399 Power System Analysis
399 Power System Analysis
Restrictions apply.
                  A n American National Standard
                   IEEE Recommended Practice for
                      Industrial and Commercial
                       Power Systems Analysis
                                Published by
                                The Institute of Electrical and Electronics Engineers, Inc
Authorized licensed use limited to: IEEE Xplore. Downloaded on November 08,2014 at 04:51:47 UTC from IEEE Xplore. Restrictions apply.
                                                                                                      AN SI/IEEE
                                                                                                      Std 399-1980
                                                          Sponsor
                                     Power System Technologies Committee
                                                    of the
                                      IEEE Industry Applications Society
Authorized licensed use limited to: IEEE Xplore. Downloaded on November 08,2014 at 04:51:47 UTC from IEEE Xplore. Restrictions apply.
                                           Approved December 20,1979
                                              IEEE Standards Board
Authorized licensed use limited to: IEEE Xplore. Downloaded on November 08,2014 at 04:51:47 UTC from IEEE Xplore. Restrictions apply.
                   IEEE Standards documents are developed within the Technical Com-
                 mittees of the IEEE Societies and the Standards Coordinating Commit-
                 tees of the IEEE Standards Board. Members of the committees serve
                 voluntarily and without compensation. They are not necessarily mem-
                 bers of the Institute. The standards developed within IEEE represent
                 a consensus of the broad expertise on the subject within the Institute
                 as well as those activities outside of IEEE which have expressed an in-
                 terest in participating in the development of the standard.
                   Use of an IEEE Standard is wholly voluntary. The existence of an
                 IEEE Standard does not imply that there are no other ways to pro-
                 duce, test, measure, purchase, market, or provide other goods and ser-
                 vices related to the scope of the IEEE Standard. Furthermore, the view-
                 point expressed at the time a standard is approved and issued is subject
                 to change brought about through developments in the state of the art
                 and comments received from users of the standard. Every IEEE Stan-
                 dard is subjected to review at least once every five years for revision or
                 reaffirmation. When a document is more than five years old, and has
                 not been reaffirmed, it is reasonable to conclude that its contents,
                 although still of some value, do not wholly reflect the present state of
                 the art. Users are cautioned t o check to determine that they have the
                 latest edition of any IEEE Standard.
                   Comments for revision of IEEE Standards are welcome from any
                 interested party, regardless of membership affiliation with IEEE. Sug-
                 gestions for changes in documents should be in the form of a proposed
                 change of text, together with appropriate supporting comments.
                   Interpretations: Occasionally questions may arise regarding the mean-
                 ing of portions of standards as they relate to specific applications. When
                 the need for interpretations is brought to the attention of IEEE, the
                 Institute will initiate action to prepare appropriate responses. Since
                 IEEE Standards represent a consensus of all concerned interests, it is
                 important to ensure that any interpretation has also received the con-
                 currence of a balance of interests. For this reason IEEE and the mem-
                 bers of its technical committees are not able to provide an instant re-
                 sponse to interpretation requests except in those cases where the matter
                 has previously received formal consideration.
                   Comments on standards and requests for interpretations should be ad-
                 dressed to:
                                       Secretary, IEEE Standards Board
                                       345 East 47th Street
                                       New York, NY 10017
                                       USA
Authorized licensed use limited to: IEEE Xplore. Downloaded on November 08,2014 at 04:51:47 UTC from IEEE Xplore. Restrictions apply.
                                                      Foreword
        (This Foreword is not a part of IEEE Std 399-1980, IEEE Recommended Practice for Industrial
      and Commercial Power Systems Analysis.)
        This Recommended Practice is the product of about ten years of effort by a work-
      ing group of the Power System Technologies Committee of IEEE Industry Applica-
      tions Society. It is intended as a practical, general treatise on the theoretical basis of
      power system analysis, and as a reference work on the analytical techniques most
      commonly applied to electric power systems in industrial plants and commercial
      buildings.
        IEEE Recommended Practice for Industrial And Commercial Power System
      Analysis, the IEEE Brown Book, joins the series of Color Books sponsored by the
      Power System Technologies Committee of IEEE Industry Applications Society. It is
      both complementary and supplementary to the other color books, extending the
      coverage of some topics which they introduce as well as discussing some entirely
      new material.
        Comments, corrections, and suggestions for the next revision of the Brown Book
      are welcome and should be submitted to the
          IEEE Standards Board
          345 East 47th Street
          New York, New York 10017.
        At the time it recommended these practices, the working group of the Power Sys-
      tem Technologies Committee had the following members and contributors :
Authorized licensed use limited to: IEEE Xplore. Downloaded on November 08,2014 at 04:51:47 UTC from IEEE Xplore. Restrictions apply.
Authorized licensed use limited to: IEEE Xplore. Downloaded on November 08,2014 at 04:51:47 UTC from IEEE Xplore. Restrictions apply.
                               Industrial and Commercial
                                Power Systems Analysis
                                                         1st Edition
Authorized licensed use limited to: IEEE Xplore. Downloaded on November 08,2014 at 04:51:47 UTC from IEEE Xplore. Restrictions apply.
Authorized licensed use limited to: IEEE Xplore. Downloaded on November 08,2014 at 04:51:47 UTC from IEEE Xplore. Restrictions apply.
                                                        Contents
      SECTION                                                                                                            PAGE
       1. Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .   21
          1.1 General Discussion .........................................                                                   21
          1.2 History of Power System Studies ..............................                                                 21
          1.3 Applying Power System Analysis Techniques t o Industrial
                 and Commercial Power Systems .............................                                                  22
          1.4 Purposes of this Recommended Practice ........................                                                 22
               1.4.1 WhyaStudy ........................................                                                      22
               1.4.2 How t o Prepare for a Power System Study . . . . . . . . . . . . . . . . .                              22
               1.4.3 The Most Important System Studies ......................                                                23
          1.5 Standard References ........................................                                                   23
       2 . Applications of Power System Analysis .............................                                               24
           2.1 Introduction ..............................................                                                   24
           2.2 Load Flow Studies .........................................                                                   25
           2.3 Fault and Short-circuit Studies ...............................                                               25
           2.4 Stability Studies ...........................................                                                 25
           2.5 Motor Starting Studies ......................................                                                 26
           2.6 System Transients Studies ...................................                                                 26
           2.7 Reliability Analysis ........................................                                                 26
           2.8 Power Generation Planning ..................................                                                  26
       3. Analytical Procedures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .        28
          3.1 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .       28
          3.2 The Fundamentals ..........................................                                                    29
              3.2.1 Linearity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .          29
              3.2.2 Superposition . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .              30
              3.2.3 The Thevenin Equivalent Circuit .........................                                                32
              3.2.4 The Sinusoidal Forcing Function ........................                                                 34
              3.2.5 Phasor Representation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .                  35
              3.2.6 The Fourier Representation ............................                                                  37
              3.2.7 The Single-phase Equivalent Circuit ......................                                               37
              3.2.8 The Symmetrical Component Analysis ....................                                                  39
              3.2.9 The Per Unit Method ..................................                                                   42
          3.3 References and Bibliography .................................                                                  43
Authorized licensed use limited to: IEEE Xplore. Downloaded on November 08,2014 at 04:51:47 UTC from IEEE Xplore. Restrictions apply.
        SECTION                                                                                                        PAGE
         4 . System Modeling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .   44
             4.1 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .    44
             4.2 Modeling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .    44
             4.3   Review of Basics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .    45
                   4.3.1   Passive Elements ...................................                                            45
                   4.3.2   Active Elements ...................................                                             46
             4.4 Power Network Solution ...................................                                                49
             4.5 ImpedanceDiagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .            52
             4.6   Extent of the Model .......................................                                             55
                   4.6.1   General ..........................................                                              55
                   4.6.2   Utility Supplied Systems .............................                                          55
                   4.6.3   Isolated Systems ...................................                                            55
                   4.6.4   Swing Bus ........................................                                              56
             4.7 Models of Branch Elements .................................                                               56
                   4.7.1   Lines ............................................                                              56
                           4.7.1.1 Long Lines ................................                                             58
                           4.7.1.2 Medium Lines ..............................                                             58
                           4.7.1.3 Short Lines ................................                                            59
                   4.7.2   Cables ............................................                                             59
                   4.7.3   Determination of Constants ..........................                                           60
                           4.7.3.1 Resistance .................................                                            60
                           4.7.3.2 Inductive Reactance .........................                                           61
                           4.7.3.3 Shunt Capacitive Reactance . . . . . . . . . . . . . . . . . . .                        62
                   4.7.4   Reactors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .      62
                   4.7.5   Capacitors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .      62
                   4.7.6   Transformers ......................................                                             63
                           4.7.6.1 Two-Winding Transformers ....................                                           63
                           4.7.6.2 Transformer Taps ...........................                                            64
                           4.7.6.3 Three-Winding Transformers . . . . . . . . . . . . . . . . . . .                        65
                           4.7.6.4 Phase-Shifting Transformers . . . . . . . . . . . . . . . . . . .                       66
                           4.7.6.5 Other Transformer Models ....................                                           66
             4.8 Power System Data Development .............................                                               66
                   4.8.1   Per Unit Representations .............................                                          66
                   4.8.2   Applications Example ...............................                                            68
             4.9 Models of Bus Elements ....................................                                               72
                   4.9.1   Loads in General ...................................                                            72
                   4.9.2   Induction Motors ..................................                                             75
                           4.9.2.1 Constant kVA Model .........................                                            77
                           4.9.2.2 Models for Short-circuit Studies . . . . . . . . . . . . . . . .                        78
                           4.9.2.3 Constant Impedance Model ....................                                           79
                   4.9.3   Synchronous Machines ..............................                                             79
                           4.9.3.1 Steady State Models .........................                                           79
                                     4.9.3.1.1 Generators ........................                                         79
                                     4.9.3.1.2 Synchronous Condenser . . . . . . . . . . . . . .                           80
                                     4.9.3.1.3 Synchronous Motors . . . . . . . . . . . . . . . .                          80
Authorized licensed use limited to: IEEE Xplore. Downloaded on November 08,2014 at 04:51:47 UTC from IEEE Xplore. Restrictions apply.
   SECTION                                                                                                              PAGE
                       4.9.3.2 Short-circuit Models .........................                                            80
                       4.9.3.3 Stability Models ............................                                             84
                                  4.9.3.3.1 Classical Model .....................                                        84
                                  4.9.3.3.2 The H Constant ....................                                          84
                                  4.9.3.3.3 Stability Model Variations . . . . . . . . . . . .                           85
                       4.9.3.4 Exciter Models .............................                                              85
                       4.9.3.5 Prime Movers and Governor Models . . . . . . . . . . . . .                                88
          4.10 Miscellaneous Bus Elements Models ...........................                                             88
               4.10.1 Lighting and Electric Heating .........................                                            88
               4.10.2 Electric Furnaces ...................................                                              88
               4.10.3 ShuqCapacitors ...................................                                                 89
               4.10.4 Shunt Reactors ....................................                                                89
          4.11 References . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .    89
     5 . Load  Flow Studies . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .     91
         5.1    Introduction .............................................                                                91
         5.2    System Representation .....................................                                               92
         5.3    System Data Organization ..................................                                               94
         5.4    Load Flow Study Example ..................................                                                94
                5.4.1 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .       94
                5.4.2 Input Requirements .................................                                                94
                5.4.3 Special Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .         101
          5.5   Input Card Preparation .....................................                                             101
          5.6 Load Flow Results . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .          102
          5.7 Load Flow Analysis .......................................                                                 105
          5.8 Load Flow Output Presentation ..............................                                               106
          5.9 Load Flow Analysis .......................................                                                 106
          5.10 Conclusions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .     108
     6.   Short-circuit Studies . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .    109
          6.1 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .   109
          6.2 Short-circuit Study Procedure ................................                                             109
              6.2.1 Preparing a One-Line Diagram ...........................                                             109
              6.2.2 Determining Depth and Accuracy of a Study . . . . . . . . . . . . . .                                110
              6.2.3 Calculating Impedance Values ...........................                                             110
              6.2.4 Developing an Impedance Diagram .......................                                              111
              6.2.5 Converting Impedances to a Common Base . . . . . . . . . . . . . . . . .                             111
              6.2.6 Interpretation and Application of the Study . . . . . . . . . . . . . . . .                          111
          6.3 Use of the Computer .......................................                                                112
          6.4 Short-circuit Study Example .................................                                              113
          6.5 Digital Computer Program Output Records ......................                                             119
          6.6 References . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .   124
     7 . Transient Stability Studies . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .       125
         7.1 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .    125
         7.2 Stability Fundamentals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .            125
             7.2.1 Definition of Stability .................................                                             125
Authorized licensed use limited to: IEEE Xplore. Downloaded on November 08,2014 at 04:51:47 UTC from IEEE Xplore. Restrictions apply.
        SECTION                                                                                                              PAGE
                     7.2.2 Steady-State Stability .................................                                               125
                     7.2.3 Transient Stability . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .            126
                     7.2.4 Two-Machine Systems .................................                                                  128
                     7.2.5 Multimachine Systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .                 128
              7.3    Problems Caused by Instability ...............................                                               128
              7.4    System Disturbances that can Cause Instability . . . . . . . . . . . . . . . . . . . 129
              7.5    Solutions t o Stability Problems ...............................                                             129
                     7.5.1 System Design .......................................                                                  129
                     7.5.2 Design and Selection of Rotating Equipment . . . . . . . . . . . . . . . 130
                     7.5.3 System Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .              130
                     7.5.4   Voltage Regulator        and    Exciter      Characteristics          . . .  . . . . . . . . . . . . 130
              7.6    Transient Stability Studies . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .            130
                     7.6.1 History ............................................                                                   130
                     7.6.2 How Stability Programs Work ...........................                                                131
                     7.6.3 Simulation of the System ..............................                                                131
                     7.6.4 Simulation of Disturbances .............................                                               132
                     7.6.5 Data Requirements for Stability Studies . . . . . . . . . . . . . . . . . . . 132
                     7.6.6 Stability Program Output ..............................                                                133
                     7.6.7 Interpreting Results-Swing Curves .......................                                              134
              7.7    Stability Studies on a Typical System ..........................                                             134
              7.8    References . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .     139
         8 . Motor Starting Studies             ..........................................                                     140
              8.1 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .     140
              8.2 Need for Motor Starting Studies ...............................                                              140
                  8.2.1 Problems Revealed . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .                140
                  8.2.2 Voltage Dips . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .           140
                  8.2.3 Weak Source Generation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .                   141
                  8.2.4 Special Torque Requirements ...........................                                                141
              8.3 Recommendations .........................................                                                    142
                  8.3.1 Voltage Dips . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .           142
                  8.3.2 Analyzing Starting Requirements ........................                                               144
              8.4 Types of Studies . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .       144
                  8.4.1 The Voltage Drop Snapshot ............................                                                 144
                  8.4.2 The Detailed Voltage Profile ............................                                              144
                  8.4.3 The Motor Torque and Acceleration Time Analysis . . . . . . . . . .                                    144
                  8.4.4 Adaptations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .          145
              8.5 Data Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .          145
                  8.5.1 Basic Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .              145
                  8.5.2 Simplifying Assumptions ...............................                                                146
              8.6 Solution Procedures and Examples .............................                                               146
                  8.6.1 The Mathematical Relationships .........................                                               147
                  8.6.2 Other Factors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .            149
                  8.6.3 The Simple Voltage Drop Determination . . . . . . . . . . . . . . . . . .                              153
                  8.6.4 Time-Dependent Bus Voltages ...........................                                                156
                  8.6.5 The Speed-Torque and Motor Accelerating Time Analysis . . . . .                                        159
Authorized licensed use limited to: IEEE Xplore. Downloaded on November 08,2014 at 04:51:47 UTC from IEEE Xplore. Restrictions apply.
    SECTION                                                                                                               PAGE
Authorized licensed use limited to: IEEE Xplore. Downloaded on November 08,2014 at 04:51:47 UTC from IEEE Xplore. Restrictions apply.
        SECTION                                                                                                                       PAGE
               12.2 The Human Factor ........................................                                              197
               12.3 The Physical Circuit .......................................                                           200
                    12.3.1 Ground Resistivity .................................                                            200
                    12.3.2 Fault Current-Magnitude and Duration . . . . . . . . . . . . . . . . . 201
                    12.3.3 Fault Current-The Role of Grid Resistance . . . . . . . . . . . . . . . 202
                    12.3.4 GridGeometry ....................................                                               203
               12.4 The Computer in Action ...................................                                             206
               12.5 Input Data Requirements ...................................                                            208
               12.6 Typical Computer Output ..................................                                             214
               12.7 Conclusion . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 214
               12.8 References ..............................................                                              214
        13. Computer Services .............................................                                                           217
             13.1 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .              217
             13.2 Computer Systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .                    217
                     13.2.1 In-House Systems ..................................                                                       217
                     13.2.2 Commercial Computing Services .......................                                                     218
             13.3 Types of Computing Service .................................                                                        218
             13.4 Use of Computing Services ..................................                                                        219
             13.5 Availability of Computing Services ............................                                                     220
        Index . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .   221
        FIGURES
        Fig 1         Linearity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .      29
        Fig 2         Superposition . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .          31
        Fig 3         The Thevenin Equivalent .....................................                                                    31
        Fig 4         Current Flow of a Thevenin Equivalent Representation . . . . . . . . . . . . .                                   33
        Fig 5         Fault Flow . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .         34
        Fig 6         The Sinusoidal Forcing Function ..............................                                                   35
        Fig 7         The Phasor Representation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .                  36
        Fig 8         The Fourier Representation ..................................                                                    36
        Fig 9         (a) Three-phase Diagram. (b) Single-phase Equivalent.
                      and (c) One-Line Diagram ....................................                                                    38
        Fig 1 0       (a) Three-phase Diagram. (b) Single-phase Equivalent.
                      and (c) One-Line Diagram ....................................                                                    39
       Fig 11         The Symmetrical Component Analysis ..........................                                                    40
       Fig 1 2        (a) Classical Ohmic Representation. (b) Per Unit Representation . . . . . .                                      43
       Fig 13         Squirrel Cage Induction Motor Model ...........................                                                  47
       Fig 1 4        Section of a Typical Industrial Plant Impedance Diagram . . . . . . . . . . . .                                  48
       Fig 15         Single Line Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .              50
       Fig 1 6        ImpedanceDi agram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .              51
       Fig 1 7        Flow Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .           53
       Fig 18         Suggested Format Raw Data Diagram ...........................                                                    54
       Fig 1 9        Equivalent Circuit of Short Conductor ..........................                                                 56
Authorized licensed use limited to: IEEE Xplore. Downloaded on November 08,2014 at 04:51:47 UTC from IEEE Xplore. Restrictions apply.
    FIGURE                                                                                                               PAGE
    Fig 20       (a) Line with Distributed Constants. (b) Long Line
                 Equivalent Circuit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .      57
    Fig 21       Medium Line Equivalent Circuits. (a) Nominal n (b) Nominal T . . . . . . .                                  59
    Fig 22       Short Line Equivalent Circuit .................................                                             59
    Fig 23       Two-Winding Transformer Equivalent Circuits ....................                                            63
    Fig 24       Two-Winding Transformer Approximate Equivalent Circuits . . . . . . . . .                                   64
    Fig 25       Three-Winding Transformer Approximate Equivalent Circuits.
                 (a) Simplified-Delta. (b) Simplified-Wye .......................                                            65
    Fig 26       Impedance and Flow Diagrams. (a) Impedance Diagram.
                 (b) Flow Diagram ..........................................                                                 67
    Fig 27       Impedance Diagram Raw Data ................................                                                 69
    Fig 28       Impedance Diagram Per Unit data ..............................                                              73
    Fig 29       Effect of Voltage Variations for Three Types of Loads . . . . . . . . . . . . . .                           74
    Fig 30       Induction Motor Equivalent Circuit ............................                                             75
    Fig 31       Induction Motor Torque Versus Speed ..........................                                              76
    Fig 32       Induction Motor Current Versus Speed ..........................                                             76
    Fig 33       Induction Motor Power Factor Versus Speed .....................                                             77
    Fig 34       Effect of Votlage Variations on Typical Induction Motor
                 Characteristics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .   78
    Fig 35       Model of Induction Motor for Short-circuit Study . . . . . . . . . . . . . . . . .                          78
    Fig 36       V--C urves. Synchronous Motor. 2000 hp. 4000 V. 180 rlmin.
                 0.8 Lead Power Factor ......................................                                                 81
    Fig 37       Models of Synchronous Machines for Short-circuit Studies . . . . . . . . . .                                 83
    Fig 38       General Model for AC Machines in Short-circuit Studies . . . . . . . . . . . .                               84
    Fig 39       Saturation Curves ..........................................                                                 86
    Fig 40       IEEE Type 1 Excitation System ...............................                                                86
    Fig 41       Lagcircuit ...............................................                                                   87
    Fig 42       Leadcircuit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .      88
    Fig 43       Generators Connected t o their Bus .............................                                             93
    Fig 44       Connection of Buses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .          93
    Fig 45       Auxiliary Bus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .      93
    Fig 46       One-Line Connection Diagram ................................                                                 95
    Fig 47       ImpedanceDiagram .........................................                                                   96
    Fig 48       InputDataSheet F o r m 1 ....................................                                                97
    Fig 49       Input Data Sheet Form 2 ....................................                                                 99
    Fig 50       Input Data Sheet Form 3 ....................................                                                100
    Fig 51       Printed Computer Output ....................................                                                103
    Fig 52       Printed Computer Output ....................................                                                104
    Fig 53       Typical Industrial Plant Electric System .........................                                          107
    Fig 54       One-Line Diagram of Industrial System for Short-circuit
                 Study Example . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .       116
    Fig 55       Impedance Diagram for Short-circuit Study Example . . . . . . . . . . . . . . .                             117
    Fig 56       Data Taken from the Impedance Diagram and Arranged for Program
                 Input Data Paper Tape Medium Voltage Interrupting Calculation . . . . . .                                   120
    Fig 57       Program Listing of Input Data from Data Tape ....................                                           121
Authorized licensed use limited to: IEEE Xplore. Downloaded on November 08,2014 at 04:51:47 UTC from IEEE Xplore. Restrictions apply.
      FIGURE                                                                                                              PAGE
       Fig 58      Sample Computer Output Listing of Remote Bus Voltages and
                   Short-circuit Contributions t o the Faulted Bus. Medium Voltage
                   Interrupting Case Short-circuit Study ...........................                                           122
       Fig 59      Computer Output Giving Fault Levels in MVA for the Four Faulted
                   Buses. Medium Voltage Interrupting Case Short-circuit Study . . . . . . . .                                 123
       Fig 60      Simplified Two-Machine Power System ..........................                                              125
       Fig 6 1     Torque Versus Rotor Angle Relationship for Synchronous
                   Machines in Steady State .....................................                                              127
       Fig 62      Computer Printout of Swing Curves for Case I Fault on
                   System in Fig 6 3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .     135
       Fig 63      Single-Line Diagram of System whose Swing Curves Appear in
                   Figs62and64 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .       136
       Fig 64      Computer Printout of Swing Curves for Case I1 Fault on System
                   ShowninFig63 ...........................................                                                    137
       Fig 65      Single-Line Diagram of a Typical Large Industrial Power System
                   with On-Site Generation .....................................                                               138
       Fig 66      Typical Generator Terminal Voltage Characteristics for Various
                   Exciter Regulator Systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .             141
       Fig 67      Typical Wound Rotor Motor Speed-Torque Characteristics . . . . . . . . . . .                                143
       Fig 68      Typical Motor and Load Speed-Torque Characteristics . . . . . . . . . . . . . .                             145
       Fig 69      Simplified Equivalent Circuit for a Motor on Starting . . . . . . . . . . . . . . .                         146
       Fig 70      Simplified Impedance Diagram ................................                                               147
       Fig 71      Typical One-Line Diagram ....................................                                               148
       Fig 72      Impedance Diagram for System in Fig 71 ........................                                             149
       Fig 73      Revised Impedance Diagram Showing Transient Reactance
                   ofGenerator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .     150
       Fig   74    Simplified Representation of Generator Exciter/Regulator System . . . . .                                   151
       Fig   75    Load Flow Computer Output - Steady State .....................                                              154
       Fig   76    Load Flow Computer Output - Voltage Dip on Motor Starting . . . . . . .                                     155
       Fig   77    Simplified System Model for Generator Representation
                   During Motor Starting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .         156
       Fig 78      Typical Output - Generator Motor Starting Program . . . . . . . . . . . . . . .                             157
       Fig 79      Typical Output .     Generator Motor Starting Program . . . . . . . . . . . . . . .                         157
       Fig 80      Typical Output .     Plot of Generator Voltage Dip . . . . . . . . . . . . . . . . . .                      158
       Fig 81      Typical Output .     Plot of Motor Voltage Dip .....................                                        158
       Fig 82      Simplified Representation of Typical Regulator/Exciter
                   Models for Use in Computer Programs ..........................                                              159
      Fig 83       Simplified System Model for Accelerating Time and
                   Speed-Torque Calculations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .             159
      Fig 84       Typical Motor Speed-Current Characteristic ......................                                           160
      Fig 85       Typical Output .     Motor Speed-Torque and Accelerating
                   TimeProgram .............................................                                                   161
      Fig 86       6.Phase, 6-Pulse Rectifier ....................................                                             165
      Fig 87       6.Phase, 6-Pulse Rectifier ....................................                                             165
      Fig 88       SeriesCircuit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .   166
Authorized licensed use limited to: IEEE Xplore. Downloaded on November 08,2014 at 04:51:47 UTC from IEEE Xplore. Restrictions apply.
   FIGURE                                                                                                            PAGE
TABLES
Authorized licensed use limited to: IEEE Xplore. Downloaded on November 08,2014 at 04:51:47 UTC from IEEE Xplore. Restrictions apply.
        TABLE                                                                                                          PAGE
Authorized licensed use limited to: IEEE Xplore. Downloaded on November 08,2014 at 04:51:47 UTC from IEEE Xplore. Restrictions apply.
                                               1. Introduction
     1.1 General Discussion. IEEE Std 399-                        ments the other IEEE color book
     1980, IEEE Recommended Practice for                          standards, and emphasizes up-to-date
     Industrial and Commerical Power System                       techniques in system studies which are
     Analysis, commonly known as the IEEE                         most applicable t o industrial and com-
     Brown Book, is published by the Institute                    mercial power systems. Today, such tech-
     of Electrical and Electronics Engineers                      niques are mostly computer oriented.
     (IEEE) as a reference source for plant                       1.2 History of Power System Studies.
     electrical engineers in making power sys-                    The planning, design, and operation of a
     tem studies. The IEEE Brown Book can                         power system require continual and
     also be helpful in preparing system                          comprehensive analyses t o evaluate cur-
     modeling and data acquisition for an                         rent system performance and t o ascertain
     outside engineering consultant t o per-                      the effectiveness of alternative plans for
     form necessary engineering studies prior                     system expansion.
     t o designing a new system or expanding                         The computational work t o determine
     an existing power system. Such informa-                      power flows and voltage levels resulting
     tion will help ensure high standards of                      from a single operating condition for
     power system reliability and maximize                        even a small network is all but insur-
     the utilization of capital investment.                       mountable if performed by manual
        The IEEE Brown Book has been pre-                         methods. The need for computational
     pared on a voluntary basis by engineers                      aids led t o the design of a special purpose
     and designers functioning as the Power                       analog computer (AC Network Analyzer)
     System Analysis Working Group within                         as early as 1929. It provided the ability
     the IEEE, under the Industrial Power                         t o determine load flows and system
     Systems Department of The Industry                           voltage during normal and emergency
     Applications Society. This recommended                       conditions and to study the transient
     practice is not intended as a replacement                    behavior of the system resulting from
     for the many excellent texts available in                    fault conditions and switching opera-
     this field. The IEEE Brown Book comple-                      tions.
21
Authorized licensed use limited to: IEEE Xplore. Downloaded on November 08,2014 at 04:51:47 UTC from IEEE Xplore. Restrictions apply.
         IEEE
         Std 399-1980                        INDUSTRIAL AND COMMERCIAL POWER SYSTEMS ANALYSIS
22
Authorized licensed use limited to: IEEE Xplore. Downloaded on November 08,2014 at 04:51:47 UTC from IEEE Xplore. Restrictions apply.
                                                                                                                IEEE
   INTRODUCTION                                                                                          Std 399-1980
   lead t o disastrous consequences in both                      lowing sections represent the most needed
   the design and operation of a system.                         studies for the design or operation of an
     Section 3 offers an excellent review of                     industrial or commercial power system :
   the most essential fundamentals in a                          Section 5 , Load Flow; Section 6, Short
   system study.                                                 Circuit; Section 7, Stability; Section 8,
     To set up a computer program for sys-                       Motor Starting; Section 9, Harmonics;
   tem analysis, certain basic data must be                      Section 10,Switching Transients; Section
   gathered with accuracy and proper pre-                        11, Reliability; and Section 12,Ground
   sentation. System modeling is a must                          Mat. Each of the above sections contains
   technique. The extent of system repre-                        a sample study which includes a com-
   sentation, choosing the swing and in-                         puter input data file and a computer
   finite bus, restrictions in terms of nodes                    print-out for that specific study. The
   (buses) and branches (lines and trans-                        purpose of each study and what can be
   formers), balanced three-phase network                        achieved by it are briefly explained.
   and a single-phase equivalent network,                          After studying these sections, a plant
   single line diagram, impedance diagram,                       engineer should be better equipped in
   etc, are all important inputs t o a mean-                     preparing necessary data and criteria for
   ingful system study.                                          a specific computer study if the necessity
     Section 4 deals with system modeling                        arises. The study can be performed in-
   and data requirements t o illustrate how                      house or by an outside consultant. There
   these basic inputs for a study can be                         is a growing number of consulting firms
   prbperly prepared or organized.                               that specialize in system studies with
     Once the basic preparations are com-                        reasonable costs if the plant engineer can
   pleted, the next step is t o look for an                      supply the necessary system data with a
   actual computer program, whether it be                        fair degree of correctness and accuracy.
   in-house or a commercial computing
   service. Today, many types of comput-                         1.5 Standard References. The following
   ing services are available, such as batch,                    standards were used as references in the
   time-sharing, and consulting services. A                      preparation of this standard :
   plant engineer must select the most                           ANSI/IEEE Std 142-1972,IEEE Recom-
   suitable configuration for his needs.                         mended Practice for Grounding of Indus-
     Section 13 discusses the basic compu-                       trial and Commercial Power Systems
   tation methods, various types of compu-
                                                                 IEEE Std 141-1976,    IEEE Recommended
   ter systems and their requirements, and
                                                                 Practice for Electric Power Distribution
   the availability of commerical computing
                                                                 for Industrial Plants
   services and their capabilities. Section 13
   gives a plant engineer the basic knowledge                    IEEE Std 241-1974,   IEEE Recommended
   and direction of approach whenever he is                      Practice for Electric Power Systems in
   called upon t o perform a power system                        Commercial Buildings
   study with the aid of a computer pro-                         IEEE Std 242-1975,IEEE Recommended
   gram.                                                         Practice for Protection and Coordination
     1.4.3 The Most Important System                             of Industrial and Commercial Power
   Studies. For the plant engineer, the fol-                     Systems
23
Authorized licensed use limited to: IEEE Xplore. Downloaded on November 08,2014 at 04:51:47 UTC from IEEE Xplore. Restrictions apply.
         IEEE
         Std 399-1980                        INDUSTRIAL AND COMMERCIAL POWER SYSTEMS ANALYSIS
                                               2. Applications of
                                             Power System Analysis
24
Authorized licensed use limited to: IEEE Xplore. Downloaded on November 08,2014 at 04:51:47 UTC from IEEE Xplore. Restrictions apply.
                                                                                                               IEEE
   APPLICATIONS OF POWER SYSTEM ANALYSIS                                                                Std 399-1980
   2.2 Load Flow Studies. Load flow studies                      breakers are called upon t o open the line
   determine the voltage, current, power,                        on both sides of the fault. Both these
   and power factor or reactive power at                         currents differ widely from the current
   various points in a power system under                        that would flow under steady-state con-
   existing or contemplated conditions of                        ditions if the fault were not isolated
   normal and emergency operation. Load                          from the rest of the system by the opera-
   flow studies are essential in planning the                    tion of circuit breakers. The proper
   system. They are used to determine the                        selection of circuit breakers and switch-
   best operating procedure for the system,                      gear depends on two factors, the current
   especially in the event of a loss of one or                   flowing immediately after the fault
   more generating units or transmission                         occurs and the current that the breaker
   lines. They offer valuable information                        must interrupt. Short-circuit calculations
   regarding system losses, data for equip-                      consist of determining these currents for
   ment specifications, overall system capa-                     various types of faults at various loca-
   bility and limitations, proper settings of                    tions in the system. The data obtained
   transformers in the system, and optimiza-                     from fault calculations also determine
   tion of circuit usage in the system. Load                     the settings of relays which control the
   flow studies can be used t o study an in-                     circuit breakers.
   dustrial power system under suddenly                            Digital computers are used effectively
   applied loads (impact loads). Impact                          in the calculation of the three-phase
   load studies are essential in determining                     short-circuit levels at various points in
   whether this type of load can be im-                          the system, and in determining the
   posed on an existing system design. Any                       momentary and interrupting ratings of
   changes needed in system design t o en-                       circuit breakers. Line-to-ground faults
   sure the successful operation of the over-                    and double-line short circuits can also be
   all system are also determined. Load                          digitally analyzed. In this aspect, the
   flow studies also determine the most                          method of symmetrical components used
   suitable location of capacitors in the                        in the computer model represents the
   system for power factor improvement.                          system sequence networks and enables
   Because of the complexity of load flow                        the calculation of unsymmetrical faults
   calculations, digital computers are used                      in the system. Without digital computers,
   extensively in such studies. Digital com-                     such calculations are tedious and time
   puter models have been developed to                           consuming.
   study practically any industrial power
   system under any loading condition and                        2.4 Stability Studies. In industrial power
   to provide the initial system data (initial                   systems, the current which flows in an ac
   system power flows, voltages at various                       generator or synchronous motor depends
   system nodes, and initial machines’ elec-                     on :
   trical angles) for transient stability                          (1)The magnitude of its generated, or
   studies.                                                      internal voltage
                                                                   (2) The phase angle OI its internal volt-
   2.3 Fault and Short-circuit Studies. The                      age with respect t o the phase angle of
   current which flows in different parts of                     the internal voltage of every other
   an industrial power system immediately                        machine in the system
   after a fault differs from that flowing a                       (3) The characteristics of the network
   few cycles later, just before circuit                         and loads
25
Authorized licensed use limited to: IEEE Xplore. Downloaded on November 08,2014 at 04:51:47 UTC from IEEE Xplore. Restrictions apply.
           IEEE
           Std 399-1980                        INDUSTRIAL AND COMMERCIAL POWER SYSTEMS ANALYSIS
26
Authorized licensed use limited to: IEEE Xplore. Downloaded on November 08,2014 at 04:51:47 UTC from IEEE Xplore. Restrictions apply.
                                                                                                                 IEEE
     APPLICATIONS OF POWER SYSTEM ANALYSIS                                                                Std 399-1980
     size, and time of availability in the sys-                   fossil unit), the fuel costs, operation and
     tem is another problem. By using modern                      maintenance costs and capacity factors
     digital computer analysis techniques, a                      are computed. Demand charges on
     thorough investigation of all such prob-                     purchased power plus other operating
     lems can be achieved.                                        parameters are calculated t o arrive at a
        Digitally Simulated Loads. The indus-                     comparative cost for the cases under
     trial load is simulated digitally. For                       investigation. The digital analysis model
     specific unit outage rates, the loss of                      proceeds to use present worth mathe-
     load probability associated with having                      matics t o plant investment costs to deter-
     insufficient generation to meet the load                     mine the present worth costs. Yearly and
     is calculated. Whether power is purchased                    total plant life fixed charges on invest-
     or generated locally, load carrying capa-                    ment, plus other fixed costs associated
     bility of the system for various specified                   with the type of generation, are com-
     and tolerable loss of load probabilities in                  puted to find a final plant cost for
     the system is then computed. The eco-                        comparison purposes. Management can
     nomics of both generation systems are                        now justify not only local generation or
     then investigated. Depending on the type                     purchased power schemes, but also the
     of units used in local generation (for                       type of units t o be used in system
     example, diesel driven, gas turbine or                       expansion.
27
Authorized licensed use limited to: IEEE Xplore. Downloaded on November 08,2014 at 04:51:47 UTC from IEEE Xplore. Restrictions apply.
        IEEE
        Std 399-1980                         INDUSTRIAL AND COMMERCIAL POWER SYSTEMS ANALYSIS
3. Analytical Procedures
        3.1 Introduction. With the development                       which exist during various power system
        of the digital computer and advanced                         network events and operating conditions.
        computer programming techniques, pow-                        Secondly, these basic analytical solution
        er system problems of the most complex                       methods will be demonstrated where not
        types can be rigorously analyzed. Pre-                       otherwise self-evident. Finally, critical
        viously solutions were usually only ap-                      restraints that must be respected t o avoid
        proximate and errors were introduced by                      serious error in app1yin.g analytical solu-
        many simplifying assumptions necessary                       tion methods will be discussed.
        to permit classical longhand calculating                       Whether a power system analysis prob-
        procedures. For progress t o be realized                     lem is t o be solved directly or by a com-
        in using the computer for power system                       puter program, proper application of
        analysis work, it has been necessary for                     sound analytical solution methods is
        the specialist involved in the creation of                   essential for three reasons. First, accu-
        power system analysis computer pro-                          racy of the solution t o each individual
        grams t o understand thoroughly the                          problem being considered will be directly
        application of basic analytical solution                     affected. Second, and perhaps the most
        methods that apply. It is also important                     important because of the significant
        for those concerned with assembling                          expense involved, accuracy of the solu-
        and preparing data for input t o a power                     tion determines the validity and effective-
        system analysis computer program and                         ness of any remedial measures suggested.
        those interpreting and applying results                      Finally, extension of erroneous resuIts t o
        generated by such a program t o under-                       related problems or t o what appears t o
        stand the application of analytical solu-                    be a trivial modification of the original
        tion methods.                                                problem, possibly in combination with
          This section attempts, first, t o identify                 other misapplied or misunderstood tech-
        and document the basic analytical solu-                      niques, can lead t o a compounding of
        tion methods that are valid for determin-                    initial error and a progression of incor-
        ing the voltage and current relationships                    rect conclusions.
28
Authorized licensed use limited to: IEEE Xplore. Downloaded on November 08,2014 at 04:51:47 UTC from IEEE Xplore. Restrictions apply.
                                                                                                                          IEEE
    ANALYTICAL PROCEDURES                                                                                         Std 399-1980
       The most common causes of errors in                         (8) The Symmetrical Component Anal-
    circuit analysis work are :                                  ysis
       (1)Failure to use a valid analytical                        (9) The Per Unit Method
    procedure because the analyst is unaware                       Rigorous treatment of these analytical
    of its existence or applicability, or both                   techniques is available in several circuit
       (2)Careless or improper use of cook-                      analysis tests [I]', [21, 131, [41, [SI, [GI,
    book methods that have neither a factual                     and is beyond the scope of this discus-
    basis, nor support in the technical litera-                  sion. In the following sections, however,
    ture, nor a valid place in electrical engi-                  a brief qualitative explanation of each
    neering discipline                                           principle is presented, along with a re-
       (3) Improper use of a valid solution                      view of major benefits and restraints
    method due t o application beyond lim-                       associated with the use of each principle.
    iting boundary restraints or in combina-                       3.2.1 Linearity. Probably the simplest
    tion with an inaccurate simplifying                          concept of all, linearity is also one of the
    assumption                                                   most important because of its influence
       Many situations occur in industrial and                   on the other principles. Linearity is best
    commercial power systems that illustrate                     understood by examination of Fig 1.
    some or all of these common causes of
    error, as well as the resulting evils. Any                                                  Fig 1
    problem investigated as a part of the                                                     Linearity
                                                                                *
    general types of power-system analysis
    studies covered in other sections of this                                                        i ( t ) =RESPONSE FUNCTION
                                                                                        /
       (9) Switching transient studies                                                        I/             RESP/ONSE
                                                                                    Y
    solving power system network circuit                                                       MAGNITUDE OF
    problems.                                                                                  SOURCE EXCITATION
      (1)Linearity                                                                                 Ic(t)l
      (2)Superposition
      (3)The Thevenin Equivalent Circuit
      (4) The Sinusoidal Forcing Function
      (5) The Phasor Representation
      (6) The Fourier Representation                               'Numbers in brackets correspond t o those in
      (7) The Single-phase Equivalent Circuit                    the References at the end of each section.
29
Authorized licensed use limited to: IEEE Xplore. Downloaded on November 08,2014 at 04:51:47 UTC from IEEE Xplore. Restrictions apply.
