Cathodic Protection
Cathodic Protection
March 2017
Information in this technical paper was excerpted from previous versions of DoD cathodic
protection criteria manuals. The information has been updated to reflect current practices
and technology.
1.1.2 Available sizes. Table 1-2 provides examples of the sizes of commercially
available graphite anodes. Manufacturers can provide material catalogs with detailed
anode information and also provide the same information on their company internet
websites. The weights indicate are for the bare graphite only and do not include the
weight of the lead wire or connection, or prepackaged backfill.
1
Electrical TP 16
March 2017
Table 1
Graphite Anode Properties
Composition
Impregnant (Linseed Oil) 6.5 wt % max
Ash 1.5 wt % max
Moisture & Volatile Matter 0.5 wt % max
Water Soluble Matter 1.0 wt % max
Graphite Remainder
Physical Properties
Density 99.84 lb/cu ft max
Resistivity 0.0011 ohm-cm max
Mechanical Requirements
Lead wire connection strength 325 lbs minimum
Figure 1
Typical anode end connection and seal
2
Electrical TP 16
March 2017
Figure 1a
Center Connected Graphite Anode
3
Electrical TP 16
March 2017
* Note for Table 1-2: Refer to manufacturers’ brochures for more specific information.
Metric sizes are soft metric conversions from U.S. standard SI units. Actual metric sizes
for materials available in foreign countries may differ.
1.1.4 Operation. Graphite anodes must be installed and operated properly in order
to insure optimum performance and life.
1.1.4.1 Current Densities. Do not exceed the current densities in Table 3 in order to
ensure optimum anode life:
Table 3
Maximum Current Densities for Graphite Anodes
Maximum Current Density (amp/sq ft)
Seawater Fresh Water Soil
3.75 0.25 1
1.1.4.2 Operating Potentials. As the potential difference between steel and graphite is
approximately 1.0 volt with the graphite being the cathode, this potential difference must
be overcome before protective current will begin to flow in the impressed current cathodic
protection system circuit. This 1.0 voltage difference must be added to the other voltage
and IR drop requirements during the selection of proper power supply driving voltage.
1.1.4.4 Need for Backfill. The deterioration of any point on a graphite anode is
proportional to the current density at that point. If the resistivity of the environment at any
one point is lower than the resistivity at other points, the current density and resulting
deterioration will be higher there. This can result in uneven consumption and premature
4
Electrical TP 16
March 2017
failure of graphite anodes, particularly if the low resistivity area is near the top of the
anode. In this case “necking” of the anode at the top occurs and the connection to the
lower portion of the anode is severed. Use carbon (coke breeze) backfill of uniform
resistivity when graphite anodes are used in soil in order to prevent uneven anode
deterioration.
1.2 High Silicon Cast Iron. Cast iron containing 14 to 15 percent silicon and one
to two percent other alloying elements such as manganese and molybdenum form a
protective film of silicon dioxide when current is passed from their surface into the
environment. This film is stable in many environments except in chloride rich
environments. The formation of this film reduces the deterioration rate of this alloy from
approximately 20 pounds per ampere-year for ordinary steel, to one pound per ampere-
year for the silicon iron. While more recently developed anodes such as mixed metal
oxide are now more often specified, high silicon cast iron anodes are still used.
1.3 High Silicon Chromium Bearing Cast Iron (HSCBCI). When using high
silicon cast iron anodes, specify the chromium-bearing alloy. The chromium-bearing alloy
of similar silicon and other alloy content was developed to help prevent premature
deterioration of high silicon cast iron in environments containing chloride.
1.3.1 Specifications. The nominal composition and typical mechanical and physical
properties of HSCBCI are as shown in Tables 4 and 5:
Table 4
HSCBCI Anode Composition
Element Percent
Silicon 14.35 min
Chromium 4.5
Carbon 0.95
Manganese 0.75
Iron Remainder
Being a metal HSCBCI has much greater mechanical strength than nonmetals such as
graphite magnetite. However, due to its low elongation under load it is brittle and should
be protected from both mechanical and thermal shock.
