user manual
cooling tower Motor
I N STA L L AT I O N - O P E R AT I O N - M A I N T E N A N C E
Z0239042_A    ISSUED 06/2016                 READ AND UNDERSTAND THIS MANUAL PRIOR TO OPERATING OR SERVICING THIS PRODUCT
installation
RECEIVING AND STORING MOTORS                                       INSTALLATION
A motor should be inspected on receipt to make sure it was         Check to see that the motor nameplate data agrees with
not damaged during shipment. Turn the shaft by hand to             the voltage and frequency of the power supply provided
see that it turns freely. Check motor nameplate for correct        for the motor. All induction motors will operate successfully
horsepower, voltage, phase and speed.                              when the frequency is not more than five percent above or
If a motor is stored before installation, place it in a building   below the nameplate rating, the voltage is not more than
in which air is kept reasonably dry and with a minimum of          ten percent above or below the nameplate rating, and the
temperature fluctuation to prevent moisture condensing in          combined variation in voltage and frequency is not more than
the motor. Do not store directly on the floor, always block up.    ten percent above or below the nameplate rating.
Windings should be meggered at the time the motors are             The power supply line for the motor should be of sufficient
put in storage.                                                    capacity to carry 125 percent of the motor’s full load current
                                                                   with a maximum voltage drop of three percent on the line.
If motors have space heaters, the heaters should be ener‑
gized when the motors are placed in storage.                       The power supply MUST conform with motor nameplate
                                                                   voltage. Motors rated 200 volts are for a 208 volt sys‑
NOTE: Remove units from containers when heaters are                tem. Motors rated 230/460 volts are for a 240 or 480
energized. Reprotect if necessary.                                 volt system. Do not use a 230 or 230/460 volt motor
If outdoor storage is necessary, protection should include         on a 208 volt system.
a vapor barrier beneath the motor. The motor should be
blocked up to prevent flooding. All external parts such as         Unbalanced voltages in the power supply will greatly in‑
shafts, machined surfaces, and threaded holes should be            crease the internal losses of the motor, reducing the safe
protected with a rust inhibitor coating.                           load the motor can carry. Have the power company correct
                                                                   any unbalanced voltage.
Rotate motor shaft monthly to insure that the bearing
surfaces are protected with lubricant.                             When motor power is supplied by overhead conductors,
                                                                   it is advisable to provide a lightning arrestor on each un‑
When a motor is removed from storage, the insulation and
                                                                   grounded line.
rotor movement should be checked. The insulation should
be checked by applying the potential from a 500 volt meg‑          Wire the motor to the power supply through a disconnect
ohmmeter between the windings and grounded frame for               switch, short‑circuit protection, and suitable magnetic starter
10 minutes. Resistance readings should be taken at 1 and           with overload protection. All wiring and fusing should be
10 minutes. Correct the readings to 40°C as discussed on           in accordance with the National Electrical Code and local
page 6 of this manual. Calculate the winding polarization          requirements. All motors should be connected as shown on
index by dividing the 10 minute reading by the one minute          the nameplate diagram.
reading. The recommended minimum value of polarization             The National Electrical Code requires a motor to be in sight
index for alternating current machine is:                          of the controller unless the disconnecting means can be
    Class A insulation 1.5                                         locked open or unless there is a manually operated switch
    Class B insulation 2.0                                         in sight of the motor which will disconnect the motor from
    Class F insulation 2.0                                         its electrical supply.
A low polarization index indicates the insulation should be        Overload protection should be installed in all three lines. Size
cleaned and dried before the motor is placed in operation. It      overload heaters in starters for nameplate service factor and
is possible to operate a motor with a polarization value less      amps. Overloads for 1.15 service factor motors must kick
than the minimum listed above but this is not considered           out at no more than 125% of nameplate current. Overloads
good practice.                                                     for 1.0 service factor motors must kick out at no more than
                                                                   115% of nameplate current.