         IEEE
         Std 399-1980                         INDUSTRIAL AND COMMERCIAL POWER SYSTEMS ANALYSIS
30
Authorized licensed use limited to: IEEE Xplore. Downloaded on November 08,2014 at 04:51:47 UTC from IEEE Xplore. Restrictions apply.
                                                                                                                 IEEE
    SYSTEM MODELING                                                                                       Std 399-1980
                                                                      =lo.2.1,:.       2.1
                                                                        5       6 5      6
                  'L
                                                        Fig 2
                                                     Superposition
Voc=l - 3 + 5
                                                                                       -10-5.3+5
                                                                                       - 6
                                                                                                   15
= 7.5 v
                                                                                         3.3
                                                                                   ZE0 = 3+3 =    s=2 a
                                                                                                  9 3
                         qzy-p
                                                                                                  1
                                                                                     I, = 7.5 '   3
                                                                                                  6+5
                                                                                          15
                                                                                        =-.-       2
                    7.5v                                                                  2       12+3
TH E V E N IN EQUIVALENT REPRESENTATION
(b)
                                                      Fig 3
                                              The Thevenin Equivalent
31
Authorized licensed use limited to: IEEE Xplore. Downloaded on November 08,2014 at 04:51:47 UTC from IEEE Xplore. Restrictions apply.
        IEEE
        Std 399-1980                        INDUSTRIAL AND COMMERCIAL POWER SYSTEMS ANALYSIS
        can practically be solved only through                        for the source voltage and branch imped-
        the use of certain simplification proce-                      ances would be substantially different
        dures, or through adjustment of calcu-                        from those used in this case. (The circuit
        lated results t o correct for nonlinearity.                   property of linearity would, incidentally,
        Both of these approaches can potentially                      allow them t o be scaled up or down.)
        lead t o significant inaccuracy. Tiresome                     The network shown in Fig 3(a), with the
        iterative calculations performed in an                        6 C? resistance shorted and the other
        instant by the digital computer make                          resistances visualized as reactances, might
        accurate solutions possible when an                           well serve as an oversimplified repre-
        equation can be written mathematically                        sentation of a power system about t o
        to describe the nonlinear circuit elements.                   experience a bolted fault with the
          3.2.3 The Thevenin Equivalent Circuit.                      closing of the switch.
        This powerful circuit analysis tool is                          The VI branch of the circuit would
        based on the fact that any active linear                      correspond t o the utility supply while
        network, however complex, can be                              the V, branch might represent a large
        represented by a single voltage source                        motor running unloaded, immediately
        equal t o the open-circuit voltage across                     adjacent t o the fault bus, and highly
        any two terminals of interest, in series                      idealized so as t o have no rotor flux leak-
        with the equivalent impedance of the                          age. For such a model, the 5 V source
        network viewed from the same two                              corresponds t o the pre-fault, air-gap
        terminals with all sources in the network                     voltage behind a stator leakage (sub-
        inactivated (that is, voltage sources                         transient) reactance of 3 C? [7]. In a
        shorted and current sources opened).                          more realistic situation where rotor leak-
        Validity of this representation requires                      age is evident, a model that accurately
        only that the network be linear. Exis-                        describes the V, branch in detail before
        tence of linearity is a necessary restraint.                  and after switch closing is much more
        Application of the Thevenin equivalent                        difficult t o develop, because the air-gap
        circuit can be appreciated by referring t o                   voltage decreases (exponentially) with
        the simple circuit of Fig 2 and develop-                      time and varies (linearly) with the steady-
        ing the Thevenin equivalent for the net-                      state &s magnitude of the motor stator
        work with the switch in the open position                     current following application of the fault.
        as illustrated in Fig 3. After connecting                     The problem of accounting for motor
        the 6 C2 load t o the Thevenin equivalent                     internal behavior is avoided altogether
        network by closing the switch, the solu-                      by use of a Thevenin equivalent. This
        tion for IL is the same as before, 1 A.                       permits the V, branch t o be represented
        Use of the simple Thevenin equivalent                         by the apparent motor reactance (or,
        shown for the entire left side of the net-                    more generally, impedance) effective at
        work makes it easy t o examine circuit                        the time following switch closure. In
        response as the load impedance value is                       shunt with the equivalent impedance for
        varied.                                                       the remainder of the network, the
          The Thevenin equivalent circuit solu-                       Thevenin equivalent impedance for the
        tion method is equally valid for complex                      motor (at any point in time of interest)
        impedance circuits. It is the type of rep-                    is simply connected in series with the
        resentation shown in Fig 3 that is the                        pre-fault open-circuit voltage t o obtain
        basis for making per unit short-circuit                       the corresponding current response t o
        calculations, although the actual values                      switch closing.
32
Authorized licensed use limited to: IEEE Xplore. Downloaded on November 08,2014 at 04:51:47 UTC from IEEE Xplore. Restrictions apply.
                                                                                                                   IEEE
  ANALYTICAL PROCEDURES                                                                                     Std 399-1980
                                                                                              1
                                                                            I", = (1 *6-5)   -
                                                                                              3
                                                                               = -1- -
                                                                                   5
                                                                                 2 6
                                                    Fig 4
                                         Current Flow of a Thevenin
                                         Equivalent Representation
    The current response obtained in each                      rent flowing in the V2 branch prior t o
  branch of a network using a Thevenin                         closing the switch ( 5 / 6 A from inspection
  equivalent circuit solution represents the                   of the circuit in Fig 3A) from the current
  change of current in that branch. The                        Ivz = l/2 A, calculated t o be flowing in
  actual current that flows is the vector                      the Thevenin equivalent for this V,
  sum of currents before and after the                         branch.
  particular switching event being con-                          In the branch of the circuit defined by
  sidered. See Fig 4.                                          the switch itself, the change of current
    In Fig 4A the current flowing in the V,                    due t o closing is normally the response
  branch circuit is shown to be 1/3 A. A                       of interest. This means the solution t o
  more detailed representation of the                          the Thevenin equivalent is sufficient. The
  Thevenin equivalent circuit previously                       resultant current in the other branches,
  examined in Fig 3 is shown in Fig 4B.                        however, cannot be determined by the
  Here, the solution for the same current                      solution t o the Thevenin equivalent net-
  Iv2 is determined by subtracting the cur-                    work alone.
33
Authorized licensed use limited to: IEEE Xplore. Downloaded on November 08,2014 at 04:51:47 UTC from IEEE Xplore. Restrictions apply.
          IEEE
          Std 399-1980                         INDUSTRIAL AND COMMERCIAL POWER SYSTEMS ANALYSIS
3sl
                                                               Fig 5
                                                             Fault Flow
            In the case where the V, branch repre-                        3.2.4 The Sinusoidal Forcing Function.
          sents a motor switched onto a bolted                          It is a most fortunate truth in nature
          fault, the motor contribution is the                          that the excitation sources (that is, driv-
          locked-rotor current minus the pre-fault                      ing voltage) for electrical networks, in
          current as illustrated in Fig 5 and not                       general, have a sinusoidal character and
          just the locked-rotor current as it is so                     can be represented by a sine wave plot
          often carelessly described. As a rule,                        of the type illustrated in Fig 6. There are
          this effect is never as significant as the                    two important consequences of this cir-
          example suggests, even when the motor                         cumstance. First, although the response,
          is loaded prior t o the fault; the load cur-                  that is, current, for a complex R, L, C
          rent is much smaller than the locked-                         network represents the solution to at
          rotor current and almost 90' out of                           least one second-order differential equa-
          phase with it.                                                tion, the result will also be a sinusoid of
             A Norton equivalent which consists of                      the same frequency as the excitation and
          a current source in parallel with a (dif-                     different only in magnitude and phase
          ferent) equivalent impedance can alter-                       angle. The relative character of the cur-
          nately be developed for the Thevenin                          rent with respect t o the voltage for
          equivalent circuit. This representation is                    simple R, L,and C circuits is also shown
          not generally as useful in power system                       in Fig 6.
          analysis work.                                                  The second important concept is that
34
Authorized licensed use limited to: IEEE Xplore. Downloaded on November 08,2014 at 04:51:47 UTC from IEEE Xplore. Restrictions apply.
                                                                                                                IEEE
    ANALYTICAL PROCEDURES                                                                                Std 399-1980
                                                     Fig 6
                                        The Sinusoidal Forcing Function
   when the sine wave shape of current is                           3.2.5 Phasor Representation. Phasor
   forced t o flow in a general impedance                        representation allows any sinusoidal
   network of R, L, and C elements, the                          forcing function t o be represented as a
   voltage drop across each element will                         phasor in a complex coordinate system
   always exhibit a sinusoidal shape of the                      as shown in Fig 7. As indicated, the ex-
   same frequency as the source. The sinu-                       pression for the phasor representation of
   soidal character of all the circuit re-                       a sinusoid can assume any of the follow-
   sponses makes the application of the                          ing shorthand forms:
   superposition technique to a network                             Exponential: E ejs
   with multiple sources surprisingly man-                          Rectangular: E cos 8 + jE sin 8
   ageable. The necessary manipulation of                           Polar: E LQ
   the sinusoidal terms is easily accom-                            For most calculations, it is more con-
   plished using the laws of vector algebra,                     venient t o work in the frequency domain
   which evolve from the next technique t o                      where any angular velocity associated
   be reviewed.                                                  with the phasor is ignored, which is equiv-
     The only restraint associated with the                      alent t o assuming the coordinate system
   use of the sinusoidal forcing function                        rotates at a constant angular velocity of W .
   concept is that the circuit must be com-                         The impedances of the network can
   prised of linear elements, that is, R, L,                     likewise be represented as phasors using
   and C are constant as current or voltage                      the vectorial relationships shown. As
   varies.                                                       illustrated, the circuit responses, that is,
35
Authorized licensed use limited to: IEEE Xplore. Downloaded on November 08,2014 at 04:51:47 UTC from IEEE Xplore. Restrictions apply.
         IEEE
         Std 399-1980                         INDUSTRIAL AND COMMERCIAL POWER SYSTEMS ANALYSIS
IMAGINARY
                                                                                                                     1
                                                                                              Z=R    +j     W L - j -=
                                                                                                                    WC
                                                                                                                         R   +j X
                                                                                             x,   =WL
                                                                                                     1
                                                                                             xc=
                                                                                             IZI =   +m
                                                                                                          X
                                                                                               @ = tan-'-
                                                                                                          R
                       R = resistance
                      XL = inductive reactance
                      Xc = capacitive reactance
                       Z = impedance
                                                            Fig 7
                                                  The Phasor Representation
                                                            Fig 8
                                                  The Fourier Representation
36
Authorized licensed use limited to: IEEE Xplore. Downloaded on November 08,2014 at 04:51:47 UTC from IEEE Xplore. Restrictions apply.
                                                                                                               IEEE
   ANALYTICAL PROCEDURES                                                                                Std 399-1980
    current, can be obtained through the                         conditions that must be satisfied to use
    simple vector algebraic manipulation of                      a Fourier representation. The only
    the quantities involved. The need for                        restraints of practical interest t o the
    solving complex differential equations                       power systems analyst are that the origi-
    to determine the circuit responses is                        nal driving function must be periodic
    completely eliminated.                                       (repeating) and the network must remain
      The restraints that apply are:                             linear.
      (1)The sources must all be sinusoidal                         3.2.7 The Single-phase Equivalent Cir-
      (2) The frequency must remain con-                         cuit. The single-phase equivalent circuit
    stant                                                        is a powerful tool for simplifying the
      (3) The circuit R, L and C elements                        analysis of balanced three-phase circuits,
    must remain constant (that is, linearity                     yet its restraints are probably most often
    must exist)                                                  disregarded. Its application is best under-
      3.2.6 The Fourier Representation. This                     stood by examining a three-phase dia-
    powerful tool allows any nonsinusoidal                       gram of a simple system and its single-
    periodic forcing function, of the type                       phase equivalent, as shown in Fig 9.
    plotted in Fig 8, t o be represented as the                  Also illustrated is the popular one-line
    sum of a dc component and a series                           diagram representation commonly used
    (infinitely long, if necessary) of ac sinu-                  t o describe the same three-phase system
    soidal forcing functions. The ac com-                        on engineering drawings.
    ponents have frequencies that are an                            If a three-phase system has a perfectly
    integral harmonic of the periodic func-                      balanced symmetrical source excitation
    tion (fundamental) frequency. The gen-                       (voltage) and load, as well as equal series
    eral mathematical form of the so-called                      and shunt system and line impedances
    Fourier series is also shown in Fig 8.                       connected t o all three phases (see Fig
      The importance of the Fourier repre-                       9(a)), imagine a conductor (shown dot-
    sentation is immediately apparent. The                       ted) carrying no current connected be-
    response to the original driving function                    tween the effective neutrals of the load
    can be determined by first solving for                       and the source. Under these conditions,
    the response t o each Fourier series com-                    the system can be accurately described
    ponent forcing function and summing                          by either Fig 9(b) or Fig 9(c).
    all the individual solutions t o find the                       The single-phase equivalent circuit is
    total superposition. Since each compo-                       particularly useful since the solution to
    nent response solution is readily ob-                        the classical loop equations is much
    tained, the most difficult part of the                       easier t o obtain than for the more
    problem becomes the determination of                         complicated three-phase network. To
    the component forcing function. The                          determine the complete solution, it is
    individual harmonic voltages can be                          only necessary t o realize that the other
    obtained, occasionally in combination                        two phases will have responses that are
    with numerical integration approximat-                       shifted by 120" and 240" but are other-
    ing techniques through several well-                         wise identical t o the reference phase.
    established mathematical procedures.                            Anything that upsets the balance of
    Detailed discussion of their use is better                   the network renders the model invalid. A
    reserved for the many excellent texts                        subtle way this might occur is illustrated
    [2], [3] that treat the subject.                             in Fig 10. If the switching devices oper-
      There are several abstract mathematical                    ate independently in each of the three
37
Authorized licensed use limited to: IEEE Xplore. Downloaded on November 08,2014 at 04:51:47 UTC from IEEE Xplore. Restrictions apply.
          IEEE
          Std 399-1980                        INDUSTRIAL AND COMMERCIAL POWER SYSTEMS ANALYSIS
                                 EL-N   6                                                       LINE TO
                                                                                                :EPJDTRAL
LOAD
                                                          Fig 9
                                        (a) Three-phase Diagram, (b) Single-phase
                                          Equivalent, and (c) One-Line Diagram
           poles, and for some reason the device in                    ing device operates in reqonse to a fault
           phase A becomes opened, the balance or                      conditon in the same phas-., as depicted
           symmetry of the circuit is destroyed.                       at location X, the system sources would
           Neither the single-phase equivalent nor                     continue to supply fault current from
           the one-line diagram representation is                      the other unopened phases through the
           valid. Even though the single-phase and                     impedance of the load. The throttling
           the one-line diagram representations                        effect of the normally substantial load
           would imply that the load has been dis-                     impedance, possibly in combination with
           connected, it continues t o be energized                    additional arc impedance, can reduce the
           by single-phase power. This can cause                       level of the current t o a point where de-
           serious damage to motors and result in                      tection may not occur in phases (b) and
           unacceptable operation of certain load                      (c). Needless t o say, substantial damage
           apparatus.                                                  can result before the fault finally burns
             More importantly, if only one switch-                     enough t o involve the other phases
Authorized licensed use limited to: IEEE Xplore. Downloaded on November 08,2014 at 04:51:47 UTC from IEEE Xplore. Restrictions apply.
                                                                                                                IEEE
    ANALYTICAL PROCEDURES                                                                                Std 399-1980
                                 0
                           EL-N 'L
                                                      # FAULT                  L I N E TO
                                                                               NEUTRAL LOAD
                                                                                    LOAD
                                  EL-N
                                                              d FAULT
                                                             (c)
                                                    Fig 10
                                   (a) Three-phase Diagram, (b) Single-phase
                                     Equivalent, and ( c ) One-Line Diagram
39
Authorized licensed use limited to: IEEE Xplore. Downloaded on November 08,2014 at 04:51:47 UTC from IEEE Xplore. Restrictions apply.
        IEEE
        Std 399-1980                           INDUSTRIAL AND COMMERCIAL POWER SYSTEMS ANALYSIS
1                 '                  1                                             BALANCED
                                                                                   LOAD
                                               I
                                               I
                                               I
                                               I
                                               I
                                               I
t A
B'*c'
                                                       Fig 11
                                          The Symmetrical Component Analysis
40
Authorized licensed use limited to: IEEE Xplore. Downloaded on November 08,2014 at 04:51:47 UTC from IEEE Xplore. Restrictions apply.
                                                                                                                IEEE
    ANALYTICAL PROCEDURES                                                                                Std 399-1980
41
Authorized licensed use limited to: IEEE Xplore. Downloaded on November 08,2014 at 04:51:47 UTC from IEEE Xplore. Restrictions apply.
        IEEE
        Std 399-1980                        INDUSTRIAL AND COMMERCIAL POWER SYSTEMS ANALYSIS
42
Authorized licensed use limited to: IEEE Xplore. Downloaded on November 08,2014 at 04:51:47 UTC from IEEE Xplore. Restrictions apply.
                                                                                                                     IEEE
   ANALYTICAL PROCEDURES                                                                                      Std 399-1980
                  w                               --A&
                m
                   It            1o:I               I2                 Z, = 20    .   (A) *   + 0.8= 1 .O R
                                                                              1000
                                                                        / =-=      10A
                                                                         '.   100
                d
                   I I             I: I
                                                 - I2                           z, = 0.8 + (1/10)2. 1000 = 400 per ()"it
                                                                                               5ooo
5MVA
l2base = 5MVA = 5 0 0 0 0 A
43
Authorized licensed use limited to: IEEE Xplore. Downloaded on November 08,2014 at 04:51:47 UTC from IEEE Xplore. Restrictions apply.
         IEEE
         Std 399-1980                        INDUSTRIAL AND COMMERCIAL POWER SYSTEMS ANALYSIS
4. System Modeling
44
Authorized licensed use limited to: IEEE Xplore. Downloaded on November 08,2014 at 04:51:47 UTC from IEEE Xplore. Restrictions apply.
                                                                                                                  IEEE
     SYSTEM MODELING                                                                                       Std 399-1980
     etc. Nonetheless, much expertise is re-                     usefulness are written in general non-
     quired to establish scaling and normaliza-                  specific terms. This exposes the analyst
     tion factors, t o construct the model, to                   to a choice of program features and
     gather meaningful data by measurement                       alternatives that require decisions t o be
     and t o interpret and extrapolate the                       made every step of the way. Finally the
     results.                                                    programs are often structured to handle
       A step in the direction of abstraction is                 extensive power systems (3000 bus pro-
     the approach used in ac and dc analyzer                     grams are not uncommon). This aspect
     boards for the study of power systems.                      suggests that the analyst should consider
     Here the power system elements are                          to what extent his system will be modeled
     modeled by modules of equivalent char-                      to avoid, on the one hand, an expensive
    acteristics but physically much smaller.                     overkill and on the other an incomplete
     Most modules do not bear visual resem-                      problem statement that ensures question-
    blance t o the components they repre-                        able answers.
     sent. A 200 mi transmission line module
     may look like a few potentiometers,
                                                                 4.3 Review of Basics. Power network
    inductances and capacitors. The modules                      elements may be classified in two cate-
    are adjustable so the system variables can                   gories, passive elements and active ele-
    be modeled easily. These modules can be                      ments.
    interconnected, each adjusted t o satisfy                      4.3.1 Passive Elements. The passive
    the conditions of the power system being                     elements comprise such components
    studied, and the required measurements                       as transmission lines, transformers, reac-
    made and interpreted. Once the board is                      tors, and capacitors. They will, in gen-
    configured for a base case, the effect                       eral, be regarded as linear. They will be
    of one variable on the overall system                        modeled by one or more of the follow-
    can be readily analyzed simply by                            ing electrical quantities:
    adjusting the affected module. Most
    analyzing boards have been abandoned                         Name                    Symbol                  -
                                                                                                                 Unit
    today in favor of the more economical                        resistance                    R                ohm
    digital method using computers.                              inductance                    L                henry
       Digital computers can be programmed                       capacitance                   C                farad
    t o solve quickly and at relatively low cost
    a large number of simultaneous equa-                           The voltage across and the current
    tions and can handle the algebra of large                    through the element will be governed by
    matrices. This makes them particularly                       these relationships :
    well suited for applications in power                                                  .        v
    system analysis. An immense variety of                            U =    Ri            1 = -
                                                                                                                (Eq 1)
                                                                                                   R
    programs have been written t o study an
    ever increasing number of problems in
    the electrical field. These programs are                          U =    L -di         i   =   '/,dt        (Eq2)
                                                                                dt                 L
    usually set up to receive the problem
    information in the form of numbers
    rather than analog settings. This then
    forces the power system analyst t o                          where the lowercase letters represent
    model the system quantitatively. The                         the instantaneous values of voltage and
    programs, designed to maximize their                         current.
45
Authorized licensed use limited to: IEEE Xplore. Downloaded on November 08,2014 at 04:51:47 UTC from IEEE Xplore. Restrictions apply.
        IEEE
        Std 399-1980                         INDUSTRIAL AND COMMERCIAL POWER SYSTEMS ANALYSIS
          In dc circuits under steady state condi-                   R, X and 2 quantities for the series (line)
        tions these equations will reduce to:                        elements and the G , B and Y quantities
                                                                     for the shunt (line t o neutral) elements.
                                                                        Note also that 2 and Y are complex
                                                                     quantities that can be expressed in the
                               di                                    rectangular form above or the polar form
        V    =   0      (since - = 0)                                2 = IZI le or Y = I YI D. Most computer
                               dt
                                                                     programs accept the 2 and Y values in
                               du                                    the rectangular form.
         I   =   0      (since dt
                               -=    0)                (Eq 4)           A final remark concerns the sign ahead
                                                                     of the reactances and susceptances. The
          In ac circuits with sinusoidal wave                        four diagrams of Fig 13 are self explana-
        shapes, the equations become :                               tory. The wise analyst will verify the
                                                                     program instructions to make sure that
        V    =   RI            I = -V                                the computer will interpret the input
                                   R                                 data properly.
        V    =   jX,Z                                                   4.3.2 Active Elements. The active ele-
                                                                     ments of a power system comprise such
                                                                      components as motors, generators, syn-
        where
                                                                      chronous condensers, other loads like
         x,= 27rfL                                                   furnaces, adjustable speed drives, etc. The
             =   inductive reactance                   (Eq 5)        active elements will be regarded as non-
                                                                      linear, although some of the components
         V   =   -jXJ
                                                                      may behave linearly under certain cir-
        where                                                         cumstances.
                  1                                                     One or more of the parameters of a
                                                                      model of an active element will vary as
                                                                     a function of time, phase angle, fre-
             =   capacitive reactance        (Eq 6,                   quency, speed, etc.
         The capital letters for voltages and cur-                      The four expressions for power quanti-
       rents represent their rms values, f is the                    ties given in Table 2 can be used t o model
       frequency in hertz, a n d j the 90" operator                  non linear elements. Given any'two of
       (=    n).  Inverting and combining these                      the four values, the remaining two can
       elements in series or parallel will define                    be defined. Power can also be expressed
       the set of quantities of Table 1.                             in polar form: S = IS1 le which yields
         It should be noted here that it is                          these relationships: PF = cos 8, P = S cos
       customary in ac power circuits t o use the                    8 and Q = S sin 8.
                                                   Table 1
                              Equation References for Conductance, Susceptance,
                                         Impedance and Admittance
                                  Name                  Symbol            Unit        Defining Esuation
                         conductance                        G           S (mho)               1 lR
                         inductive susceptance              B           S (mho)               1l X
                         capacitive susceptance             B           S (mho)               1l X
                         impe danc e                        Z           S (ohm)             ( R+ i X )
                         admittance                         Y           S (mho)             (G + j B )
46
Authorized licensed use limited to: IEEE Xplore. Downloaded on November 08,2014 at 04:51:47 UTC from IEEE Xplore. Restrictions apply.
                                                                                                                 IEEE
    SYSTEM MODELING                                                                                      Std 399-1980
8 2 = R + jx,
Y G + jBc
                                                    Fig 13
                                     Squirrel Cage Induction Motor Model
                                                         Table 2
                                   Four Expressions for Power Quantities
                          Name                   Symbol               Unit                 Exmession
                     complex power                 S                  VA               S    =P+jQ
                     active power                  P                   w               P    =dL?-zp
                     reactive power                 Q                 var              Q    = d m
                     power factor                   PF              per unit           PF   =e
                                                                                                S
47
Authorized licensed use limited to: IEEE Xplore. Downloaded on November 08,2014 at 04:51:47 UTC from IEEE Xplore. Restrictions apply.
         IEEE
         Std 399-1980                        INDUSTRIAL AND COMMERCIAL POWER SYSTEMS ANALYSIS
                                                                Fig 14
                                                    Section of a Typical
                                            Industrial Plant Impedance Diagram
                                                                  JX
                                                                                             +
                                                                                    (REFERENCE A X I S )
48
Authorized licensed use limited to: IEEE Xplore. Downloaded on November 08,2014 at 04:51:47 UTC from IEEE Xplore. Restrictions apply.
                                                                                                                 IEEE
     SYSTEM MODELING                                                                                      Std 399-1980
                                                       Table 3
                                             Fundamental Equations for
                                              Translation and Rotation
                                                                                                   dt2
                torque                              T             N-m                          T = rF
                work                                W              J                           W = STde
                power                               P              W                           P = To
                angular momentum                    M             J slrad                      M = Io
     for electrical engineering work have been                    It also requires that a reference voltage
     tabulated in Table 3, with the MKS                           and angle be specified for one bus.
     system of units and the defining equa-                         Consider for instance Fig 1 5 which
     tions.                                                       shows a small section of the typical plant
                                                                  electrical system of Section 5, Load
     4.4 Power Network Solution. Before                           Flow. Assume that the voltages at buses
     dealing with the detailed models of power                    2, 4 and 24 (also called A, B and C , to
     system components, it is important t o                       simplify notations) and the impedances
     review what constitutes the solution of a                    of T2 and line 8 are known. They are
     network.                                                     summarized on Fig 16 and listed as
       It can be said that a network is resolved                  follows :
     if all the bus voltages and the relative
     phase angles between these voltages are                        V, = V, = 69.00 kV /o"
     known. This of course requires that the                        V4 = VB = 13.60 kV /-1.6"
     impedance between the buses be known.                         V2, = V, = 13.51 kV 1-1.82"
49
Authorized licensed use limited to: IEEE Xplore. Downloaded on November 08,2014 at 04:51:47 UTC from IEEE Xplore. Restrictions apply.
        IEEE
        Std 399-1980                         INDUSTRIAL AND COMMERCIAL POWER SYSTEMS ANALYSIS
                            A            15 M V A
                                         69 - 13.8 k V
                                         8 OIo 2
                               A
                               3
                               \L
                                     1200A
                                           500 MVA
                                             SG2
3 c A W G 310
                                             500 M V A
                                                SG3
                                                             Fig 15
                                                      Single Line Diagram
50
Authorized licensed use limited to: IEEE Xplore. Downloaded on November 08,2014 at 04:51:47 UTC from IEEE Xplore. Restrictions apply.
                                                                                                               IEEE
   SYSTEM MODELING                                                                                      Std 399-1980
69.00
Z = 3. I 7 4 t j 2 5 . 3 9 SZ
Z = 0.12 7 0 + j 1.016 4
1 3 . 6 0 /-I 6 "
Z = 0 I 9 1 3 8 t jO.12119 SZ
1 3 . 5 7 /-1.82O
                                                                                             (.>
                                                          Fig 16
                                                     Impedance Diagram
51
Authorized licensed use limited to: IEEE Xplore. Downloaded on November 08,2014 at 04:51:47 UTC from IEEE Xplore. Restrictions apply.
         IEEE
         Std 399-1980                        INDUSTRIAL AND COMMERCIAL POWER SYSTEMS ANALYSIS
52
Authorized licensed use limited to: IEEE Xplore. Downloaded on November 08,2014 at 04:51:47 UTC from IEEE Xplore. Restrictions apply.
                                                                                                                IEEE
    SYSTEM MODELING                                                                                      Std 399-1980
I S = 5 4 2 5 t j2118 ( k V A )
t S = - 5 4 0 3 - j 1938 ( k V A )
13.60 / - I . S 0
                                 13.57 1-1.82'                           I
                                                                                                  (c>
                                                        Fig 17
                                                     Flow Diagram
    bok of resistances, inductances and cap-                        fectly well. Along this line, the graphical
    acitances is superfluous since the expres-                      representation described by Fig 18 is
    sions for impedances alongside a straight                       suggested as a method for bridging the
    line do describe the line elements per-                         gap between the single line diagram and
53
Authorized licensed use limited to: IEEE Xplore. Downloaded on November 08,2014 at 04:51:47 UTC from IEEE Xplore. Restrictions apply.
        IEEE
        Std 399-1980                        INDUSTRIAL AND COMMERCIAL POWER SYSTEMS ANALYSIS
                                                        -D
                                     L I N E OR CABLE                                       LINE IMPEDANCE I N Q
                                                                                                /
                                     NUMBER
0.04 t JO.ll0 ( Z )
0 00 + j0.02 (Y)
                                                                                                \
                                                                                            L I N E ADMlTTANCE
                                                                                            IN S ( m h o )
                                         LOAD
                                         RATED k V
                                                                     I                      LSYNCHRONOUS
                                                                                                MOTOR DATA
                                  CONSTANT kVA       .
                                                           Fig 18
                                                      Suggested Format
                                                      Raw Data Diagram
54
Authorized licensed use limited to: IEEE Xplore. Downloaded on November 08,2014 at 04:51:47 UTC from IEEE Xplore. Restrictions apply.
                                                                                                                IEEE
     SYSTEM MODELING                                                                                     Std 399-1980
     the computer input document. A skele-                        to 6000 buses. It is also probable that
     ton drawing of the power system show-                        the engineer’s time t o prepare the data
     ing buses, lines, generators, and loads,                     will cost more than the computer time.
     each with its assigned numbers, can be                         A rough guideline would be: when in
     duplicated for multiple use as impedance                     doubt, model the more extensive system.
     diagrams and as a flow diagram. It should                    Of course, there are penalties in doing so:
     be noted that these diagrams are working                       (1)More data preparation time required
     tools and as such do not require stan-                         (2) Increased possibilities of input error
     dardization. However, the analyst should                       (3) More output data generated
     adopt a method suitable for keeping track                      (4) Significant results become a smaller
     of masses of data, for even small system                     section of the output
     studies require and generate a large
     amount of information.                                         The objectives of the study should
       (3) In power systems analysis the term                     always be kept in focus. This will help in
     bus does not always have the meaning                         eliminating useless work.
     understood by a plant electrician, for                         4.6.2 Utility Supplied Systems. A large
     instance. The analyst calls bus any point                    number of industrial and commercial
     of the system where voltages are calcu-                      establishments are supplied by stiff
     lated. The term is interchangeable with                      utility systems. Stiffness is a relative
     node. Fictitious buses may be introduced                     function of the size of the plant load and
     on the network to obtain voltage solu-                       local generation. If the external power
     tions at certain points of interest. An                      system or utility is large compared with
     example of this may be a 150 mi trans-                       that of the plant, disturbances within the
     mission line broken down in 5 sections                       plant do not affect the voltage at the
     of 30 miles (that is, a bus introduced                       point of connection. In such a case the
     every l/5 of the length) in order t o avoid                  utility system is said t o be an infinite
     the complicated but exact model of the                       system. The connection point will be
     long line.                                                   an infinite bus.
       (4)In the same vein, the term line is                         This concept can be extended within
     often given the more general meaning of                      the plant electrical distribution system
     branch, that is, any element between two                     when studies are concerned with small
                                                                  areas electrically remote from the utility
     nodes. For example, the transformer
                                                                  supply. Conversely sections of utility
     data will be entered on a computer input
                                                                  systems may require modeling in cases
     document called line data.
                                                                  where this stiffness does not exist. It is,
     4.6 Extent of the Model                                      therefore, important that a sound know-
       4.6.1 General. No rigid rules can be                       ledge of the utility supply systems be
     established on how much of a power                           acquired before going ahead full bore
     system should be modeled for a given                         with studies.
     study. The system analyst has to exercise                       4.6.3 Isolated Systems. The question
     judgment and develop a feel for this as                      of whether an isolated system should be
     he gains experience.                                         modeled in full or in part is easier t o
       The capability of available computer                       determine. These are usually relatively
     programs will not likely be the limiting                     small and as such could be represented
     factor in industrial and commercial                          fully for most kinds of studies. The extra
     power system applications. There are                         effort of gathering a set of data for the
     load flow programs that can handle up                        entire system, even though a smaller sec-
55
Authorized licensed use limited to: IEEE Xplore. Downloaded on November 08,2014 at 04:51:47 UTC from IEEE Xplore. Restrictions apply.
          IEEE
          Std 399-1980                        INDUSTRIAL AND COMMERCIAL POWER SYSTEMS ANALYSIS
          tion would suffice, will not be lost since                   4.7 Models of Branch Elements
          the additional data will be used in some                       4.7.1 Lines. Four parameters affect the
          future study. The nature of an isolated                      performance of a line connecting a source
          system is such that a modification or a                      t o a load: series resistance, series induc-
          disturbance is more apt t o be felt through-                 tance, shunt capacitance, and shunt con-
          out the system.                                              ductance. A short length of conductor
            4.6.4 Swing Bus. The requirement that                      can be modeled as in Fig 19. A line can
          a reference voltage and angle be specified                   be considered as many short lengths of
          at one bus for a network solution t o be                     conductors placed in series t o yield the
          possible (see 4.4) introduces the concept                    model of Fig 20(a). The individual lengths
          of swing or slack bus.                                       of conductor could be made shorter thus
             For the network t o be in equilibrium                     increasing the number of lengths for a
          at any instant the total generation must                     given length of line. Continuing this pro-
          equal the total load plus the total losses.                  cess t o the limit defines the model called
          Since the line losses are not specified as                   line with distributed constants. This
          an input, at least one bus of the network                    model has been reduced t o the equivalent
          has t o be capable of adjusting the gen-                      circuit shown in Fig 20(b), where the
          erated power for the equilibrium t o be                       series arm is defined by
          achieved.
            This bus is called the swing or slack
          bus. It is usually the bus assigned the
          fixed voltage and reference angle. It is
                                                                       and the shunt branches by:
          usually a generator bus in the case of iso-
          lated systems, or the infinite bus behind                    y’      Y tanh (yQ/2)
          the source impedance for a utility sup-
          plied system.
                                                                       z-- 21 (CoshyQ-1)
                                                                               ($/a)
            The system analyst should always                                - _
          specify the swing bus. It should be that                             2,      sinh yQ                       (Eq 10)
          bus in the system that maintains the                           TWO figures of merit appear in these
          closest voltage regulation.                                  equations:
                                                          Fig 19
                                          Equivalent Circuit of Short Conductor
56
Authorized licensed use limited to: IEEE Xplore. Downloaded on November 08,2014 at 04:51:47 UTC from IEEE Xplore. Restrictions apply.
                                                                                                              IEEE
  SYSTEM MODELING                                                                                      Std 399-1980
                                                  Fig 20
                                    (a) Line with Distributed Constants
                                     (b) Long Line Equivalent Circuit
57
Authorized licensed use limited to: IEEE Xplore. Downloaded on November 08,2014 at 04:51:47 UTC from IEEE Xplore. Restrictions apply.
          IEEE
          Std 399-1980                             INDUSTRIAL AND COMMERCIAL POWER SYSTEMS ANALYSIS
58
Authorized licensed use limited to: IEEE Xplore. Downloaded on November 08,2014 at 04:51:47 UTC from IEEE Xplore. Restrictions apply.
                                                                                                                  IEEE
     SYSTEM MODELING                                                                                       Std 399-1980
Q y
                                                    Fig 21
                                        Medium Line Equivalent Circuits
                                         (a) Nominal 71 (b) Nominal T
     fictitious bus in the middle of the line.                   medium line model, the nominal n,
     Entering data into the program, for the                     should be used for cables in the order of
     nominal n circuit follows the same                          one mile in length (approximately '/40 of
     requirements as for the long line model.                    50 mi). The shorter the cable run the
          4.7.1.3 Short Lines. For overhead                      better the accuracy when using this
     lines shorter than 50 mi, neglecting the                    model. However, the computer program
     shunt capacitance in the models presented                   used may have a limitation as t o how
     earlier will not greatly affect the results                 small a quantity it will accept.
     of load flow, short-circuit or stability                      It is doubtful that any medium voltage
     calculations. This yields the model of                      system will have feeder lengths requiring
                                                                  -
     Fig 22.                                                     representation of the capacitive reac-
        4.7.2 Cables. The overhead line models                   tance.
     are equally applicable to cables. While
     the resistances are substantially the same,                                    Fig 22
     the relative values of reactances are                               Short Line Equivalent Circuit
     vastly different. Table 4 compares two
     cases, one at 69 kV, the other at 13.8 kV.
     The cable inductive reactance is about
     1/4 that of the line, but the capacitive
     reactance is 30 t o 40 times that of the
     line.
        This comparison suggests that the                         0                                    0
Authorized licensed use limited to: IEEE Xplore. Downloaded on November 08,2014 at 04:51:47 UTC from IEEE Xplore. Restrictions apply.
         IEEE
         Std 399-1980                        INDUSTRIAL AND COMMERCIAL POWER SYSTEMS ANALYSIS
                                                     Table 4
                                 Comparison of Overhead Lines and Cable Constants
                                                       Values in     /mile for 500 kcmil Cu Conductors
                                                          69 kV                              13.8 kV
                                            Overhead L i n e *   Cable**            Overhead Linet           Cable?
               Resistance                    0.134             0.134                 0.134                0.134
               Inductive reactance           0.695             0.176                 0.613                0.146
               Capacitive reactance          0.162 x l o 6     0.005 X l o 6         0.142 X l o 6        0.003 X l o 6
                *Open-wire equilateral conductor spacing of 8 ft
               **Three-conductor oil-filled paper-insulated cable rated 69 kV
                *Open-wire equilateral conductor spacing of 4 f t
                +Three-conductor oil-filled paper-insulated cable rated 1 5 kV
                                                           Table 5
                                                        Conductor Data
                          Aluminum alloys
                           5005-H19                                 53.5         overhead line conductors
                           6201-T81                                 52.5         overhead line conductors
                          Galvanized steel
                           Siemens-Martin                            12.0
                           high strength                             10.5
                           extra high strength                        9.4
60
Authorized licensed use limited to: IEEE Xplore. Downloaded on November 08,2014 at 04:51:47 UTC from IEEE Xplore. Restrictions apply.
                                                                                                               IEEE
    SYSTEM MODELING                                                                                     Std 399-1980
   has 100% conductivity (IACS standards).                       ductors or metallic masses in its proximity
   This is equivalent t o 875.2 52 for a one                     thus generating voltages in those parts.
   mile long round wire weighing one pound                       These voltages may cause currents t o flow
   at 20 "C. All other materials can have                        through closed circuits and thus cause
   their conductivities expressed as a per-                      12R losses other than those of the con-
   centage of the standard, a few of which                       ductor itself. These losses can be repre-
   are listed in Table 5.                                        sented as an additional component of
     The conductor resistance will vary                          resistance in series with the conductor
   with temperature according t o the fol-                       resistance. The reader should consult [ 11
   lowing formula:                                               and [ 21 for information on this subject.
                                                                     4.7.3.2 Inductive Reactance. The in-
   R,   = R,[l    + a(t2- t, )]                                  ductive reactance of a circuit has two
   R,   =  resistance at temperature t,                          components: that due t o its own circuit
   R,   =  resistance at temperature tl                          (self) and that due t o other circuits in its
     a temperature coefficient per de-
        =                                                        vicinity (mutual). The inductance of a
           gree at temperature t, .                              conductor also has two components: that
      At 20 'C, the coefficient a per degree                     caused by the current in itself and that
    Celsius is:                                                  caused by the currents in other conduc-
      Copper: 0.00393                                            tors of the same circuit. Finally the in-
      Aluminum: 0.00403                                          ductance of a conductor due t o ,its own
      Galvanized steel:                                          current is divided in two parts: the first
        SM: 0.0039                                               part considers the flux internal t o the
        HS: 0.0035                                               conductor; the second part, the flux
        EHS: 0.0032                                              external t o the conductor. This last divi-
      It is not possible t o predict the exact                   sion has been modified t o simplify tables
    operating conductor temperature if the                       of conductor characteristics. Tables list
    conductor current is not known. The                          the conductor inductive reactance & at
    analyst has the choice of either estimat-                    one foot spacing even if the actual spac-
    ing the conductor temperature or assum-                      ing is larger or smaller than one foot.
    ing the worst case, which, in some studies,                    A second table, valid for any type or
    might be the maximum allowable temper-                       size of conductor, lists spacing factors
    ature of the cable. Other studies might                      X, which, added t o the one foot reac-
    require that the minimum conductor                           tance will give the correct total reactance
    temperature be used for the worst case.                      for the given circuit conductor spacing.
