Capacitor Bank                       5th Harmonic Bank                  7th harmonic Bank
KVAR                                   2.564 MVAR                   2.3235
Voltage                                14.81 kV                      14.94
X c at 50 Hz                           85.54         KV2/MVA         96.06
C=                    1/(2xΠxFxXc)
F=                                     50                                50
Π=                                   3.14                      3.142857143
C=                            0.00003719                        0.00003312
                                    37.19 micro F                     33.12 micro F
Reactor
Reactance value, L                   12.876 mH                        2.724 mH
At Tuning frequency   XL=XC
XL=                   2xΠxFxL
2ΠL=                         0.0809348571                      0.017122286
2ΠC=                          0.000233796                      0.000208196
F ²=                  1/(2ΠL)( 2ΠC)
F ²=                    52847.7492886888                       280521.9071
F=                        229.8863834347 Hz                    529.6431885
Harmonic no=                 4.5977276687                      10.59286377
                                         Voltage harmonics is considered to be 5%
rmonic Bank                      5th harmonics                                                     11th harmonics
                   tuning       4.73%                                               tuning         0.89%
                                           XL-XC       I           Irms
              XL            4.046743       81.50     99.9545    100.92814465         XL      0.856114
              XC                85.54                                                XC          96.06
              XC5            17.1089      3.124814 13.68171                         XC5       19.2127
              XL5           20.23371                                                XL5      4.280571
              XC7           12.22064      16.10656 2.654372                         XC7      13.72336
              XL7            28.3272                                                XL7        5.9928
              XC11          7.776773      36.7374    1.16374                        XC11     8.733048
              XL11          44.51417                                                XL11     9.417257
                        90
                         Imp
                        80          I                                               XC13     7.389502
                               81.5                                                 XL13     11.12949
                        70
              5th           3.1248 14
                        60
              7th          16.1066 3                                                XC15     6.404235
                        50 36.73 1                                 Imp
              11th                                                                  XL15     12.84171
                                                                   I
                        40                                                      100
                                                                   Column K
                        30                                         Column L      90          Imp         I
                        20                                                       80              95.21
                        10                                                     5th70         14.93213 3
                                                                               7th60         7.730561 6
                            0
                                  5th   7th 11th                               11th
                                                                                  50         0.684209 63
                                                                               13th
                                                                                  40         3.739984 12
                                                                               15th
                                                                                  30         6.437479 7
                                                                                 20
                                                                                 10
                                                                                    0
                                                                                           5th 7th 11th 13th 15th
11th harmonics
             XL-XC               I         Irms
             95.21   89.79072   89.8     109.8865
           14.93213 2.888272 2.8882721
           7.730561 5.578905 5.5789052
           0.684209 63.03343 63.033427
           3.739984 11.53162 11.531618
           6.437479 6.699527 6.6995268
                                       Imp
                                       I
                                       Column Q
                                       Column R
7th 11th 13th 15th
Load on Rectifier
case1                 Present Load
direct current                 18 kA
Voltage                       180 V
Power DC                    3240 Kw
Rectifier AC to DC con       0.94
Input AC power         3446.8085 KW
Uncompensated power          0.82 assumed
Input KVA               4203.425 KVA
Primary Voltage                11 kV
Input current           220.6226
Harmonic current calculation assuming 6 pulse operation
                    PU current Value in A      Effective current Worst case     Selected rating
Fundamental                    1        220.62
5th                        0.192         42.36              42.36         42.36             99.95
7th                        0.132         29.12
11th                       0.073         16.11              45.23         87.59              89.8
13th                       0.057         12.58
Conclusion: Total Harmonic current up to 11th is 87.59 A, both the banks are suitable for worst case of sucking all the ha
Case 2                Full load
direct current                   22 kA
Voltage                         200 V
Power DC                      4400 Kw
Rectifier AC to DC con         0.94
Input AC power         4680.8511 KW
Uncompensated power            0.82 assumed
Input KVA               5708.355 KVA
Primary Voltage                  11 kV
Input current          299.61093
Harmonic current calculation assuming 12 pulse operation
                    PU current Value in A      Effective current Worst case     Selected rating
Fundamental                    1        299.61
5th                        0.192         57.53              17.26         17.26             99.95
7th                        0.132         39.55              11.86
11th                       0.073         21.87              21.87         50.99              89.8
13th                       0.057         17.08              17.08
Conclusion: Both the bank ratings are more than worst case of 50.99 A, hence adequate
Notes:
30 % of 5th and 7th Harmonic current is considered for the 12 pulse operation while computing effective current
Harmonic filter bank is expected to suck all harmonics numbers below it as worst case
Refer page no 82 of IEEE519 for pu values of harmonic currents
            Basis for worst case
            all harmonics up to 5th
            all harmonics up to 11th
worst case of sucking all the harmonics uo to 11th
            Basis Worst case                KVAR of Bank
            all harmonics up to 5th         2563.88466
            all harmonics up to 11th        2323.74015
uting effective current