The rotor movement is checked by rotating the shaft by
hand. If shaft is not free, contact the motor manufacturer’s       Overloads should be at the same ambient temperature as
authorized repair shop. Grease in the motor bearings should        motor. Do not use ambient compensated overloads.
be purged at the time of removal from storage. Refer to
LUBRICATION on pages 5 and 6.
                                                                                                                              ➠
                                                                                                                               3
installation – operation
If a two-speed motor is used, be sure control characteristics     OPERATION
are compatible with the motor. A two-speed single-winding
                                                                  Sleeve bearing motors are usually shipped without oil and
motor requires a different starter than a two-speed two-
                                                                  must be oiled before operation. Ball bearing motors are lu‑
winding motor. Starters for two-speed motors must include
                                                                  bricated for the initial operation by the motor manufacturer;
a minimum time delay of 20 seconds when switching from
                                                                  however, it is recommended that the grease and relief plugs
high to low speed.
                                                                  be removed and the motor bearing housing be examined
When a disconnect switch is installed between motor and           for presence of adequate grease before motor is placed in
starter for two speed or part winding start single- speed         operation. Add grease if necessary. See instructions on pages
motor, a 6‑pole disconnect must be used.                          5 and 6 for lubricating ball bearing or sleeve bearing motors.
SAFETY NOTE: Use of two 3‑pole disconnects can                    Turn the rotor by hand to see that it rotates freely. Motor
result in one disconnect not being off and unexpected             shaft should be parallel to driven shaft so that there are no
starts or motor damage.                                           stresses in motor frame.
If reverse operation of mechanical equipment is required,         INITIAL STARTING: The motor should bring the fan up to
provide minimum time delay of two minutes before en‑              speed in less than 15 seconds. If it does not, check connec‑
ergizing motor when changing direction of rotation.               tions, fuses, overloads and voltage at motor terminals during
Check the wiring system for grounds and check the                 start‑up period. Run the motor to check the connections
resistance between all leads for open, bad or incorrect           and direction of rotation. If the rotation is incorrect, change
connections before operating the motor.                           any two of the three motor leads for a three phase motor
                                                                  or interchange the connections of either the main or start
The conduit system should be arranged so that trapped
                                                                  windings for single phase capacitor start motor.
water will collect in a sump equipped with suitable drain
and will not go into the motor terminal box.                      CAUTION: Excessive fan cycling may shorten the mo‑
                                                                  tor's expected service life. On fans 20 feet (6 meter)
When the motor must be moved for coupling removal or belt
                                                                  diameter and smaller allow for 4 to 5 starts per hour.
adjustment, a short section of flexible, watertight metallic
                                                                  On larger fans, 2 or 3 starts per hour may be the limit.
conduit should be used in place of rigid conduit to protect
                                                                  On two speed motors each low speed start and each
the leads to the motor.
                                                                  high speed start count as one start.
Remove all water drain plugs from totally-enclosed motors.
                                                                  If a two-speed motor is used, allow a time delay of a minimum
These plugs will be located in the lowest part of the installed
                                                                  of 20 seconds after de‑energizing the high speed winding
motor. Because of inaccessability of drain plugs with motor
                                                                  and before energizing the low speed winding. Tremendous
installed on supports, it is sometimes necessary to remove
                                                                  strains are placed on driven machinery and motor unless
plugs before the motor is bolted in place.
                                                                  the motor is allowed to slow to low speed rpm or less before
The drain plugs on explosion-proof motors are automatic           the low speed winding is energized.
and must not be removed.
                                                                  When changing fan direction of rotation, allow a minimum
NOTE: After motor is installed, it should be run for              of two minutes time delay before energizing the fan motor.
three hours at least once a month, even if the tower is
                                                                  DETERMINE LOAD AT MOTOR: With design water rate
not in operation. This serves to dry out windings and
                                                                  and design heat load on the tower, test motor hp as follows:
relubricate bearing surfaces. If motors are purchased
with space heaters, they should be energized as soon              1.	Run motor for 30 minutes. Record motor name plate
as possible. Use an auxiliary contact on the starter to              data.
turn heater off when motor is running.                            2.	 Measure voltage between all lines at motor terminals.