      The ac resistance of conductors is                         The spacing factor table is calculated
    higher than the dc resistance due t o skin                   from the equation:
    effects. The effect is more pronounced
    as the conductor cross section or the                        xd = 4.657         f log GMD
    operating frequency increases. Conductor                         =52/(conductor * mile)    (Eq 22)
    data tables usually include ac resistances                   where
    at power frequencies. The skin effect is a
                                                                 GMD = geometric mean distance of the
    major factor in the design of high current
    (several thousand amperes) ac bus sys-                               conductors
                                                                  For three conductors spaced d, , d,, d3
    tems, such as for electric furnaces.
      The flux established by alternating cur-
    rent in a conductor may link other con-                      GMD = d d ,        d,   *   d,.
61
Authorized licensed use limited to: IEEE Xplore. Downloaded on November 08,2014 at 04:51:47 UTC from IEEE Xplore. Restrictions apply.
          IEEE
          Std 399-1980                        INDUSTRIAL AND COMMERCIAL POWER SYSTEMS ANALYSIS
          Note that in Eq 22 a GMD smaller than                             4.7.4 Reactors. Reactors are used as
          1yields a negative spacing factor.                             branch elements in the following applica-
            Cables in steel conduit exhibit higher                       tions:
          reactances than in free air. The calcula-                         (1) To limit current during fault condi-
          tions are too complex t o develop by                           tions
          hand, hence, the curves presented in                              (2) To buffer cyclic voltage fluctuations
          Section 4 of [ l ] and Section .691 of                         caused by repetitive loads (in conjunction
          [21] should be used for estimating                             with condensers)
          purposes. Tables are also available in                            (3) To limit motor starting currents
          Chapter 1 of [17].                                             They are modeled as impedances consist-
              4.7.3.3 Shunt Capacitive Reactance.                        ing of an inductive reactance in series
          The determination of the capacitive reac-                      with a resistance expressed as R + jX.
          tance follows the same pattern as the in-                      Manufacturers' design or test data should
          ductive reactance. Conductor tables give                       be obtained for existing applications.
          the value of reactance X' at one-foot                             The resistance section of this model
          spacing. A spacing factor X ' is added t o                     can usually be neglected in motor start-
          X' t o yield the total capacitive reactance                    ing studies since it is small with respect
          of the conductor, Spacing factor tables                        t o the reactance and the power factor of
          are calculated from:                                           the motor is low during starting.
                                                                            4.7.5 Capacitors. Series capacitors are
                                                                         sometimes used on transmission and
                   =                    -
                       !2/(conductor mile)              (Eq 23)          distribution lines t o compensate for the
                                                                         inductive reactance drop or t o improve
             The capacitive reactance of shielded                        the system stability by increasing the
           cables is determined from:                                    amount of power that can be transmit-
                                                                         ted on tie lines. They are represented by
          xc =
               ,     1.79 G * l o 6                                      a negative reactance of the form 0 -JX,
                         f ' k                                           in series with the line impedance.
                   = CL/(phase * mile)                  (Eq 24)             For capacitors specified in microfarads
                                                                         per phase, the reactance may be expressed
           where                                                         in the general form:
           G = geometric factor
           k = dielectric constant of cable insula-                      x = -lo6        = !2/(per phase)            (Eq 26)
                                                                               2 7r fc
               tion
           f = frequency                                                   When specified in kilovars per phase
                                                                         (Qc), the capacitor voltage rating (Vc)
                                   2r                                    must also be known t o calculate:
           G       =   2.303 log                        (Eq 2 5 )
           where                                                         X = -
                                                                             Qc
                                                                                "C
                                                                                     - lo3   = !2/(per phase)        (Eq 27)
           r       =   inside diameter of shield
           d = outside diameter of conductor                               It should be noted that the series capa-
             Typical values of k are 6.0 for rubber,                     citor voltage rating is a function of the
           5.0 for varnished cambric, 2.6 for poly-                      amount of compensation of the design
           ethylene, and 3.7 for paper.                                  and will generally be a fraction of the
62
Authorized licensed use limited to: IEEE Xplore. Downloaded on November 08,2014 at 04:51:47 UTC from IEEE Xplore. Restrictions apply.
                                                                                                                IEEE
     SYSTEM MODELING                                                                                     Std 399-1980
     system line-to-neutral voltage. The appli-                     It can be demonstrated that Fig 23(a)
     cation of series capacitors should always                    is equivalent t o Fig 23(b). In the latter
     be accompanied by thorough studies,                          the secondary resistance and reactance
     since it is easy t o create destructive over-                has been reflected to the primary side of
     voltage and ferro-resonance conditions.                      the ideal transformer by multiplication
       4.7.6 Transformers                                         with the inverse of the square of the
         4.7.6.1 Two-Winding Transformers.                        turns ratio N.A close approximation of
     The equivalent circuit of a transformer is                   this circuit is possible by moving the
     shown in Fig 23(a). The rectangle repre-                     shunt branch and combining the primary
     sents an ideal voltage transformation                        and secondary impedances as shown on
     ratio ns/np = N, where n, and np are the                     Fig 24(a). Another simplification con-
     number of turns of the primary and                           sists in eliminating the shunt branch al-
     secondary windings respectively. & and                       together t o yield Fig 24(b). In many
     R, are the effective resistances of the                      types of studies, the resistance RT,being
     windings X,, and X,, their leakage reac-                     small with respect t o X,, is also neglec-
     tances. Go, the shunt conductance,                           ted thus reducing the model of the trans-
     models the iron losses that remain con-                      former to a single series reactance.
     stant when the transformer is energized                         Transformer nameplate specifies the
     at rated voltage and &, the shunt in-                         impedance 2, and the transformation
     ductive susceptance, is equivalent t o the                   ratio. An assumption may be made that
     quadrature magnetizing current at no                         X , E &. and the single series reactance
     load.                                                         model used.
                                                      Fig 23
                                              Two-Winding Transformer
                                                Equivalent Circuits
                                                             63
                                                                                          i
Authorized licensed use limited to: IEEE Xplore. Downloaded on November 08,2014 at 04:51:47 UTC from IEEE Xplore. Restrictions apply.
         IEEE
         Std 399-1980                        INDUSTRIAL AND COMMERCIAL POWER SYSTEMS ANALYSIS
                                                        Fig 24
                                               Two-Winding Transformer
                                             Approximate Equivalent Circuits
           Use of Fig 24(b) model requires that an                         4.7.6.2 Transformer Taps. Thus far,
         estimate of R be made from typical data                      only single ratio transformers have been
         [l],and a value for XTcalculated from                        dealt with. In real life, transformers have
                                                                      taps, normally on the high voltage wind-
        XT =     4
                 2
                 -                                                    ings, t o provide a voltage ratio best suited
                                                                      t o the power system. The taps may be
           Transformer test data will usually be                      changeable automatically under load
         sufficient t o calculate all the parameters                  (LTC transformer) or fixed (manually
         for the circuits of Figs 23(a), 23(b) and                    changed in de-energized condition).
         24(a). When maximum accuracy is needed                          The resistance and leakage reactance of
         the effective resistance R, should include                   the tapped windings are slightly different
         the winding resistances corrected for the                    at different taps. This may be ignored if
         operating temperature and another series                     the correct values are not known. On the
         resistance to account for stray losses                       other hand, transformer test data may
         [2], [3]. The model of Fig 23 necessi-                       specify values for the taps, in which case
         tates the creation of a fictitious bus for                   these values should be used. The main
         entry of the shunt admittance data in                        effect of changing taps is the change of
         the program.                                                 voltage ratio and therefore the change of
64
Authorized licensed use limited to: IEEE Xplore. Downloaded on November 08,2014 at 04:51:47 UTC from IEEE Xplore. Restrictions apply.
                                                                                                              IEEE
  SYSTEM MODELING                                                                                      Std 399-1980
                                             Fig 25
                   Three-Winding Transformer Approximate Equivalent Circuits
                            (a) Simplified-Delta (b) Simplified-Wye
  voltage base for which the impedance                          bus is required, the computer program
  diagram should be prepared. This will be                      will, upon request, automatically adjust
  described in more detail in 4.8.                              the taps and modify the system imped-
    The analyst should pay particular atten-                    ances as necessary for the new turns
  tion to the specific requirements of pro-                     ratio.
  grams for specifying taps. For instance                           4.7.6.3 Three-winding Transformers.
  the tap value 1.05 per unit (105%),inter-                     The circuits of Figs 23 and 24 apply to
  preted as an additional 5% to the voltage                     any two windings of the three-winding
  ratio, yields opposite results if applied t o                 transformers.
  the opposite sides of the transformer.                          The three possible combinations, put
    Once the data is input for a given con-                     together using Fig 24(b) as basic model,
  dition and a certain voltage on a specified                   form a delta as shown on Fig 25(a), where
65
Authorized licensed use limited to: IEEE Xplore. Downloaded on November 08,2014 at 04:51:47 UTC from IEEE Xplore. Restrictions apply.
           IEEE
           Std 399-1980                            INDUSTRIAL AND COMMERCIAL POWER SYSTEMS ANALYSIS
          the new subscript T denotes the tertiary                     has the same magnitude but that the angle
          winding. Elimination of the ideal trans-                     is shifted back another 2" by the wind-
          former symbols is made possible by cal-                      ing arrangement within the transformer,
          ling the voltages at nodes A, B and C,                       and that the rest of the information on
          1.0 per unit and remembering that those                      Fig 17 is the same as before. The new
          nodes have base voltage values E,, E, and                    impedance diagram will appear as shown
          Et respectively. Assuming that the 3-                        in Fig 26(a).
          phase system is balanced, the fictitious                       Now resolve as before with V, = 13.60
          neutral will be common to all three                          /-1.6" -2.0". The results are shown in
          voltage levels and can be eliminated t o                     Fig 26B. Note that the phase shift of a
          simplify the diagram.                                        mere 2" has caused the real power from
             The loop formed by the delta (A) cir-                     A t o B to jump from 5425 t o 22 803 kW,
          cuit can also be eliminated. This requires                   but the reactive power decreased from
          making a delta-wye transformation. The                       2118 t o 1605 kvar.
          end result shown in Fig 25(b) is a format                      This example illustrates the main pur-
          acceptable to computer programs. The                         pose of phase-shifting transformers to
          new node D at the center of the Y                            control the flow of real power between
          creates a fictitious bus that cannot be                      two buses.
          identified physically but that is necessary                    These transformers usually have load
          t o identify the impedance values to the                     tap changing mechanisms that will vary
          computer.                                                    the phase angle between primary and
                                                                       secondary automatically or manually.
            The relationships for reduction from                       Thus computer programs will be set up
           A t o Yare:                                                 to vary the amount of angle shift (plus
                                                                       or minus), within limits specified in the
           z'=                            1                            input, t o achieve the desired amount and
            p          (ZPS   +   ZPt   - 9 Zst)        (Eq 28)
                                              1                        the direction of real power flow.
                                                                         The data required by computer pro-
           2,'   =
                      1 zs,+ z,
                     %(2                  - Z,,)        (Eq 29)        grams will generally include the follow-
                        NI                                             ing:
                                                                         (1) Center (0"shift) position impedance
           z     =   lh(Z,t   +
                                   1
                                  91 zs, - 2,s)         (Eq 30)
                                                                         (2) Positive limit position impedance
                                                                         (3) Negative limit position impedance
                                                                         (4)Angle shift interval between taps
             The relationship as a function of the Y                     (5) Number of taps
           values is:                                                  Program subroutines allow the computer
                                                                       to automatically estimate the value of
           z,,=       2,: + 2,'                         (Eq 31)        the impedances at the intermediate taps.
                                                                            4.7.6.5 Other Transformer Models.
           qt =       2,:   +z;                         (Eq 32)        The foregoing discussion has been in-
                                                                       tended to give the reader a running start
           Z,, = N ; (2;+ 2,')                          (Eq 33)        on the subject of transformer modeling.
                                                                       It is far from being complete.
              4.7.6.4 Phase-Shifting Transformers.
           Consider again the example of 4.4. As-                      4.8 Power System Data Development
           sume this time that the voltage at bus B                      4.8.1 Per Unit Representations. Net-
66
Authorized licensed use limited to: IEEE Xplore. Downloaded on November 08,2014 at 04:51:47 UTC from IEEE Xplore. Restrictions apply.
                                                                                                                    IEEE
   SYSTEM MODELING                                                                                           Std 399-1980
67
Authorized licensed use limited to: IEEE Xplore. Downloaded on November 08,2014 at 04:51:47 UTC from IEEE Xplore. Restrictions apply.
          IEEE
          Std 399-1980                         INDUSTRIAL AND COMMERCIAL POWER SYSTEMS ANALYSIS
            For three-phase systems, the nominal                        expressed in terms of their own kVA and
          line-to-line system voltages are normally                     voltage ratings which differ from the
          used as the base voltages. The base kVA                       base values of a circuit, it is necessary to
          is assigned the three-phase kVA value.                        refer these values to the system base
          The derived values of the remaining two                       values. This may also happen when ma-
          quantities are:                                               chines rated at one voltage may actually
                                                                        be used in a circuit at a different voltage.
                                  base kVA                              In such cases, the per unit impedance of
             Base amperes =                            (Eq 37)
                                  fibase kV                             the device must be changed to either a
                                                                        new base kVA or new base voltage, or
                              (base kV)’                                both, by the equation:
             Base ohms =                               (Eq 38)
                              base MVA
                                                                        Per unit 2, = per unit 2,
            It is convenient in practice t o convert                                    (base kV,)’ base kVA2
          directly from ohms to per unit ohms                                           (base kV2)2base kVA,
          without first determining base ohms
          according to the following expression:                                                                    (Eq 40)
             Per unit ohms =
                                           -
                                   ohms base MVA                        where subscripts 1 and 2 referto the old
                                      (base kV)’                        and new base conditions, respectively.
                                                        (Eq 39)              4.8.2 Applications Example. A sec-
                                                                        tion of the power system described in
             For a three-phase system, the imped-                       4.5 has been repeated in Fig 27 as an
                                                                        illustration of the per unit system. The
          ance is in ohms t o neutral and the base
                                                                        transformer ratios were changed slightly
          kVA is the three-phase value.
                                                                        to improve this example. The steps in
             Where two or more systems with dif-
                                                                        reducing the data to per unit are as
          ferent voltage levels are interconnected
                                                                        follows:
          through transformers, the kVA base is
                                                                           (1)Select base power: S = 10 000 kVA
          common for all systems, but the base
                                                                           (2) Determine base voltages
          voltage of each system is forced by the
                                                                               (a) Select bus 2 nominal voltage of
          turns ratio of the transformer connect-
                                                                                   69 kV as base
          ing the systems, starting from the one
                                                                               (b) Calculate base voltages at other
          point for which the base voltage has been
                                                                                   system levels
          declared. Base ohms and base amperes                                                          13.8
          will thus be correspondingly different                                   BUS4: kV = 69.0 -
                                                                                                         66
          for systems of different voltage levels.
                                                                                               = 14.427 kV
             Once the system quantities are expres-
                                                                                                             2.4
          sed as per unit values, the various sys-                                 BUS36: kV = 14.427 *               13.2
          tems with different voltage levels can be
          treated as a single system and the neces-                                                   =   2.623 kV
          sary variables can be solved. Only when                                                                     0.48
                                                                                    BUS37: kV = 14.427                -
                                                                                                                      13.2
          reconverting the per unit values t o actual
          voltage and current values is it necessary                                                  =   0.525 kV
          t o recall that different base voltages
          exist throughout the system.
             When impedance values of devices are
68
Authorized licensed use limited to: IEEE Xplore. Downloaded on November 08,2014 at 04:51:47 UTC from IEEE Xplore. Restrictions apply.
                                                                                                                IEEE
    SYSTEM MODELING                                                                                      Std 399-1980
                          T2           66.0 - 13.8
                               N       1.0+j8.0
                                    510'               2865'
                                    I - 3 ~            I - 3 ~
                                    400 MCM            310
                                                                                            -@
                                                GI
                                                         L
                                                                                            485'
          13.2 k V                             13.8 k V                                     I-3C
          I O 000 h p                          8 . 5 MW                                     AWG N O 4
          0.8 POWER                            0.8POWER
          FACTOR                               FACTOR
          9800 kVA                             x; = 0.20
          x i = 0.28                                                                        -Q
                                                                                       T I4
                                                                          2.5             a M I 0
                                                             TI3          13.2 - 2 . 4         13.2 -0.48
                                                                          0.8+ j5.75           0.8tJ 5.75
                                                   Fig 27
                                         Impedance Diagram Raw Data
69
Authorized licensed use limited to: IEEE Xplore. Downloaded on November 08,2014 at 04:51:47 UTC from IEEE Xplore. Restrictions apply.
         IEEE
         Std 399-1980                        INDUSTRIAL AND COMMERCIAL POWER SYSTEMS ANALYSIS
                                                          Table 6
                                                     System Base Values
                                                  (Base Power 1 0 000 kVA)
                            Bus              Base kV                    Base 2                      Base I
                             2                69.00                   476.1                          83.67
                             4                14.427                   20.82                        400.2
                             8                14.427                   20.82                        400.2
                            24                14.427                   20.82                        400.2
                            31                14.427                   20.82                        400.2
                            32                14.427                   20.82                        400.2
                            36                 2.623                    0.688                      2201.0
                            37                 0.525                    0.027 56                 11 000.0
70
Authorized licensed use limited to: IEEE Xplore. Downloaded on November 08,2014 at 04:51:47 UTC from IEEE Xplore. Restrictions apply.
                                                                                                                    IEEE
    SYSTEM MODELING                                                                                         Std 399-1980
                                                            Table 7
                                                           Cable Data
            Length                r           ( a/1000’)    x1 ( n / 1 0 0 0 ’ )   Conductor Outside Insulation Thickness
     Line    (ft)  Conductor Size               (ft)               ( ft)           Diameter (inches)        (inches)
        7     510         400MCM               0.0297           0.0370                   0.728              0.175
        8    2865            310               0.0668           0.0423                   0.470              0.185
      18      340            4                 0.2992           0.0516                   0.232              0.220
      19      485            4                 0.2992           0.0516                   0.232              0.220
                  z=
                         0.8 + j5.75         .-.-
                                              0.48*     10                         (d) Line 18:
                                                                                                  -
                                                                                       Xc = 4683 5280/2865
                             100              0.525*    1
                                                                                           = 8630 S2
                     =   0.066 87 + j0.480 65                                                         -
                                                                                        R = 0.2992 340/1000
                                                                                           = 0.101 73 S2
       (7) Calculate line impedance in ohms
           (a) Lines 7, 8, 18 and 1 9 are 3/c,                                                        -
                                                                                       X , = 0.0516 340/1000
                                                                                           = 0.017 54 S2
               copper cables, paper insulated,
               shielded conductors; dielectric
                                                                                       Xc = (neglect due t o
               constant: 3.7. See Table 7.                                                   short length)
71
Authorized licensed use limited to: IEEE Xplore. Downloaded on November 08,2014 at 04:51:47 UTC from IEEE Xplore. Restrictions apply.
         IEEE
         Std 399-1980                        INDUSTRIAL AND COMMERCIAL POWER SYSTEMS ANALYSIS
                  . , Generator G1
                  (b)
                       X: = j0.20 ___
                                     13.8'
                                                  -
                                              10 000
                                                                                   ID I):('
                                   14.4272 8500/0.8
                         = j0.1722                                                                              Qi   (Eq 43)
                                                                                   L                       J
       =):(     k):(
                                                                        The problem of assigning correct values
                                                                      to the constants (h, , k 2 , A through H ) is
72
Authorized licensed use limited to: IEEE Xplore. Downloaded on November 08,2014 at 04:51:47 UTC from IEEE Xplore. Restrictions apply.
                                                                                                                  IEEE
     SYSTEM MODELING                                                                                       Std 399-1980
0.0061
                                T2
                                     N
14.427 ( k V b )
                                          0.000 73           0.00919
                                          + j O . 0 0 0 91   +j0.00582 (Z)
                                                             0.00
                                                             +j0.002 41 ( Y )
                                          .@ -
               M                                                              0.004 89           0.006 97
                                                                              + j 0.000 84       t j0.0012
                   j0.2392                               j0.1722
                                                                              -Q             --@
                                                                              0.026 79           0.066 97
                                                                              .IO.I92 55         +j0.481 35
                                                                         U.   hl             a   U
                                                                   TI3                               t14
                                                     Fig 28
                                         Impedance Diagram Fer Unit Data
73
Authorized licensed use limited to: IEEE Xplore. Downloaded on November 08,2014 at 04:51:47 UTC from IEEE Xplore. Restrictions apply.
         IEEE
         Std 399-1980                          INDUSTRIAL AND COMMERCIAL POWER SYSTEMS ANALYSIS
                                1.4 -                                                /
                                                         IM PEDANCE
                                1.3 .-
                                1.2 '-
                          -c,
                                1.1 -
                          3
                          a
                                1.0 -
                          W
                          Q
                          a
                          ;
                          W
                                0.9   -                                                      POWER
                                      I    I        I       1         I         I        I       I           I
                                          0.7     0.8      0.9      1.0        1.1    1.2       1.3      1.4
                                                        VOLTAGE ( P E R U N I T )
                                                        Fig 29
                                Effect of Voltage Variations for Three Types of Loads
         very difficult when studying utility type                    tems are relatively modest in size. More-
         systems, because the nature of the load                      over bus loads are often arranged in such
         is not known accurately. Additionally,                       a way that grouping by type is easy to
         the tasks of simulating the load in all its                  do, thus facilitating the preparation of
         details would require a computer pro-                        computer input data and offering the
         gram of such size and cost that the effort                   possibility of combining large sections of
         would be prohibitive [4], [ 5 ] , [6], [ 7 ] .               the system to reduce the overall size of
           Industrial and commerical power sys-                       the study sections.
74
Authorized licensed use limited to: IEEE Xplore. Downloaded on November 08,2014 at 04:51:47 UTC from IEEE Xplore. Restrictions apply.
                                                                                                                IEEE
    SYSTEM MODELING                                                                                      Std 399-1980
RI x2
                                                   Fig 30
                                      Induction Motor-Equivalent Circuit
75
Authorized licensed use limited to: IEEE Xplore. Downloaded on November 08,2014 at 04:51:47 UTC from IEEE Xplore. Restrictions apply.
        IEEE
        Std 399-1980                         INDUSTRIAL AND COMMERCIAL POWER SYSTEMS ANALYSIS
PERCENTOFSYNCHRONOUSSPEED
                                                       Fig 31
                                         Induction Motor Torque Versus Speed
                                                      25                50                75   IO0
                                                           PERCENT OF SYNCHRONOUS SPEED
                                                       Fig 32
                                         Induction Motor Current Versus Speed
76
Authorized licensed use limited to: IEEE Xplore. Downloaded on November 08,2014 at 04:51:47 UTC from IEEE Xplore. Restrictions apply.
                                                                                                                  IEEE
   SYSTEM MODELING                                                                                         Std 399-1980
                    I                    I                   I                    I                    I
                                        25                  50                   75                   100
                                             PERCENT OF SYNCHRONOUS SPEED
                                                Fig 33
                               Induction Motor Power Factor Versus Speed
77
Authorized licensed use limited to: IEEE Xplore. Downloaded on November 08,2014 at 04:51:47 UTC from IEEE Xplore. Restrictions apply.
         IEEE
         Std 399-1980                        INDUSTRIAL AND COMMERCIAL POWER SYSTEMS ANALYSIS
I50
140
I30
                         120
                     z
                     a
                     I
                     0   ll0
                     +
                     z
                     W
                     g   100
                     w
                     a
90
                         ao                                                                        /            \
                                                                                                 P F AT 7 5 %
                                                                                                 LOAD
                                                       I                           1                             I
                               90                     I00                         110                           I20
                                                           PERCENT VOLTAGE CHANGE
                                                         Fig 34
                                            Effect of Voltage Variations on
                                         Typical Induction Motor Characteristics
78
Authorized licensed use limited to: IEEE Xplore. Downloaded on November 08,2014 at 04:51:47 UTC from IEEE Xplore. Restrictions apply.
                                                                                                               IEEE
    SYSTEM MODELING                                                                                     Std 399-1980
79
Authorized licensed use limited to: IEEE Xplore. Downloaded on November 08,2014 at 04:51:47 UTC from IEEE Xplore. Restrictions apply.
          IEEE
          Std 399-1980                        INDUSTRIAL AND COMMERCIAL POWER SYSTEMS ANALYSIS
         bus will have t o be specified for the spe-                   a particular motor. The reactive power is
         cific voltage.                                                calculated as follows:
            (2) Specify fixed kW and kvar and let                        (1)Draw a vertical line for the fixed
         the voltage fall where it may.                                excitation current
            The last alternative suggests that a gen-                    (2) Read the armature current I, at the
         erator may be considered analytically as                      intersection of the load line representing
         a negative constant power load. Many                          the motor running load, and the I line
         computer programs will accept negative                          (3) Estimate the motor terminal voltage
         power signs. Thus negative kW input t o                       (line t o line)
         the bus load data would model a gen-                            (4)Calculate the reactive power
         erator.
                4.9.3.1.2 Synchronous Condenser.                       kvar = d 3 ( VI)2- kW2
         One difference between this machine
         and a generator is that the condenser will                      Alternately, if the power factor curves
         be a fixed load with very small kW value                      are shown on the graph, replace above
         t o represent its losses. Otherwise, it will                  steps 3 and 4 with:
         generally be equipped with a voltage reg-                       (3) Read the power factor at the inter-
         ulator similar t o a generator and have its                   section of the load line and I line
         reactive power output, specified within                         (4)Calculate the reactive power
         certain limits, adjusted by the computer
         program t o maintain a specified voltage                      kvar     =   kW tan 8                        (Eq 53)
         at its own terminals or elsewhere in the
         system.
                4.9.3.1.3 Synchronous Motors. The
         synchronous motors may or may not be                              4.9.3.2 Short Circuit Models. The
         equipped with regulators t o control the                      current contributed t o a fault by a syn-
         excitation. Those equipped with regu-                         chronous machine varies with time, from
         lators may control voltage, power factor,                     a high initial value t o a moderate final
         reactive power or even current, at their                      steady state value. Equations 55, 56 and
         terminals or elsewhere. The real power in                     57 depict this variation of current as a
         kW will be a function of the load driven                      function of time for a short circuit at the
         by the motor, and will not be adjustable                      terminals of a machine operating initially
         for the given set of conditions under                         at no-load.
         study.
            The analyst may, therefore, resort t o
         modeling the motors as negative generat-
         ors with reactive power limits, if a volt-
         age or current control device is supplied.
         In the case of power factor or reactive
         power regulators, the specified kW will
         define a value of kvar using Eqs 52
         through 54.                                                                E   a ,.t/Td
            For motors with fixed excitation and a                     hc   =
                                                                                     X”
         given fixed load, vee-curves must be used
         t o calculate the equivalent reactive
         power. Figure 36 shows the V curve for                        IT   =di?Xg
80
Authorized licensed use limited to: IEEE Xplore. Downloaded on November 08,2014 at 04:51:47 UTC from IEEE Xplore. Restrictions apply.
                                                                                                                  IEEE
     SYSTEM MODELING                                                                                      Std 399-1980
250
200
            a
            w
            z
            -
            1
100
50
RATED
                  0
                      0               25             50                75               100              I25
                                                          FIELD A
                                                    Fig 36
                                   Vee-Curves: Synchronous Motor, 2000 hp,
                                   4000 V, 180 r/min, 0.8 Lead Power Factor
81
Authorized licensed use limited to: IEEE Xplore. Downloaded on November 08,2014 at 04:51:47 UTC from IEEE Xplore. Restrictions apply.
        IEEE
        Std 399-1980                        INDUSTRIAL AND COMMERCIAL POWER SYSTEMS ANALYSIS
82
Authorized licensed use limited to: IEEE Xplore. Downloaded on November 08,2014 at 04:51:47 UTC from IEEE Xplore. Restrictions apply.
                                                                                                                 IEEE
     SYSTEM MODELING                                                                                      Std 399-1980
      The offset current will decay more                          work at times t = 0 or t = t', or both,
    rapidly the farther away (electrically)                       using the models of Fig 37. Network
    the machine is from the point of fault.                       solutions at t = CY are meaningless since
      The voltage E , in all the above equa-                      the machine field excitation has likely
    tions, is equal t o the terminal voltage V,,                  been changed at that time.
    since it was assumed that the machine                           Depending on the study objectives, the
    was carrying no load before the short                         effect of the offset current       may or
    circuit. If the machine is carrying a                         may not be important. In power circuit
    current IL before the short circuit, the                      breaker applications, however, it is a
    voltage E will be different in each equa-                     very important consideration. To obviate
    tion, to satisfy prefault conditions. For                     the difficulties in resolving Eq 63, the
    the case of a generator the voltage in                        breaker standards specify multipliers for
    Eqs 58,62 and 61 will be:                                     the X y and XA current components.
                                                                  These are a function of machine type
     E"   =   V, + IL X l                                         and of the time from the inception of
                                                                  the short circuit. Figure 22 of [ l o ] lists
                                                                  those multipliers, gives examples of their
                                                                  use and expands on this important aspect
                                                                  of short circuit studies.
                                                                    The models of Figs 37 and 38 are also
     respectively. These voltages have been                       applicable t o synchronous motors and
     called, voltage behind subtransient reac-                    synchronous condensers, the difference
     tance (E"), voltage behind transient reac-                   being that the E", E' and E voltages are
     tance ( E ' ) , and voltage behind synchro-                  calculated with :
     nous reactance ( E ) . It is not practical, in
     short circuit studies, t o calculate the sys-
     tem currents for the entire period -from
     the time of fault t o the time that the
     current reaches a steady state value. The
     normal procedure is t o resolve the net-
                                              Fig 37
                       Models of Synchronous Machines for Short-Circuit Studies
83
Authorized licensed use limited to: IEEE Xplore. Downloaded on November 08,2014 at 04:51:47 UTC from IEEE Xplore. Restrictions apply.
        IEEE
        Std 399-1980                             INDUSTRIAL AND COMMERCIAL POWER SYSTEMS ANALYSIS
                                 FE                                   H = -KE
                                                                           =-       J
                                                                           S       VA
                  MF   =
                                 L
                           multiplier specified
                                                                      units.
                                                                        To calculate the H constant use:
                                                                      H = 0.231
                                                                                    ( w R ~(r/minl2
                                                                                            )       10-~  -
                                                                                                        (Eq 75)
                           in A N S I / I E E E C37.010-1979                                MVA
84
Authorized licensed use limited to: IEEE Xplore. Downloaded on November 08,2014 at 04:51:47 UTC from IEEE Xplore. Restrictions apply.
                                                                                                                IEEE
    SYSTEM MODELING                                                                                      Std 399-1980
    where WR2 is the moment of inertia in                         those of the first improved model will
    pounds-feet squared and r/min is the                          increase the accuracy in the case of a
    speed in revolutions per minute. The H                        generator with solid iron rotor. But, as
    constant values will fall within the nar-                     before, the damping effect will have
    row range of approximately 1 t o 15,                          been mostly neglected. The solid iron
    irrespective of the size of the machines.                     rotor will be fully represented by all
          4.9.3.3.3 Stability Model Varia-                        direct- and quadrature-axis, synchronous,
    tions. In the discussion of 4.9.3.2, only                     transient and subtransient reactances and
    the direct-axis parameters were consid-                       associated time constants.
    ered on the basis that short circuits pro-                      The transient quadrature-axis reactance
    duce currents of low power factor (quad-                      of salient-pole machines has the same
    rature currents predominate). This as-                        value as the equivalent synchronous reac-
    sumption may not be acceptable for dis-                       tance. Thus salient-pole machines can be
    turbances considered in stability analysis.                   fully modeled as the solid-iron rotor
    Therefore, additional synchronous ma-                         machine by omission of the XA and TAo
    chine parameters are required t o more                        parameters.
    accurately model the behavior and ac-                              4.9.3.4 Exciter Models.
    count for the differences in the magnetic                        (1) Saturation. The field poles saturate
    construction types, such as: salient poles,                   as the excitation current exceeds a certain
    smooth rotor, laminated rotor, solid                          level (see Fig 39). Computer programs
    iron rotor with or without dampers.                           will usually account for the related non-
       Quadrature-axis reactances and open-                       linearity of air-gap voltage and field cur-
    circuit time constants are defined for                        rent from input data representing two
    that purpose. Chapter 1 of [ l l ] is                         points on the saturation curve. Refer t o
    especially recommended as a clear and                         program instructions for which two
    basic text in the subject.                                    points t o use.
      The classical model may be improved                            (2)Standard Models. An IEEE com-
    one step by taking account of the varia-                      mittee has developed a number of models
    tion of XA with time from its initial value                   to represent excitation systems and the
    to a steady state value of xd. The varia-                     dynamic characteristics of synchronous
    tion will be an exponential described by                      machines for stability studies [12]. A
    a time constant TAo (transient, open-                         tutorial paper [13] supplements refer-
    circuit time constant). The three para-                       ence [ 121 by discussing the transfer func-
    meters &, X i and TAo will ignore the                         tion blocks and their practical meanings
    major effect of dampers.                                      as well as other topics related t o excita-
      Another improvement will involve                            tion system response. Only type (1)is
    adding the effect of dampers which pre-                       repeated here (Fig 40) t o illustrate the
    dominate during fast changing condi-                          following points.
    tions, that is, the subtransient state. The                      Consider the simple circuit of Fig 41.
    additional parameters X: and Tt0 will                         If the input voltage V is a step function
    take care of this effect.                                     (voltage changes suddenly at t = 0 from
      The saliency of the rotor will be repre-                    0 t o 1.0 pu V), the output voltage V will
    sented by the quadrature-axis parameters,                     be an exponential function of time:
    X,,X; and X t and the associated time
    constants TAo, TA:.
      Adding the parameters X; and           to     go            that may be rearranged
85
Authorized licensed use limited to: IEEE Xplore. Downloaded on November 08,2014 at 04:51:47 UTC from IEEE Xplore. Restrictions apply.
           IEEE
           Std 399-1980                      INDUSTRIAL AND COMMERCIAL POWER SYSTEMS ANALYSIS
NO LOAD SATURATION
                                                                                             A-B -    A
                                                                           S E = f (EFD) =   -B
                                                                                                 -   - -I
                                                                                                      B
                                                            Fig 39
                                                       Saturation Curves
-SE=K(EFD) -
      T'    -          I
                   I + STR
                                                       -
                                                                                                      I
                                                                                                 KE + STE
                                                                                                             -     -      EFD
                                 SIGNALS
                                                L                             SKF
                                                        Fig 40
                                             IEEE Type 1 Excitation System
86
Authorized licensed use limited to: IEEE Xplore. Downloaded on November 08,2014 at 04:51:47 UTC from IEEE Xplore. Restrictions apply.
                                                                                                               IEEE
    SYSTEM MODELING                                                                                     Std 399-1980
                                                        Fig 41
                                                      Lag circuit
87
Authorized licensed use limited to: IEEE Xplore. Downloaded on November 08,2014 at 04:51:47 UTC from IEEE Xplore. Restrictions apply.
         IEEE
         Std 399-1980                        INDUSTRIAL AND COMMERCIAL POWER SYSTEMS ANALYSIS
                                                            Fig 42
                                                          Lead Circuit
              4.9.3.5 Prime Movers and Governor                       lighting. In utility type networks where
         Models. Basic models for speed-governing                     substations are equipped with voltage
         systems and turbines in power system                         regulators, lighting and heating can be
         stability studies have been presented in                     represented as constant P + jQ.
         an IEEE Committee Report [14]. As                              To calculate the admittances determine
         mentioned earlier, the models are in the                     the watts P and vars Q at rated voltage V
         form of block diagrams with transfer                         and resolve
         functions describing the system compo-
         nents’ performance. Two more papers                                        P+jQ
                                                                      Y (siemens) =-
         [15], [16] cover some of the basics and                                     E*
         will help the novice t o understand the
         relationships between the physical ele-                      The fluorescent and mercury vapor light-
         ments and the transfer functions.                            ing power factors will be determined from
           Typical parameter values are also avail-                   manufacturers’ data in order t o calculate
         able in these references. Of course, the                     the vars Q. Incandescent lights and elec-
         analyst will be well advised to seek from                    tric heating will have unity power factors.
         the manufacturer the data applicable to                        4.10.2 Electric Furnaces. In load flow
         his equipment before compromising with                       studies this load will usually be repre-
         typical data.                                                sented by constant power which will re-
                                                                      flect a desired controlled operating con-
         4.10 Miscellaneous Bus Element Models                        dition to be analyzed. In the case of
           4.10.1 Lighting and Electric Heating.                      short circuit and stability studies the
         Lighting and electric heating often con-                     electric furnaces may behave like a con-
         stitute a large section of a plant load,                     stant impedance load. It is unlikely that
         particularly in commercial buildings.                        automatic load tap changers and electrode
         This type of load can be modeled as                          position controls will have had time t o
         constant admittance as suggested by Figs                     change from the prefault condition t o
         4.10, 4.11,and 4.12 of [17]. The con-                        the end of the period covered in transient
         stant admittance model would seem ap-                        stability studies. This may very well be
         propriate for fluorescent and mercury                        the case also in dynamic stability studies
         vapor lighting as well as for incandescent                   extending t o several s. Since furnace
88
Authorized licensed use limited to: IEEE Xplore. Downloaded on November 08,2014 at 04:51:47 UTC from IEEE Xplore. Restrictions apply.
                                                                                                              IEEE
  SYSTEM MODELING                                                                                      Std 399-1980
89
Authorized licensed use limited to: IEEE Xplore. Downloaded on November 08,2014 at 04:51:47 UTC from IEEE Xplore. Restrictions apply.
          IEEE
          Std 399-1980                        INDUSTRIAL AND COMMERCIAL POWER SYSTEMS ANALYSIS
90
Authorized licensed use limited to: IEEE Xplore. Downloaded on November 08,2014 at 04:51:47 UTC from IEEE Xplore. Restrictions apply.
                                          5. Load Flow Studies
    5.1 Introduction. Load flow is the ter-                      requirements change. In any practical
    minology applied to the flow of power                        operating system, load distribution shifts
    from one or more sources through avail-                      each time a user turns a light, a motor,
    able paths to loads consuming energy.                        or other power consuming device on or
    Direction and amount of power flowing                        off. Consequently, load flow is a fluid
    in each path or branch can be shown on                       and ever-changing thing. Where parallel
    a system map commonly referred to as                         paths or circuits exist t o supply power
    the system single line (or one-line) dia-                    loads, the operation of switches, break-
    gram - a simplified visual model of a                        ers, etc (whether manually by an opera-
    balanced three-phase electrical system.                      tor or automatically by relay action)
      When the system is radial and has no                       will change the circuit configuration and
    parallel paths, power flows directly to                      cause a redistribution of power flow
    the load. Most systems today, however,                       through interconnecting lines. Large
    are much more complex and have many                          industrial plants and electric utility com-
    paths or branches over which power can                       panies with complex system netwarks
    flow. Such a system forms a network of                       face a difficult task. They must provide
    series and parallel paths.                                   operators and dispatchers with informa-
      Electric power flow in a network, like                     tion necessary to ensure efficient opera-
    water flow in a complex water system,                        tion, minimize losses, maintain reliability
    divides the flow among branches accord-                      of service, and coordinate protective
    ing to their respective impedances until                     relaying for unexpected and emergency
    a pressure or voltage balance is reached                     conditions.
    in accord with Kirchhoff’s laws.                               In addition, the power system planner
      As long as the circuit remains un-                         must look at future power requirements
    changed, the balanced conditions hold.                       and allow for additions and changes. It
    The flow will shift however, any time                        is necessary to meet projected loads
    the circuit configuration is changed or                      when they occur, and still maintain or
    modified, generation is shifted, or load                     improve the efficiency and reliability of
91
Authorized licensed use limited to: IEEE Xplore. Downloaded on November 08,2014 at 04:51:47 UTC from IEEE Xplore. Restrictions apply.
         IEEE
         Std 399-1980                         INDUSTRIAL AND COMMERCIAL POWER SYSTEMS ANALYSIS
92
Authorized licensed use limited to: IEEE Xplore. Downloaded on November 08,2014 at 04:51:47 UTC from IEEE Xplore. Restrictions apply.
                                                                                                                   IEEE
    LOAD FLOW STUDIES                                                                                    Std 399-1980
                                                                          1 3 . 8 kV
                                                                          1MAIN
                                                                                               Q              I
        13.8 kV
        7       (24) G:NERATOR                           I
                                              BUS NAME
                                          BUS NO SYMBOL
                        1.0 PU VOLTS
                        8.5 + j 5 . 2 6
   GENERATOR 1
                        (P+Q)
                                                                          13.8 kV      Io
                                                                                               @       FDR 31
                        Fig 43                                                         Fig 44
                Generators Connected                                              Connection of Buses
                    t o their Bus
   Buses can be named as well as numbered.                             t o bus 9 (FDR 31) and is shown t o be
   Interconnecting lines are shown with                                650 ft long with R = 0.0845 S2 and X =
   their R + jX values entered or cross ref-                           0.03074S2.
   erenced with tables of values. For in-                                 Transformers are usually shown be-
   stance, generators are shown connected                              tween two buses with the primary on
   t o their bus as illustrated in Fig 43 with                         one bus and the secondary winding
   their equipment parameters specified.                               identified by an auxiliary bus (identified
   Each line originates on a bus and termi-                            by number and a suitable name, see Fig
   nates on a different bus as depicted in                             45). The auxiliary bus can then be tied
   Fig 44. Line 1 runs from bus 3 (main 1)                             by a line t o the other bus.
