ENGINEERING REVIEW COMMENTS
CONTRACT NO : 7200027719                                                                                                                                              EWR/memo No : PJ-Y-17-1342
     CONTRACT TITLE: Upgrade Of Plant Air & Instrument Air Compressor At GTG Area-YANBU                                                                                    DISCIPLINE: Documentation
     CONTRACTOR : BABCOCK BORSIG SERVICE ARABIA
     REVIEW SUBJECT: O&M Manuals & As Built-Drawings
      Sr.        Ref. Dwg. /                                                                              COMMENTS                                                                                           ACTION
      No.         Doc. No.               (The review comments are only documentation point of view. Ensure that it is review by the concern).
                                                  Operation and maintenance manuals shall contain the functional description of the system and “As Built” status of
                                                   the equipment.
                                                  System description shall have the complete details of the equipment provided and interface details of the
                                                   current/existing system with its tag numbering.
                                                  Provide details of the equipment supplied/installed with all the technical specification data sheets and other relevant
                                                   information.
                                                  PEL, MEL & RSPL – Please add TAG numbers of the equipment and location details as a minimum.
                                                  Provide Soft Copy in PDF searchable format.
                                                  Provide Contract Scope and Technical specification.
                                         Provide complete package for review.
                                         Send it to the end user.
                                                                                                                                                                                                             Line Item
                    As Built                       Title blocks are missing from the drawing. (01369-PD-A0-0002,PD-A2-151) – SASEC SCOPE                                                                1,2,3,4,7,8 – To be
                                                   Breaking line connection are found in the drawing. (2-ME-A0-653,) – SASEC SCOPE
                   Drawings                                                                                                                                                                             updated by SASEC
                                                   Most of the drawing content is not visible. (01369-PD-A0-0002 , PD-A2-151) – SASEC SCOPE
                                                   It is unclear from the status of the drawing weather it is As-Built or under demolition. (01369-IN-A2-2712,2713) –
                                                    SASEC SCOPE
                                                   Incorrect representation of section is found in the drawing. (27719-EE-A1-002) – BBSA Already incorporated
                                                   Incorrect section references are found in the drawing. (27719-EE-A1-002,003) – BBSA Already incorporated
                                                   A consolidated list of all the drawings shall be provided in the attached excel format. (Below) – SASEC SCOPE
                                                   All of the above comments are based on random check only. Contractor shall check, verify and correct all the
                                                    drawings based RC CAD standards and RCGDCTG. – SASEC SCOPE
     Drawing list format in excel:
                                                               Sheet
Sr#          Contract#            Drawing Number                            Rev.           Date                            Drawing Title                                              Dwg. Path in CD
                                                                No.
1.
            PIC-B-1191A            1191A-EE-A1-001                1           1        dd-mm-yyyy                               XXXXXX                                 D:\PIC-B-1191A\EE\1191A-EE-A1-001.dgn
     Disclaimer: Review and any comments or omissions, errors/discrepancies in the comments by Marafiq on this submittal shall not relieve Contractor from the responsibility of verifying and checking the design with respect to the
     Contract Specification and Requirements prior to Approval.