ENERGY CABLES 0.
6/1 kV
N2XY
Underground cable with XLPE insulation and PVC sheath
DESIGN TECHNICAL DATA
Standard:
DIN VDE 0276-603 (HD 603)
Rated voltage:
0.6/1 kV
Test voltage:
4 kV/50 Hz
Temperature range:
4 3 2 1
laying temperature: min. –5 °C
operating temperature: –50 °C up to +90 °C
conductor temperature: max. +90 °C
1 | Copper conductor, round solid (RE), round stranded (RM), short-circuit temperature: max. +250 °C/5 s
resp. sector-shaped stranded (SM)
2 | Core insulation (XLPE) Bending radius (min.):
3 | Inner covering (EPDM) 15 x ∅ of cable (single core)
4 | Sheath (PVC black, UV resistant) 12 x ∅ of cable (multi-core)
Core identification:
HD 308 S2
Fire properties:
APPLICATION
flame retardant:
EN 60332-1-2
Power distribution cables in power stations, industrial installa-
tions and switchgears, as well as in local mains. For fixed installa-
tion underground, in interior premises, cable ducts, in the open
air, in water – as permitted by the local building regulations – if
no risk of any mechanical damage is to be expected.
Number of Max. conductor Current rating Current rating Outer diameter Total weight Standard
cores x resistance in the ground1) in the air1) (mm) ca. (kg/km) ca. lengths/
nominal cross (Ω/km) (A) (A) packing
section (m)
(mm²)
N2XY
1 x 10 RE 1.830 136 99 8.9 190 500 D, 1,000 D
1 x 16 RE 1.150 176 131 10.0 230 500 D, 1,000 D
4 x 16 RM 1.150 112 98 22.0 1,065 1,000 D
1 x 25 RM 0.727 229 177 12.1 350 500 D, 1,000 D
4 x 25 RM 0.727 145 133 26.7 1,580 1,000 D
1 x 35 RM 0.524 275 217 13.1 445 500 D, 1,000 D
4 x 35 RM 0.524 174 162 29.3 2,060 1,000 D
1 x 50 RM 0.387 326 265 14.6 575 500 D, 1,000 D
4 x 50 SM 0.387 206 197 34.4 2,470 1,000 D
1 x 70 RM 0.268 400 336 16.5 780 500 D, 1,000 D
4 x 70 SM 0.268 254 250 38.1 3,330 1,000 D
1 x 95 RM 0.193 480 415 18.2 1,030 500 D, 1,000 D
4 x 95 SM 0.193 305 308 43.2 4,500 500 D
1 x 120 RM 0.153 548 485 19.9 1,280 500 D, 1,000 D
4 x 120 SM 0.153 348 359 46.6 5,510 500 D
1 x 150 RM 0.124 616 557 22.1 1,560 500 D, 1,000 D
44
ENERGY CABLES 0.6/1 kV
PRAKAB PRAŽSKÁ KABELOVNA
N2XY
Number of Max. conductor Current rating Current rating Outer diameter Total weight Standard
cores x resistance in the ground1) in the air1) (mm) ca. (kg/km) ca. lengths/
nominal cross (Ω/km) (A) (A) packing
section (m)
(mm²)
N2XY
4 x 150 SM 0.124 392 412 48.6 6,690 500 D
1 x 185 RM 0.099 698 646 24.2 1,920 500 D, 1,000 D
4 x 185 SM 0.099 444 475 50.4 7,340 500 D
1 x 240 RM 0.075 815 774 26.9 2,500 500 D, 1,000 D 4
4 x 240 SM 0.075 517 564 55.2 9,610 500 D
1 x 300 RM 0.060 927 901 29.4 3,100 500 D, 1,000 D
1 x 400 RM 0.047 1,064 1,060 32.6 3,920 500 D, 1,000 D
1 x 500 RM 0.037 1,227 1,252 36.4 4,970 500 D, 1,000 D
1 x 630 RM 0.028 1,421 1,486 41.1 6,400 500 D, 1,000 D
1) basic rated current acc. to DIN VDE 0276-603 (HD 603)
Subject to technical changes.
PRAKAB.CZ | MEMBER OF SKB-GROUP 45