                                                        Fig 45
                                                     Auxiliary Bus
                                           13.8 kV       -                   @ FDR 41
                                           1.5 MVA   &           TI0
                                               0.48 kL
                                                                  @TI0
                            AUXILIARY BUS’
                                                 7           h
                            ( TRANSFORM ER
                            SECONDARY
                            TERMINALS)                       0
                                                         .7
                                                             +
                                                             f
                                                             0
                                                         0
                                                         0
                                                         0
93
Authorized licensed use limited to: IEEE Xplore. Downloaded on November 08,2014 at 04:51:47 UTC from IEEE Xplore. Restrictions apply.
         IEEE
         Std 399-1980                        INDUSTRIAL AND COMMERCIAL POWER SYSTEMS ANALYSIS
            If the auxiliary bus is used, transform-                  diverse systems tend to use the more
         er impedance is entered along with line                      sophisticated programs. Industrial plants
         impedance. Otherwise, their series com-                      that use less sophisticated programs find
         bination is entered. If the transmission                     them satisfactory.
         or distribution line is long (5 mi or                          The balance of this section uses one of
         more), it will require charging (charging                    the less sophisticated programs t o illus-
         conductance G , and line leakage suscept-                    trate a load flow study for an industrial
         ance B ) . One half of the total for the line                plant. Programs are available with various
         is usually shown on each of the two                          levels of sophistication. This one was
         buses.                                                       arbitrarily chosen for convenience. The
            If MVA capability of the line is known,                   following is a case study for a large in-
         it can be entered also. Tap voltages, where                  dustrial plant and illustrates in detail
         required, should be entered to modify                        how a load flow study is undertaken.
         the nominal ratios. If transformers are of
         the tap changing under load type, the                        5.4 Load Flow Study Example
         tap limits and incremental tap values                           5.4.1 General. To illustrate the use of a
         should be given. If transformer imped-                       load flow program a typical industrial
         ance is given in percent (or per unit), it                   plant will be studied. The single line con-
         is expressed on its own self-cooled MVA                      nection diagram of the plant electrical
         rating as base.                                              system is shown in Fig 46. The base case
                                                                      solves the system in the normal operat-
         5.3 System Data Organization. A load                         ing mode supplying present maximum
         flow solution gives the power flow in all                    loads. A case identified as case A1 is
         branches for a given set of conditions. It                   solved t o show what happens t o the
         represents a steady state in which the in-                   system when lightning causes relays to
         fluential parameters are in balance and a                    open breakers at bus 3 and bus 26 to
         solution has been found. A load flow                         isolate transmission line 3.
         study is a series of such calculations made                     The impedance diagram in Fig 47 is
         when certain equipment parameters are                        similar to the single line diagram except
         set at different values, or circuit config-                  that impedances of the interconnecting
         uration is changed by operning or closing                    lines, equipment parameters, load re-
         breakers, adding or removing a line, etc.                    quirements, and nominal bus voltages
            Many load flow programs have been                         have been added.
         written for digital machines. They differ                       5.4.2 Input Requirements. The follow-
         in some ways, mainly by solution tech-                       ing input data apply specifically to this
         niques and sophistication (taking into                       program, but similar data will be required
         account more and more influencing para-                      for almost any load flow program. Three
         meters). Power flow is very sensitive to                     data input forms are used for entering
         circuit changes of impedances, intercon-                     required data in the proper format for
         nections, and location of loads and equip-                   this particular load flow program.
         ment. In general, less sophisticated pro-                       The input data sheet shown in Fig 48
         grams will give satisfactory results, al-                    is used t o identify the company, location,
         though more sophisticated ones will have                     date, and title of the study, and who
         increased accuracy. As programs become                       made the study. Also included is an un-
         more sophisticated additional input data                     limited number of statements defining
         is required. Utility companies with large                    power system conditions under which
94
Authorized licensed use limited to: IEEE Xplore. Downloaded on November 08,2014 at 04:51:47 UTC from IEEE Xplore. Restrictions apply.
                                                                                                                  IEEE
    LOAD FLOW STUDIES                                                                                   Std 399-1980
95
Authorized licensed use limited to: IEEE Xplore. Downloaded on November 08,2014 at 04:51:47 UTC from IEEE Xplore. Restrictions apply.
         IEEE
         Std 399-1980                        INDUSTRIAL AND COMMERCIAL POWER SYSTEMS ANALYSIS
96
Authorized licensed use limited to: IEEE Xplore. Downloaded on November 08,2014 at 04:51:47 UTC from IEEE Xplore. Restrictions apply.
                                                                                                               IEEE
   LOAD FLOW STUDIES                                                                                    Std 399-1980
97
Authorized licensed use limited to: IEEE Xplore. Downloaded on November 08,2014 at 04:51:47 UTC from IEEE Xplore. Restrictions apply.
         IEEE
         Std 399-1980                         INDUSTRIAL AND COMMERCIAL POWER SYSTEMS ANALYSIS
            Figure 49 is used for entering all data                       Figure 50 is used for entering line and
          relating t o system buses, that is, bus                      transformer data for the system, that is,
          name, bus number, bus type (see listing                      from and to bus numbers, conductance
          at bottom), nominal bus voltage and                          G and susceptance B (usually neglected
          angle, generation, loads, and associated                     for in-plant distribution lines), resistance
          capacitors or reactors.                                      and reactance of the line or transformer,
                                                                       MVA rating, and transformer tap voltages.
            Figure 49 shows the information filled
                                                                          Figure 50 shows data for the illustrative
          in with data for the load flow study
                                                                       example.
          example.
                                                                         Most programs allow changes to be
           Bus types are used t o direct the com-                      made t o a base case with a minimum of
         puter t o properly process bus data. Types                    input data. Change data is entered on
         of buses are as follows:                                      Fig 49 for bus changes, and in Fig 50 for
                                                                       line and transformer changes. A change
            Bus Type                   Function                        code number must be entered in the
                                                                       proper column on the figures t o instruct
               0       Slack or swing bus. Takes the                   the computer of the change. The program
                       swings in loads and adjusts to                  will recognize the following changes t o a
                       supply MW and Mvar losses.                      base case:
Authorized licensed use limited to: IEEE Xplore. Downloaded on November 08,2014 at 04:51:47 UTC from IEEE Xplore. Restrictions apply.
                                                                                                                                            IEEE
   LOAD FLOW STUDIES                                                                                                                 Std 399-1980
                                                l I 11 11 11 1I J1 11           1 1 1 1 1 I 1 l 1l 11 11 11 11 11 la
                                    0
                  ~
                  - 3 "   ~         ~   ~                                                                          1 1           1    1   =
                  .*, =" . ,, * >
                                I           I   I   I   I   I   I   I   I   I     I    I   I   I   I   I   I   1   I   1 I . D
                                                                                                                                                Y
                                                                                                                                                7
             m
                                                                                                                                                a
                                                                                                                                                E
                                                                                                                                                H
      0 ,         U
                  Y                                                                                                              >
             0
             0
             CL
             a
     -'rq
     0
     w   R
99
Authorized licensed use limited to: IEEE Xplore. Downloaded on November 08,2014 at 04:51:47 UTC from IEEE Xplore. Restrictions apply.
          IEEE
          Std 399-1980                        INDUSTRIAL AND COMMERCIAL POWER SYSTEMS ANALYSIS
p7
              m:
                   S
              ag
                   0
                   n
                   CL
100
Authorized licensed use limited to: IEEE Xplore. Downloaded on November 08,2014 at 04:51:47 UTC from IEEE Xplore. Restrictions apply.
                                                                                                               IEEE
    LOAD FLOW STUDIES                                                                                   Std 399-1980
101
Authorized licensed use limited to: IEEE Xplore. Downloaded on November 08,2014 at 04:51:47 UTC from IEEE Xplore. Restrictions apply.
         IEEE
         Std 399-1980                        INDUSTRIAL AND COMMERCIAL POWER SYSTEMS ANALYSIS
         processing, the results will be returned                     numbered bus is shown with name, bus
         (with the input cards) to the user. For                      number and voltage at solution, and
         remote terminal entry, the computer                          phase angle with respect to the swing
         service usually has keypunch machines                        bus. If the bus is a load bus, load MW
         and operators, who can punch cards and                       and Mvar are printed. Printed next is the
         verify input data. The computer service                      bus number of the From bus, then the
         will also assist in entering the cards by                    To bus number and name, MW, Mvar,
         remote terminal reader and will notify                       and MVA flowing in the line. A plus (+)
         the user when output results are ready.                      indicates flow of power from the first
         In some instances, data can be punched                       bus t o the second bus. A negative sign
         into paper or magnetic tape and sub-                         (-) indicates the flow t o be in the oppo-
         mitted. However, punched cards are                           site direction. Note that MW flow and
         most frequently used. For the less exper-                    Mvar flow can be in opposite directions
         ienced, there are consultants who can do                     in the same line. This is not a desirable
         the analysis and present the user with a                     condition, but is entirely possible in
         complete report including a technical                        real systems. For each line the MW and
         analysis of the computer output and                          Mvar line loss is printed. All lines con-
         suggestions and advice on system im-                         nected t o this bus are given. If a trans-
         provement.                                                   former connects the two buses, the
                                                                      transformer tap voltages used in the
         5.6 Load Flow Results. Output from the                       calculations are printed. Finally, the bus
         computer for each case is printed in                         error, or mismatch, is printed. When all
         report form. For input data checking, a                      buses with inter-connecting lines have
         page of input data is printed from the                       been printed, the total accumulated bus
         computer file for all lines and trans-                       error is printed. The last item printed is
         formers. The number of iterations the                        the total loss for the system. There are
         computer required is also printed (see                       instances where a solution is found for
         Fig 51).                                                     specified conditions without exceeding
           If a satisfactory solution cannot be                       the iteration limit, but does have exces-
         obtained in the specified number of                          sive bus error or mismatch (power into
         iterations (500), a message is printed                       the bus does not match power out of the
         stating that the number of specified                         bus, within a reasonable tolerance). When
         iterations has been exceeded. In this                        this occurs, voltage tolerance should be
         event, the full report is printed, but                       decreased for a more accurate solution.
         caution should be used, as the values                        The amount of mismatch is a good indi-
         printed do not give a satisfactory bal-                      cator of the validity of the solution.
         anced solution. The full report is often                        Some programs print certain values
         quite helpful in analyzing the system                         (usually bus voltages) in per unit values
         trouble that might have led t o the un-                      rather than actual. This method allows
         satisfactory solution.                                       a relative evaluation. Multiplication by
           Assuming a solution has been reached,                      the per unit value permits determination
         the report will be printed on as many                        of actual values. If the program does not
         sheets as required. Printed on the first                      reach a satisfactory solution (as evi-
         line are the case number and description                      denced by exceeding the specified num-
         for identification purposes. Reference t o                    ber of iterations) the reason can be
         Fig 52 verifies the following: The lowest                     because of incomplete or inconsistent
102
Authorized licensed use limited to: IEEE Xplore. Downloaded on November 08,2014 at 04:51:47 UTC from IEEE Xplore. Restrictions apply.
                                                                                                                                                               IEEE
     LOAD FLOW STUDIES                                                                                                                                  Std 399-1980
                                                                 O O O O O O O O O o O O O O O O O O O O o o o o o o o * m m m ~ * ~ m ~ m m o
                                                            4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . , . . . .
                                                            > 0 0 0 0 0 0 0 0 0 0 0 0 6 0 0 0 0 0 0 0 0 0 0 0 0 m m . 4 ~ 4 . 4 m m 0 . 4 . 4 ~ t w . 4
                                                                                                                                   4 4
                                                            ~ o o o o o o o o o o o o o o o o o o o o o o o o o ~ o m m m m m w m m m m m m
                                                            Y . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
                                                            w O 0 0 0 0 0 0 0 0 o O O O O O Q 0 0 0 o o o o o o m m m m m m m m m m m m m m
                                                            a                                                      .na.4-.44.-I44+-l.4.44
                                                            m
                                                            .........................................
                                                                 o o o o o o o o o o o o o o o o o o o o o o o o o ~ m ~ ~ m m ~ ~ m t n m m ~ ~
                                                            a o o o o o o o o o o o o o o o o o o o o o o o ~ o m m ~ ~ o o ~ ~ o o o o ~ o
                                                            a                                                                      3.4
                                                                 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 m ~ m m m m ~ m ~ m w w
                                                            ........................................
                                                            a o o o o o o o o o o o o o o o o o o o o o o o o o ~ ~ m m m m m ~ m m m m m m
                                                            a                                                                      oa.4-.3-.4-.-.4444.4
                                                            C
aoooooooooooooooooooooooooooooo~ooooo~oo
                                                            >.......................................
                                                            a o o o o o o o o o o ~ o o o o ~ o o o o o o o o o o o c u ~ m m c ~ ~ m m m m o
                                                            ~ o o o o o o o o o o o o o o o o o o o o o o o o o m u ~ - - ~ - m m o ~ ~ - ~Y-
                                                            z                                                                      3 4                                 7
                 m
                 - . m c
                 4     c
                                I
                                -
                                                            -I
                                                                                                                                                                       a
                                                                                                                                                                       U
                 I . .
                 a
                       m v l
                       u        a
                                                            ........................................
                                                                 000000000000000000000000000000000000000
                                                                                                                                                                       5
a
I-
                 rr
                 w
                 O
                 u
                      I -
                       a
                            u
                                >
                                    .       m
                                                ~
                                                a
                                                o
                                                            -
                                                            - J 0 0 ~ 0 0 0 0 0 0 0 0 0 0 0 0 3 0 0 0 0 0 3 c J 0 0 0 3 0 3 7 0 0 0 0 0 0 0 0 ~
                                                            -7
                                                            n
                                                            m
n                n     o        m               2
I-
3
                                                *
                                                c           ...........................................
                                                              ooooooooooooooooouoo3ocoooooo~oo~o3oooo
                                                            - J o o o o o o o o o o o o o o o v o 0 o o o o o o o 3 o o o o o o o 0
a
Z
-
     I
     u
            2
            Lu
                       U'
                       Y
                                                0)
                                                4       -
                                                            -
                                                            J
     I-
     vl
            C
            m
                       -
                       I-
                       I-
                                                r
                                                3
                                                            o
                                                                               - --                                  --
     >
     m
     -I
     4
     U
     I
            >
            U)
            -
            a
            U
                       z - l -
                       I
                       0
                       U
                       m
                            U
                                3
                                .
                                        )
                                                L
                                                X
                                                4                - -
                                                              .t w > o c )m
                                                              n 0' CF
                                                                                j       r~ c f i r - .D N IC OY, c
                                                                                                                 .   P      1 o o o o 3 D 13 o a o o 3 o o
                                                                                                                          r~c
                                                                 o 7 m v in P Q N a m NU\m o' mm m 0 ffi a N U m r- ? a o o LP in o o LT in LP U- in U-
                                                                        a ( P O m 3 .t in m c IC. m m CF 01 IP .+ (c m Q -* -4 o o 0 ~nc c m a c e c c c r-
                                                            x . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
                                                                 .+
                                                                 0 3 3 N 0 0 .c: m 3 1 3 Ia Im .t m 0 3 0 m U v 0 c J. m 0 I           n .D . D U I in in VI m in in
     U      U          3
                       m        Y
                                u               I                                                      N N         N N m I U Y
     +      C                   Q           U       I
                       *    -       I       m
     2-     2          -        n           e
     2I
     U
     c
     z
     a
     a
     -I
103
Authorized licensed use limited to: IEEE Xplore. Downloaded on November 08,2014 at 04:51:47 UTC from IEEE Xplore. Restrictions apply.
           IEEE
           Std 399-1980                                  INDUSTRIAL AND COMMERCIAL POWER SYSTEMS ANALYSIS
                                                0.C     JEGREE
                                                         GENElATICN                5.32      VU             2.lb WAR
                                                5.32     Yk          2.16         YVAR            5.75     HVA  LGSSES =            0.02   Mn     0.1E   WAR
                                                         T D 4 N S F C d H E S T 4 P 49.30        KV       13.20 KV
                                                                              R J S ERAOR                0.00    #VI         0.90   WAR
                                                 '.4 3 E G R E i
                                               - ~ . 9 i MU     -5.03 Y V A R         11.14 V V A             =    Lrss=s           2 . 0 0 MY    5.71   MVAR
                                                         T~ANSFLRUFR T L P      13.90 K V       69.05 KV
                                                1.52     MA       3.93 H V A Q         i . e i M V A LPSSES =                       O.JO   wu     0.00   WAR
                                                4.54     Y i      3 . 3 7 YVAR         5.4d     CVA    LPSSES =                     0.01   YW     0.00   MVAR
                                                i.tl     4n       0.9*     YVAF        2 - 7 0 MV4     CCSSES =                     0.00   YW     0.00   MVLR
                                                1.24     NW       3. 34 MVAP           1.24 MVA L O S S F S =                       0.00   MU     3.00   MVAC
                                                                         qUS E*AClR           0 . 5 3 HU     v.33                   CVAh
                                               -1.t     JEG'I"
                                               -E.>b Uh          -1.99 * V A P            5.bC Y V A       LGSSES =                 J.02   Ubi    0.1E   WVAF
                                                          TF4hS=CPME3 TAD       1 3 . E ~ KV      h i . J J KL
                                                 1.14 Y n         2 . ~ 7 YVAR            2.72 W 4         LOSSES                   0.00 Mh       J.00   WAF
                                                 7 . 1 : 1.1     -5.4'1 u v A a           e.ce W A         LOSSZS =                 u.01 v h      J.01   MVbP
                                                 3.24 Y.4         2.14 Y V 4 Q            2.80 M V A L O S S E S =                  0.31 MW       0.00   MVAR
                                               -t.14 Y *          2 - 7 3 HVAR            5.74 Y V A       LGSjcS =                 3.05 YW       3.03   YVAQ
                                                                        3JS E P 9 J P         - 3 . l J VU      -3.91               WAF
                                                +.A     DzLake
                                               -1.52     *d       -0.93 UVAK                      1.31 W A          LCSSCS =        3.Od M k      J.00   HVAQ
                                                 1.52    *m        i.97 F V I R                   1.80 M Y 4        LCSSES          0.02 Y h      0.12   YVA"
                                                         TQA'!SFO?MER T A P     13.80             KV        *.lb        KV
                                                                       9US E F a O R                      0.30   Mk          0.01   HVA'
                                                 4.+ DCGPFE
                                               - 6 . 5 3 Yn         -3.34     dVAE      5.47               MVA      LOSSFS =        0.01   Mn     0.00 MVA9
                                                  1-25 9h             C.39    YVAQ      1.52               WVA      Lnsscs =        0.01   w      0.59 YVAR
                                                         TKA\j=O2MER         T13   13.U~KV                  2.40        <V
                                                 3.27    Ma           7 - 1 6 MVAG      3.92               nVA      LPSSE.2 =       0.03 CW       3.51 W A R
                                                                             B J S ER4OK                 -0.00     hk      0.01     YVA4
                                               -1.5     0Fr.2EC
                                               -l.l+     Yrl        -2.47      NVAR               7.72     MVA      LGSSES    =     0.00 YU       0.90 MVbG
                                                 0.61 Y.4            5.45      NYAC               3.75     PVA      LPSSES    =     0.00 M Y      0.QO WVAR
                                                 2 - 5 5 yh           2.32     cvp:,              2.09     MVA      LCSSES    =     0 . 0 0 r(n   0.dO WVAQ
                                                                        Fig 52
                                                               Printed Computer Output
104
Authorized licensed use limited to: IEEE Xplore. Downloaded on November 08,2014 at 04:51:47 UTC from IEEE Xplore. Restrictions apply.
                                                                                                                IEEE
    LOAD FLOW STUDIES                                                                                    Std 399-1980
    system data, or the system base might be                      A case is defined as system power flow
    too large or too small for the computer                       in all branches for given system data. It
    t o accurately represent the numbers in-                      represents a balanced stable flow of
    volved. Short, low impedance lines in                         power distributed throughout the system
    close proximity with long lines usually                       t o satisfy Kirchhoff’s laws and the law of
    make convergence more difficult.                              conservation of energy. Current flow in-
       A load flow program requires at least                      t o a point is equal t o that flowing out of
    one swing bus. This is a bus designated                       the point (within an allowable small
    by the user as a bus on which system                          tolerance) and bus voltages and line drops
    losses or excess power can be handled.                        are compatible throughout the system.
    Most programs also allow for a tie inter-                        When analyzing a system load flow it
    change or transfer of power from one                          should be noted that the real power
    system t o another. Problems of converg-                      (watt) is flowing in one direction from a
    ing t o a solution can occur in some pro-                     given bus t o another, while the imaginary
    grams when zero impedance or high                             power (var) is flowing in the opposite
    impedance lines are entered. Usually                          direction. This results from votlage on
    special handling is required for these                        the second bus being greater than on the
    lines and the methods can vary with dif-                      given bus. The real power must flow to
    ferent programs.                                              the load, but t o equalize the voltage,
       As mentioned briefly in 5.4.2, change                      reactive power must flow in the opposite
    cases can be run with only minor input                        direction.
    changes on most programs. The usual                              Proper transformer tap settings can re-
    procedure is to run a base case, usually                      duce or change this condition. Many
    an existing operating condition, which is                     load flow programs have an automatic
    checked against known conditions for                          tap changing feature that changes taps t o
    accuracy. Then by changing, adding, or                        minimize reactive flow. Remember that
    omitting lines, changing loads, and equip-                    var flow can be controlled by tap chang-
    ment, &, dimige cases c a i be pun con-                        ing and that reactive power will flow
     secutively as desired. In more sophisti-                      from the bus with greater (relative) volt-
     cated programs, provision is made for a                      age. The taps must be selected t o equalize
     data base where system parameters                            this difference when done manually. Real
     (equipment sizes, line impedances, bus                        power (watt) will flow t o the load by the
     numbers, loads, transformer sizes, volt-                      difference of the phase angle of the
     ages, ratios, taps, etc) are all stored for
                                                                   supply leading the phase angle of the
     use in short circuit programs, load flow                     load bus.
     programs, and stability programs. The
                                                                     It must be stressed that input data t o a
     stored parameters provide data for the
                                                                   load flow must be real values and as
     base case. Then changes are made by
                                                                   accurate as possible. Rounding off, or
     temporarily substituting the change data
                                                                   not including enough decimal places in
     for the permanently stored data for a
     change case. Most programs using a data                       certain parameters can be disastrous t o
     base allow for retaining any specified                        the results in many cases. Do not ignore
     case, which can become the base case for                      influential parameters. Results are no
     future changes if desired.                                    better than input.
                                                                     The study of several such cases of a
     5.7 Load Flow Analysis. A load flow                           system, under the various operating con-
     study usually consists of several cases.                      ditions specified, leads t o a knowledge of
105
Authorized licensed use limited to: IEEE Xplore. Downloaded on November 08,2014 at 04:51:47 UTC from IEEE Xplore. Restrictions apply.
        IEEE
        Std 399-1980                         INDUSTRIAL AND COMMERCIAL POWER SYSTEMS ANALYSIS
        expected performance and behavior.                            illustrates this method using case 1 load
        Recognition of, and the appreciation for                      flow results. In the illustration all perti-
        performance and behavior of the system                        nent system data for equipment and
        under desired conditions is defined as a                      operating conditions are entered 011 the
        load flow analysis.                                           system one-line diagram. From the load
           A load flow analysis is used to deter-                     flow report output, then bus voltage,
        mine optimum bus voltages for normal                          voltage angle, load kW and kvar, capa-
        operation, and yet continue t o furnish                       citor kvar, etc are entered. By each inter-
        reliable flows through alternate branches                     connecting line (transmission line) the
        when one or more lines become inopera-                        kW and kvar flowing in the line is
        tive due to line damage, lightning strokes,                   entered. Note that arrows are drawn t o
        failure of transformers, etc. The study of                    show direction of real power. Reactive
        multiple load flow cases and analysis of                      power then carries a positive (+) sign
        the results provide operating intelligence                    when it is flowing to the same bus as real
        in a short time that might take years of                      power. When flowing in the opposite
        actual operating experience to obtain.                        direction a minus (-) sign is shown.
           In addition t o optimum bus voltages, a                    Where sizeable line loss occurs, power
        study of reactive power flows in the                          leaving the bus is shown near that bus,
        branches can lead t o reduced line losses,                    while power arriving at the receiving bus
        improved voltage distribution, and less                       is shown near it with power loss indi-
        var supply equipment. Transformer and                         cated near the center of the line. At a
        line capacities are related to their maxi-                    convenient location on the drawing, or
        mum load flow requirements thus pre-                          on a facing page in the analytical report,
        venting burnout from overloads or ad-                         comments can be entered as t o good or
        verse conditions. Transformer tap settings                    poor conditions, or both, that exist in
        should be optimized to reduce reactive                        circuit parameters or configuration. It is
        var flows t o a minimum for practical                         desirable to list corrective action taken
        operation. Knowledge of branch power                          for the next load flow run t o hopefully
        flow supplies the protection engineer                         improve the operation.
        with requirements for proper relay set-
        tings t o ensure normal operation and can                     5.9 Load Flow Analysis. Now that a load
        provide data for automatic load and de-                       flow has been run for conditions that
        mand control if needed.                                       exist, what has been learned about the
                                                                      system, and what can be done t o improve
        5.8 Load Flow Output Presentation.                            the operation? Analysis of load flow out-
        Maximum benefit results from a com-                           put now presented on the one-line dia-
        puter output report when power flows                          gram shows the following:
        are graphically shown on a one-line dia-
        gram of the system. System flows can be                          (1)Voltage on bus 3 is low - 13.3,
        quickly analyzed from this visual pre-                        while voltage on bus 4 is 13.62
        sentation which relates system configura-                        (2) Inspection of all bus voltages sup-
        tion, operating conditions, and equip-                        plied from main bus 3 are relatively low
        ment parameters t o an ideal or optimum                          (3) Voltage on bus 39 is too low for
        operation. Another system one-line dia-                       good operation. This is due partially to
        gram is used t o enter the case load flow                     low voltage on bus 3
        results in much the same way the imped-                          (4) Generator 1 is absorbing vars when
        ance diagram was prepared. Figure 53                          it should be supplying vars t o the system
106
Authorized licensed use limited to: IEEE Xplore. Downloaded on November 08,2014 at 04:51:47 UTC from IEEE Xplore. Restrictions apply.
                                                                                                                IEEE
     LOAD FLOW STUDIES                                                                                   Std 399-1980
COOP.
                                             -
                                                                          '
                                                                          a:
                                                                          I
107
Authorized licensed use limited to: IEEE Xplore. Downloaded on November 08,2014 at 04:51:47 UTC from IEEE Xplore. Restrictions apply.
        IEEE
        Std 399-1980                        INDUSTRIAL AND COMMERCIAL POWER SYSTEMS ANALYSIS
108
Authorized licensed use limited to: IEEE Xplore. Downloaded on November 08,2014 at 04:51:47 UTC from IEEE Xplore. Restrictions apply.
                                       6. Short-circuit Studies
    6.1 Introduction. Even the most carefully                    voltage levels in the overall system for
    designed power systems are subject t o                       short circuits in specific areas
    damaging effects of high magnitude cur-                        Details of fundamental concepts in-
    rents flowing from short circuits occur-                     volved in the rigorous calculation of
    ring in system components. To ensure                         short circuit currents are included in
    that circuit protective equipment can                        Section 3. Simplifying techniques and
    isolate faults quickly and minimize dam-                     their limitations, and step-by-step pro-
    age and personnel hazard, it is essential                    cedures t o follow for manual short
    that a short circuit analysis be included                    circuit calculations are given in [ l ] and
    in the electrical design of new plants and                    PI   *
    also for modifications t o existing plants.                     The intent of this section is t o comple-
      A power system short circuit analysis                      ment these sources by providing a brief
    can be used t o determine any or all of                      overview of the steps required t o per-
    the following:                                               form a short circuit study and then
       (1)Calculated system fault current                        illustrate how the computer can be used
    duties which can be compared with the                        as an effective tool t o aid in the calcula-
    first cycle (momentary) and interrupting                     tions.
    short circuit current rating of circuit in-
    terrupting devices, such as circuit break-                   6.2 Short-circuit Study Procedure
    ers and fuses                                                  6.2.1 Preparing a One-Line Diagram.
       (2) Calculated system fault current du-                   The starting point in performing a short-
    ties t o compare with short-time, or with-                   circuit study is the preparation of a basic
    stand ratings of system components such                      system one-line diagram. Accuracy and
    as cables, transformers, reactors, etc                       usefulness of study results depends
       (3) Selection and rating or setting of                    mainly on the reliability of this diagram.
    short circuit protective devices, such as                    All major components such as motors,
    direct-acting trips, fuses, and relays                       transformers, reactors, generators, utility
       (4)Evaluation of current flow and                         supplies, feeder cables and ducts, and
109
Authorized licensed use limited to: IEEE Xplore. Downloaded on November 08,2014 at 04:51:47 UTC from IEEE Xplore. Restrictions apply.
         IEEE
         Std 399-1980                        INDUSTRIAL AND COMMERCIAL POWER SYSTEMS ANALYSIS
110
Authorized licensed use limited to: IEEE Xplore. Downloaded on November 08,2014 at 04:51:47 UTC from IEEE Xplore. Restrictions apply.
Authorized licensed use limited to: IEEE Xplore. Downloaded on November 08,2014 at 04:51:47 UTC from IEEE Xplore. Restrictions apply.
        IEEE
        Std 399-1980                         INDUSTRIAL AND COMMERCIAL POWER SYSTEMS ANALYSIS
         recommendations for system changes (in                       used in all other steps in the develop-
         the case of existing plants) or for initial                  ment of a system short-circuit study.
         design (in the case of new plants).                          Various programs are available which can
            General guidelines for interpretation                     be used for:
         and application of study results are usu-                      (1)Complex short-circuit studies using
         ally not very useful since sound engineer-                   fundamental circuit analysis
         ing judgment can only be made on the                           (2) Short-circuit studies using simplify-
         basis of treating each case individually.                    ing techniques for specific use studies
         Some important questions t o ask, how-                          (3) Only certain aspects of a study
         ever are:                                                       Some of the most common uses rang-
           (1)Is circuit interrupting equipment                       ing from simplest t o most complex are:
         adequately rated for maximum short                              (1)Reduction of a number of system
         circuit momentary and interrupting                           impedances in series or parallel, or both,
         availability? If not, what is the most                       to a single equivalent impedance value
         economical method of making system                              ( 2 ) Calculation of Y or A equivalent
         changes while still maintaining a satis-                     impedances to assist in impedance reduc-
         factory degree of system flexibility?                        tion
            (2) Is there any short-circuit capability                    (3) Simple calculation of three-phase
         margin for future expansion? If not, is it                   faults. No load flow data is required t o
         necessary? If it is necessary, what is the                   establish initial conditions for input t o
         most suitable method of effecting                            the short circuit program. Output gives
         changes t o the system?                                      total fault E/X current, line currents to
            (3) Is non-interrupting equipment such                    faulted buses and system voltages.
         as reactors, cables, interrupting equip-                        (4)Calculation of three-phase short
         ment bus systems, bus duct, overhead                         circuit duties for use in comparing with
         lines, transformers, etc, adequately rated                   interrupting device ratings. No load flow
         to withstand short-circuit current until                     data required (see (3)). Output gives
         cleared by circuit interrupting equip-                       total fault E/X current, line current
         ment?                                                        flows from other selected buses, X / R
            (4)Is special protective equipment or                     ratio values, and applies appropriate
         circuitry necessary to provide protective                    multipliers t o fault values t o allow direct
         device selectivity for both maximum and                      comparison with interrupting device rat-
         minimum values of short-circuit current?                     ings based on applicable American Na-
            (5) Does voltage of unfaulted buses in                    tional Standards.
         the system drop to values which will                            (5) Calculations of three-phase, line-to-
         cause motor-starter contactor drop out                       line, and line-to-ground short circuits in
         or unnecessary operation of undervolt-                       either simple or complex systems. Load
         age relays? If so, is special equipment                      flow data is required for input t o estab-
         necessary t o prevent a total system                         lish initial conditions. Output gives posi-
         outage?                                                      tive, negative, and zero sequence line
                                                                      currents, and system voltages.
         6.3 Use of the Computer. With the ex-                           For most computer programs, user
         ception of system one-line diagram de-                       manuals are available for assistance in
         velopment and selection of impedance                         transferring information contained on
         values for individual system components,                     the one-line diagram and the impedance
         computer short-circuit programs can be                       diagram t o a form which can be accepted
112
Authorized licensed use limited to: IEEE Xplore. Downloaded on November 08,2014 at 04:51:47 UTC from IEEE Xplore. Restrictions apply.
                                                                                                                IEEE
    SHORT-CIRCUIT STUDIES                                                                                Std 399-1980
113
Authorized licensed use limited to: IEEE Xplore. Downloaded on November 08,2014 at 04:51:47 UTC from IEEE Xplore. Restrictions apply.
         IEEE
         Std 399-1980                         INDUSTRIAL AND COMMERCIAL POWER SYSTEMS ANALYSIS
114
Authorized licensed use limited to: IEEE Xplore. Downloaded on November 08,2014 at 04:51:47 UTC from IEEE Xplore. Restrictions apply.
                                                                                                                 IEEE
    SHORT-CIRCUIT STUDIES                                                                                 Std 399-1980
                                                  Table 9
                                       Assumed Values for Motors when
                                       Exact Impedances are not Known
                       Induction motor                                1 hp = 1 kVA
                       Synchronous motor, 0.8 PF                      1 hp = 1 kVA
                       Synchronous motor, 1.0 PF                      1 hp = C.8 kVA
                       Lumped induction motors not greater            Xz = X1,= 0.25 per unit
                         than 600 V
                       Individual induction motors greater            X;; = XI,= 0.17 per unit
                         than 600 V
                       Synchronous motors not less than               X;; = 0.15 per unit
                         1200 r/min
                       Synchronous motors less than 1200              % = 0.20 per unit
                         r/min but greater than 450 r/min
                       Svnchronous motors 450 r/min and less          x1: = 0.28 Der unit
                       NOTE: Motor impedances are in per unit on motor kVA rating.
                       Reactances and motor base kVA ratings listed above were taken
                       from data and assumptions in [ 11.
                                          Table 10
             Modification Factors for Momentary and Interrupting Duty Calculations
                                                             Impedance Value for
                                                           Medium and High Voltage
                                                               Calculations per     Impedance Value for
        Duty                                               ANSI/IEEE C37.010-1979 Low Voltage Calculations
     Calculation        System Component                    and ANSI C37.5-1979 ANSI/IEEE C37.13-1980*
   First cycle    Utility supply                                   4                                 4
     (momentary) Plant generators                                  X;                                X;;
     calculations Synchronous motors                                %                                X;;
                      Induction Motors
                        Above 1000 hp > 1200 r/min                  X;;***                           X;;***
                        Above 250 hp > 1800 r/min                   X;;***                           x;***
                        All other motors
                          50-1000 hp                                1.2  x;***                       X;;***
                          Less than 50 hp                           neglect                          X;;***
   Interrupting       Utility supply                                4                                **
     calculations     Plant generators                              X;                               **
                      Synchronous motors                            1.5 X$                           **
                      Induction Motors
                        Above 1000 hp > 1200 r/min                  1.5 Xi***                        **
                        Above 250 hp > 1800 r/min                   1.5 X;***                        **
                        All other motors
                         50-1000 hp                                 3 xi***                          **
                          Less than 50 hp                           neglect
     *Impedance ( 2 )values can be used for low voltage breaker duties.
    **Not applicable.
   ***X&,for induction motors = locked rotor reactance.
115
Authorized licensed use limited to: IEEE Xplore. Downloaded on November 08,2014 at 04:51:47 UTC from IEEE Xplore. Restrictions apply.
        IEEE
        Std 399-1980                        INDUSTRIAL AND COMMERCIAL POWER SYSTEMS ANALYSIS
                                      a
                                      I
                                      0
116
Authorized licensed use limited to: IEEE Xplore. Downloaded on November 08,2014 at 04:51:47 UTC from IEEE Xplore. Restrictions apply.
                                                                                                               IEEE
   SHORT-CIRCUIT STUDIES                                                                                Std 399-1980
                             d
                             ul
                             m
                                       t
                            rcl
                            IJl
                                                                 $
                                                                 a I
                                                           117
Authorized licensed use limited to: IEEE Xplore. Downloaded on November 08,2014 at 04:51:47 UTC from IEEE Xplore. Restrictions apply.
         IEEE
         Std 399-1980                             INDUSTRIAL AND COMMERCIAL POWER SYSTEMS ANALYSIS
          XinterruDtine.=
                 .   -
                         1.5
                             9.1
                             (see Table 10) 2.20
                                                                       Xmomentary =      0.28 - -
                                                                                              loo= 1 4
                                                                                              2.0
                       = 3.30
                         3.30 - 3.30 - o.094                               (b) 1.75 MVA of induction motors
          enterrupting - x/R      35                                   between 50 hp and 1000 hp
                                                                       tary impedance
          Xmomentary   = 0.28 -  loo= 1 4
                                 2 .o
          Xinterrupting= 1.5 1 4 = 21                                                      -   14       9.7 = 5.73
                          21     21
          Rinterrupting- x / R - 25 - 0.84
                                                                       Xmomentary total    - 1 4 + 9.7
118
Authorized licensed use limited to: IEEE Xplore. Downloaded on November 08,2014 at 04:51:47 UTC from IEEE Xplore. Restrictions apply.
                                                                                                               IEEE
   SHORT-CIRCUIT STUDIES                                                                                Std 399-1980
                 -
                 -     0.25 * 100                               rupting duty with its associated multiply-
   &omentan
                   total motor MVA                              ing factor
                 - 0.25 100
                 -         -                                       (5) Symmetrical and asymmetrical cur-
                       1.5                                      rent for breaker momentary duty
                 = 16.7                                            (6) Local and remote fault contribu-
                 - 16.7 - 1.85
                                                                tions.
   Rmomentary        9                                             To arrange system data contained on
                                                                the impedance diagram so it can be ac-
   NOTE: Interrupting impedances are generally                  cepted by the computer program, it is
   not applicable for low voltage calculations.
                                                                necessary t o make up an input data tape
                                                                for medium voltage momentary calcula-
     For the example all motors and the                         tion, medium voltage interrupting calcu-
   generator are assumed t o be operating.                      lation, and low voltage calculation. Fig-
   This creates the highest possible short                      ure 56 shows the data arranged for typ-
   circuit currents the equipment may be                        ing paper input data tape for medium
   subjected t o since total short-circuit cur-                 voltage interrupting calculations.
   rents from all system motors, generator,                        Input data tape is a paper tape which,
   and utility connection are present. Note,                    when fed into the computer, becomes a
   however, that the 13.8 kV bus tie is                         file for data storage. Change cases can
   normally open and always will be unless                      then easily be run by modifying data
   one utility transformer is out of service.                   lines in the file. The data file must be
   If the tie breaker were closed for normal                    given a name. In this sample study the
   operation the fault duty would be more                       data file name for medium voltage inter-
   severe and the study would be based on                       rupting calculation is CSP 100.
   this operating mode.                                            Figure 57 shows the program listing of
     The example study does not inchide                         input data from data file CSP 100. Data
   prefault steady-state load currents. The                     is usually listed in this way so it can be
   effect of system load currents is usually                    checked for errors before proceeding
   negligible in short-circuit current studies                  with short circuit calculations.
   for industrial and commercial power                             Figure 58 is a sample of the computer
   distribution systems.                                        output for the medium voltage interrupt-
                                                                ing case giving remote bus voltages in per
   6.5 Digital Computer Program Output                          unit of normal voltage, and short-circuit
   Records                                                      contributions in MVA.
     (1)Total and symmetrical short-circuit                        Figure 59 is computer output showing
   current duty at the faulted bus t o com-                     total fault level in MVA at each faulted
   pare directly with circuit breaker capa-                     bus, and also contributions from all con-
   bility                                                       necting buses.
     (2) Short-circuit contributions from all                      Also shown are X I R ratios a t the faulted
   buses connected t o the faulted bus or                       bus, multipliers taken from the standards
   between any other two buses specified in                     t o apply t o the E/X values for both 8
   the input, or both                                           cycle and 5 cycle breakers, and the fault
     (3) Voltage at the remote buses where                      duty for direct comparison with the cir-
   fault contributions are specified by (2)                      cuit breaker rating. Remote (in this case
     (4)System X / R ratio at the fault point                   the utility system), and local (in this case
   for medium voltage circuit breaker inter-                    the in-plant generator), sources of short
119
Authorized licensed use limited to: IEEE Xplore. Downloaded on November 08,2014 at 04:51:47 UTC from IEEE Xplore. Restrictions apply.
