Root Cause analysis:-
1. Due to vibration on Generator top the RTD element of stator winding outlet temperature
malfunctioned, This RTD element is used in Primary water temperature control loop.
2. Because of this malfunctioning, the value of primary water stator winding outlet temperature goes
below 40 deg which is used as process value of Primary Water temperature control loop .Set point of
PW temperature control valve is 40 deg .As SP=40 deg and PV = Below 40 deg temperature control
valve got closed and primary water temperature increased rapidly up to tripping value and Unit 08
Turbine tripped on Primary water temperature very High.
(Tripping Value = 60 deg)
Remedial Action taken :-
1.In the place of temperature gauge at primary water stator winding outlet, An additional capillary type RTD
element is installed and its signal is taken in DCS.
Logic Modication work carried out as per below:
Before Modification:
PV
PW Temp. RTD element
PV-SP
SP
Set point = 40 Deg C
After Modification:
Old PW Temp. RTD element PV
MAX
Installed PW Temp. RTD PV-SP
SP
Set point = 40 Deg C
2. Primary water temperature control valve protection open command value is modified from >55 deg to
>50 deg of primary water temperature after cooler.