                                                                  3.	 Measure amps in all three lines.
 4
   operation – maintenance
   4.	Average the measured volts and amps and calculate                                                  Factor (75°F)                100.8
                                                                         hp (75°F) = hp (40°F) X                           = 7.8 x             = 7.43
      test horsepower using the following equation:                                                      Factor (40°F)                105.9
                    Volts x Amps (average)                               	 If it is desired to correct for high or low test barometric
   hp (test) =                                        x hp (nameplate)
                    Volts x Amps (nameplate)                               pressure, multiply the predicted horsepower by standard
                                                                           station barometric pressure and divide by test station
   5.	 For a given fan pitch setting and RPM, horsepower will              barometric pressure.
       vary directly with the air density which is a function of         	      *Use ambient dry‑bulb temperatures if checking a forced
       temperature and barometric pressure. Because fans are                    draft cooling tower.
       generally pitched for summer weather horsepower, it is
                                                                         	 Fan motor overloads sized for summer weather will
       expected that the motor nameplate horsepower will be
                                                                           handle the higher winter horsepower without adjustment
       exceeded during winter operation. Assuming 100% heat
                                                                           providing they are at the same ambient temperature as
       load, the temperature rise in the motor will be greater at
                                                                           the motor and there is ample heat load on tower.
       the higher horsepower, but the operating temperature
       of the motor will actually be lower due to the drop in            NORMAL OPERATION: Class B insulated motors are rated
       ambient temperature. Under these conditions, the higher           at a maximum total operating temperature of 130°C (266°F).
       horsepower should not be detrimental to the motor.                A thermometer in contact with the winding may indicate a
                                                                         temperature up to 100°C (212°F). on a protected motor or
   	 If the horsepower measurement is taken during cold
                                                                         up to 115°C (239°F) on a totally enclosed motor without the
     weather conditions, the predicted horsepower which will
                                                                         motor being too hot. Therefore, a motor that appears to be
     result during summer operation may be determined by
                                                                         hot is not necessarily overloaded. Check with thermometers.
     applying the Factor from Figure 1. For a given location,
     the barometric pressure will not normally vary enough               CAUTION: Normal operating temperatures of electric
     to cause significant error and for this reason, has not             motors can be hot enough to cause burns. Avoid any
     been included in the Factors.                                       unprotected contact with the surface of an operating
                                                                         motor.
         96
          97                                                             MAINTENANCE
         98                                                              SAFETY NOTE: When working on the fan or fan drive,
                                                                         make sure the electric motor cannot be started. See
         99                                                              "Installation" section.
         100                                                             To obtain maximum motor life, establish a schedule of main‑
         101                                                             tenance based on the particular application of the motor and
                                                                         observe the following procedures and precautions:
FACTOR
         102
                                                                         CLEANING: Remove any oil, dust or scale deposits from the
         103                                                             motor. They can cause excessive insulation temperatures.
         104                                                             LUBRICATION:
         105                                                             Ball Bearing Motors: The following table may be used as
                                                                         a guide in determining greasing periods for motors:
         106                                          Figure 1
         107
         108                                                                               Duty              1 – 30 hp           40 – 250 hp
               0   10   20   30   40   50   60   70     80   90 100
                                                                             I n te rm itte n t             12 m on ths              12 m on th s
   Example: The horsepower on an induced draft cooling tower* is
                                                                             8 to 16 h ou rs pe r da y      12 m on th s             6 m on th s
   7.8 hp on a 40°F ambient wet‑bulb day. What is the predicted
   hp on a 75°F ambient wet‑bulb day?                                        Con tin u ou s                  8 m on th s             4 m on th s
                                                                                                                                                    5
operation – maintenance
All greases will deteriorate in time depending upon bearing                                     race. If the bearing feels rough or binds in spots, it should
size, speed and temperature. The grease used should be                                          be replaced.