          IEEE
          Std 399-1980                                INDUSTRIAL AND COMMERCIAL POWER SYSTEMS ANALYSIS
                                            + -
             LINE NUMBER                FOR TAPE                                            /=IInput            d a t a t o be l i s t e d
                                                                    -           __     --
                                                                                       __--
              +
                                                                .
                                                                           --                 -
              I
             10     JX AND
                                F
                               R RED,
                                                     I
                                               CHECK, YES*, 100 4------- S t u d y Base MVA
                                                                                                         Qemote b u s i n f o . t o h e p r o v i d e d
                         -
              184 0 , 3 6 , . 2 9 1 , 1 0 . 2
              185 0 , 3 7 , 1 1 . 9 , 1 0 7
              186 0 , 3 9 , . 4 9 , 1 4 . 6
              230 0,O                                  End o f d a t a f i l e
                                                   Fig 56
                          Data Taken from the Impedance Diagram and Arranged €or
                    Program Input Data Paper Tape Medium Voltage Interrupting Calculation
Authorized licensed use limited to: IEEE Xplore. Downloaded on November 08,2014 at 04:51:47 UTC from IEEE Xplore. Restrictions apply.
                                                                                                               IEEE
   SHORT-CIRCUIT STUDIES                                                                                Std 399-1980
            P R I N T A L L B U S E S ? no
              3 C Y C . MF FOR WHICH 5 B U S E S ? 3,4,24,19,0
            P R I N T A L L B U S E S ? no
              3 C Y C . MF FOR WHICH 5 B U S E S ? O,O,O,O,O
                                                                        --            ONLY SELECTED FAULTED
                                                                                      BUSES ARE CONSIDERED IN
                                                                                      THIS EXAMPLE STUDY
            P R I N T A L L B U S E S ? NO
            I N P U T 5 B U S NUMBERS? 3,4,24,19,0
                                                  Fig 57
                              Program Listing of Input Data from Data Tape
                                                               121
Authorized licensed use limited to: IEEE Xplore. Downloaded on November 08,2014 at 04:51:47 UTC from IEEE Xplore. Restrictions apply.
          IEEE
          Std 399-1980                            INDUSTRIAL AND COMMERCIAL POWER SYSTEMS ANALYSIS
                  REMOTZ L I N E ? 40,2
                  CONTRIBUTION FROM     40                (    0.854       V)   TO           2 ( 0.856 V ) = 4.59                 XV.4
                  RENOTE L I N E ? 2,4
                  CONTRIBUTION FROM               2   ( 0.856 V )               TO       4 ( 0.88 V ) = 4.59                 >!VA
                  RENOTE L I N E ? 3,15
                  CONTRIBUTION FROM     4             (       0.8b    V ) TO         1 5 ( 0.88 V ) = 0.676                   YVP
                  REMOTE L I N E ? 4,7
                  CONTRISUTION FROM               4 ( 0.88            V) TO          7       (       U.879 V ) = 13.283           YVA
                  REMOTE L I N E ? 4,8
                  CONTRIBUTION FROM               4 ( 0.88            V ) TO         6 ( 0.8d V ) = 3.627                    PlVA
                  REMOTE L I N E ? 4,24
                  CONTRIBUTION FROM     4             (       0.88    V) T U         24 ( 0.889                V ) = 13.372         MVA
                  REMOTZ L I N E ? 1U,27
                  CONTRIBUTION FROM    1 0 ( 0.877                         V) TO             27 ( 0.677           V ) = 0.154        ?lVA
&EMOTE L I N E 1 0.U
               SUS p  FAULTED     ? 4
                  REMOTE L I N E ? 4U,1
                  CONTRIBUTION FROM     40                (    0.843       V) T O            1 ( 0.84          V ) = 8.233        YVA
                  REMOTE L I N E ? 40.2
                  CONTRIBDTION FROI.1   40                (    0.843       V) T O            2 ( 0.793          V ) = 148.691            MVA
                  REMOTE L I N E       ? 1,3
                  CONTAIBUTION         FROM       1   (       0.84    v)    TO       3 ( 0.796 V I = a.233                    YVA
                  REMOTE L I N E ? 3,5
                  CONTRISUTION FROM               3 ( 0 . 7 Y 6 V ) TO                   5       (    0.796 V ) = 1.127           MVA
                  RE:4CTE L I N E ? 3,6
                  CONTRIBdTIOK FZOM               3 ( 0.796            V ) TO            6       (    0.797    V ) = 2.275        YVA
                  REMOTE L I N E          ? 3,9
                  C O N T R I B U T I O d FROM    3 ( 0.’96            V ) TO            9 ( 0.795 V ) = 5.724                    YVA
                  REMOTE L I N E ? 3,26
                  CONTRIBUTION FROM     3             (       0.796    V) T O            26 ( 0.795 V ) = 5.958                     ?lVA
                  REMOTE L I N E 1 1U,27
                  CONTRIBUTION FROI.1   10                ( 0.004          V) TO             27 ( 0.004           V)= 1 . 2 4 8      NVA
REMOTE L I N E ? 0.0
                                                     Fig 58
                             Sample Computer Output Listing of Remote Bus Voltages
                                and Short Circuit Contributions to the Faulted Bus
                              Medium Voltage Interrupting Case Short Circuit Study.
122
Authorized licensed use limited to: IEEE Xplore. Downloaded on November 08,2014 at 04:51:47 UTC from IEEE Xplore. Restrictions apply.
                                                                                                                 IEEE
   SHORT-CIRCUIT STUDIES                                                                                Std 399-1980
     RESULTS IN MVA
     BUS 3
     E/X= 183.915 MVA                X/R= 8.209
     MF FOR 8 CY(.O667 SEC. CONT. PART)TOT CB = 1 ,CB DUTY = 183.915
     IYF FOR 5 C Y ( . O ~ O OSEC. CONT. PARTISYM ca = 1 ,CB DUTY = 183.915
     CONTRIBUTION :
     BUS 1 = 150.613              BUS 5 = 5.5175       BUS 6 = 11.1686
     BUS 9 = 8.9544              BUS 26 = 7.6373
           B U S NO.  LOCAL(MVA)  REMOTE(MVA)                              GEN VOLTS
               40     0           146.023                                  0.854
               24     1.38        11.002                                   0.889
               REMOTE / REMOTE+LOCAL = 0.991
     BUS 4
     E/X= 312.053 MVA          X/R= 10.262
     M F FOR 8 CY(.O667 SEC. CONT. PART)TOT CB = 1 ,CB DUTY = 312.053
     MF FOR 5 CY(.0500 SEC. CONT. PART)SYM CB = 1 ,CB DUTY = 312.053
     CONT2IBUTION :
     BUS 2 = 148.69        BUS 7 = 14.4201       BUS 8 = 30.2067
     BUS 1 5 = 7.2972       BUS 24 = 111.437
            BUS NO.  LOCAL(MVA)   REMOTE(MVA)                               GEN VOLTS
               40     0           156.924                                   0.843
               24     95.827      7.359                                     0.071
               REMOTE / REMOTE+LOCAL = 0.632
     BUS  24
     E/X= 297.764 MVA         X/R= 21.523
     NF FOR b CY(.O667 SEC. CONT. PART)TOT CB = 1.048 ,CB DUTY = 312.087
     MF FOR 5 CY(.0500 SEC. CONT. PART)SYM CB = 1.018 ,CB DUTY = 303.103
     CONTRIBUTION :
     BUS 4 = 177.791       BUS 31 = 7.974       BUS 32 = 0.13721
     GEN = 111.111
            BUS NO.  LOCAL(MVA)   REMOTE(MVA)                               GEN VOLTS
               40    0            139.068                                   0.861
               24    111.111      0                                         0
               REMOTE / REMOTE+LOCAL = 0.556
      BUS   19
      E/X= 57.2469 NVA          X/R= 7.565
      M F FOR 8 CY(.0667 SEC. CONT. PART)TOT CB = 1 ,CB DUTY = 57.247
      MF FOR 5 CY(.OSOO SEC. CONT. PART)SYM CB = 1 ,CB DUTY = 57.247
      CONTRIBUTION :
      BUS 14 = 47.4432        GEN = 9.8039
            BUS NO.   LOCAL (MVA)  REMOTE (MVA)                             GEN VOLTS
               40      0           39.485                                   0.961
                24     0.101       3.247                                    0.97
                REHOTE / REMOTE+LOCAL = 0.998
                                         Fig 59
                      Computer Output Giving Fault Levels in MVA for
       the Four Faulted Buses, Medium Voltage Interrupting Case Short Circuit Study
123
Authorized licensed use limited to: IEEE Xplore. Downloaded on November 08,2014 at 04:51:47 UTC from IEEE Xplore. Restrictions apply.
          IEEE
          Std 399-1980                          INDUSTRIAL AND COMMERCIAL POWER SYSTEMS ANALYSIS
                                                 Table 11
                          Sample Summary of Results for Example Short Circuit Study
                                     Short Circuit Duty t o Compare
                                     Directly with Equipment Rating                         Voltage in Per Unit o n
                                                                                               Associated Buses
             Short                   Momentary             Interrupting                (Interrupting Case Calculations)
             Circuit                (first '/i cycle)        5 Cycle
            Location                   Asym kA              Sym MVA                  Bus1       Bus4        Bus3        Bus24
         13.8 kV
         Bus 3 ( F 3)                    13.4                  183.9                  0.80       0.88          0         0.89
         13.8 kV
         Bus 4 ( F 4 )                   22.7                  31 2                   0.84         .o        0.80         .o 4-
         13.8 kV
         Bus 24 ( F 24)                  21.4                  303                    0.86       0.11        0.82         .o
         2.4 kV
         Bus 19 (F 19)                   26.1                   57.2                  0.95       0.97        0.74        0.97
         480 V
         Bus 30 (F 30)                   68.9*            Not applicable              0.96       0.92        0.92        0.92
          circuit current are listed separately.                       [2] IEEE Std 242-1975, IEEE Recom-
            Table 11 shows a sample summary of                         mended Practice for Protection and Co-
          the short-circuit study results. Not all                     ordination of Industrial and Commercial
          computer output information is shown                         Power Systems.
          since it is not possible to clearly present
          this information on one table. Several                       [3] A N S I / I E E E C37.13-1980, I E E E
          tables might be necessary to present                         Standard for Low Voltage AC Power
          complete study results, or in some cases,                    Circuit Breakers Used in Enclosures.
          short circuit diagrams showing all system                    [4] ANSI/IEEE C37.010-1979, IEEE
          voltages and short circuit flows, provide                    Application Guide for AC High Voltage
          the best means of presenting study                           Circuit Breakers Rated on a Symmetrical
          results.                                                     Current Basis (Consolidated edition).
            Using the complete computer output
          information, study results can be ana-                       [5] ANSI/IEEE C37.5-1979, IEEE Guide
          lyzed and applied to specific equipment                      for Calculation of Fault Currents for
          shown on the one-line diagram.                               Application of AC High-Voltage Circuit
                                                                       Breakers Rated on a Total Current Basis
          6.5 References. The following references                     (Revision of ANSI C37.5-1969).
          were used in the preparation of Section
          6.                                                           [6] IEEE Transactions Paper 69TP146-
          [l]IEEE Std 141-1976, IEEE Recom-                            IGA Sep/Oct 1969, Interpretation of
          mended Practice for Electric Power                           New American National Standards for
          Distribution for Industrial Plants.                          Power Circuit Breaker Application.
124
Authorized licensed use limited to: IEEE Xplore. Downloaded on November 08,2014 at 04:51:47 UTC from IEEE Xplore. Restrictions apply.
                                 7. Transient Stability Studies
    7.1 Introduction. For years, system sta-                        7.2.2 Steady-State Stability. Although
    bility has been a problem almost exclu-                       the discussioli in the rest of this section
    sively t o electric utility engineers. Within                 revolves around stability under transient
    the past decade, however, increasing                          conditions such as faults, switching oper-
    numbers of industrial and commercial                          ations, etc, there should also be an aware-
    facilities have installed local generation,                   ness that a power system can become un-
    large synchronous motors, or both. This                     . stable under steady-state conditions.
    means that system stability is of concern                       The simplest power system t o which
    to a growing number of industrial plant                       stability considerations apply consists of
    electrical engineers and consultants.                         a pair of synchronous machines, one act-
                                                                  ing as a generator and the other acting as
    7.2 Stability Fundamentals                                    a motor, connected together through a
      7.2.1 Definition of Stability. Funda-                       reactance. See Fig 60. (In this model the
    mentally, stability is a property of a                        reactance is the sum of the transient
    power system containing two or more                           reactances of the two machines and the
    synchronous machines. The system is
    stable, under a specified set o f conditions,                                     Fig 60
    if all of its synchronous machines remain                                Simplified Two-Machine
    in step with one another (or having pulled                                   Power System
    out of step, regain synchronism soon
    afterwards). The emphasis on specified
    conditions in this definition is intended
    to stress the fact that a system which is
    stable under one set of conditions can be
    unstable under some other set of condi-                                                        G:
    tions.
125
Authorized licensed use limited to: IEEE Xplore. Downloaded on November 08,2014 at 04:51:47 UTC from IEEE Xplore. Restrictions apply.
          IEEE
          Std 399-1980                        INDUSTRIAL AND COMMERCIAL POWER SYSTEMS ANALYSIS
         mentarily slow down the rotor of a                            within the steady-state stability limits of
          synchronous motor to permit the rotor                        the system, an overshoot can result in
         field to fall farther behind the stator                       loss of synchronism. If not, both rotors
         field and thus increases 6,. The rate at                      will undergo a damped oscillation and
         which rotor speed can change is deter-                        ultimately settle t o their new steady-state
         mined by the moment of inertia of the                         values.
         rotor, plus whatever is mechanically                             An important concept here is syn-
         coupled to it, prime mover, load, reduc-                      chronizing power. The more real power
         tion gears, etc. This means a machine                         transmitted over the transmission link
         with high inertia is less likely to pull out                  between the two machines, the more
         under a disturbance of brief duration                         likely they are to remain in synchronism
         than a low-inertia machine, all other                         in the face of a transient disturbance.
         characteristics being equal.                                  Synchronous machines separated by a
            7.2.4 Two-Machine Systems. The pre-                        sufficiently low impedance behave as
         vious discussion of transient behavior of                     one composite machine, since they tend
         synchronous machines is based on a single                     to remain in step with one another re-
         machine connected to a good approxima-                        gardless of external disturbances.
         tion of an infinite bus. An example is the                       7.2.5 Multimachine Systems. At first
         typical industrial situation where a syn-                     glance, it appears that a power system in-
         chronous motor of at most a few thou-                         corporating many synchronous machines
         sand horsepower, is connected t o a utility                   would be extremely complex to analyze.
         company system with a capacity of                             This is true if a detailed, precise analysis
         thousands of megawatts. Under these                           is needed; a large digital computer and a
         conditions we can safely neglect the                          sophisticated program are required for a
         effect of the machine on the power                            complete transient stability study of a
         system.                                                       multimachine system. However, many of
            A system consisting of only two ma-                        the multimachine systems encountered
         chines of comparable size connected                           in industrial practice contain only syn-
         through a transmission link, however,                         chronous motors which are similar in
         becomes more complicated, because the                         characteristics, closely coupled electric-
         two machines can affect one another’s                         ally, and connected to a high-capacity
         performance. The medium through                               utility system. Under most types of
         which this occurs is the air gap flux. This                   disturbance, motors will remain syn-
         is a function of machine terminal voltage,                    chronous with each other, although they
         which is affected by the characteristics                      can all lose synchronism with the utility.
         of the transmission system, the amount                        Thus, the problem is similar to a single
         of power being transmitted, and the                           synchronous motor connected through
         power factor, etc.                                            an impedance to an infinite bus. The
            In the steady state, the rotor angles of                   simplification should be apparent. More
         the two machines are determined by the                        complex systems, where machines are of
         simultaneous solution of their respective                     comparable sizes and are separated by
         torque equations. Under a transient dis-                      substantial impedances, will usually in-
         turbance, as in the one-machine system,                       volve a full-scale computer stability study.
         the rotor angles move toward values
         corresponding to the changed system                           7.3 Problems Caused by Instability. The
         conditions. Even if these new values are                      most immediate hazards of asynchronous
128
Authorized licensed use limited to: IEEE Xplore. Downloaded on November 08,2014 at 04:51:47 UTC from IEEE Xplore. Restrictions apply.
                                                                                                               IEEE
   TRANSIENT STABILITY STUDIES                                                                          Std 399-1980
TORQUE
                                     PULLOUT TORQUE
                                                                      (MOTOR AC1
                                                Fig 61
                               Torque Versus Rotor Angle Relationship for
                                 Synchronous Machines in Steady State
  a pole. Unless the load torque is reduced                     a gradual change occurs in one or more
  below the 90" level (the pullout torque),                     of the parameters of the torque equation,
  the motor will continue slipping poles                        the rotor angle will tend t o overshoot the
  indefinitely. The problems that can fol-                      final value determined by the changed
  low from extended operation in this out-                      conditions. This disturbance can be severe
  of-step condition will be discussed further                   enough t o carry the ultimate steady-state
  in this section.                                              rotor angle past go", or the transient
    A generator operates similarly. Increas-                    swing rotor angle past 180". Either event
  ing torque input until the rotor angle                        results in the slipping of a pole. If the
  exceeds 90" results in pole slipping and                      conditions which caused the original dis-
  loss of synchronism with the power sys-                       turbance are not corrected, the machine
  tem, assuming constant electrical load.                       will then continue t o slip poles, in short,
    Similar relations apply to the other                        pull out of step with the power system
  parameters of the torque equation. For                        t o which it is connected.
  example, air-gap flux &R is a function of                        Of course, if the rotor angle overshoot
  voltage at the machine. Thus if the other                     does not transitorily exceed 180°,or if
  factors remain constant, a change in sys-                     the disturbance causing the rotor swing
  tem voltage will cause a change in rotor                      is promptly removed, the machine may
  angle. Likewise, changing the field excita-                   remain in synchronism with the system.
  tion will cause a change in rotor angle, if                   The rotor angle then oscillates in de-
  constant torque and voltage are main-                         creasing swings until it settles t o its final
  tained.                                                       value (less than 90"). The oscillations are
    The preceding discussion refers t o                         damped by mechanical load and losses in
  rather gradual changes in the conditions                      the system, especially in the damper
  affecting the torque angle, so that ap-                       windings of the machine.
  proximately      steady-state conditions                         A change in rotor angle of a machine
  always exist. The coupling between the                        generally requires a change in speed of
  stator and rotor fields of a synchronous                      the rotor. For example, if we assume
  machine, however, is somewhat elastic.                        that the stator field frequency is con-
  This means that if an abrupt rather than                      stant, it is necessary to at least mo-
127
Authorized licensed use limited to: IEEE Xplore. Downloaded on November 08,2014 at 04:51:47 UTC from IEEE Xplore. Restrictions apply.
              IEEE
              Std 399-1980                     INDUSTRIAL AND COMMERCIAL POWER SYSTEMS ANALYSIS
               mentarily slow down the rotor of a                     within the steady-state stability limits of
               synchronous motor t o permit the rotor                 the system, an overshoot can result in
               field t o fall farther behind the stator               loss of synchronism. If n o t , both rotors
               field and thus increases 6,. The rate a t              will undergo a damped oscillation and
               which rotor speed can change is deter-                 ultimately settle t o their new steady-state
               mined by the moment of inertia of the                  values.
               rotor, plus whatever is mechanically                      An important concept here is syn-
               coupled t o it, prime mover, load, reduc-              chronizing power. The more real power
               tion gears, etc. This means a machine                  transmitted over the transmission link
               with high inertia is less likely t o pull o u t        between the two machines, the more
              under a disturbance of brief duration                   likely they are t o remain in synchronism
              than a low-inertia machine, all other                   in the face of a transient disturbance.
              characteristics being equal.                            Synchronous machines separated by a
                  7.2.4 Two-Machine Systems. The pre-                 sufficiently low impedance behave as
              vious discussion of transient behavior of               one composite machine, since they tend
              synchronous machines is based o n a single              t o remain in step with one another re-
              machine connected t o a good approxima-                 gardless of external disturbances.
              tion of an infinite bus. An example is the                 7.2.5 Multimachine Systems. At first
              typical industrial situation where a syn-               glance, it appears that a power system in-
              chronous motor of a t most a few thou-                  corporating many synchronous machines
              sand horsepower, is connected t o a utility             would be extremely complex t o analyze.
              company system with a capacity of                       This is true if a detailed, precise analysis
              thousands of megawatts. Under these                     is needed; a large digital computer and a
              conditions we can safely neglect the                    sophisticated program are required for a
              effect of the machine on the power                      complete transient stability study of a
              system.                                                 multimachine system. However, many of
                  A system consisting of only t w o ma-               the multimachine systems encountered
              chines of comparable size connected                     in industrial practice contain only syn-
              through a transmission link, however,                   chronous motors which are similar in
              becomes more complicated, because t h e                 characteristics, closely coupled electric-
              two machines can affect one another’s                   ally, and connected t o a high-capacity
              performance. The medium through                         utility system. Under most types of
              which this occurs is the air gap flux. This             disturbance, motors will remain syn-
              is a function of machine terminal voltage,              chronous with each other, although they
              which is affected by the characteristics                can all lose synchronism with the utility.
              of the transmission system, the amount                  Thus, the problem is similar to a single
              of power being transmitted, and the                     synchronous motor connected through
              power factor, etc.                                      an impedance t o an infinite bus. The
                 In the steady state, t h e rotor angles of           simplification should be apparent. More
              t h e t w o machines are determined by the              complex systems, where machines are of
              simultaneous solution of their respective               comparable sizes and are separated by
              torque equations. Under a transient dis-                substantial impedances, will usually in-
              turbance, as in the one-machine system,                 volve a full-scale computer stability study.
              t h e rotor angles move toward values
              corresponding t o the changed system                    7.3 Problems Caused by Instability. The
              conditions. Even if these new values are                most immediate hazards of asynchronous
128
Authorized licensed use limited to: IEEE Xplore. Downloaded on November 08,2014 at 04:51:47 UTC from IEEE Xplore. Restrictions apply.
                                                                                                               IEEE
   TRANSIENT STABILITY STUDIES                                                                          Std 399-1980
   operation of a power system are the high                        (4)Starting a motor which is large
   transient mechanical torques and currents                     relative t o a system generating capacity
   which usually occur. To prevent these                           (5) Switching operations
   transients from causing mechanical and                          (6) Impact loading on motors
   thermal damage, synchronous motors                              (7) Abrupt decrease in electrical load
   and generators are almost universally                         on generators
   equipped with pullout protection. For                           The effect of each of these disturbances
   motors of small t o moderate sizes, this                      should be apparent from the previous
   protection is usually provided by a                           discussion of stability fundamentals.
   damper protection of pullout relay                            Items (1)through (5) tend t o reduce volt-
   which operates on the low power factor                        age levels, ultimately requiring an increase
   occurring during asynchronous operation.                      in machine angles t o maintain a given
   The same function is usually provided                         load. Items (6) and (7) directly increase
   for large motors, generators, and syn-                        the rotor angles of affected machines.
   chronous condensers by loss-of-field re-
   laying. In any case, the pullout relay                        7.5 Solutions t o Stability Problems. Gen-
   trips the machine breaker or contactor.                       erally, anything which decreases the
   Whatever load is being served by the ma-                      severity or duration of a transient dis-
   chine is naturally interrupted. Conse-                        turbance will make the power system
   quently, the primary disadvantage of a                        less likely t o become unstable under that
   system which tends t o be unstable is the                     disturbance. In addition, increasing the
   probability of frequent process inter-                        moment of inertia per rated kVA of the
   ruptions.                                                     synchronous machines in the system will
     Out-of-step operation also causes large                     raise stability limits by resisting changes
   oscillatory flows of real and reactive                        in rotor speeds required t o change rotor
   power over the circuits connecting the                        angles.
   out-of-step machines. Impedance or dis-                         7.5.1 System Design. System design
   tance-type relaying protecting these lines                    primarily affects the amount of synchro-
   can falsely interpret power surges as a                       nizing power that can be transferred
   line fault, tripping the line breakers and                    between machines. Two machines con-
   breaking up the system. Although this is                      nected by a low-impedance circuit such
   primarily a utility problem, large indus-                     as a short cable or bus run will probably
   trial systems or those where local genera-                    stay synchronized with each other under
   tion operates in parallel with the utility                    all conditions except a fault on the con-
   can be susceptible.                                           necting circuit, a loss of field excitation,
                                                                 or an overload. The greater the impedance
   7.4 System Disturbances that Can Cause                        between machines, the less severe a dis-
   Instability. The most common disturb-                         turbance will be required t o drive them
   ances that produce instability in indus-                      out of step. This means that from the
   trial power systems are (not necessarily                      standpoint of maximum stability all syn-
   in order of probability):                                     chronous machines should be closely
      (1)Short circuits                                          connected t o a common bus. Limitations
      (2) Loss of a tie circuit t o a public                     on short circuit duties, economics, and
   utility                                                       the requirements of physical plant lay-
      (3) Loss of a portion of on-site genera-                   out usually combine t o render this radical
   tion                                                          solution impractical.
129
Authorized licensed use limited to: IEEE Xplore. Downloaded on November 08,2014 at 04:51:47 UTC from IEEE Xplore. Restrictions apply.
         IEEE
         Std 399-1980                         INDUSTRIAL AND COMMERCIAL POWER SYSTEMS ANALYSIS
130
Authorized licensed use limited to: IEEE Xplore. Downloaded on November 08,2014 at 04:51:47 UTC from IEEE Xplore. Restrictions apply.
Authorized licensed use limited to: IEEE Xplore. Downloaded on November 08,2014 at 04:51:47 UTC from IEEE Xplore. Restrictions apply.
         IEEE
         Std 399-1980                         INDUSTRIAL AND COMMERCIAL POWER SYSTEMS ANALYSIS
            As additional data on the machines be-                     late line t o line or ground faults, the
         come available, better approximations                         effects of these faults on synchronizing
         can be used. This permits more accurate                       power flow can be duplicated by apply-
         results which remain reliable for longer                      ing a three-phase fault with a properly
         time periods. Modern large-scale stability                    chosen fault impedance. This means the
         programs can simulate all of the follow-                      effects of any type of fault on stability
         ing characteristics of a rotating machine:                    can be studied.
            (1)Voltage regulator and exciter                             In addition t o faults, stability programs
            (2) Steam system or other prime mover,                     can simulate switching of lines and gen-
         including governor                                            erators. This is particularly valuable in
            (3) Mechanical load                                        the load-shedding type of study, which
            (4)Damper windings                                         will be covered in the following section.
            (5) Salient poles                                             Finally, starting of large motors on
            (6) Saturation                                             relatively weak power systems and im-
         Induction motors can also be simulated                        pact loading of running machines can be
         in detail, together with speed-torque                         analyzed.
         characteristics of their connected loads.                        7.6.5 Data Requirements for Stability
            In addition t o rotating equipment, the                    Studies. The data required t o perform a
         stability program can include in its simu-                    transient stability study, and the recom-
         lation practically any other major sys-                       mended format for organizing and pre-
         tem component, including transmission                         senting the information for most con-
         lines, transformers, capacitor banks, and                     venient use are covered in detail in the
         voltage regulating transformers and dc                        application guides for particular stability
         transmission links in some cases.                             programs. The following is a summary of
            7.6.4 Simulation of Disturbances. The                      the generic classes of data needed. Note,
         versatility of the modern stability study                     that some of the more esoteric informa-
         is apparent in the range of system dis-                       tion is not essential; omitting it merely
         turbances that can be represented. The                        limits the accuracy of the results, espe-
         most severe disturbance which can occur                       cially at times exceeding five times the
         on a power system is usually a three-phase                    duration of the disturbance being studied.
         bolted short circuit. Consequently, this                      The more essential items are marked by
         type of fault is most often used t o test                     an asterisk (*).
         system stability. Stability programs can                         (1)System data.
         simulate a three-phase fault at any loca-                          (a) Impedances (R + jX) of all sig-
         tion, with provisions for clearing the                        nificant transmission lines, cables, reac-
         fault by opening breakers either after a                      tors, and other series components.*
         specified time delay, or by the action of                          (b) For all significant transformers
         overcurrent, underfrequency ,overpower,                       and autotramsformers
         or impedance relays. This feature permits                              (i) kVA rating*
         the adequacy of proposed protective                                   (ii) Impedance*
         relaying t o be evaluated from the stability                         (iii) Voltage ratio*
         standpoint.                                                          (iv) Winding connection*
            Short circuits other than the bolted                               (v) Available taps and tap in use*
         three-phase fault cause less disturbance                             (vi) For regulators and load tap-
         t o the power system. Although most                            changing transformers : regulation range,
         stability programs cannot directly simu-                      tap step size, type of tap changer control*
132
Authorized licensed use limited to: IEEE Xplore. Downloaded on November 08,2014 at 04:51:47 UTC from IEEE Xplore. Restrictions apply.
                                                                                                               IEEE
   TRANSIENT STABILITY STUDIES                                                                          Std 399-1980
        (c) Short circuit capacity (steady-                           (c) For major induction machines or
   state basis) of utility supply, if any*                       groups of machines
        (d) kvar of all significant capacitor                                (i) Mechanical and/or electrical
   banks*                                                        power ratings*
        (e) Description of normal and alter-                                (ii) Inertia*
   nate switching arrangements*                                            (iii) Speed*
      (2) Load data: real and reactive elec-                               (iv) Positive-sequence equivalent
   trical loads on all significant load buses                    circuit data (for example, R I , X I , X,,
   in the system*                                                R2, X2)*
      (3) Rotating machine data                                             (v) Load speed-torque curve*
        (a) For major synchronous machines                                 (vi) Negative-sequence equivalent
   (or groups of identical machines on a                         circuit data
   common bus)                                                            (vii) Description of reduced-voltage
               (i) Mechanical and/or electrical                  or other starting arrangements, if used*
   power ratings (kVA, hp, kW, etc)*                                   (d) For minor induction machines:
              (ii) Inertia constant H or inertia                 detailed dynamic representation not
   W K 2 of rotating machine and connected                       needed, represent as a static load
   load or prime mover*                                            (4) Disturbance data
            (iii) Speed*                                               (a) General description of disturb-
             (iv) Real and reactive loading, if                  ance t o be studied, including (as appli-
   base-loaded generator*                                        cable) initial switching status; fault type,
              (v) Speed-torque curve or other                    location and duration; switching opera-
   description of load torque, if motor*                         tions and timing; manufacturer, type,
             (vi) Direct-axis s u b t r a n si e n t ,*          and setting of protective relays and
   transient,* and synchronous reactances*                       clearing time of associated breakers*
            (vii) Qua-hature-axis subtransient,                        (b) Limits on acceptable voltage, cur-
   transient,* and synchronous reactances                        rent, or power swings*
           (viii) Direct-axis and quadrature-                       ( 5 ) Study parameters
   axis subtransient and transient* time                               (a) Duration of study*
   constants                                                           (b) Integrating interval*
             (ix) Saturation information                               (c) Output printing interval*
              (x) Potier reactance                                     (d) Data output required*
             (xi) Damping data
            (xii) Excitation system type time                       7.6.6 Stability Program Output. Most
    constants, and limits                                        stability programs give the user a wide
           (xiii) Governor and steam system                      choice of results t o be printed out. The
    or other prime mover type, time con-                         program can calculate and print any of
    stants, and limits                                           the following information as a function
         (b) For minor synchronous machines                      of time :
    (or groups of machines)                                         (1)Rotor angles, torques, and speeds
             (i) Mechanical and/or electrical                    of synchronous machines
    power ratings"                                                  (2) Real and reactive power flows
            (ii) Inertia"                                        throughout the system
           (iii) Speed*                                             (3) Voltages and voltage angles at all
           (iv) Direct-axis synchronous reac-                    buses
    tance*                                                          ( 4 ) System frequency
133
Authorized licensed use limited to: IEEE Xplore. Downloaded on November 08,2014 at 04:51:47 UTC from IEEE Xplore. Restrictions apply.
        IEEE
        Std 399-1980                         INDUSTRIAL AND COMMERCIAL POWER SYSTEMS ANALYSIS
          (5) Torques and slips of all induction                     disturbance applied. This is a reproduc-
        machines                                                     tion of an actual computer printout. A
          The combination of these results                           simplified one-line diagram of the system
        selected by the user can be printed out                      appears as Fig 63. Note that while the
        for each printing interval (also user-                       three-phase bolted fault on a synchronous
        selected) during the course of the study                     bus feeder, Case I, cleared by instanta-
        period.                                                      neous tripping of the feeder breaker,
          The value of the study is strongly                         causes all five generators t o experience
        affected by the selection of the proper                      swings of varying magnitude, the oscilla-
        printing interval and the total duration                     tions in the rotor angles are obviously
        of the simulation. Normally a printing                       damped and can be expected to die out.
        interval of 0.01 or 0.02 s is used;longer                      By contrast, in Case I1 the fault is
        intervals reduce the computer costs                          applied t o the tie between the synchro-
        slightly, but increase the risk of missing                   nizing bus and one of the generator buses
        fast swings of rotor angle. The computer                     and is cleared by tripping the tie circuit
        time cost is nearly proportional to the                      breaker. The swing curves for this con-
        total study time, so this parameter                          dition are shown in Fig 64. Generator
        should be closely controlled for the sake                    No 1 is disconnected from the system
        of economy.                                                  and suffers a severe overload, causing it
          This is especially important if the sys-                   to decelerate, as shown by a unidirec-
        tem and machines have been represented                       tional negative change in rotor angle.
        approximately or incompletely, because                       The other machines stay in synchronism.
        the errors will accumulate and render the
        results meaningless after some point. A                      7.7 Stability Studies on a Typical System.
        time limit of five times the duration of                     Probably the best way to examine some
        the major disturbance being studied is                       of the typical applications of stability
        generally long enough to show whether                        analysis to industrial power systems is to
        the system is stable or not, while keeping                   look at the stability studies which would
        costs t o a reasonable level.                                go into the design of a typical large in-
          7.6.7 Interpreting Results-Swing                           dustrial system including 20 MVA of lo-
        Curves. The results of a computer transi-                    cal generation and 40 MVA of purchased
        ent stability study are fairly easy to                       power capacity. The stability studies
        understand once the user learns the basic                    which might be applied to this system
        principles underlying stability problems.                    are :
        The most direct way t o determine from                         (1)The basic layout of the primary
        the study results whether a system is                        system can be affected by stability con-
        stable is to look at a set of swing curves                   siderations. For example, an initial de-
        for the machines in the system. Swing                        sign choice might be to connect the
        curves are simply plots of rotor angles                      generated and purchased power buses
        against time; if the curves of all the                       through only one tie circuit. However,
        machines involved are plotted on com-                        stability studies could show that in-
        mon axes, we can easily see whether                          adequate synchronizing power is avail-
        they diverge (indicating instability) or                     able to prevent the generators and the
        settle to new steady-state values.                           utility from losing synchronism during
          For example, Fig 62 shows swing curves                     primary system faults unless two ties are
        for a system which is stable under the                       provided. The same sort of considera-
134
Authorized licensed use limited to: IEEE Xplore. Downloaded on November 08,2014 at 04:51:47 UTC from IEEE Xplore. Restrictions apply.
                                                                                                                 IEEE
     TRANSIENT STABILITY STUDIES                                                                          Std 399-1980
                                                                                                                   1.0
                                                         TIME, S E C O N D S
                                                   Fig 62
                                    Computer Printout of Swing Curves for
                                      Case I Fault on System in Fig 63
    tions might dictate that the 4160 V bus                      a selectively coordinated system, how-
    ties be operated closed, to ensure the                       ever, unless expensive zone protection
    lowest possible impedance between the                        schemes (bus differential, pilot wire, etc)
    synchronous motors and the power                             are used. Balancing all of these factors,
    sources t o enhance stability.                               probably the best procedure is t o design
      (2) Related to the design of the basic                     the system layout around process require-
    layout is the problem of protective re-                      ments, provide the fastest relaying pos-
    laying. The system can be designed for                       sible within the constraints of selectivity
    maximum inherent stability by closely                        and economics, and then check the pro-
    coupling all machines. Or the same ob-                       posed layout and relaying by a series of
    jective can often be obtained by design-                     stability studies simulating the more
    ing the protective scheme for the fastest                    probable fault conditions. In the system
    possible clearing of faults. Since the                       shown in Fig 65, three-phase faults are
    former choice may involve economic                           applied on one 138 kV utility line ahead
    sacrifices in the form of higher capacity                    of the plant transformers, on a feeder
    switchgear, often the latter choice repre-                   from each of the 13.8 kV buses, and on
    sents the best solution. Extra-fast relay-                   a feeder from each 4160 V bus. Of
    ing can conflict with the requirements of                    course, the simulation would include
Authorized licensed use limited to: IEEE Xplore. Downloaded on November 08,2014 at 04:51:47 UTC from IEEE Xplore. Restrictions apply.
        IEEE
        Std 399-1980                         INDUSTRIAL AND COMMERCIAL POWER SYSTEMS ANALYSIS
                    ro>
                        a
              k
              =!
              t-
              3
LL
136
Authorized licensed use limited to: IEEE Xplore. Downloaded on November 08,2014 at 04:51:47 UTC from IEEE Xplore. Restrictions apply.
                                                                                                                  IEEE
     TRANSIENT STABILITY STUDIES                                                                          Std 399-1980
37
    m       16
    W
    W
    CK
    W
    W
    n
    m-
    -I
           -3
    c3
    z                        A GEN NO I
    a                        B GEN NO 2
    [ZT
    0                 a      C GEN N O 3
                      W
    0                 IX     D GEN NO 4
          -24 -a      U-     E GEN NO 5
                 li d
            5  J 5
            2 :3 =2
            3
          - 45
                 0     0.1        0.2       0.3        0.4     0.5   0.6               0.7        0.8        (   3      1.0
                                                         TIME, SECONDS
                                                     Fig 64
                                     Computer Printout of Swing Curves for
                                    Case I1 Fault on System Shown in Fig 63
     clearing of the fault via the proposed                       perfectly sound generation is available to
     relaying. If any of these studies show an                    maintain service to the most critical
     unstable condition, further stability                        loads. Obviously, a method of auto-
     studies might be required to test the                        matically interrupting noncritica1 loads
     effectiveness of various proposed solu-                      commensurately with the loss of system
     tions.                                                       capacity would be valuable.
       (3) In the systeni shown in Fig 65                           One such possibility would be to trip
     some considerations should certainly be                      noncritical feeders whenever the utility
     given to automatic load shedding. If the                     tie breakers are opened. However, this
     power company suffers an outage on the                       wired-in scheme lacks flexibility. To
     138 kV lines while the plant is running                      permit shedding only the amount of
     at nearly full load, the 20 MVA of local                     load required to prevent system collapse,
     generation will abruptly be subjected t o                    many industrial plants with local genera-
     an overload approaching 300%. This                           tion use underfrequency relaying. This
     overload will promptly cause the gener-                      scheme depends on the fact that an over-
     ators to trip off, leaving the plant with                    loaded generator slows down, dropping
     no power at all, even though 20 MVA of                       the system frequency.
137
Authorized licensed use limited to: IEEE Xplore. Downloaded on November 08,2014 at 04:51:47 UTC from IEEE Xplore. Restrictions apply.
        IEEE
        Std 399-1980                        INDUSTRIAL AND COMMERCIAL POWER SYSTEMS ANALYSIS
                                                               CURRENT      -                0
                                                                                             0
                                                                                             0
                                                               LIMITING                      c;t
                                                                  Ivm
                                                               REACTOR
138
Authorized licensed use limited to: IEEE Xplore. Downloaded on November 08,2014 at 04:51:47 UTC from IEEE Xplore. Restrictions apply.
                                                                                                                 IEEE
     TRANSIENT STABILITY STUDIES                                                                          Std 399-1980
139
Authorized licensed use limited to: IEEE Xplore. Downloaded on November 08,2014 at 04:51:47 UTC from IEEE Xplore. Restrictions apply.
