is sticking                             5.5 check process valve
6. E05                       6. Pressure fail                                          6.1 check air supply line
                                                                                       6.2 check that the air filter regulator is
                                                                                       properly set
                                                                                       6.3 check that the wiring to air supply
_____________________________________________________________________________________
        STI s.r.l. via pascoli 10 A/B 24020Gorle (Bg) – ITALY www.stistrumentazione.com
                                                           pressure transducer
7. E06                7. Low signal fail limit             7.1 check that the signal wires are
                                                           properly connected to the terminal
                                                           board
                                                           7.2 check with a multimeter the value of
                                                           the signal
                                                           7.3 check that the internal flat cables
                                                           between the two terminal boards are
                                                           properly connected
8. E07                8. High signal fail limit            8.1 check that the signal wires are
                                                           properly connected to the terminal
                                                           board
                                                           8.2 check with a multimeter the value of
                                                           the signal
                                                           8.3 check that the internal flat cables
                                                           between the two terminal boards are
                                                           properly connected
9. E08                9. Position excess error             9. see point 4. of this table
10. E09               10. Position excess warning          10. see point 4. of this table
11. E11               11. Low power fail                   11.1 check that the power wires are
                                                           properly connected to the terminal
                                                           board
                                                           11.2 check with a multimeter the value
                                                           of the power supply
                                                           11.3 check that the fuses are not blown
12. E12               12. Hard limits error                12.1 check the probe is working
                                                           properly
                                                           12.2 check that the air supply value is
                                                           not too low
13. E13               13. DSP timeout                      13. replace the display electronic board
14. E14               14. Watch dog error                  14. replace the display electronic board
15. E15               15. High power fail                  15.1 check that the power wires are
                                                           properly connected to the terminal
                                                           board
                                                           15.2 check with a multimeter the value
                                                           of the power supply
16. E16               16. Error on solenoid valve SOV1     16.1 check that the solenoid valve’s coil
                                                           is not burnt
                                                           16.2 check the wiring between the
                                                           solenoid valve and the controller
                                                           16.3 if the solenoid valve is supposed to
                                                           be energized check that the yellow light
                                                           on the side of the SOV1 connector is
                                                           ON.
17. E17               17. Error on solenoid valve SOV2     17.1 check that the solenoid valve’s coil
                                                           is not burnt
                                                           17.2 check the wiring between the
                                                           solenoid valve and the controller
                                                           17.3 if the solenoid valve is supposed to
                                                           be energized check that the yellow light
                                                           on the side of the SOV2 connector is
                                                           ON.
18. E18               18. Error on solenoid valve SOV3     18.1 check that the solenoid valve’s coil
                                                           is not burnt
                                                           18.2 check the wiring between the
                                                           solenoid valve and the controller
                                                           18.3 if the solenoid valve is supposed to
                                                           be energized check that the yellow light
                                                           on the side of the SOV3 connector is
                                                           ON.
19. E19               19. DSP restart                      19.1 restart again the controller and
                                                           check whether the error is cleared
_____________________________________________________________________________________
        STI s.r.l. via pascoli 10 A/B 24020Gorle (Bg) – ITALY www.stistrumentazione.com
Le informazioni riportate sul seguente manuale sono coperte da copyright. Tutti i diritti sono riservati. Nessuna parte di questo
manuale e della relativa documentazione citata e/o allegata può essere riprodotta senza il preventivo consenso scritto della STI s.r.l.
STI s.r.l. non si assume alcuna responsabilità per eventuali danni a persone, apparecchiature o dati conseguenti all’uso improprio del
prodotto a cui il manuale si riferisce.
Le informazioni contenute in questo documento sono soggette a modifiche senza preavviso.
Information in this manual is protected by copyright. All rights are reserved. No part of this manual and relevant mentioned and/or
enclosed documentation may be reproduced without written authorization by STI s.r.l.
STI s.r.l. is not responsible for possible damage to people, equipment or data which might arise from incorrect use of the product to
which the manual is referred.