recommended by the motor manufacturer. See instructions                                         Sleeve Bearing Motors: Check oil in sleeve bearings at
attached to motor for recommended lubricant. If these                                           least every three months. When journal size is less than two
instructions have been lost or misplaced, obtain informa‑                                       inches, stop the motor to check the oil level. Old oil should
tion on lubricant to use and local supply source from motor                                     be drained and replaced at least every year. Clean out oil
manufacturer’s nearest authorized service facility or from                                      well if there is evidence of dirt and sludge.
the motor manufacturer. Give complete motor nameplate
data and state clearly that the motor is used on a water                                        Motor shaft must be stopped when motor is oiled. The
cooling tower. Chevron SRI‑2 is recognized by many motor                                        oil used should be a good grade of mineral oil of light or
manufacturers as a suitable grease for ball bearing motors                                      medium viscosity (such as SAE No. 10). Turbine oil rather
for cooling tower service. In general, a polyurethane or lithium                                than automotive crankcase oil is recommended.
base grease with rust and oxidation inhibitors is recom‑                                        Check bearing wear yearly by measuring the air gap with a
mended. Use a grease of NLGI No. 2 consistency. Do not                                          feeler gauge. Measure gap in at least four equally spaced
mix greases which are of different types or specifications.                                     positions at each end of the motor with two of the places
If a change is desired, the motor bearing housing grease                                        being the lowest point and the point subject to the load pull.
reservoir should be completely cleaned of old grease before                                     INSULATION: Check insulation resistance with a meg‑
repacking with new grease.                                                                      ohmmeter at the end of each shutdown period. Apply the
The relief method of greasing motors tends to purge the                                         megohmmeter potential to the winding for one minute
bearing housing reservoir of used grease by forcing out                                         before taking a reading. Correct the reading to 40°C by
old grease with new grease. Use a plunger type grease                                           using the equation:
gun which will not fit the bearing grease fill hole too tightly.                                                               R40°C= Kt x Rt and the curve below
Either an excess or insufficient amount of lubricant in the
bearings can cause overheating. To prevent this occurrence,                                                           100
use the following greasing procedure:
                                                                                                                       50
1.	 Stop motor.
2.	Wipe grease plugs, outside of bearing housing, and
   relief plug, clean.
                                                                   Insulation Resistance Temperature Coefficient Kt
3.	Remove grease and relief plugs and free relief hole of
                                                                                                                       10
   any hardened grease. Use a thin piece of wire in open‑
   ing.
                                                                                                                        5
4.	Add grease with a hand operated pressure gun until
   new grease appears at the relief hole. Take special care
   when greasing the fan end bearing of TEFC motors. The
   long relief might be too small for the bearing to relieve
   properly.                                                                                                           1.0
5.	 Run the motor for approximately one hour after greasing
                                                                                                                       0.5
    to permit rotating parts of the bearing to expel excess
    grease. Take out some of the excess grease with a thin
    piece of wire.
6.	Replace plugs and wipe the outside of the bearing
   housing clean.                                                                                                     0.1
Every few years the motor end brackets should be removed                                                              0.05
                                                                                                                                     To Convert Observed Insulation Resistance Rt to 40°C
and the grease reservoirs cleaned and repacked full with                                                                            Multiply by the Temperature Coefficient Kt , Rc – Rt x Kt
approved ball bearing grease. Open bearings should be                                                                    -10    0   10   20     30     40   50     60    70    80     90    100
cleaned and repacked.
                                                                                                                                                     Winding Temperature °C
Bearings should be checked for "roughness" by turning the
outer race slowly with the fingers while holding the inner                                      Approximate Insulation Resistance Variation with Temperature
                                                                                                for Rotating machines.