       IEEE
       Std 399-1980                         INDUSTRIAL AND COMMERCIAL POWER SYSTEMS ANALYSIS
        8.1 Introduction. This section discusses                    widely recognized and studied effect of
        benefits obtained from motor starting                       motor starting is the voltage dip experi-
        studies and examines various types of                       enced throughout an industrial power
        computer-aided studies normally per-                        system as a direct result of starting large
        formed. Data or information required t o                    motors. Available accelerating torque
        permit these studies along with expected                    drops appreciably at the motor bus as
        results of a motor starting study effort                    voltage dips t o a lower value, extending
        are also reviewed.                                          the starting interval and affecting, some-
                                                                    times adversely, overall motor starting
        8.2 Need for Motor Starting Studies                         performance. During motor starting,
          8.2.1 Problems Revealed. Motors on                        voltage level at the motor terminals
        modern industrial systems are becoming                      should be maintained at approximately
        increasingly larger. Some are considered                    80% of rated voltage or above for a stan-
        large even in comparison t o the total                      dard National Electrical Manufacturers
        capacity of large industrial power sys-                     Association (NEMA) type B motor. This
        tems. Starting large motors, especially                     value results from examination of speed-
        across-the-line, can cause severe disturb-                  torque characteristics of this type motor
        ances t o the motor and any locally con-                    (150% starting torque at full voltage)
        nected load, and also t o buses electrically                and the desire t o successfully accelerate
        remote from the point of motor starting.                    a fully loaded motor at reduced voltage
        A brief discussion of major problems                        (that is, torque varies with the square of
        associated with starting large motors,                      the voltage). When other motors or
        and therefore of significance in power                      lower shaft loadings are involved, the
        system design and evaluation, follows.                      speed-torque characteristics of both the
           8.2.2 Voltage Dips. Probably the most                    motor and its load should be examined
140
Authorized licensed use limited to: IEEE Xplore. Downloaded on November 08,2014 at 04:51:47 UTC from IEEE Xplore. Restrictions apply.
                                                                                                               IEEE
   MOTOR STARTING STUDIES                                                                               Std 399-1980
                                               Fig 66
                          Typical Generator Terminal Voltage Characteristics
                                for Various Exciter Regulator Systems
/-,-
NO REGULATOR
                    I                                                 *
                    0                        TIME
141
Authorized licensed use limited to: IEEE Xplore. Downloaded on November 08,2014 at 04:51:47 UTC from IEEE Xplore. Restrictions apply.
          IEEE
          Std 399-1980                        INDUSTRIAL AND COMMERCIAL POWER SYSTEMS ANALYSIS
142
Authorized licensed use limited to: IEEE Xplore. Downloaded on November 08,2014 at 04:51:47 UTC from IEEE Xplore. Restrictions apply.
                                                                                                               IEEE
   MOTOR STARTING STUDIES                                                                               Std 399-1980
                        LII
                        2W    80
                        VI
                        VI
                        3
                        g
                        0
                               60
                        e:
                        c
                        U
                        z
                        %      40
                        w
                        z
                        W
                        U
                        4      20
                        a
                                0
                                         40       80       120      160      200       240       250
                                                PERCENT FULL-LOAD TORQUE
                                            Fig 67
                      Typical Wound Rotor Motor Speed-Torque Characteristics
   whether the capacitor and motor can                           information t o assist in selecting proper
   be switched together, or because of an                        taps and ensure that light-load voltages
   excessive voltage drop that might result                      are not excessively high.
   from the impact of capacitor transient                          The motor starting study can be used
   charging current when added to the                            to prove effectiveness of several other
   motor inrush current the capacitor must                       solutions to the voltage dip problem as
   be energized momentarily ahead of the                         well. With a wound rotor motor, differ-
   motor. The switching procedure can                            ing values of resistance are inserted into
   appreciably affect the cost of final                          the motor circuit at various times during
   installation.                                                 the starting interval t o reduce maximum
     Use of special starters or capacitors to                    inrush (and accordingly starting torque)
   minimize voltage dips can be an expen-                        to some desired value. Figure 67 shows
   sive method of maintaining voltage at                         typical speed-torque characteristic curves
   acceptable levels [l]. Where possible,                        for a wound rotor motor. With appropri-
   off-nominal tap settings for distribution                     ate switching times (dependent on motor
   transformers are an effective, economical                     speed) of resistance values, practically
   solution for voltage dips. By raising no-                     any desired speed-torque (starting) char-
   load voltage in areas of the system ex-                       acteristic can be obtained. A motor start-
   periencing difficulties during motor                          ing study aids in choosing optimum
   starting, voltage dip can often be mini-                      current and torque values for a wound
   mized. In combination with a load flow                        rotor motor application whether resist-
   study, a motor starting study can provide                     ances are switched in steps by timing
143
Authorized licensed use limited to: IEEE Xplore. Downloaded on November 08,2014 at 04:51:47 UTC from IEEE Xplore. Restrictions apply.
         IEEE
         Std 399-1980                        INDUSTRIAL AND COMMERCIAL POWER SYSTEMS ANALYSIS
144
Authorized licensed use limited to: IEEE Xplore. Downloaded on November 08,2014 at 04:51:47 UTC from IEEE Xplore. Restrictions apply.
                                                                                                                    IEEE
     MOTOR STARTING STUDIES                                                                                Std 399-1980
145
Authorized licensed use limited to: IEEE Xplore. Downloaded on November 08,2014 at 04:51:47 UTC from IEEE Xplore. Restrictions apply.
        IEEE
        Std 399-1980                        INDUSTRIAL AND COMMERCIAL POWER SYSTEMS ANALYSIS
                                                        Fig 69
                                           Simplified Equivalent Circuit for a
                                                   Motor on Starting
       For additional accuracy, speed versus                         The ratio of 0.746 t o efficiency times
       current, and speed versus power factor                        the power factor approaches unity for
       characteristics should be given for as                        most motors giving the 1 hp/kVA ap-
       exact a model as possible for the motor                       proximation. Therefore, for synchronous
       during starting. For some programs, con-                      motors operating at 1.0 PF, a reasonable
       stants for the motor equivalent circuit                       assumption is 1 hp equals 0.8 kVA.
       given in Fig 69 can be either required or                        ( 2 )Inrush Current. Usually, a conserva-
       alternatively utilized as input informa-                      tive multiplier for motor starting inrush
       tion. This data must be obtained from                         currents is obtained by assuming the
       the manufacturer since values are critical.                   motor to have a code G characteristic
         8.5.2 Simplifying Assumptions. Besides                      with locked rotor current equal to ap-
       using standard impedance values for                           proximately 6 times the full load current
       transformers and cables, it is often neces-                   with full voltage applied at motor ter-
       sary t o use typical or assumed values for                    minals, [6].
       other variables when making motor start-                         (3) Starting Power Factor. The power
       ing voltage drop calculations. This is                        factor of a motor during starting deter-
       particularly true when calculations are                       mines the amount of reactive current
       for evaluating a preliminary design and                       that is drawn from the system, and thus
       exact motor and load characteristics are                      t o a large extent the maximum voltage
       unknown. Some common assumptions                              drop. Typical data [2] suggest the fol-
       used in the absence of more precise data                      lowing:
       follow:                                                             (a) Motors under 1000 hp, PF = 0.20
         (1)Horsepower to kVA Conversion. A                                (b) Motors 1000 hp and over, PF =
       reasonable assumption is 1 hp equals 1                        0.15
       kVA. For induction motors and synchro-
       nous motors with 0.8 leading, running                         8.6 Solution Procedures and Examples.
       power factor, it can easily be seen from                      Regardless of the type of study required,
       the equation :                                                a basic voltage drop calculation is always
                                                                     involved. When voltage drop is the only
                 (kVA) (0.746)                                       concern, the end product is this calcula-
        hp   =                      (See Ref [5] .)                  tion when all system impedances are at
                  (EFF) (PF)                                         maximum value and all voltage sources
146
Authorized licensed use limited to: IEEE Xplore. Downloaded on November 08,2014 at 04:51:47 UTC from IEEE Xplore. Restrictions apply.
                                                                                                                 IEEE
     MOTOR STARTING STUDIES                                                                               Std 399-1980
Authorized licensed use limited to: IEEE Xplore. Downloaded on November 08,2014 at 04:51:47 UTC from IEEE Xplore. Restrictions apply.
       IEEE
       Std 399-1980                         INDUSTRIAL AND COMMERCIAL POWER SYSTEMS ANALYSIS
       pedance method is a very convenient and                        The quantities involved should be ex-
       acceptable means of calculating system                       pressed in complex form for greatest
       bus voltages during motor starting. Val-                     accuracy although reasonable results can
       idity of the impedance method can be                         be obtained by using magnitudes only
       seen and is usually used for working                         for first order approximations.
       longhand calculations. Where other than                        The disadvantage t o this method is
       simple radial systems are involved, the                      that since all loads are not of constant
       digital computer greatly aids in obtain-                     current type, the current t o each load
       ing necessary network reduction. To ob-                      varies as voltage changes. An iterative
       tain results with reasonable accuracy,                       type solution procedure is therefore
       however, various system impedance ele-                       necessary t o solve for the ultimate volt-
       ments must be represented as complex                         age at every bus, and such tedious com-
       quantities rather than as simple reac-                       putations are readily handled by a digital
       tances.                                                      computer.
         (2) Current Method. For any bus in                           (3) Load Flow Solution Method. From
       the system represented in Figs 71 and 72,                    the way loads and other system elements
       the basic equations for the current                          are portrayed in Figs 71 and 72, it ap-
       method are as follows:                                       pears that bus voltages and the voltage
                                                                    dip could be determined by a conven-
                                                                    tional load flow program. This is true.
                     at 1 per
        Iperunit = MVA1d            .o       unit voltage
                                                                    By modeling the starting motor as a con-
                   MVAbe
                   ~
                                                         Fig 71
                                                Typical One-Line Diagram
5000 kVA
Bus 3
0.85 PF 1000 Hp
148
Authorized licensed use limited to: IEEE Xplore. Downloaded on November 08,2014 at 04:51:47 UTC from IEEE Xplore. Restrictions apply.
                                                                                                               IEEE
   MOTOR STARTING STUDIES                                                                               Std 399-1980
0. 061 + j 0.61
                                                         A
                             4000 kVA                3000 kVA
                             0.85 PF                 o m    PF                    1000 H p
                                                                                  LRA - 6 - F L A
                                                                                   0.15 PF
F L A = F U L LOAD C U R R U T
                                                   Fig 12
                                        Impedance Diagram for System
                                                 in Fig 71
149
Authorized licensed use limited to: IEEE Xplore. Downloaded on November 08,2014 at 04:51:47 UTC from IEEE Xplore. Restrictions apply.
          IEEE
          Std 399-1980                         INDUSTRIAL AND COMMERCIAL POWER SYSTEMS ANALYSIS
A V = 1.0564
                                  4000 kVA
                                                            3000 kVA                        1000 HP
                                    0.85 PF
                                                            0.85 PF                       LRA = 6 . F L A
                                                                                           0.15 PF
                                    L R A =LOCKED R O T O R C U R R E N T
                                                          Fig 73
                                            Revised Impedance Diagram Showing
                                             Transient Reactance of Generator
          of system bus voltages as mentioned                           use of the transient reactance as the rep-
          earlier. For steady-state conditions it is                    resentation for the machine results in
          assumed that generator voltage regulators                     calculated bus voltages and, accordingly,
          have had time t o increase field excitation                   voltage drops, that are reasonably ac-
          sufficiently t o maintain the desired gen-                    curate and conservative, even for excep-
          erator terminal voltage. Accordingly, the                     tionally slow-speed regulator systems.
          presence of the internal impedance of                           Assuming for example that bus No 7 in
          any local generators connected to the                         the system shown in Fig 72 is at the line
          system is ignored. During motor start-                        terminals of a 12 MVA generator rather
          ing, however, the influence of machine                        than being an infinite source ahead of a
          transient behavior becomes important.                         constant impedance utility system, the
          To model the effect of a close-connected                      transient impedance of the generator
          generator on the maximum voltage drop                         would be added to the system. The re-
          during motor starting requires inclusion                      sulting impedance diagram is shown in
          of generator transient reactance in series                    Fig 73. A new bus 99 is created. Voltage
          with other source reactances. In general,                     at this new bus is frequently referred to
150
Authorized licensed use limited to: IEEE Xplore. Downloaded on November 08,2014 at 04:51:47 UTC from IEEE Xplore. Restrictions apply.
                                                                                                               IEEE
  MOTOR STARTING STUDIES                                                                               Std 399-1980
                                                                                   t
                          T=   EXCITER
RE GU LATO R
                          where
                          XG varies with time as
                             + Xi xd, and EG varies with the time
                                    -+
                                                  Fig 74
                                  Simplified Representation of Generator
                                         Exciter/Regulator System
151
Authorized licensed use limited to: IEEE Xplore. Downloaded on November 08,2014 at 04:51:47 UTC from IEEE Xplore. Restrictions apply.
          IEEE
          Std 399-1980                         INDUSTRIAL AND COMMERCIAL POWER SYSTEMS ANALYSIS
          erator is equally applicable t o all three                    the actual inrush multiplier used for de-
          solution methods described above. Such                        termining the appropriate motQr repre-
          an approach cannot give any detail re-                        sentation in the calculations is (6) (0.64)
          garding the response of the generator                         = 4.2 times full load current.
          voltage regulator or changes in machine                          Resistor or reactor starting limits the
          characteristics with time. For a more                         line starting current by the same current
          detailed solution which considers time                        as motor terminal voltage is reduced
          dependent effects of machine impedance                        (that is, 65% of applied bus voltage gives
          and voltage regulator action, the appro-                      65%of normal line starting current).
          priate impedance and voltage terms in                            Y-start, A-run starting delivers 33% of
          each expression must be continuously                          normal starting line current with full
          altered t o accurately reflect changes                        voltage a t the motor terminals. The start-
          which occur in the circuit. This pro-                         ing current at any other voltage is, cor-
          cedure is also applicable t o any solution                    respondingly, reduced by the same
          methods considered. Figure 74 shows a                         amount. Part winding starting allows
          simplified representation of the machine                      60% of normal starting line current at
          parameters which must be repeatedly                           full voltage and reduces inrush accord-
          modified t o obtain the correct solution.                      ingly at other voltages.
            Some type of reduced voltage starting                          When a detailed motor speed-torque
          is often used t o minimize motor inrush                        and accelerating time analysis is re-
          current and thus reduce total voltage                          quired, the following equations found in
          drop, when the associated reduction in                         many texts apply [lo]. The equations
          torque accompanying this starting meth-                        in general apply t o both induction and
          od is permissible. Representation used                         synchronous motors since the latter be-
          for the motor in any solution method                           have almost exactly as do induction
          for calculating voltage drop must be                           machines during the starting period.
          modified t o reflect the lower inrush cur-
          rent. If auto-transformer reduced voltage                      T a V2
          starting is used, motor inrush will be re-
          duced by the appropriate factor from                           T = I,&
          Table 12.If, for example, normal inrush
          is six times full load current and an 80%                            WK2
          tap auto-transformer starter is applied,                       I,= -lb-ft-s2
                                                                                g
                                                            Table 12
                                                     Auto-Transformer-Line
                                                        Starting Current
152
Authorized licensed use limited to: IEEE Xplore. Downloaded on November 08,2014 at 04:51:47 UTC from IEEE Xplore. Restrictions apply.
                                                                                                              IEEE
  MOTOR STARTING STUDIES                                                                               Std 399-1980
153
Authorized licensed use limited to: IEEE Xplore. Downloaded on November 08,2014 at 04:51:47 UTC from IEEE Xplore. Restrictions apply.
          IEEE
          Std 399-1980                                          INDUSTRIAL AND COMMERCIAL POWER SYSTEMS ANALYSIS
                                 W          '
                                                            0
                                                                                  -0
                                                                                               0
                                                                                               0
                                 *X                         0                      0           0
                                 -U
                                 0-
                                 W.
                                 X I
                                 zy1                                               0           0
                                 w
                                 -
                                 C-S                                               0           0
                                                            0
                                                            0                      1
                                                                                   0           8
                                                                                               0
                                 e.
                                 U
                                 L t
                                   O
                                                    .                     --a              -
                                 0                                                         I
                                 "
                                 *.
                                 e-
                                 a?
                                 90-
                                                    0
                                                    0
                                                                           ...
                                                                          0 0 0
                                                                          0 0 0
                                                                                           0
                                                    -
                                 c
*NZ
                                                                                           .
                                                                                           0
                                                                           ...
                                                    0                     nN               0
                                                                          c--0Q
                                                                          -                0
                                 c *                n
                                 Z >
                                 W X                c                     c u n
                                 e,
                                 zu
                                 W.
                                       .
                                       y1
                                                mm
                                                mm
                                                ..
                                                0
                                                N0N
                                                4 -
                                                                       9oc
                                                                       In4
                                                                      ....
                                                                          umnm
                                                                      0ra.D
                                                                      0nN-
                                                                       I
                                                                           0
                                                                                       --
                                                                                       0 0
                                                                                       cJ
                                                                                       ..
                                                                                       O
                                                                                       N
                                                                                         c
                                                                                       I N
                                                                                         1
                                       L.
                                                4 4                       - 0 0
                                       bl                                 (DD?         0 0
                                       c                                               0 0
                                                                                         3
                                 e*
                                 W .1
                                 2              ..
                                                0 0
                                                Q Q
                                                                      ....
                                                                      0m-N
                                                                          I--o
                                                                      0 0 u m
                                                                           I
                                                                                       5.:
                                                                                       nn
                                                                                       I   1
                                       W
                                                                                           I
                                                0
                                                                      -
                                                                      0
                                                0                     N
                                                                      I
                                                0                     c
                                                                      c
                                                0                     0
                                                *
                                                -
                                                0
                                                                 s
                                                                 .o
                                       0             N           '
                                                                 1
                                                                           -nu
                                 W
                                 -J xO               1
                                                      I          I'        I l l
                                                                           NNN
                                                                                           I
                                                                                           n
                                       k
                                                      II
                                                        I                                      I
                                  v,
                                       .
                                       W
                                       z
                                                -
                                                U
                                                                 ,I
                                                                      a
                                                                       I
                                                                      IC
                                 ffi            ul
                                                1
                                                                                                     !*       I,
                                                                                                     ,    I
                                                                                               1
                                       0        I                                      n :
154
Authorized licensed use limited to: IEEE Xplore. Downloaded on November 08,2014 at 04:51:47 UTC from IEEE Xplore. Restrictions apply.
                                                                                                                 IEEE
  MOTOR STARTING STUDIES                                                                                Std 399-1980
                               1                                                         I
                                       '           e                       '     0
                     U                             0
                     c                                                                   0
                                                                           1 :
                     a x                           0                                     0
                                                   -
                     -U                                                    i     o
                     a
                     w
                       -
                     X *L
                     a m                                                         0
                     -
                     w
                     C -X                          0
                                                   0
                                                                                 0
                                                                                 0
                                                                                         0
                                                                                         0
                     I-.
                     K O
                     U Z               --                  ---       I
                     0                                               I
                                                                     I
                     c
                     a.
                     =?
                     %5
                       -
                                       0 0
                                       0 0
                                           ..              ...
                                                           0 0 0
                                                           0 0 0
                                                                                     0
                                                                                     0
                     c
                                                                     I
                                       c
                                       EO
                                         -                 In**
                                                           - aa -y
                                                           c                         f
                                       --..                - ..
                                       a*
                                       ncl
                     +a
                     w
                     Z -X
                                                           t-c                       s
                                                           O t O
                                                                                     2
                                                                                                    E
                                                                                                    0
                         m
                                                                                                    a
                                       0 -
                                       cW
                                       4 e                                                          3
                     t,
                     w0
                     2
                       6
                       *            ...
                                   3 - -
                                   0 0
                                     1 0
                         x
                         VI
                                    a
                                    P
                                      -
                                    0 -0
                                                         - 0 0
                                                         cm.
                                                       ....
                                                         CY--
                                    ...
                         c
                     c*            oee                 o c a -
                     z *1
                     w
                                   o n e               ocni
                                           1               I
                         w
                         -
                     IL' w
                         VI                            0
                                   P
                                   0
                                                       a
                     $Z            a                   c
                     Z.IU
                     <
                         2
                     W             N
                     *2- 3..
                     U-
                                   V
                     on            0                   0
                      >-
                                       ,
                                       D N
                     U:!
                     L,,
                     20                --  I   1
                         L
                                       !
                               1       I
                                       I
                               I   I
                                       !
                                   f
                               I
                                   -
                                   a
                         U         1
z L
                     U
                     E
                                   -
                                   z
                                   6
.I
                         z
                         3
                                   -, I
                                       I
155
Authorized licensed use limited to: IEEE Xplore. Downloaded on November 08,2014 at 04:51:47 UTC from IEEE Xplore. Restrictions apply.
           IEEE
           Std 399-1980                        INDUSTRIAL AND COMMERCIAL POWER SYSTEMS ANALYSIS
                                                                     GENERATOR
                                                                     12 MVA
                                                        Fig 77
                                             Simplified System Model for
                                    Generator Representation During Motor Starting
          voltages. It is seen from the motor start-                    time. The digital computer is used to
          ing bus voltage computer report in Fig                        solve several simultaneous equations that
          76 that when this representation is used                      describe the voltage of each bus in a sys-
          and subsequent motor starting calcula-                        tem at time zero and the end of succes-
          tions are made, the voltage at bus No 4                       sive time intervals.
          is 0.7940 L -9.55' per unit. This voltage                       Figures 78-81 show in detail the type
          is well below the 0.85 criterion establish-                   of input information required and the
          ed earlier for proper operation of ac                         output obtained from a digital computer
          control devices.                                              voltage drop study. The system shown in
             8.6.4 Time-Dependent Bus Voltages.                         Fig 77 contains certain assumptions
          The load flow solution method for ex-                         which include the following:
          amining effects of motor starting allows                        (1)Circuit losses are negligible-reac-
          a look at the voltage on the various sys-                     tances only used in calculations
          tem buses at a single point in time. A                          (2) Initial load is constant kVA type
          more exact approach is t o model gen-                           (3) Motor starting load is constant im-
          erator transient impedance characteris-                       pedance type
          tics and voltage sources closer t o give                        (4) Motor starting power factor is in
          results for a number of points in time                        the range 0 t o 0.25
          following the motor starting event.                             (5) Mechanical effects such as governor
          Although the solution methods are                             response, prime mover speed changes,
          applicable t o multiple generator/motor                       and inertia constants are negligible
          systems as well, equations can be devel-                        Plotted results obtained from the com-
          oped for a system of the form shown in                        puter compare favorably t o those ex-
          Fig 77 t o solve for generator, motor, and                    pected from an examination of Fig 66.
          exciter field voltages as a function of                       In the particular computer program used
156
Authorized licensed use limited to: IEEE Xplore. Downloaded on November 08,2014 at 04:51:47 UTC from IEEE Xplore. Restrictions apply.
                                                                                                                               IEEE
    MOTOR STARTING STUDIES                                                                                              Std 399-1980
                                               Fig 78
                           Typical Output-Generator Motor Starting Program
                                             Fig 79
                          Typical Output-Generator Motor Starting Program
157
Authorized licensed use limited to: IEEE Xplore. Downloaded on November 08,2014 at 04:51:47 UTC from IEEE Xplore. Restrictions apply.
         IEEE
         Std 399-1980                          INDUSTRIAL AND COMMERCIAL POWER SYSTEMS ANALYSIS
                             W
                             W
                             a
                             0
                              ’0.8
                                    0      I     2      3       4     5   6       7      8     9      IO
                                                              TIME IN SECONDS
                                                              Fig 80
                                                     Typical Output - Plot of
                                                      Generator Voltage Dip
“r
                                     0     I     2       3      4     5   6        7     8      9     IO
                                                              TIME IN SECONDS
                                                              Fig 81
                                                     Typical Output - Plot of
                                                       Motor Voltage Dip
158
Authorized licensed use limited to: IEEE Xplore. Downloaded on November 08,2014 at 04:51:47 UTC from IEEE Xplore. Restrictions apply.
                                                                                                                 IEEE
    MOTOR STARTING STUDIES                                                                               Std 399-1980
                                                                                    Fig 83
                     Fig 82                                                   Simplified System
          Simplified Representation of                                      Model for Accelerating
           Typical Regulator/Exciter                                        Time and Speed-Torque
               Models for Use in                                                 Calculations
              Computer Programs
                                                                                    I .o            0"
   t o obtain this report, the excitation sys-
   tem models available are similar t o those
   described in Reference [ 131 . Excitation                                                     z sys
   system models are shown in simplified
   form in Fig 82. Continuously acting reg-
   ulators of modern design permit full
   field forcing for minor voltage variations
   (as little as 0.5%), and these voltage
   changes have been modeled linearly for                                                                7000 kVA
                                                                                    1000 HP
   simplicity.                                                                                           0 . 8 5 PF
159
Authorized licensed use limited to: IEEE Xplore. Downloaded on November 08,2014 at 04:51:47 UTC from IEEE Xplore. Restrictions apply.
         IEEE
         Std 399-1980                         INDUSTRIAL AND COMMERCIAL POWER SYSTEMS ANALYSIS
                                                        Table 13
                                          Average Values for Accelerating Torque
                                             Over Time Interval Defined by a
                                                      Speed Change
                                    speed        Tmotor      r
                                                             oad            Tnet            Tnet
                                      0%         100%        30%             -              -
                                      -            -          -             77.5%      2260.4 lb-ft2
                                     25%         120%        35%             -              -
                                      -            -          -            100%        2916.7lb-ft2
                                     50%         160%        45%             -              -
                                      -            -          -            120%        2500.0 lb-ft2
                                     75%         190%        65%             -              -
                                      -           -           -             62.5%      1822.9 lb-ft2
                                     95%          80%        80%             -              -
         t75-95 =
                      (1080) (1710 - 1350)
                         (308) (1822.9)    = 0.6925 s                 q
                                                                      c
                                                                       J
                                                                           200
                                                                                                                         \
         and therefore, the total time t o 95% of
                                                                      E
                                                                      w
                                                                            100
160
Authorized licensed use limited to: IEEE Xplore. Downloaded on November 08,2014 at 04:51:47 UTC from IEEE Xplore. Restrictions apply.
                                                                                                                 IEEE
   MOTOR STARTING STUDIES                                                                                Std 399-1980
                                                             i
                                          I
                           I
                                          1
                                          I
                                          I                  I
                                                                                      i
                                                                                      I
                                                             i             I
                       I                  i                  I
                                                             i
                                                             I
                                                                           I         1
                                                                                     I
                                                                                     I
                       I
                       I
                                          I                  I                       I
                                                             i
                                          I
                                         4
                       ~
                                         i
                       I
                       I
                                         I d
                                         Ir zz
                                                             I
                                                             ,
                                                                                     iI
                           0
                                           .-
                                I
                           0
                           4
                           D                                                         I
                                              Lnc
                                              *z
                                              -a                                     I
                                                     0
                           >
                           I
                           0
                           W
                           c
                                I
                                I             ac
                                                U
                                              cI z
                                              2 -0
                                              W
                                                     m
                                                     0
                                                     0
                                                         I       <
                                                                 c
                                                                       i
                                                                       ,
                                                                               W
                                                                               3
                           <
                           U
                                     I        1 3
                                              u
                                              3Uw
                                                     U)
                                                     .J
                                                      L                         "
                                :I
                                              *2 .
                                              O W    .*.                       J
                                                                               w
                                                                               W
                           -c
                           0                  0      '
                                                     b-I                       a
                           t    I
                                I         JJ
                                              2-     -
                                                     z
                                                                       I
                                                                       I
                                                                               v)
                                                                               W
                                                                               3
                                                                               0
                                                                                I
                                                -
                           I              3 U
                                          L >
                           Jl
                           c    I               z    I
                                                     0                         r
                                                                               0
                           , ,*
                           J
                           0
                                                VI
                                                     r
                                                     0
                                                                               c
                                     L
                                                                               U
                           I                                                   W
                           w    I               cc
                                                0
                           c
                           n    I                                              t
                                                                               c
                           >
                           VI                   t
                                                3                              U
                           C                                                   w
                       w
                           I    I                                              z
                           -
                       L
                       c   *                                                   J
                                                                               a
                                                                               U
                                                                 Y             .
                                                                               4
                                                                               1
                   ' S
                                                                               c
                                                                               t
                       z
                                                                               z
                                                                               U
                   /I-
                       -                             0
                                                                 I
                                                                 : I
                                                                               2
                                                                                2
                  ;1
                       r-l
                                                     7.
                                                     d
                                                                 ..            VI
                                                                               U-,
                                                                               a
                       "
                       1   l                         I
                                                                               r
                                                     -
                                                     J
                                                     a
                                                     c
                                                     J
                                                                               n
                       .,
                       0
                       0                             I
                                                     I
                                                     3
                       I
                       a
                       n,
                  80
                   1
161
Authorized licensed use limited to: IEEE Xplore. Downloaded on November 08,2014 at 04:51:47 UTC from IEEE Xplore. Restrictions apply.
          IEEE
          Std 399-1980                        INDUSTRIAL AND COMMERCIAL POWER SYSTEMS ANALYSIS
162
Authorized licensed use limited to: IEEE Xplore. Downloaded on November 08,2014 at 04:51:47 UTC from IEEE Xplore. Restrictions apply.
                                                                                                               IEEE
 MOTOR STARTING STUDIES                                                                                Std 399-1980
163
Authorized licensed use limited to: IEEE Xplore. Downloaded on November 08,2014 at 04:51:47 UTC from IEEE Xplore. Restrictions apply.
         IEEE
         Std 399-1980                         INDUSTRIAL AND COMMERCIAL POWER SYSTEMS ANALYSIS
          9.1 Introduction. This section discusses                     loads or small three phase loads fitting
          the basic concepts involved in studies of                    into the above categories normally have
          harmonic analysis of industrial and                          minimal effect on the system harmonic
          commercial power systems. The need for                       content and therefore are neglected.
          such analysis, recognition of potential
          problems, corrective measures, required                      9.2 History. For years motors and other
          data and benefits derived from perform-                      loads requiring dc power derived their
          ance of a harmonic analysis study are                        energy from ac motor driven dc genera-
          also discussed. Benefits of using a com-                     tors (MG sets). Mechanical linkage be-
          puter as a tool for a harmonic analysis                      tween the two systems transmitted power
          study will also be addressed within this                     between them and at the same time
          section.                                                     electrically isolated each system from
            The prevailing sources of harmonics                        the other. However, these MG sets were
          in a system are rectifiers, dc motor                         bulky and tended t o be high maintenance
          drives (converters/inverters),uninterrupt-                   pieces of equipment.
          ible power supplies (UPS), cycloconvert-                       The first attempt at electrical rectifica-
          ers, arc furnaces, or any other device                       tion was accomplished through mechani-
          with nonlinear characteristics, which                        cal means. A motor driven cam physically
          derive their power from a linear/sinu-                       opened and closed switches at precisely
          soidal electric system. Systems composed                     the right instant on the voltage wave-
          of these types of loads have the potential                   form to supply dc voltage and current t o
          to develop harmonic related problems                         the load. At best this approach was
          and are therefore prime candidates for a                     cumbersome since timing the switches
          harmonic analysis study. Fractional                          and keeping them timed was extremely
          horsepower drives and other single phase                     difficult. In addition, contact arcing plus
164
Authorized licensed use limited to: IEEE Xplore. Downloaded on November 08,2014 at 04:51:47 UTC from IEEE Xplore. Restrictions apply.
                                                                                                                  IEEE
     HARMONIC ANALYSIS STUDIES                                                                            Std 399-1980
                                                                           m+
     cal rectifiers were soon replaced by static
     equipment including mercury, selenium,
     and silicon diodes, and finally thyristors
     (SCRs).
        Although solid-state rectification ap-
     peared t o be the panacea to the problems
     of the older methods, other system prob-
     lems soon became noticeable especially
     as the size of each converter unit and as
     the total converter load became a sub-                                             Fig 86
     stantial section of the total system power                                     6-Phase, 6-Pulse
     requirements.                                                                     Rectifier
        The most noticeable initial problem
     was the inherent poor power factor asso-
                                                                                     b
     ciated with static rectifiers. Economics
     as well as system voltage regulation re-
     quirements made it desirable to improve
     the overall system power factor which
     normally was accomplished using shunt                                   Iac
     power factor correction capacitors. How-
     ever, when these capacitor banks were
     applied, other problems involving har-
     monic voltages and currents affecting
     these capacitors and other related equip-                                   Idc
     ment became prevalent.
        Another initial problem was the exces-                                           I
     sive amount of interference induced into
     telephone circuits due to mutual coupling                                          Fig 87
     between the electrical system and the                                          6-Phase, 6-Pulse
     communication system at these harmonic                                            Rectifier
     frequencies.
       More recent problems involve the per-                      of the fundamental (normally 60 Hz)
     formance of computers, numerical con-                        frequency. Typical values are the 5th
     trolled machines and other sophisticated                     (300 Hz), 7th (420 Hz), 11th (660 Hz)
     electronic equipment which are very sen-                     and so on.
     sitive to power line pollution. These de-                      To better understand harmonic related
     vices can respond incorrectly to normal                      problems, it is necessary to understand
     inputs, give false signals, or possibly not                  how and where harmonics are generated.
     respond at all.                                                In converting ac power to dc power, a
                                                                  rectifier effectively breaks or chops the
     9.3 General Theory.                                          alternating current waveform by allow-
       9.3.1 What are Harmonics? Harmonics                        ing the current to flow only during a
     are voltages or currents, or both, present                   section of the cycle. The example in
     on an electrical system a t some multiple                    Figs 86 and 87 for a 6-phase, 6-pulse
165
Authorized licensed use limited to: IEEE Xplore. Downloaded on November 08,2014 at 04:51:47 UTC from IEEE Xplore. Restrictions apply.
       IEEE
       Std 399-1980                        INDUSTRIAL AND COMMERCIAL POWER SYSTEMS ANALYSIS
       rectifier indicates the waveforms for the                    for these harmonics to flow. If this
       direct current and the corresponding ac                      occurs, harmonic related problems can
       line current. The square alternating cur-                    have a detrimental effect on the ac sys-
       rent waveform represents a distorted                         tem.
       sinusoidal waveform rich in harmonic                           Various parameters particular to each
       content which can be resolved into                           system determine the magnitude of these
       components using Fourier analysis tech-                      harmonic problems.
       niques [ l ] . The Fourier series for this                     9.3.2 Resonance. The application of
       waveform is :                                                capacitors with harmonic generating ap-
                                                                    paratus on a power system necessitates
                                                                    the consideration of the potential prob-
                                                                    lem of an excited harmonic resonance
                1         1                                         condition.
              + - cos 7e - - cos l i e                                Inductive reactance increases directly
                7        11
                1                                                   with frequency and capacitive reactance
              + - cos 138 . . .)                                    decreases directly with frequency. At the
                13
                                                                    resonant frequency of any inductive-
       The higher frequency terms are the har-                      capacitive (LC) circuit, inductive reac-
       monic components.                                            tance equals the capacitive reactance.
          A similar Fourier analysis of the                           There are two forms of resonance to
       distorted sinusoidal waveforms of other                      be considered, series resonance and paral-
       harmonic generating equipment as men-                        lel resonance. For the series circuit in
       tioned previously will yield similar har-                    Fig 88, the total impedance at the reso-
       monic current components.                                    nant frequency reduces to the resistance
          Arc furnaces differ from drives and                       component only. For the case where this
       rectifiers in that harmonic voltages are                     component is small, high current magni-
       generated instead of harmonic currents.                      tudes a t the exciting frequency will flow.
       Arc resistance and the voltage/current                         Figure 89 is a plot of impedance versus
       characteristis are continually varying due                   frequency of this series circuit.
       t o movement of scrap, bubbling of                                                   Fig 88
       molten metal, magnetic repulsion of the                                           Series Circuit
       arc from the other two phases, and so
       forth. In addition, magnetic repulsion
       forces between furnace flexible cables
       cause swinging of these cables resulting
       in variation of the reactance of secondary
       circuit. The overall result of the non-                                           I             '-j\
                                                                                                       7'
       linearity of the arc and arc furnace
                                                                                     Fig 89
       parameters is the generation of harmonic
       voltages in the secondary circuit. Because                          Impedance Versus Frequency
                                                                                   +V
       of the unpredictable nature of the arc,
       harmonic magnitudes are not readily
       determined. Only lower order harmonics                                     IZ I
       are generated, however.
          With harmonic sources present, all that                                                  r
       remains is t o have a path in the ac system                                           f +
166
Authorized licensed use limited to: IEEE Xplore. Downloaded on November 08,2014 at 04:51:47 UTC from IEEE Xplore. Restrictions apply.
                                                                                                                  IEEE
      HARMONIC ANALYSIS STUDIES                                                                            Std 399-1980
         Parallel resonance is similar to series                     For this same circuit assume a current
      resonance in that at its exciting frequen-                   source equal in magnitude t o l/7 A If/7 at
      cy, capacitance reactance equals the in-                     the 7th harmonic (420 Hz). At this
      ductive reactance. However, its parallel                     frequency the inductive reactance be-
      impedance is significantly different.                        comes 4.2 52 and the capacitive reac-
       Figure 91 is a plot of impedance versus                     tance becomes -4.4 52. The parallel
      frequency for the parallel circuit of Fig                    combination can be calculated to be
      90. At the resonant frequency f,, the                        92.4 i2. Again, using Ohm's law, the
      impedance is very high and when excited                      voltage across the load (V,) now is
      from a source at this frequency, a high                      13.20 V with the current through the
      circulating current will flow in the                         capacitor being 3.0 A.
      capacitance-inductance loop although                           In actual electrical systems utilizing
      the source current is small in comparison.                   power factor correction capacitors, either
         To illustrate parallel resonance further,                 type of resonance or a combination of
      select 60 Hz reactances of 0.60 i2 and                       both can occur if the resonant point
      -30.23 i2 for X , and X , respectively.                      happens to be close t o one of the fre-
      The parallel impedance of the capacitor                      quencies generated by harmonic sources
      and inductor at 60 Hz can be calculated                      in the system. The result can be the flow
      to +0.61 52. For illustration purposes, in-                  of excessive amounts of harmonic cur-
      ject 1 A (60 Hz) current If into the cir-                    rent or the appearance of excessive har-
      cuit. Using Ohm's law, the voltage across                    monic overvoltages, or both. Possible
      the load V, due to the fundamental                           consequences of such an occurrence are
      frequency is then 0.61 V.                                    excessive capacitor fuse operation, capa-
                                                                   citor failures, telephone interference, or
                             Fig 90                                overheating of other electrical equip-
                         Parallel Circuit                          ment.
                                                                   9.4 Modeling. To analyze a system for
                                                                   resonance effects requires calculation of
                                                                   various harmonic currents throughout
                                                                   the system and the harmonic voltages
                                                                   these currents cause. At each frequency,
                                                                   system impedances are different. For all
                                                                   conditions the circuit remains the same.
                        Fig 91                                     Rectifiers and other similar harmonic
              Impedance Versus Frequency                           generating equipment are represented as
                                                                   current sources at each harmonic fre-
                                                                   quency. With reference to the previous
                                                                   Fourier expansion, the maximum theo-
                                                                   retical harmonic current magnitude from
                                                                   each converter equals the fundamental
                                                                   frequency full load current magnitude
                           L
                           r                                       divided by the order of the harmonic.
                              f+
                                                                     Harmonic current magnitudes are also
                                                                   functions of converter pulses. Magnitudes
                                                                   of system harmonic voltages are a result
                                                                   of harmonic currents flowing back into
167
Authorized licensed use limited to: IEEE Xplore. Downloaded on November 08,2014 at 04:51:47 UTC from IEEE Xplore. Restrictions apply.
       IEEE
       Std 399-1980                          INDUSTRIAL AND COMMERCIAL POWER SYSTEMS ANALYSIS
168
Authorized licensed use limited to: IEEE Xplore. Downloaded on November 08,2014 at 04:51:47 UTC from IEEE Xplore. Restrictions apply.
                                                                                                                IEEE
    HARMONIC ANALYSIS STUDIES                                                                            Std 399-1980
                                                                   where
                                                                   h = order of harmonic (including the
                                                                        first or fundamental)
     where                                                         V = fundamental or harmonic voltage
                                                                    I = fundamental or harmonic current
        h = order of harmonic (including the                       X = fundamental or harmonic reactance
            first or fundamental)                                  Capacitors must also have sufficient
       Detailed results of a computerized har-                   dielectric to withstand anticipated peak
     monic analysis study should include the                     voltages resulting from the fundamental
     four main points mentioned above: total                     and the harmonics. This peak voltage is
     capacitor bank kVac loading, peak volt-                     calculated as the arithmetic sum of all
     ages, rms current, and rms voltage. Volt-                   the component voltages (not as rms
     age and current values should be pro-                       value).
     vided at all critical system locations sus-
     ceptible to harmonic problems where                          9.5 Solutions t o Harmonic Problems. The
     appropriate values can be compared to                        primary solution to any harmonic related
     the device's ratings in question.                            problem is accomplished by shifting the
169
Authorized licensed use limited to: IEEE Xplore. Downloaded on November 08,2014 at 04:51:47 UTC from IEEE Xplore. Restrictions apply.
       IEEE
       Std 399-1980                         INDUSTRIAL AND COMMERCIAL POWER SYSTEMS ANALYSIS
170
Authorized licensed use limited to: IEEE Xplore. Downloaded on November 08,2014 at 04:51:47 UTC from IEEE Xplore. Restrictions apply.