 6
maintenance
A record of these corrected readings will show a trend in        Do not start motor without determining that there will
the insulation condition. It is considered good practice to      be no interference with free rotation of the fan drive.
recondition a winding if the resistance, having been high on
previous readings, drops to near the recommended minimum         MOTOR WARRANTY
value as calculated by:
                                                                 Motor manufacturers’ warranties run for 12 months in service
Megaohms = 1000 + Rated Voltage of Machine                       but not to exceed 18 months from date of manufacture. Mo‑
                        1000                                     tor manufacturers warrant their products to be of the type
                                                                 and quality described, suitable for the service for which they
Motors in continuous operation will stay at a temperature
                                                                 are supplied, and free of defects in materials and workman‑
sufficiently above ambient temperature to prevent conden‑
                                                                 ship. Failures from causes external to the motor (e.g., single
sation of moisture on and about the windings, even if the
                                                                 phasing, operation under prolonged or extensive overload,
location is very humid. Idle motors, however, accumulate
                                                                 damage from handling, improper maintenance, use on other
moisture readily which causes gradual deterioration of in‑
                                                                 than the service for which supplied, defect in wiring to power
sulation. Where motors are idle for a long time, single‑phase
                                                                 supply, or deficiency or defect in controls) are not covered
heating or space heaters may be required to prevent water
                                                                 by the motor manufacturers’ warranties.
condensation.
                                                                 If a motor failure occurs within the warranty period
Check insulation resistance at least once a year with the        because of defect in material or workmanship, the
motor at normal operating temperature. Comparison with           motor manufacturer is liable and has the right to
several previous readings will give an indication of improve‑    remedy the failure by adjustment, repair, or supplying
ment or deterioration of insulating value. Readings, to have     a replacement motor F.O.B. his factory or authorized
comparison value, should be taken under the same condi‑          repair facility. In such event, the motor must be delivered
tions (temperature, operating time since last shutdown, etc.).   to the nearest repair facility authorized by the motor
Low or falling resistance readings indicate the need for         manufacturer with notification that the motor is from
maintenance. Contact the nearest repair facility authorized      a Marley product and that warranty consideration is
by the motor manufacturer for repair service.                    requested. Prompt notification of such failure should
                                                                 be directed to a Marley sales representative.
VIBRATION: If vibration occurs, it should be corrected
without delay. Use the following procedure to determine          Motor manufacturers will not accept warranty obligation
source of trouble:                                               for repair of motors by other than their authorized repair
1. Check motor mounting to see that fasteners are tight.         facility nor warranty obligation for materials or workman‑
                                                                 ship employed in making repairs. Repair shops, including
2. Disconnect motor from load and run motor separately.
                                                                 authorized repair facilities, generally warrant their material
   If motor still vibrates, rebalance rotor.
                                                                 and workmanship for a period of 12 months.
3. If vibration is in mechanical equipment*, check:
                                                                 Motor manufacturers’ warranties do not cover cost of
	 a. 	Alignment of motor with mechanical equipment.              dismounting, transportation to and from repair facilities, or
	   b.	Tightness of Geareducer, or belt driven components,      remounting motors.
        mounting bolts.
	 c. 	Unbalance in drive shaft or fan.                           MOTOR OPERATION NOTE:
*Refer to service manuals for operating and maintenance          Higher density of cold air at fan increases motor horsepower.
recommendations.                                                 If motor overloads will not allow fan motor operation at high
                                                                 speed in forward direction, one of the following might be done:
SEASONAL SHUTDOWN                                                1.	If overloads are adjustable, set at a higher value
If a motor is used only seasonally, it should be cleaned and        (+15%) for cold weather operation. Readjust for sum‑
lubricated at the close of each season. Refer to motor manu‑        mer operation.
facturer’s recommendations for lubrication and maintenance       2.	 Operate motor (fan) in reverse (reverse 2 loads).
instructions. At start of new season, make sure bearings are     3.	 Operate two‑speed motor at low speed.
adequately lubricated before returning motor to operation.
When tower is not in operation, the motor should be run
for three hours at least once a month. This serves to dry
out windings and relubricate bearing surfaces.
                                                                                                                            7
                                                                                          cooling tower Motor
SPX COOLING TECHNOLOGIES, INC.
7401 WEST 129 STREET                Z0239042_A | ISSUED 06/2016
OVERLAND PARK, KS 66213 USA         COPYRIGHT © 2016 SPX CORPORATION
913 664 7400 | spxcooling@spx.com   In the interest of technological progress, all products are subject to design
spxcooling.com                      and/or material change without notice.