                                                                                                                  IEEE
      HARMONIC ANALYSIS STUDIES                                                                            Std 399-1980
                                                                                     * *
      phase cancellation of lower order har-
      monics can be employed to greatly re-
      duce harmonic magnitudes. From an
      economic and manufacturing viewpoint,
      it is impractical to construct rectifier
                                                                                  6 Phase           6 Phase
      transformers with more than twelve
      phases. However, they can be selected
                                                                                          Fig 96
      to collectively appear as more phases
                                                                                     6-Phase Rectifier
      than they actually are.
                                                                                       Transformers
        In Fig 96, both rectifier transformers
      are individually 6-phase units but when
      viewed from bus A and when they are                          shifting of the rectifier transformers
      both equally loaded, they collectively                       themselves. For example, one rectifier
      appear t o be a 12-phase system. Similarly                   rated as 12-phase but with six phases
      in Fig 97, buses C and D appear to have                      shifted -30" and six phases at 0" with
      12-phase rectification but due to differ-                    respect t o the primary system will ap-
      ing connections of the power trans-                          pear to be a 24-phase system when
      formers, the system becomes a 24-phase                       operated with another identically rated
      system at bus B.                                             and loaded 12-phase rectifier which has
        Other methods of accomplishing phase                       -15" and +15" phase shifts.
      multiplication entail different phase                          It must be stressed that lower order
                                                            Fig 97
                                                       24-Phase System
BUS B
                                  SHIFT           A+-psIL
                                             I 5 O k
                                             A
                                                 LYTTC
                                                       AA               A A
                                             AT+T AT T
                                              6 Phase 6 Phase 6 Phase              6 Phase
171
Authorized licensed use limited to: IEEE Xplore. Downloaded on November 08,2014 at 04:51:47 UTC from IEEE Xplore. Restrictions apply.
        IEEE
        Std 399-1980                         INDUSTRIAL AND COMMERCIAL POWER SYSTEMS ANALYSIS
        harmonic cancellation using phase multi-                       Tables 14 and 1 5 are abbreviated copies
        plication techniques is only applicable                      of the computer solutions for this system.
        when each component is equally rated                         The first solution modeled the system
        and loaded. Where not all units are                          without any filters to determine if a
        equally loaded or some are off line only                     resonant condition would exist after
        partial lower order harmonic cancella-                       application of the proposed capacitor
        tion occurs. A harmonic analysis study                       banks. As indicated by the harmonic
        should also include probable imbalanced                      profile at C3 bus ( 2 banks), the system
        loading conditions with only partial lower                   is resonant very close t o the 7th har-
        order harmonic cancellation considera-                       monic. A comparison of capacitor bank
        tions.                                                       ratings t o the values listed in the com-
          Often an installation using phase multi-                   puter printout indicated that filtering
        plication for harmonic reduction might                       was indeed required.
        not need any filtering at all or requires                      The application of tuning reactors R3A
        only small tuning reactors opposed to a                      and R3B tuned t o the 4.7th harmonic
        complex RLC filtering scheme. The net                        was sufficient to suppress this resonant
        economic effect is significant.                              condition to acceptable levels. The
          Examples: The partial one-line diagram                     second computer solution indicates the
        in Fig 98 was taken from an actual har-                      7th harmonic to be almost gone with
        monic analysis study performed in the                        the totalized quantities greatly reduced.
        design stages for an electro-chemical                        The rms voltage was lowered from 1.766
        plant.                                                       per unit to 1.102 per unit of the system
          This particular system required the                        base value. The current and reactive
        addition of tuning reactors in series with                   power loads were well within ratings.
        each capacitor bank to minimize har-                         The voltage ratings of the proposed banks
        monic resonance problems.                                    were increased to 109% of the nominal
                                                          Fig 98
                                                 Partial One-Line Diagram
UAAJ
                                       12       12
                                                           T
                                                           20.75
                                                                 T
                                                                 20.75
                                     MVA,      MVX          MVA           MVA        TO CELL LINES
                                                                                        ( d c LOAD)
172
Authorized licensed use limited to: IEEE Xplore. Downloaded on November 08,2014 at 04:51:47 UTC from IEEE Xplore. Restrictions apply.
                                                                                                                  IEEE
     HARMONIC ANALYSIS STUDIES                                                                            Std 399-1980
                                                       Table 14
                                               First Computer Solution:
                                                     Without Filters
BUS N A M E S C 3 c2 C l R3 A2 R 1
173
Authorized licensed use limited to: IEEE Xplore. Downloaded on November 08,2014 at 04:51:47 UTC from IEEE Xplore. Restrictions apply.
           IEEE
           Std 399-1980                           INDUSTRIAL AND COMMERCIAL POWER SYSTEMS ANALYSIS
                                                           Table 15
                                                   Second Computer Solution:
                                                          With Filters
S O L U T I O N F3R F Y I T C H I N G C O N D I T I O N l 9S
BU’S N A M E S c 3 c2 c1 R3 RI ‘a 1
l l T H H A R M O N I C B U S VOLTAGES A N 0 S H U N T L O A D C U R R E N T S
1 9 T H H A R N O N I C B U S VOLTAGES AN0 S N U N T L O A O C U R R E N T S
TO T A L I Z E D O U A N f I T I E S INCLUDING ALL A U O V C H A R M O N I C S P L U S ’ r U N O A M C N I A L
174
Authorized licensed use limited to: IEEE Xplore. Downloaded on November 08,2014 at 04:51:47 UTC from IEEE Xplore. Restrictions apply.
                                                                                                               IEEE
   HARMONIC ANALYSIS STUDIES                                                                            Std 399-1980
   system voltage, bringing all ratings safely                  operating in conjunction with capacitor
   within limits.                                               banks
     The values listed under bus R3 are those                     Occasionally , when harmonics .appear
   of the main bus. Very satisfactory system                    to be the cause of system problems, it is
   harmonic filtering is also achieved.                         desirable t o determine the system har-
     The previous example illustrates how                       monic resonance point. To determine
   effective filtering can be when properly                     this resonance point, the short circuit
   engineered. However, filtering is not al-                    capacity at each capacitor bank location
   ways the best solution. In another electro-                  is required. A close approximation of
   chemical plant with a very large complex                     this resonance point is the equation:
   electrical system, harmonic filtering was
   not implemented. The existing system
   utilized power factor correction capaci-
   tors at each major rectifier location.
   Plant expansion required an additional                        where
   rectifier and capacitor bank. Initial filter                        h, = resonance point in per unit of
   design simulation corrected harmonic                                   fundamental frequency
   problems for the new bank but shifted                           MVA = short circuit capacity
   the resonant point t o another location                         MV,, = Mvar rating of the unfiltered
   which caused harmonic problems with                                    capacitor bank at that location
   existing capacitor banks. The practical
   and economical solution in this case was                       This equation is useful for an initial
   to oversize the new capacitor bank’s                         evaluation. If the resonance point is close
   voltage rating to compensate for har-                        to one of the harmonic frequencies pre-
   monic content without filtering.                             sent on the system, then possible har-
                                                                monic related problems could occur.
    9.6 When is a Harmonic Study Required?                        9.6.1 Data Required. The following
    Although a specific answer is not always                    data are required for a typical study:
    available, the following points are indi-                     (1)Single-line interconnection diagram
    cators.                                                       (2) Short circuit capacity and X / R ratio
      (1)Application of capacitor banks t o                     of the utility supply system
    systems comprised of 20% or more of                           ( 3 ) Subtransient reactance and kVA of
    converters or other harmonic generating                     all rotating machines. Where possible, all
    equipment                                                   machines on a given bus should be lumped
      (2) History of harmonic related prob-                     together into one composite equivalent
    lems including excessive capacitor fuse                     machine
    operation                                                     (4)Percent reactance and resistance of
      (3) In the design stage of a facility                     all lines, cables, bus work, current limit-
    composed of capacitor banks and har-                        ing reactors, and saturable reactors on a
    monic generating equipment                                  given kVA base and rated kV of the cir-
      (4)Strict electric power company re-                      cuit in which the circuit element is
    quirements which limit harmonic injec-                      located
    tion back into its system to very small                       (5) The percent impedance and kVA
    magnitudes                                                  of all power transformers
      (5) Plant expansions which add signifi-                     (6) The three-phase kvar rating of all
    cant harmonic generating equipment                          shunt capacitors and shunt reactors
175
Authorized licensed use limited to: IEEE Xplore. Downloaded on November 08,2014 at 04:51:47 UTC from IEEE Xplore. Restrictions apply.
        IEEE
        Std 399-1980                         INDUSTRIAL AND COMMERCIAL POWER SYSTEMS ANALYSIS
176
Authorized licensed use limited to: IEEE Xplore. Downloaded on November 08,2014 at 04:51:47 UTC from IEEE Xplore. Restrictions apply.
                                 10. Switching Transient Studies
177
Authorized licensed use limited to: IEEE Xplore. Downloaded on November 08,2014 at 04:51:47 UTC from IEEE Xplore. Restrictions apply.
      IEEE
      Std 399-1980                         INDUSTRIAL AND COMMERCIAL POWER SYSTEMS ANALYSIS
       and capacitances. Depending upon resist-                     restriking in switches and breakers, inter-
       ances present, losses will extract energy                    mittent or arcing faults, clearing by fuse
       which will be supplied by various sources                    blowing, and so forth. While in this
       within the system. Each steady-state                         broad sense lightning is also a switching-
       condition entails its own unique set of                      produced transient, it is usually listed in
       energy storage and exchange rates in and                     a class by itself.
       among the various circuit elements.
          Thus a redistribution of energy must                     10.3 Control of Switching Transients.
       occur among the various system elements                     The philosophy of mitigation and con-
       to change from one steady-state condi-                      trol of switching transients revolves
       tion to another. This change cannot occur                   around :
       instantly; a finite period of time, the                        (1)Minimizing the number and severity
       transient period, prevails during which                     of switching events
       transient voltages and currents develop                        (2) Limitation of the rate of exchange
       to bring about these changes. These                         of energy that prevails among system ele-
       transient voltages and currents develop                     ments during the transient period
       and proceed in an orderly manner,                              (3) Extraction of energy
       prescribed by the network configuration                        (4)Shifting of resonance points to
       and conditions prevailing before and                        avoid amplification of particularly offen-
       after the switching event. The precise                      sive frequencies
       nature and timing of the switching event                       (5) Provision of energy reservoirs to
       itself will profoundly affect the charac-                   contain released or trapped energy with-
       teristics of the ensuing transients. These                  in safe limits of current and voltage
       transient voltages and currents are com-                       (6) Provision of preferred paths for
       posed of damped natural-frequency                           elevated-frequency currents attending
                                                                   switching
       oscillations which potentially can mag-
                                                                      This philosophy is implemented prac-
       nify to many times normal. The transi-
                                                                   tically through the judicious use of:
       ent environment is based on Kirchhoff’s
                                                                      (1) Temporary insertion of resistance
       law. Since changing quantities and their
                                                                   between circuit elements, for example,
       associated rates of change are involved                     insertion resistors in circuit breakers
       throughout the transient period, the                           (2) Inrush control reactors
       mathematics describing transients in-                          (3) Damping resistors in filter circuits
       volves differential equations. Classical                    and surge protective circuits
       mathematical computation of electrical                         (4)Tuning reactors
       transients, therefore, requires a certain                      (5) Surge capacitors
       degree of mathematical proficiency and                         (6) Filters
       effort.                                                        (7) Surge arresters
          In the broad sense, virtually all electrical                (8) Necessary switching only, with
       transients are switching-produced transi-                   properly maintained switching devices
       ents if switching is anything that suddenly                    (9) Proper switching sequences
       changes the network configuration or
       any of its elements. Switching, for                          10.4 Methods of Analysis. While very
       example, is considered to be not only                        few practicing industrial plant engineers
       the intentional actions of opening and                       are proficient at the type of mathematics
       closing circuit breakers and switches, but                   used in the description and analysis of
       also the occasions of fault inception,                       transients, a very useful insight into the
178
Authorized licensed use limited to: IEEE Xplore. Downloaded on November 08,2014 at 04:51:47 UTC from IEEE Xplore. Restrictions apply.
                                                                                                                   IEEE
       SWITCHING TRANSIENT STUDIES                                                                         Std 399-1980
179
Authorized licensed use limited to: IEEE Xplore. Downloaded on November 08,2014 at 04:51:47 UTC from IEEE Xplore. Restrictions apply.
       IEEE
       Std 399-1980                        INDUSTRIAL AND COMMERCIAL POWER SYSTEMS ANALYSIS
       puters. Such augmentation, for example,                      minimum and future maximum short-
       offers an economical way to obtain a                         circuit duty conditions, with MVA and
       statistical distribution of switching surge                  voltage bases if impedances are in per
       magnitudes. Further, TNA modeling has                        unit
       become a refined art and is becoming in-                          (b) Voltage spread: maximum and
       creasingly enhanced by electronic tech-                      minimum voltage limits
       niques. Traditionally and presently, most                        (c) Operation: description of reclos-
       switching transient studies are conducted                    ing procedures and contractual or other
       through TNA.                                                 limitations, if any
         There are various equipment approach-                        (3) Individual power transformer data
       es and methods t o aid the calculation of                    and other transformer data, if any
       switching-produced transients to some                            (a) Rating, connections, no-load tap
       extent these methodoligies utilize over-                     voltages for both positions of the Y-A
       lapping technologies. While the TNA                          switch, if any, and LTC voltages, if any.
       continues to be the most used aid in the                     Location of taps, in LV or HV windings.
       calculated determination of transients,                      Normal position of the no-load tap if
       the method employed depends upon                             seldom varied.
       preferences, experiences, and equipment                          (b) No-load saturation data: Curve of
       available to the analysts. The industrial                    no-load voltage versus exciting current,
       plant user should entrust transient anal-                    additionally specifying rated voltage
       ysis only to experts using the particular                    magnetizing impedance (or exciting
       equipment of their preference.                               current at rated voltage) and air-core
       10.6 Data Required for a Switching                           impedance. Definition of winding ar-
       Transient Study. Compared to conven-                         rangement for which the data apply.
       tional power system studies, switching                       Bases should be given for voltages or
       transient analysis data requirements are                     currents in percent or per unit.
       often more detailed and unusual or                               (c) Positive and zero sequence leakage
       special. These requirements remain es-                       impedances, R and X,, for all trans-
       sentially unchanged regardless of basic                      former tap connections. Impedance of
       analysis tools and aids that are employed,                   series reactor, if any
       be they digital computer, hybrid simu-                           (d) Neutral grounding details
       lator, or transient network analyzer, or                       (4)Capacitor data, for each Mvar sup-
       a combination of these. The generalized                      ply bank and surge protection unit
       data listed below encompass virtually all                        (a) Mvar or microfarad rating, volt-
       information areas required in an indus-                      age rating, catalog number, connections,
       trial power system switching transient                       neutral grounding details
       study :                                                          (b) Description of switching device
          (1)One-line diagram of the system                         for Mvar supply bank
       showing all circuit elements and connec-                         (c) Description of tuning reactors, if
       tion options                                                 any, for Mvar supply bank
          (2) Utility information, for each tie, at                   (5) Feeder cables or lines: Impedances
       the connection to the plant, exclusive of                    per phase, R , X,, X,, both positive and
       the plant load or backfeed                                   zero sequence, for each circuit of appre-
            (a) Impedances R , X,, Xc, both pos-                    ciable length. If these impedances are
       itive and zero sequence, representing                        not available directly, t o permit their cal-
       utility system or systems under present                      culation, data must be given as follows:
180
Authorized licensed use limited to: IEEE Xplore. Downloaded on November 08,2014 at 04:51:47 UTC from IEEE Xplore. Restrictions apply.
                                                                                                                IEEE
    SWITCHING TRANSIENT STUDIES                                                                          Std 399-1980
         (a) Length of circuit, wire size, con-                   release relatively large quantities of
    ductor arrangement and material, for                          energy. Similarly, highly inductive ap-
    phase conductors and ground conductors,                       paratus possesses energy storage capabil-
    or other return circuit paths. If cable,                      ity which can release large quantities of
    whether in magnetic or non-magnetic                           electromagnetic energy during a rapid
    duct, voltage rating, insulation specifica-                   current decrease. Since transient voltages
    tion, shield and sheath description.                          and currents arise in conjunction with
         (b) If multiple conductors per phase,                    energy redistribution that occurs during
    a dimensioned cross section of the feeder                     the transient period between steady-state
    installation (for example, of a duct bank                     conditions, the greater the energy storage
    for multiple under ground cables) show-                       in associated system elements, the greater
    ing several conductors of each phase and                      the transient magnitudes become. This
    ground return conductors.                                     has been confirmed countless times in
       (6) Other power system elements.                           studies.
         (a) Surge arresters: location, rating,                      Generalized switching transient studies
    catalog or model number                                       have provided many important criteria
         (b) Grounding resistors (and reactors,                   to enable system designers t o avoid ex-
    if any): rating, impedance of each                            cessive transients in most common cir-
         (c) Buffer reactors: rating, imped-                      cumstances. Criteria for proper system
    ance for all taps of each                                     grounding t o avoid transient over voltages
         (d) Rotating machines: rating of                         on the occasion of a ground fault are a
    each, subtransient and transient react-                       prime example. Results of these general-
    ance, type of regulator.                                      ized studies have formed the basis of
       (7) Operating modes and procedures.                        several IEEE Committee reports on
         (a) Sequence and occasion for clos-                      switching surges. There are also several
     ing each switch and circuit breaker                          not-to-common potential transient prob-
         (b) Action of existing protection                        lem areas that are analyzed on an indi-
     scheme during system overvoltages and                        vidual basis. The following is a partial
     undervoltages                                                list of transient-related problems which
       Transformer data requirements (3) in-                      can, and have been, analyzed in com-
    clude items which require considerable                        puter studies:
     time for the transformer manufacturer                           (1)Energizing and deenergizing transi-
     to develop. This should be factored into                      ents in arc furnace installations
     the lead time in projecting the date of                         (2) Ferroresonance
     study completion.                                               (3) Lightning and switching surge
                                                                  response of motors, generators, trans-
     10.7 Switching Transient Problem Areas.                       formers, transmission towers, cables, etc
     Switching of predominately reactive                             (4)Lightning surges in complex station
     equipment represents the greatest poten-                      arrangements and optimum surge arrester
     tial for creating excessive transient duties.                 location
     Principal offending situations are switch-                      ( 5 ) Surge transfer through transformers
     ing capacitor banks with inadequate or                          ( 6 ) Switching of large-magnitude induc-
     malfunctioning switching devices and                         tive current
     energizing and deenergizing transformers                        (7) Switching capacitors
     with the same switch deficiencies. Capa-                        (8) Restrike phenomena in dropping
     citors can store, trap, and suddenly                         lines, cables, and capacitor banks, includ-
181
Authorized licensed use limited to: IEEE Xplore. Downloaded on November 08,2014 at 04:51:47 UTC from IEEE Xplore. Restrictions apply.
         IEEE
         Std 399-1980                         INDUSTRIAL AND COMMERCIAL POWER SYSTEMS ANALYSIS
182
Authorized licensed use limited to: IEEE Xplore. Downloaded on November 08,2014 at 04:51:47 UTC from IEEE Xplore. Restrictions apply.
                                                                                                               IEEE
   SWITCHING TRANSIENT STUDIES                                                                          Std 399-1980
183
Authorized licensed use limited to: IEEE Xplore. Downloaded on November 08,2014 at 04:51:47 UTC from IEEE Xplore. Restrictions apply.
        IEEE
        Std 399-1980                         INDUSTRIAL AND COMMERCIAL POWER SYSTEMS ANALYSIS
184
Authorized licensed use limited to: IEEE Xplore. Downloaded on November 08,2014 at 04:51:47 UTC from IEEE Xplore. Restrictions apply.
                                                                                                                IEEE
   SWITCHING TRANSIENT STUDIES                                                                          Std 399-1980
185
Authorized licensed use limited to: IEEE Xplore. Downloaded on November 08,2014 at 04:51:47 UTC from IEEE Xplore. Restrictions apply.
          IEEE
          Std 399-1980                         INDUSTRIAL AND COMMERCIAL POWER SYSTEMS ANALYSIS
ic
Authorized licensed use limited to: IEEE Xplore. Downloaded on November 08,2014 at 04:51:47 UTC from IEEE Xplore. Restrictions apply.
                                                                                                              IEEE
   SWITCHING TRANSIENT STUDIES                                                                         Std 399-1980
  citor and a furnace transformer by clos-                      99, only one run was conducted and the
  ing a breaker wherein one pole (phase C)                      most severe overvoltage was 2.87 per
  remains open. The description also indi-                      unit as a result of ferroresonance which
  cates the breaker used no resistor inser-                     developed as a consequence of breaker
  tion and a pole-closing span of 180' was                      malfunction (one pole remaining open).
  searched t o attain a maximized transient                     The magnitude of this overvoltage is
  of 2.87 per unit voltage which occurred                       determined by scaling the oscillogram
  at the energized transformer primary                          which displays the greatest instantaneous
  (that is, location 2; the measuring probe                     voltage or by direct read-out from a
  locations are indicated by circles).                          digital peak-holding voltmeter. Figure
    The right half of the case sheet consists                   100 shows an oscillogram which discloses
  of a tabulated format so transient and                        the characteristic ferroresonant pattern
  sustained voltage magnitudes can be                           as well as the magnitude of associated
  recorded up t o ten probe locations each.                     peaks. It also discloses that the predomi-
  Provision is made to show both pre-                           nant frequency of the ferroresonance is
  switching and post-switching (and pre-                        60 Hz. Those familiar with switching
  fault and post-fault) sustained voltage                       transient analysis will immediately recog-
  levels. Also, an index is included for                        nize that ferroresonance has developed
  oscillograms (which in the TNA report                         as a result of a 60 Hz impedance match
  are generally reproduced on the page(s)                       (or a near match) between the magnetiz-
  immediately following the case sheet).                        ing reactance of the transformer being
  Oscillograms are photos of CRO displays,                      energized and its       p F surge capacitor.
  generally a separate photo for each phase.                    This inductive-capacitive combination is
    At the bottom right half sheet there is                     excited by a zero-sequence driving volt-
  a listing of electrical scale factors used in                 age occasioned by the open breaker pole.
  the modeling, that is, the relationship                       The multi-frequency nature of the oscil-
  between the TNA model and system                              logram is a result of the nonlinear mag-
  electrical quantities.                                        netizing reactance of a transformer,
    Note in the case sheet illustrated in Fig                   particularly in the period immediately
                                                  Fig 100
                                     Oscillogram 12-10-2 as Described
                                       in TNA Case Sheet of Fig 99
187
Authorized licensed use limited to: IEEE Xplore. Downloaded on November 08,2014 at 04:51:47 UTC from IEEE Xplore. Restrictions apply.
          IEEE
          Std 399-1980                        INDUSTRIAL AND COMMERCIAL POWER SYSTEMS ANALYSIS
188
Authorized licensed use limited to: IEEE Xplore. Downloaded on November 08,2014 at 04:51:47 UTC from IEEE Xplore. Restrictions apply.
                                                                                                                  IEEE
     SWITCHING TRANSIENT STUDIES                                                                          Std 399-1980
     satisfactory for this purpose. Addition-                     single-trace surge test oscilloscope with
     ally, it is essential that signal circuit                    direct CRT (cathode ray tube) connec-
     terminations be made carefully with high                     tions is sometimes used to record such
     quality hardware and be carefully imped-                     transients with least possible distortion
     ance matched to avoid spurious reflec-                          (2) A multi-channel magnetic light
     tions. It is desirable that signal circuits                  beam oscillograph with high input im-
     and instruments be laboratory tested as                      pedance amplifiers
     an assembly before field measurements                           (3) A peak-holding digital-readout
     are undertaken. This testing should in-                      memory voltmeter (sometimes called
     clude the injection of a known steep                         peak picker), usually manually reset
     wave into the input end of the signal                           The storage scope should have at least
     circuit and comparison of this wave                          threechannel capability to permit simul-
     shape with that on the receiving instru-                     taneous display of the three phase-voltage
     ments (scopes). Only after a close agree-                    signals. An additional channel is desirable
     ment between the two wave shapes is                          to allow a spare or to display another
     achieved should the assembly be approv-                      signal of interest. The single-trace surge
     ed for switching transient field measure-                    test oscilloscope with direct CRT input
     ments. These tests also aid overall cali-                    is capable of producing the highest
     bration.                                                     resolution of specific signals of interest
       All the components of the measure-                         on faster sweep speeds, normally from
     ments system should be grounded via a                        10 to 200 ps/divisions.
     continuous conducting grounding system                          From the standpoint of conducting
     of lowest practical inductance to mini-                      switching transient field measurements,
     mize internally induced voltages. The                        one of the most difficult aspects is secur-
     grounding system should be configured                        ing an acceptable and reliable triggering
     to avoid so-called ground loops which                        method for the storage scope when multi-
     can result in noise injection. Where signal                  channel switching is used t o record more
     cables are unusually long, excessive volt-                   than one signal. Considerable experi-
     ages can become induced in their shields,                    menting may be necessary in order t o
     but industrial switching transient mea-                      catch the transient activity due to its
     surement systems have not as yet in-                         short duration. One successful approach
     volved such cases.                                           in some tests on systems with open (non-
       10.10.3 Transient Measurement/h4oni-                       shielded) bus has been to use a simple
     toring Instrumentation. The complement                       wire antenna connected to the external
     of instruments used depends on circum-                       trigger of the scope. The antenna will
     stances and purpose of the test program.                     sense air-born signals emanating from the
     Major items comprising the total comple-                     power circuit bus in concert with initia-
     ment of display and recording instru-                        tion of the switching. Associated sweep
     mentation for transient measurements                         speeds of 200 t o 1000 psldivisions have
     are one or more of the following:                            been found generally most useful for
       (1)One or more oscilloscopes including                     recording all but the very fastest switch-
     a storage-type scope with multi-channel                      ing transient voltages.
     switching capability. When the presence                         The magnetic oscillograph displays all
     of the highest speed transients (that is,                    voltages and signals being monitored.
     with front times of a small fraction of a                    Current signals derived from special cur-
     microsecond) is suspected, a high-speed,                     rent transformers or shunts are fed
189
Authorized licensed use limited to: IEEE Xplore. Downloaded on November 08,2014 at 04:51:47 UTC from IEEE Xplore. Restrictions apply.
       IEEE
       Std 399-1980                         INDUSTRIAL AND COMMERCIAL POWER SYSTEMS ANALYSIS
190
Authorized licensed use limited to: IEEE Xplore. Downloaded on November 08,2014 at 04:51:47 UTC from IEEE Xplore. Restrictions apply.
                                          11. Reliability Studies
191
Authorized licensed use limited to: IEEE Xplore. Downloaded on November 08,2014 at 04:51:47 UTC from IEEE Xplore. Restrictions apply.
         IEEE
         Std 399-1980                        INDUSTRIAL AND COMMERCIAL POWER SYSTEMS ANALYSIS
192
Authorized licensed use limited to: IEEE Xplore. Downloaded on November 08,2014 at 04:51:47 UTC from IEEE Xplore. Restrictions apply.
                                                                                                               IEEE
    RELIABILITY STUDIES                                                                                 Std 399-1980
   tions as: throwover to an alternate cir-                      11.4 Data Needed for System Reliability
   cuit, opening or closing a sectionalizing                     Evaluations. Data needed for quantitative
   switch or circuit breaker, reclosing a cir-                   evaluation of system reliability depends
   cuit breaker following a trip-out from a                      t o some extent on the nature of the sys-
   temporary fault, etc.                                         tem being studied and the detail of the
   system. A group of components con-                            study. In general, however, data on the
   nected or associated in a fixed configura-                    performance of individual components
   tion t o perform a specified function of                      together with the times required to per-
   distributing power.                                           form various switching operations are
                                                                 required.
   unavailability. The long-term average                            System component data generally re-
   fraction of time that a component or                          quired are summarized as follows:
   system is out of service caused by fail-                         (1)Failure rates (forced outage rates)
   ures or scheduled outages. An alternative                     associated with different modes of com-
   definition is the steady-state probability                    ponent failure
   that a component or system is out of                             (2) Expected average time to repair or
   service. Mathematically, unavailability =                     replace failed component
   (1- availability).                                               (3) Scheduled maintenance outage rate
                                                                 of component
   11.3 System Reliability Indexes. The                             (4)Expected average duration of a
   two basic system reliability indexes                          scheduled outage event
   which have proven most useful and                                If possible, component data should be
   meaningful in power distribution system                       based on historical performance of com-
   design are load interruption frequency                        ponents in the same environment as
   and expected duration of load interrup-                       those in the proposed system being
   tion events. These indexes can be readily                     studied. The reliability surveys conducted
   computed using the methods in [l]. The                        by the Power Systems Reliability Sub-
   two basic indexes of interruption fre-                        committee [2], [3] allow a source of
   quency and expected interruption dura-                        component data when such specific data
   tion can be used t o compute other in-                        is not available.
   dexes which are also useful:                                     Switching time data needed includes :
     (1)Total expected average interrup-                            (1)Expected times t o open and close a
   tion time per year, or other time period                      circuit breaker
     (2) System availability or unavailability                      (2) Expected times to open and close a
   as measured at the load supply point in                       disconnect or throwover switch
   question                                                         (3) Expected time to replace a fuse link
     (3) Expected energy demanded, but                              (4)Expected times to perform such
   unsupplied, per year                                          emergency operations as cutting in clear,
     Note that the disruptive effect of                          installing jumpers, etc
   power interruptions is often non-linearly                        Switching times should be estimated
   related t o the duration of the interrup-                     for the system being studied based on
   tion. Thus, it is often desirable t o com-                    experience, engineering judgment, and
   pute not only an overall interruption fre-                    anticipated operating practice :
   quency but also frequencies of irter-
   ruptions categorized by the appropriate                       11.5 Method for System Reliability Eval-
   durations.                                                    uation. The general method for system
193
Authorized licensed use limited to: IEEE Xplore. Downloaded on November 08,2014 at 04:51:47 UTC from IEEE Xplore. Restrictions apply.
               IEEE
               Std 399-1980                     INDUSTRIAL AND COMMERCIAL POWER SYSTEMS ANALYSIS
               reliability evaluation which is recom-                 (voltage dip) together with the minimum
               mended has evolved over a number of                    duration of such reduced voltage period
               years. The method is well suited t o the               which results in substantial degradation
               study and analysis of electric power                   or complete loss of function of t h e load
               distribution systems as found in indus-                or process being served. Frequency reli-
               trial plants and commercial buildings.                 ability studies are conducted on a con-
               The method is systematic and straight-                 tinuity basis in which case interruption
               forward and lends itself t o either manual             definitions reduce t o a minimum dura-
               or computer computation. An important                  tion specification with voltage assumed
               feature of the method is that system                   t o be zero during the interruption.
               weak points can be readily identified,                    11.5.2 Failure Modes and Effects
               both numerically and non-numerically ,                 Analysis. Failure modes and effects
               thereby focusing design attention on                   analysis (FMEA) for power distribution
               those sections of the system which con-                systems amount t o determination and
               tribute most t o service unreliability.                listing of those component outage events
                  The procedure for system reliability                or combinations of component outages
               evaluation is outlined as follows:                     which result in an interruption of service
                  (1) Assess the service reliability require-         a t the load point being studied according
               ments of the loads and processes supplied              t o the interruption definition adopted,
               and determine appropriate service inter-               This analysis must be made considering
               ruption definition or definitions                      the different types and models of out-
                  (2) Perform a failure modes and effects             ages which components can exhibit and
               analysis (FMEA) identifying and listing                the reaction of the system’s protection
               those component failures and combina-                  scheme t o these events. Component out-
               tions of component failures which result               ages are categorized as:
               in service interruptions and constitute                   (1)Forced outages or failures
               minimal cut-sets of the system                            (2) Scheduled or maintenance outages
                  ( 3 ) Compute interruption frequency                   (3) Overload outages
               contribution, expected interruption dur-                  Forced outages or failures are either
               ation, and the probability of each of the              permanent forced outages or transient
               minimal cut-sets of (2)                                forced outages. Permanent forced out-
                  (4)Combine results of ( 3 ) t o produce             ages require repair or replacement of the
               system reliability indexes                             failed component before it can be re-
                 The above steps are discussed in more                stored t o service while transient forced
               detail in later sections.                              outages imply no permanent damage t o
                  11.5.1 Service Interruption Definition.             the component thus permitting its restor-
               The first step in any electric power system            ation t o service by a simple re-closing or
               reliability study should be a careful                  re-fusing operation. Additionally, com-
               assessment of the power supply quality                 ponent failures can be categorized by
               and continuity required by the loads                   physical mode or type of failure. This
               which are served. This assessment should               type of failure categorization is important
               be summarized and expressed in a ser-                  for circuit breakers and other switching
               vice interruption definition used in the               devices where the following failure
               succeeding steps of the reliability evalua-            modes are possible:
               tion procedure. The interruption defini-                  (1)Faulted, must be cleared by back-up
               tion specifies the reduced voltage level               devices
194
Authorized licensed use limited to: IEEE Xplore. Downloaded on November 08,2014 at 04:51:47 UTC from IEEE Xplore. Restrictions apply.
                                                                                                               IEEE
  RELIABILITY STUDIES                                                                                   Std 399-1980
                                               Table 16
                           Frequency and Expected Duration Expressions for
                          Interruptions Associated with Forced Outages Only
                                 cutsets
                           rs = expected interruption duration
                             =             f a i r c s i / fs
                                  min
                                 cutsets
                        f, rs = total interruption time per time period
195
Authorized licensed use limited to: IEEE Xplore. Downloaded on November 08,2014 at 04:51:47 UTC from IEEE Xplore. Restrictions apply.
         IEEE
         Std 399-1980                         INDUSTRIAL AND COMMERCIAL POWER SYSTEMS ANALYSIS
         per year and the expected duration. If                        maintenance outages, switching after
         the expected duration is expressed in                         faults t o restore service, and incomplete
         years, the expected down-time will have                       redundancy of parallel facilities is given
         the units of years per year and can be                        in [l].
         regarded as the relative proportion of
         time or probability the system is down                        11.6 References
         due t o the minimal cut-set in question.                      [l] IEEE Std 493-1980, Recommended
         More commonly, expected duration is                           Practice for the Design of Reliable In-
         expressed in hours and the expected                           dustrial and Commercial Power Systems.
         down-time has the number of hours                             [2] IEEE COMMITTEE REPORT, Re-
         per year.                                                     port on Reliability Survey of Industrial
           Approximate expressions for frequency                       Plants, Part I: Reliability of Electrical
         and expected duration of the most com-                        Equipment, IEEE Transactions on Indus-
         monly considered interruption events                          try Applications, pp. 213-235, March/
         associated with first-, second-, and third-
                                                                       April 1974.
         order minimal cut-sets are given in Table
         16. Note that expressions for the calcula-                    [3] IEEE COMMITTEE REPORT, Reli-
         forced outages (failures) only. A detailed                    ability of Electric Utility Supplies to
         treatment of expressions for the calcula-                     Industrial Plants, Conference Record
         tion of interruption frequency and dura-                      1975 I & CPS Technical Conference,
         tion considering forced outages as well as                    pp. 131-133.
196
Authorized licensed use limited to: IEEE Xplore. Downloaded on November 08,2014 at 04:51:47 UTC from IEEE Xplore. Restrictions apply.
                                    12. Grounding Mat Studies
Authorized licensed use limited to: IEEE Xplore. Downloaded on November 08,2014 at 04:51:47 UTC from IEEE Xplore. Restrictions apply.
       IEEE
       Std 399-1980                        INDUSTRIAL AND COMMERCIAL POWER SYSTEMS ANALYSIS
       from these references). Although the test                    the sum of the intervals of the individual
       results on ventricular fibrillation were                     shocks. The same series of tests also
       actually taken from animals with body                        showed that the body can tolerate much
       and heart weights comparable t o those                       more current flowing from one leg to the
       of a man, the results have been generally                    other than it can when current flows
       accepted as being valid for human beings.                    from one hand to the legs.
       These studies have determined that 99.5                         Figures 101 and 102 show two typical
       percent of all healthy men can tolerate a                    shock hazard situations and the equiva-
       current through the heart region defined                     lent resistance diagrams. Figure 101
       by                                                           shows a touch contact with current flow-
                                                                    ing from operator’s hand t o his feet. Fig-
                                                                    ure 102 shows a step contact where cur-
                                                                    rent flows from one foot t o the other. In
                                                                    each case the body current Ib is driven
       where                                                        by the potential difference between
             =   maximum body current in amperes                    points A and B. Exposure t o touch po-
                                                                    tential normally poses a greater danger
          T = duration of current in seconds                        than exposure to step potential. The step
                                                                    potentials are usually smaller in magni-
       without going into ventricular fibrilla-                     tude, the corresponding body resistance
       tion. Obviously, this equation precludes                     greater, and the permissible body current
       choosing a single value for the fibrilla-                    higher than for touch contacts. (The cur-
       tion threshold current. Even a high cur-                     rent magnitude in the heart region that
       rent through the heart region can be                         causes fibrillation is the same for both
       tolerated for a brief period. Other tests                    types of contacts. In the case of step
       show that this threshold current is ap-                      potentials, however, not all current flow-
       proximately five times greater for direct                    ing from one leg to the other will pass
       current [5] and as much as 25 times                          through the heart region.) The worst
       greater for 3000 Hz [6]. Therefore, Eq 1                     possible touch potential (called mesh
       should embody sufficient conservatism                        potential) occurs at or near the center of
       for all cases where an individual might be                   a grid mesh. Accordingly, industry prac-
       exposed to 60 Hz ac fault potentials                         tice has made mesh potential the standard
       (the dc component of asymmetrical fault                      criterion for determining safe ground mat
       current is accurately recognized by a                        design. In most cases, controlling mesh
       suitable correction factor described in a                    potential will bring step potentials well
       later section).                                              within safe limits inside the area defined
         Tests indicate that the heart requires                     by the grounding mat. Step potentials
       about five minutes to return t o normal                      can, however, reach dangerous levels at
       after experiencing a severe shock [l].                       points immediately outside the grid.
       This implies that two or more closely                          Since the body of a man exposed to an
       spaced shocks (such as those that would                      electrical shock forms a shunt branch in
       occur in systems with automatic re-                          an electrical circuit, the resistance of this
       closing) would tend to have a cumulative                     branch must be determined to calculate
       effect. Present industry practice considers                  the corresponding body current. Gen-
       two closely spaced shocks to be equiva-                      erally, the hand and foot contact resis-
       lent to a single shock whose duration is                     tances are considered to be negligible.
198
Authorized licensed use limited to: IEEE Xplore. Downloaded on November 08,2014 at 04:51:47 UTC from IEEE Xplore. Restrictions apply.
                                                                                                                   IEEE
       GROUNDING MAT STUDIES                                                                                Std 399-1980
                                                         Fig 101
                                                      Touch Potential
                                                          Fig 102
                                                       Step Potential
       However, resistance of the soil directly                     mate resistance of 3p, where ps is the soil
       underneath the foot contact area is con-                     resistivity [ 3 ] . The body itself has a
       sidered significant. Treating the foot as a                  total measured resistance of about 2300
       circular plate electrode gives an approxi-                   52 hand to hand or 1100 52 hand t o foot.
199
Authorized licensed use limited to: IEEE Xplore. Downloaded on November 08,2014 at 04:51:47 UTC from IEEE Xplore. Restrictions apply.
       IEEE
       Std 399-1980                         INDUSTRIAL AND COMMERCIAL POWER SYSTEMS ANALYSIS
       In the interest of simplicity and con-                       therefore depends solely upon the char-
       servatism, IEEE Std 80-1976 [6] recom-                       acteristics of the permanent physical
       mends the use of 1000 S2 as a reasonable                     installation. Grid voltages depend upon
       approximation for body resistance. This                      three basic factors: ground resistivity,
       yields a total branch resistance of                          available fault current, and grid geometry.
                                                                    Proper consideration of each of these
                                                                    factors allows the analyst t o recognize
                                                                    both hazardous and overly conservative
       for foot t o foot currents and                               designs.
                                                                       12.3.1 Ground Resistivity. Obviously,
                                                                    the simplest grounding mat analysis in-
                                                                    volves a grid in a homogeneous medium.
       for hand t o foot currents where p, is the
                                                                    Unfortunately, substations must be
       surface resistivity in ohm meters and R is                   located according to factors other than
       expressed in ohms. If the station surface                    the ease of calculating grid voltages.
       has been dressed with crushed rock or                        Fortunately for those concerned with
       some other high resistivity material,                        such calculations, the homogeneous
       resistivity of the surface layer material                    medium assumption is sufficiently accu-
       should be used in Eq 2 and Eq 3.                             rate for most soils. Also, a number of
         Because potential is easier to both cal-                   nonhomogeneous soils can be modeled
       culate and measure than current, the                         by two-layer techniques [7], [8] . Al-
       fibrillation threshold given by Eq 1 is                      though reasonably straightforward, these
       normally expressed in terms of voltage.                      methods involve many tedious calcula-
       Combining Eq 1, Eq 2, and Eq 3 gives                         tions making computation by hand diffi-
       the maximum tolerable step and touch                         cult. The two-layer model is necessary
       potentials:                                                  only for locations where bedrock and
                                                                    other natural soil layers are close enough
                                                                    to the surface to severely affect the dis-
                                                                    tribution of current.
                                                                       Of far more serious concern are soils
                                                                    which experience drastic and unpredict-
                    (1000 S2 + 1.5pS)(0.116)
        Etouc h =                                      (Eq 5)       able changes in resistivity at the earth’s
                                 0                                  surface. These situations present prob-
                                                                    lems :
        12.3 The Physical Circuit. Although in                         (1)Difficulty of modeling soil in calcu-
        each of the cases discussed above man’s                     lations
        body resistance shunts a part of the                           (2) Physical difficulties in finding dis-
        ground resistance, its actual effect on                     continuities in the field and measuring
        voltage and current distribution in the                     local soil resistivity.
        overall system is negligible. This becomes                     At present, these cases are normally
        obvious when the normal magnitude of                        handled by the inclusion of a safety
        the ground fault current (as much as                        margin in the value used for the soil
        several thousand amperes) is compared                       resistivity.
        to the desired body current (usually no                        A description of a simple method of
        more than several hundred milliamperes).                    measuring soil resistivity of homogene-
        Voltage rise of any point within the grid                   ous soils is given in [ 6 ] . Techniques also
200
Authorized licensed use limited to: IEEE Xplore. Downloaded on November 08,2014 at 04:51:47 UTC from IEEE Xplore. Restrictions apply.
                                                                                                                  IEEE
      GROUNDING MAT STUDIES                                                                                Sts 399-1980
                                                                   where
      exist for measuring the resistivity of each
      layer of two-layer soils [ 8 ] . Because soil                    I = maximum fault current, amperes
      resistivity varies with moisture content                             (note that this is not the same as
      and, to a lesser degree, with temperature,                           the current, Ib,in Eq 1)
      these measurements should be made over                          V = phase to neutral voltage, volts
      a period of time under different weather                       Rg = grid resistance t o earth, ohms
      conditions. If for some reason actual                          R, = positive sequence system resis-
      measurement of resistivity is impractical,                           tance, ohms
      tables of approximate values of resistivity                    R2 = negative sequence system resis-
      for soils of various composition have                                tance, ohms
      been compiled by several sources. Table
                                                                     Ro = zero sequence fault path resis-
      1 7 is a sample table [9]. These values are
                                                                           tance, ohms
      only approximations and should be re-
      placed in the study by more accurate                          X y = positive sequence subtransient
      figures whenever possible.                                           system reactance, ohms
        12.3.2 Fault Current-Magnitude and                           X 2 = negative sequence system reac-
      Duration. Determination of ground fault                              tance, ohms
      current normally entails a separate study.                     X o = zero sequence fault path reac-
      Techniques and problems of making fault                              tance, ohms
      studies are covered in numerous sources.
      This section will only cover aspects                         This current will, in general, be a sinu-
      peculiar t o grounding grid studies.                         soidal wave with a dc offset. Since dc
        After the system impedance and grid                        current can also cause fibrillation, the
      resistance have been determined, the                         current value I must be multiplied by an
                                                    Table 18
                                     Decrement Factor for Use in Calculating
                                           Electrical Shock Effect of
                                           Asymmetrical ac Currents
                                    Shock and Fault Duration
                                   Seconds      Cycles (60 Hz)             Decrement Factor
                                 0.008                  Ih                         1.65
                                 0.1                     6                         1.25
                                 0.25                  15                          1.10
                                 0.5 o r more          30 or more                  1.o
201
Authorized licensed use limited to: IEEE Xplore. Downloaded on November 08,2014 at 04:51:47 UTC from IEEE Xplore. Restrictions apply.
       IEEE
       Std 399-1980                        INDUSTRIAL AND COMMERCIAL POWER SYSTEMS ANALYSIS
       appropriate correction factor for this                          Study of maximum ground fault cur-
       effect. This multiplier is called the decre-                 rent alone is not sufficient. Any low mag-
       ment factor in [ 6 ] , and a table of ap-                    nitude ground fault current that might
       proximate values for it is provided (re-                     persist for several minutes or more also
       produced in Table 18). For more ac-                          presents the very real danger of asphyxi-
       curate results, the exact value for the                      ation. A fault current capable of induc-
       decrement factor D is given by the                           ing body currents of 10 to 25 mA can
       equation                                                     cause muscular paralysis in a man, in-
                                                                    cluding his lungs. Since the majority of
                                                                    people resume normal respiration upon
                                                                    removal of the current, interruption
                                                                    times of a minute or so at this level
       where                                                        should prevent any lasting injury from
                                                                    this particular effect. A grounding mat
          T = duration of fault, seconds                            design can be checked for this hazard by
          o =system frequency in radians per                        first finding the ground fault current
              second                                                that will result in a body current of 10
          X =total system reactance, ohms                           mA, then considering the protective re-
          R =total system resistance, ohms                          laying scheme to determine the time
         The current value calculated in Eq 6                       required to detect and interrupt this
       must be multiplied by this factor to find                    current. If the time is one minute or less,
       the effective fault current. Note that                       asphyxiation should not be a danger.
       time T in Eq 7 is the same as that used in                     An accurate estimation of the ultimate
       Eqs 1, 4, and 5. To determine the fault                      system fault capability is necessary to
       duration it is necessary t o analyze the                     ensure a safe design throughout the life
       relaying scheme t o find the interrupting                    of the substation or plant. Normal indus-
       time for the current calculated by Eq 6.                     try experience indicates that fault cur-
       Substitution of this time into Eqs 4 and                     rents rise as power systems are expanded
       5 will fix the maximum allowable step                        and modernized. After the initial con-
       and touch potentials at the appropriate                      struction phase, however, changes t o the
       values. These maximum allowable poten-                       ground mat are prohibitively expensive.
       tials are used t o check the voltages actu-                  Therefore, it is vital to consider the total
       ally present within the grid. If any volt-                   future expansion in the initial ground
       ages exceed maximum limits, the grid                         mat design.
       should be redesigned.                                           12.3.3 Fault Current-The Role of Grid
         The choice of the clearing time of                         Resistance. Accurate calculation of
       either the primary protective devices or                     ground fault currents presupposes that
       the backup protection for the fault dura-                    an accurate and dependable value for the
       tion depends on the individual system.                       grid resistance can be calculated. More
       Designers must choose between the two                        literature exists on this aspect of ground-
       on the basis of the estimated reliability                    ing mat design than any other, so finding
       of the primary protection and the desired                    an approximate value for the required
       safety margin. Choice of backup device                       grid resistance is not particularly diffi-
       clearing time is more conservative, but it                   cult. Most of the equations and tech-
       will result in a more costly ground mat                      niques developed to calculate grid re-
       installation.                                                sistance are based on several simplifying
202
Authorized licensed use limited to: IEEE Xplore. Downloaded on November 08,2014 at 04:51:47 UTC from IEEE Xplore. Restrictions apply.
                                                                                                                   IEEE
       GROUNDING MAT STUDIES                                                                                Std 399-1980
       assumptions, however, and produce re-                         Another method for determining grid
       sults that are, by necessity, both con-                     resistance (with greater accuracy than
       servative and somewhat inaccurate. For                      the previously described method) offers
       the most part the accuracy of the grid re-                  the advantage of lending itself t o use in a
       sistance equations depends upon how                         computer program that can precisely cal-
       well they account for the different grid                    culate voltages at any location within a
       configurations likely to be encountered.                    general grid configuration. It simply ex-
         A formula for a quick simple calcula-                     presses grid-to-ground resistance as the
       tion of resistance when a minimum of                        total voltage rise of the grid (relative t o a
       design work has been completed is given                     “remote” ground reference) divided by
       in [GI                                                      total fault current. This method can be
                                                                   applied t o any grid configuration with
       R = -P+ - P                                                 any number of conductor elements.
            4r L                                                   However, because an accurate determin-
                                                                   ation of the total voltage rise depends on
       where                                                       the solution to a potentially overwhelm-
         R = grid resistance t o ground, ohms                      ing array of involved mathematical ex-
          p = soil resistivity, ohm meters                         pressions, this method is not well suited
         L = total length of grid conductors,                      for hand calculations.
              meters                                                 Since grid resistance is viewed as a
          r = radius of a circle with area equal                   measure of the grid’s ability to disperse
              to that of the grid, meters                          ground fault current, many designers are
         Grid resistance depends on soil resistiv-                 tempted t o use resistance as an indicator
       ity, grid area, and total length of the                     of relative safety of a ground mesh. In
       conductors forming the grid. These vari-                    general, however, there is no direct cor-
       ables influence the resistance so heavily,                  relation between grid resistance and
       that Eq 8 does not consider any others.                     safety. At high fault currents, dangerous
       By inspecting Eq 8 it also becomes evi-                     potentials exist within low resistance
       dent that adding grid conductors to a                       grids. The only occasion when a low grid
       mat to reduce its resistance eventually                     resistance can guarantee safety is when
       becomes ineffective. As the conductors                      maximum potential rise of the entire
       are crowded together, their mutual inter-                   grid (that is, grid potential) is less than
       ference increases to the point where new                    allowable touch potential.
       conductors tend only to redistribute                            12.3.4 Grid Geometry. The potential
       fault current around the grid, rather than                   rise of points protected by a grounding
       lower its resistance.                                        mat depends on such factors as: grid
         The first term of Eq 8 gives the resis-                    burial depth, length and diameter of con-
       tance of a circular plate with the same                      ductors, spacing between each conductor,
       area as the grid. The second term allows                     distribution of current throughout the
       for the grid’s departure from the idealized                  grid, proximity of the fault electrode
       plate model. The more the length of the                      and the system grounding electrodes to
       grid conductors increases, the smaller                       the grid conductors, along with many
       this term becomes. This equation is ideal                    other considerations of lesser importance.
       for the initial stages of a study where                      A perfectly rigorous analysis of all these
       only the most basic data about the ground                    variables for a grounding grid with any
       mat are available.                                           number of conductor elements would,
203
Authorized licensed use limited to: IEEE Xplore. Downloaded on November 08,2014 at 04:51:47 UTC from IEEE Xplore. Restrictions apply.
       IEEE
       Std 399-1980                         INDUSTRIAL AND COMMERCIAL POWER SYSTEMS ANALYSIS
        at the very least, involve solving a like       Coefficients K, and & are calculated
        number of (1)differential equations (to     by two reasonably simple equations based
        find the current distribution along each    upon the number of grid elements, their
        line) [ 8 ] , [5], and (2) simultaneous     spacing and diameter, and depth of burial
        linear algebraic expressions (to find the   of the grid. Many assumptions made in
        current distribution throughout the         developing these equations were not
        entire grid) [ 161 . Although unfortunate,  meant to describe rigorously either
        it is hardly surprising that the quantita-  industry practices or physical law, but
        tive effect of these factors upon touch     were instead intended to simplify and
        and step potentials is one of the most      make manageable what would otherwise
        infrequently discussed aspects of grid      be a very involved analytical procedure.
        analysis.                                   Equations 9 and 10 incorporate an irreg-
           Paradoxically, these factors include     ularity factor Ki to compensate for the
        most of the elements of grid design that    inaccuracies introduced by these simpli-
        normally must be changed to control         fying assumptions. Except for applica-
        grid voltages. Obviously, any analytical    tions involving very simple grid config-
        method that cannot predict the effect       urations, proper selection of a value for
        of important changes in grid geometry is    Kiis totally dependent upon the experi-
        of limited utility for design purposes.     ence and judgment of the designer. Most
        Fortunately, some of these factors can      choose to err on the side of safety and
        be (and, for the sake of practicality,      make Ki large, which results in an over
        should be) safely ignored, while (un-       designed ground mat installation-usually
        fortunately) others are vitally important   safe, but often expensive.
        to a reliable and accurate analysis.            Equations 9 and 10 yield a single value
           Until recently, [6] provided the only    of Emeshand Esteprespectively, for any
        practical formulas for computing the ef-    particular ground grid system. Values
        fects of the grid geometry upon the step    obtained for Em& and Estepare intended
        and touch potentials (Eq 9 and Eq 10)       t o represent the worst case condition for
                                                    the ground grid system without provid-
                           Z
        Emesh = Km       .                   (Eq 9) ing the analyst with any information as
                                                    to where (or how often) these worst case
                                                    conditions exist within the system.
                                                    After &esh and Estepof the grid are cal-
                                                    culated, they are compared to the calcu-
                                                    lated values of the tolerable Etouch and
        where                                       Estepas determined from Eq 4 and Eq 5,
            p = soil resistivity, ohm meters        respectively, in order to establish whether
             Z = maximum total fault current, or not the design can be judged to be
                 amperes (adjusted for the decre- safe. If, in fact, Emeshexceeds EtoWh-
                 ment factor)                       t o l e r a e andlor Estep exceeds Estep-tolerable
                                                    it is sometimes possible by inspection of
            L = total length of grid conductors,
                                                    the grid to determine mesh locations
                 meters
                                                    where additional cross-conductors should
          Km = mesh coefficient                     be added in order to achieve a safe de-
           Ks = step coefficient                    sign. The more general approach, how-
           Ki = irregularity factor                 ever, especially when either of the toler-
204
Authorized licensed use limited to: IEEE Xplore. Downloaded on November 08,2014 at 04:51:47 UTC from IEEE Xplore. Restrictions apply.
                                                                                                                     IEEE
    GROUNDING MAT STUDIES                                                                                     Std 399-1980
     able values is more than only slightly ex-                  below the earth's surface. The element
     ceeded, is to uniformly increase the                        runs from point (xl, yl, zl) to (xl, y 2 , zl)
     number of subdivisions in the original                      and is radiating current to the surround-
     system of grid meshes so as t o result in a                 ing earth at the linear current density
     lower calculated value of either Emeshor                    U, (the current per unit length). By inte-
     Estep (or both). Accordingly, substantial                   grating U, over the length of the grid
     overdesign and unnecessary investment                       element, the current flux 6 can be found
     in buried conductor may result.                             at any desired point a as follows:
       Although this traditional method for
     calculating step and mesh potential has
     given long and faithful service, grounding
     mat analysis computer programs provide
     more information about the effectiveness                     where
     of the ground mat design. Greater accu-                         6   =   current/unit area at any point
     racy results because calculation by com-                        o, = current     flowing to ground/unit
     puter program does not require as many                                  length of conductor (current den-
     simplifying assumptions.                                                sity)
       More specifically, the key t o an accur-
     ate ground grid analysis is the considera-
     tion of each individual grid element,                          R = J (-i              + (j - y ) 2 + ( h - z1)2
     rather than the en masse treatment used                                  (i - x l ) i + (j - y ) j + ( h - z l ) h
     in [ 6 ] . Fig 103, for example, shows a                         r=
     single grid element located some depth h                                d(i- x1)2 + 0' - y ) 2 + ( h - Z1)*
                                                  Fig 103
                                 Physical Model Used in Calculating Voltage
                                    at Point a Due to a Single Conductor
205
Authorized licensed use limited to: IEEE Xplore. Downloaded on November 08,2014 at 04:51:47 UTC from IEEE Xplore. Restrictions apply.
          IEEE
          Std 399-1980                         INDUSTRIAL AND COMMERCIAL POWER SYSTEMS ANALYSIS
          Once 6 has been determined, the E-field                      lady important consideration when find-
          at the same point a can be expressed as                      ing the potential at points near the end
          follows for a homogeneous soil:                              of an element (that is, at the comers of a
                                                                       ground mat). It can handle grid designs
                                                                       with large degrees of asymmetry with no
                                                                       sacrifice of accuracy (symmetry is not
          where p is soil resistivity. From this, the                  presupposed as with the calculating pro-
          voltage at point a can be obtained by                        cedures in [6]).Further, since point a
          performing the classical integration:                        can be located anywhere and examined
                                                                       as often as required, detailed analysis of
                                                                       grid design is possible. The most signifi-
                                                                       cant disadvantage of this and other simi-
                                                                       lar techniques is the number of tedious
                                                                       calculations that must be performed t o
                                                                       accurately model a system. However,
                   P9                                                  modem digital computers have all but
              = --In        ci, - y 2                                  eliminated this concern.
                   4a
206
Authorized licensed use limited to: IEEE Xplore. Downloaded on November 08,2014 at 04:51:47 UTC from IEEE Xplore. Restrictions apply.
                                                                                                                 IEEE
    GROUNDING MAT STUDIES                                                                                Std 399-1980
                                          39
                                         136)
GRID A GRID8
GRID C GRID D
                                                                        8 0 84 85
                                                                       I 0 84 185 184)
                                                                        8 4 8 7 8 9 8 6
                                                                       (85)187) 188 1871
                                                                                              57
                                                                                              1571
GRID E GRID F
                                            Fig 104
                     Experimental Grids Showing Various (Mesh) Arrangements
207
Authorized licensed use limited to: IEEE Xplore. Downloaded on November 08,2014 at 04:51:47 UTC from IEEE Xplore. Restrictions apply.
        IEEE
        Std 399-1980                         INDUSTRIAL AND COMMERCIAL POWER SYSTEMS ANALYSIS
        two calculated point voltages (taken one                      needed for each area of the grid through
        meter apart) should be compared with                          the use of the ground mat analysis com-
        the maximum allowable step voltage.                           puter program.
           Figure 104 (especially grids E and F)
        illustrates the accuracy of the program.                      12.5 Input Data Requirements. Like all
         Errors are typically on the order of 5 per-                  other system studies, a grounding mat
         cent, and never worse than 1 0 percent.                      analysis study has specific data require-
         Even the results for grids E and F, both                     ments. The omission of some critical bit
         of which are highly irregular, are well                      of data during a study can significantly
        within acceptable design accuracy.                            affect the validity of the entire study
           The most impressive feature of this                        and its conclusions.
        program, however, is its ability t o calcu-                      Normally, the first step in any ground
        late voltages at any point of interest                        mat study is the determination of the
        within or around the mat’s geometric                          soil resistivity. If the soil resistivity varies
         boundaries. By repeated use of the pro-                      significantly from location to location,
         gram throughout the design process, a                        the calculated point potentials should be
        grounding mat layout can be fine-tuned                        multiplied by an adjustment factor (on
        t o achieve the desired protection with-                      the order of 0.8 to 0.9) to compensate
        out the need to overdesign any section                        for uncertainty about the exact resistiv-
        of the mat.                                                   ity at any given location. Any extremes in
           This process is illustrated in Figs 105-                   weather conditions that might seriously
        108 using the typical ground mat design                       affect the soil’s resistivity should also
        from [Appendix B, 181. Figure 105                             be examined. This usually applies to
        shows the grid layout and all pertinent                       droughts that can dry out the soil or
        grid information. Figure 106 gives the                        unusually severe winters that could
        results of a computer analysis of the grid                    freeze the soil below the effective depth
        clearly defining the areas of maximum                         of the grid. If the substation surface is
        danger. Figures 107 and 108 show the                          covered with a layer of crushed rock, its
        results of modified grid designs. Note in                     resistivity must also be determined.
        Fig 108 that the amount of additional                            The next logical step is the determina-
        conductor required to safely control                          tion of the maximum permissible mesh
        mesh potentials in the grid has been                          potential. Many industries have estab-
        minimized and that the use of the com-                        lished a standard value for the maximum
        puter program has permitted the loca-                         mesh potential. Otherwise, the estimated
        tion of this conductor t o be optimally                       fault duration and resistivity of the
        determined (that is, the conductor has                        material at the surface must be used to
        been added only where required).                              calculate the maximum safe mesh poten-
           Normally, mesh potentials are greater                      tial from Eq 5. If a layer of crushed rock
        along the outside perimeter of a grid,                        has been applied to the surface, the cor-
        especially at the corner. These potentials                    rect value of soil resistivity should be
        can be controlled by decreasing the dis-                      used to calculate the maximum safe
        tance between grid elements, but if the                       mesh potential for locations without
        same spacing is used throughout the grid                      surface treatment.
        the interior areas of the grid will, in                          To determine the “total” fault current,
        general, be overprotected. Again, the                         the maximum future value of the avail-
        designer can determine the exact spacing                      able symmetrical ground fault current
208
Authorized licensed use limited to: IEEE Xplore. Downloaded on November 08,2014 at 04:51:47 UTC from IEEE Xplore. Restrictions apply.
                                                                                                                 IEEE
     GROUNDING MAT STUDIES                                                                                Std 399-1980
                                                                                         - rn
                                                                      psoil=   1316
                                                                     Psudace = 3 0 0 0
                                                                     ‘fault, =    A
                                                                                         ’      rn
                                                                     K, = 368
                                                                     K,=.814
                                                                      Ki = 2.0 (touch), 2.5ktep)
                                                                     Etouch/worse case =   21
                                                                     Estep/worse case = 2010
                                                     Fig 105
                                      Typical Ground Mat Design Showing
                                       All Pertinent Soil and System Data
209
Authorized licensed use limited to: IEEE Xplore. Downloaded on November 08,2014 at 04:51:47 UTC from IEEE Xplore. Restrictions apply.
      IEEE
      Std 399-1980                         INDUSTRIAL AND COMMERCIAL POWER SYSTEMS ANALYSIS
                                                                                   DANGEROUS
                                                                             @#    MARGINAL
                                                                                   SAFE
                                                        Fig 106
                                        Typical Ground Mat Design Showing
                                          Meshes with Hazardous Potentials
                                         as Identified by Computer Analysis
210
Authorized licensed use limited to: IEEE Xplore. Downloaded on November 08,2014 at 04:51:47 UTC from IEEE Xplore. Restrictions apply.
                                                                                                                   IEEE
       GROUNDING MAT STUDIES                                                                                Std 399-1980
                                                                                   DANGEROUS
                                                                                   MARGINAL
                                                                              0SAFE
                                                  Fig 107
                                 Typical Ground Mat Design, First Refinement
                               Showing Meshes with Hazardous Touch Potentials
211
Authorized licensed use limited to: IEEE Xplore. Downloaded on November 08,2014 at 04:51:47 UTC from IEEE Xplore. Restrictions apply.
        IEEE
        Std 399-1980                        INDUSTRIAL AND COMMERCIAL POWER SYSTEMS ANALYSIS
                                                                                    DANGEROUS
                                                                               a     MARGINAL
                                                                               0SAFE
                                                         I
                                                         1
                                                    Fig 108
                                   Typical Ground Mat Design, Final Refinement
                                       with no Hazardous Touch Potentials
212
Authorized licensed use limited to: IEEE Xplore. Downloaded on November 08,2014 at 04:51:47 UTC from IEEE Xplore. Restrictions apply.
                                                                                                                     IEEE
    GROUNDING MAT STUDIES                                                                                    Std 399-1980
                                                                           Grid
                                                                           Conducterr
    can then be multiplied by one another t o                             d                        d z 1 mete!
213
Authorized licensed use limited to: IEEE Xplore. Downloaded on November 08,2014 at 04:51:47 UTC from IEEE Xplore. Restrictions apply.
          IEEE
          Std 399-1980                        INDUSTRIAL AND COMMERCIAL POWER SYSTEMS ANALYSIS
214
Authorized licensed use limited to: IEEE Xplore. Downloaded on November 08,2014 at 04:51:47 UTC from IEEE Xplore. Restrictions apply.
                                                                                                                IEEE
   GROUNDING MAT STUDIES                                                                                Std 399-1980
215
Authorized licensed use limited to: IEEE Xplore. Downloaded on November 08,2014 at 04:51:47 UTC from IEEE Xplore. Restrictions apply.
         IEEE
         Std 399-1980                                      INDUSTRIAL AND COMMERCIAL POWER SYSTEMS ANALYSIS
           .- . . . ...
                     , , a
          *          . . a
          >          I . ,
          3
          L
          -a
            - . . . ...
                     . . a
                     . I .
                     . a .
                     I . ,
               .. .. .. ....
                     8 . B
                     . . o
                     , I *
. . a
               .. .. .. ...
                     , I .
                     , . a
                     . . I
                           .
                     ., * . . . .....             -
                     .. .I I I
                                                  -8
                                                  4
                     I       ,       ,
                     a . ,
                                                  c
                     . . I                        z
                      .. .. .. ...
                                                  r
                                                  .
                                                  Y
                     , a .
                     1 . 1                        0
                     Q  I  I
* a , I
                                   .
                                                  3
                                                  U
                           ..
                     . . I
                     1 . 1
                     .,,
                     . . a
                     .,. .  ..
                     . . I
                     .       I       *
                                             0
                     ..,
                     . ....
                     1 . 1                   0
                                             0
                     . , a .
                     ,o.
                                 . I
           I
                Y    .-. ..
                     . 0 .
                     . 0 .
                     . 0 .
                      I              .
          W
           2-
          ?IZ
                 O
                     '.' :...
                     .
                     I
                      .
                                     e
                                     I
                                     I
                                                  w
                                                  c
                                                  3
                         - ..
                     . > e                        A
          0     -    ,r,                          o
                =J   .c.                          ng
                     .". - ...
           Y         ,>.                          D
                                                  4
           2-        . - e                   0
           * m        . t o                  0
           L         .n,                     0
           - U        ...e
                     . . . ...
           I
           ..
           * ) L      Q U I
                      .a.
                      1              .
                     . . . ...
                      . I .
                      1 . 1
                                                                      . . --
                ... ,.... .. ...
                      m Q S
                      . I .
                      1 . 1
. -- a .
.,. . . I
                               .             0
                                                       a
                                                                        .-
                                                                        .
                                                                                                     0
                                                                                                     n
                                                                                                         .
                                                                                                         .
                                                                                                                 y
                 ....* .. .. ...
                                                                                                                 7
                                                                      -
                      0 . .                  0
                      1 . 1                  el                                                          .   N
                                                                                                         . N
                      . . I
                         I , ,
                      1 . 1    ..                                     - .                            n
                                                                                                     4
                                                                                                     O
                                                                                                         .
                                                                                                         .
                         .I . ,a .
           0             1 . 1
                   ::: :  - .:..
           3             1 . 1
                   .*.
           r             I . .
           . . . . . ..
           U
           U
                         1 . 1               e
                                             I
                                             U
                   . . . :...
           c             . I .               L
           -8            1 1 1
           - :::
           P
           0
           I
           0              -.
                         Q 1 1
                         e . .
                         I . .
                         Q Q t
                                             2
                                             r
                                             -8
                                             3
                   . . . ..
                         .Q.                 L
           0             . . e
           I             S L Q
           3             Q I @
           0             I I Q
                         . . I
           0
216
Authorized licensed use limited to: IEEE Xplore. Downloaded on November 08,2014 at 04:51:47 UTC from IEEE Xplore. Restrictions apply.
                                         13. Computer Services
     13.1 Introduction. The bulk of this book                    turn-around time, output interpretation,
     is concerned with the details of power                      and with the sources of aid when prob-
     system analysis by the use of computers.                    lems arise.
     Very little, t o this point, has been said
     about computers, programs, or require-                      13.2 Computer Systems. There are basic-
     ments for their use. Many readers are                       ally two types of computer systems avail-
     not aware of the wide variety of compu-                     able t o prospective users
     tational aids available, or factors that are                   (1)In-house company owned or leased
     important in choosing the most appro-                       systems
     priate aids for their particular needs.                       (2) Commerical computing services
     This chapter discusses computer systems,                    available in a wide variety of types
     services, their use, and the availability of                  13.2.1 In-House Systems. The in-house
     such services. Factors impacting the se-                    system is normally used by firms with a
     lection of such things as in-house sys-                     considerable amount of data processing
     tems, commercial services, time sharing,                    requirements. Most of these systems are
     batch systems, and other decisions which                    general purpose installations with re-
     must be made when selecting the most                        sources shared by several company de-
     appropriate computing aids are discussed.                   partments (for example, Engineering,
       The efficiency of these computing tools                   Accounting, Project Control, etc). Some-
     can be increased considerably if the user                   times a company requires special purpose
     has an idea of what to expect and is well                   computer equipment to support its
     prepared before beginning his analysis.                     engineering operations, and can buy or
     This section will strive t o acquaint pro-                  lease analog or hybrid computer systems.
     spective computer users with the prob-                      These systems are used almost exclusively
     lems of data preparation, job submittal,                    for technical applications. Resources,
217
Authorized licensed use limited to: IEEE Xplore. Downloaded on November 08,2014 at 04:51:47 UTC from IEEE Xplore. Restrictions apply.
          IEEE
          Std 399-1980                         INDUSTRIAL AND COMMERCIAL POWER SYSTEMS ANALYSIS
21 8
Authorized licensed use limited to: IEEE Xplore. Downloaded on November 08,2014 at 04:51:47 UTC from IEEE Xplore. Restrictions apply.
                                                                                                                IEEE
  COMPUTER SERVICES                                                                                     Std 399-1980
  for computer programs, batch and on-                          sultant comes t o the user and helps find
  line. Batch programs are initiated and                        the necessary data for the analysis. The
  executed by submitting a job via card                         consultant then performs the computer
  deck, or terminal input. Once initiated, a                    study and informs the user of the result.
  batch program runs t o completion with-                       This type of study is quite expensive
  out interfacing with the user. On-line, or                    when compared to studies in which the
  time sharing programs, are executed                           user is more involved. Between these
  from terminals. They may require the                          extremes is a wide variety of services
  user to interact by responding t o prompt-                    which can be piece meal or complete
  ing by the computer through the remote                        analysis reports. In a piece-meal analysis
  terminal.                                                     the results of initial computer runs must
      Batch and on-line programs are avail-                     be manually transcribed and input to
  able either on commercial services or on                      later runs. For example, load flow analy-
  in-house systems. In either case, program                     sis results are required for short circuit,
  initiation is via remote terminal (for                        motor starting, and stability program in-
  example, batch entry card reader, or on-                      put data. Complete analysis systems
  line time sharing terminals). Batch pro-                      allow results of these initial studies to be
  grams are run by the service upon re-                         stored and reused as input, with only the
  ceiving the user data in the mail. On-line                    additional data necessary for the later
  programs are more costly in the use of                        study required from the user.
  computer resources and in general cost                          Commercial services include user man-
  the user more per computation than                            uals and input data sheets (for batch
  batch programs. On-line programs do, on                       programs) and in most cases some
  the other hand, allow more timely                             amount of consultation for the user.
  answers, which means reduced turn-                            This consultation is very valuable in im-
  around time. The user can quickly scan                        proving the effectiveness of using a
  the results and make changes t o the data                     service. The availability of consultation
   if necessary for subsequent runs. Turn-                      varies between services and should be
   around time is defined as the elapsed                        considered when selecting a commercial
   time between submittal of a problem                          service. This consultation should be
   and receiving the output results.                            sought early in the analysis to avoid
      As mentioned previously, the amount                       problems and wasted man-hours and
   of service varies greatly in the amount of                   computer runs.
   consultation available between comput-
   ing services. A greater amount of service                    13.4 Use of Computing Services. After
   implies a higher cost. At one extreme,                       deciding which type of computing
   programs obtained from free sources                          service is most appropriate for the user’s
   might not have enough documentation.                         present needs, several service representa-
   In these cases input and output format                       tives should be contacted by mail or
   can be determined from analyzing the                         phone. The larger national computing
   program code and the usability of the                        services have representatives in most
    output format may be questionable. On                       large cities and will gladly send informa-
   the other end of the spectrum is the                         tion or a representative on request. A
   total hands-off analysis by a consultant                     user should study available user manuals
    type computer based on the user’s speci-                    and company literature to determine if
    fications and data. In this case, the con-                  the computing service in question has
219
Authorized licensed use limited to: IEEE Xplore. Downloaded on November 08,2014 at 04:51:47 UTC from IEEE Xplore. Restrictions apply.
          IEEE
          Std 399-1980                        INDUSTRLAL AND COMMERCIAL POWER SYSTEMS ANALYSIS
          clear and complete instructions for data                     manuals normally have a section explain-
          entry. They should also give some ex-                        ing output reports. What is lacking in
          planation on how t o interpret the out-                      many user manuals is trouble-shooting
          put, or results.                                             advice if the results appear to be not as
            In general, input data is the same as                      expected. All results of computer pro-
         that needed for hand calculations. It                         grams should be scrutinized for answers
         may, however, be required in a different                      which are contrary t o what the user’s
         form than is immediately available t o the                    experience would predict. If the cause of
         user. Some programs require data in per-                      the discrepancy is not obvious from the
         cent or per unit on a defined base, while                     printout or cannot be discerned from the
         others can be on the specific base of the                     user manual, the computing service’s
         piece of equipment. The user must con-                        consultant should be contacted. Reports
         sult the user manual and give the input                       can be mailed to the user or printed di-
         data as required. It should be noted that                     rectly at his location, depending on the
         most problems encountered through a                           amount of hardware the user has.
         computer program are caused by errors
         in input data. One should be extremely                        13.5 Availability of Computing Services.
         careful when converting data to the form                      Computing services are available to any-
         required by the program. Data should be                       one who has access to a telephone. Tele-
         as complete as possible whether sub-                          phone lines are the normal means of
         mitted via mailed input data sheets, time                     communication when remote terminals
         sharing terminal, or card deck to a batch                     are used. These lines can be leased or
         card reader. The results will be only as                      paid for on a usage basis. In many cases
         good as the input data. The computer                         additional transmission hardware is re-
         has no intelligence and can only work                         quired which is usually available from
         with the data given, in exactly the man-                      the telephone company.
         ner prescribed by the program. Most                             Depending on the size of the comput-
         computing services have a consultation                       ing service being used, a large library of
         service t o aid the user in defining input                   analysis programs is available. Most
         data requirements and t o help him debug                     power system analysis programs contain
         the input data in case of program failure.                   short circuit, load flow, stability, and
         The user should take full advantage of all                   motor starting programs. The complexity
         consultation available from the comput-                      and sophistication of these programs or
         ing service.                                                 program systems vary widely. The user
            Once the input has been entered the                       must be careful to select a service whose
         time required for a response (turn-                          programs meet his needs. For example
         around time) will be a function of not                       a load flow program which can only
         only the type of program (batch or on-                       handle 50 buses may be of no use t o a
         line) but the time of day. Computing                         large utility , while being perfectly suited
         services have busy hours (prime time)                        for a small industrial application. In gen-
         which are normally described in their                        eral, the larger the computing service,
         literature. Turn-around is usually better                    the wider the selection of available pro-
         during non-prime time hours.                                 grams. Large services normally have pro-
            Output reports from most commercial                       grams of varying complexity and sophis-
         computing services are complete and                          tication to satisfy more customers.
         well labeled to aid interpretation. User                        For some users the best decision is to
220
Authorized licensed use limited to: IEEE Xplore. Downloaded on November 08,2014 at 04:51:47 UTC from IEEE Xplore. Restrictions apply.
                                                                                                                        IEEE
     INDEX                                                                                                      Std 399-1980
     contract with a general service agency                       pensive than performing the analysis in-
     which can perform most of the analysis.                      house, but is desirable if time or man-
     These services are available from engi-                      power constraints dictate so.
     neering consultants or some of the large                       Much of the information used in the
     equipment manufacturers. They permit                         preparation of this section was obtained
     an analysis as complete as the user re-                      from literature published by companies
     quests and can give advice or opinions if                    interested in data processing equipment
     desired. This type of service is more ex-                    and computing services.
                             A                                      regulated, 98
                                                                    slack or swing, 22, 52, 95, 105
     ac control devices, 1 4 1                                      unregulated active, 101
     ac fault potentials, 22                                        var limited, 101
     ac generator, 25                                               voltages, 105, 149,153, 156
     ac mesh potential, 214
     ac network analyzer, 21                                                                  C
     Acceleration factors, 101
     Accelerating time study, 144, 150, 161                       Cables, 58, 60, 175, 182, 189
     Active elements, 44                                          Capacitor starting system, 142
     Air-gap flux, 127                                            Capacitors, 1 4 2 , 1 4 3 , 1 6 6 , 1 6 7 , 1 6 9 , 1 7 5 ,
     Analog computers, 21, 24                                           179,181,185,188
     Analysis                                                     Case studies, 101, 188
       grounding mat, 206, 208, 214                               Cathode ray tube (CRT), 189
       interruptions, 26                                          Circuit breakers, 25,105, 185, 192, 194
       load flow, 217                                             Commutating reactance fact (CRF), 168
       power system, 216, 217;219                                 Component, 191-195
       reliability, 26                                            Computer services
     Analytical solution methods                                   availability of, 219
       Fourier representation, 37                                  commercial, 22, 217-219
       linearity, 29                                               systems, 216, 217
       per unit method, 42                                         types of, 217
       phasor representation, 35                                   use of, 218
       single-phase equivalent circuit, 37                        Connected load, 8 3
       sinusoidal forcing function, 34                            Contactors, 141, 161
       superposition, 30                                          Control devices
       symmetrical component analysis, 39                          ac, 141
       Thevenin equivalent circuit, 31                             dc, 141
     Applied loads, 25                                            Current
     Automatic load shedding, 134                                  harmonic, 165, 167
     Auto-transformer starter, 143,144, 149                        inrush, 1 4 1 , 1 4 2 , 1 4 9
     Availability, 191, 193                                        locked rotor, 71
     Available fault current, 198                                 Current method, 148
                                                                                             D
                             B
                                                                  Dalziel, Charles, 197
     Batch programs, 217, 218, 219                                Data
     Brake horsepower, 80                                           load, 146
     Bus (buses)                                                    machine, 146
      floating, 98                                                Data references, 8 3
      infinite, 23, 49                                            dc control devices, 143
      lighting, 140                                               dc motor drives, 164
      motor, 142                                                  Demand
      passive, 98                                                   instantaneous, 8 3
      power circuit, 182                                            maximum, 8 3
221
Authorized licensed use limited to: IEEE Xplore. Downloaded on November 08,2014 at 04:51:47 UTC from IEEE Xplore. Restrictions apply.
       IEEE
       Std 399-1980                            INDUSTRIAL AND COMMERCIAL POWER SYSTEMS ANALYSIS
                                 E                                                          I
       Electromagnetic models, 181                                    Impact loads, 24
       Expected interruption duration, 192,193,                       Impedance amplifier, 182
             195,196                                                  Impedance diagram, 22, 44, 46, 49, 55,
       Exposure time, 191                                                    56,114,119,150,151
                                                                      Impedance method, 1 4 7 , 1 4 8
                                                                      Impedances
                                F                                       circuit, 34, 147
                                                                        generator, 145
       Failure, 191, 192, 194                                           locked rotor, 147
       Failure modes and effects analysis (FMEA),                       parallel, 167
             193,194,195                                                system, 168
       Failure rate, 191, 1 9 3                                         transfer, 181
       Fault                                                            transient, 140, 141, 149
         line-to-ground, 25                                             utility, 145
         local contributions, 118                                     Induction motors, 26, 148, 153
         remote contributions, 118                                    Infinite bus, 22, 49
        switching, 190                                                In-house computer systems, 23, 216, 217,
       Fault current, 201                                                    218. 219
         multiplier, 114, 201                                         Inrush current, 1 4 1 , 1 5 2 , 1 4 9
       Fault studies, 25                                              Interrupting calculations, 114
       Floating bus, 98                                               Interruption frequency, 192, 193, 196
       Forced outages                                                 Interruptions, 21, 25,191, 192, 194,195,
         permanent, 194                                                      201
         transient, 194                                               Iteration, 100, 101
       Forced unavailability, 1 9 2
       Fourier representation, 22,29,41,42,165
       Frequency reliability studies, 194
       Frolich’s approximation, 159
                                                                      Kirchoff’s laws, 91, 178
                                G
       Galvanometers, 189, 190
       Gauss-Side1 iteration method, 101                              Lighting buses, 140
       Generator voltage regulator, 147,149,150                       Line drops, 105
       Generators, 44, 55, 66, 79, 118,144,149,                       Line-to-ground faults, 25
             156.179.181                                              Linearity, 29, 30, 31, 34, 37, 42
        impedances, 145                                               Load bus, 105
        ratings, 8 5                                                  Load data, 145
       Grid                                                           Load diversity, 80
        geometry, 197, 198                                            Load flow
        resistance, 201, 203, 208, 213                                 analysis, 105, 218
        voltages, 197                                                  harmonic, 167
222
Authorized licensed use limited to: IEEE Xplore. Downloaded on November 08,2014 at 04:51:47 UTC from IEEE Xplore. Restrictions apply.
                                                                                                                  IEEE
     INDEX                                                                                                Std 399-1980
223
Authorized licensed use limited to: IEEE Xplore. Downloaded on November 08,2014 at 04:51:47 UTC from IEEE Xplore. Restrictions apply.
              IEEE
              Std 399-1980                     INDUSTRIAL AND COMMERCIAL POWER SYSTEMS ANALYSIS
224
Authorized licensed use limited to: IEEE Xplore. Downloaded on November 08,2014 at 04:51:47 UTC from IEEE Xplore. Restrictions apply.