5
Electrical TP 16
March 2017
Table 5
Physical Properties of HSCBCI Anodes
Tensile Strength 15,000 PSI
Compressive Strength 100,000 PSI
Hardness 520 Brinell
Specific Gravity 7
Melting Point 2,300 Degrees F
Specific Resistance 72 micro ohms/cu cm
Coefficient of Expansion per
degree F 7.33 micro inches per inch
1.3.2 Available sizes. HSCBCI anodes are available in a wide variety of standard
sizes and shapes. Tables 6 and 7 provide examples of sizes of solid rod and tubular
HSCBCI anodes. Manufacturers can provide material catalogs with detailed anode
information and also provide the same information on their company internet websites.
The weights indicated are for the bare anodes only and do not include the weight of the
lead wire or connection, or prepackaged backfill. Special configurations can be produced
at extra cost and are usually practical when standard anodes have been shown to be
unsatisfactory for a particular application and where a large number of special
configuration anodes are required. In most case, however, commercially available sizes
are specified.
The anode sizes and shapes in Tables 6 and 7 are the most commonly used anodes in
DoD applications. In addition to solid rod and tubular anode configurations, HSCBCI
anodes are also available in button, bullet, and other shapes and sizes of anodes, where
needed for particular applications. Refer to manufacturers’ brochures for more specific
information.
The solid rod anodes shown in Table 6 had been commonly used in the past. Lead wire
connections at the end of the anode often resulted in a higher rate of consumption, or
“necking”, at that end of the anode that resulted in premature loss of lead wire connection.
To help prevent the necking of the anode at the connection point, select anodes that were
manufactured with an enlarged end if solid rods are to be specified. In addition, specify
external epoxy encapsulation as shown in Figure 3 to help reduce the necking of the
anode. The tubular anodes listed in Table 7 with the lead wire connected in the center of
the anode are now preferred over solid rod anodes as these help reduce the chance of
premature failure due to necking. Figures 4 and 5 are illustrative examples of tubular
anodes.
6
Electrical TP 16
March 2017
Figure 2
Anode to cable connection – Teflon seal.
7
Electrical TP 16
March 2017
Figure 3
Anode to cable connection – Epoxy seal.
8
Electrical TP 16
March 2017
Figure 4
Anode to cable center connection
9
Electrical TP 16
March 2017
1.3.4 Operation. HSCBCI anodes are consumed at a rate of about one (1) pound
per ampere year when used at a current not exceeding their nominal discharge rates.
The potential difference between and steel HSCBCI can be neglected in the selection of
impressed current rectifiers. HSCBCI anodes do not require backfill in most applications,
but backfill can reduce the anode to electrolyte resistance in many cases and its use
should be evaluated based upon a tradeoff between the cost of the backfill and the
savings in power associated with the lower circuit resistances and required driving
potentials.
* Note for Table 6: Refer to manufacturers’ brochures for more specific information.
Metric sizes are soft metric conversions from U.S. standard SI units. Actual metric sizes
for materials available in foreign countries may differ.
10
Electrical TP 16
March 2017
* Note for Table 7: Refer to manufacturers’ brochures for more specific information.
Metric sizes are soft metric conversions from U.S. standard SI units. Actual metric sizes
for materials available in foreign countries may differ.
Figure 5
Tubular HSCBCI Anodes
1.5 Lead-Silver Alloy. Lead alloyed with silver, antimony or tin has been used in
the past as anodes for impressed current cathodic protection systems in seawater. The
chief advantage of these anodes was their low operating cost. The consumption rate for
silverized lead is 2 to 3 pounds per ampere year initially but drops off to approximately 0.2
pounds per ampere year after 2 years, as the anode surface develops a passivating film.
Alloyed lead anodes have been unreliable in many specific applications either because
they failed to passivate, their consumption rate remained in the 2 to 3 pound per ampere
year range and they were completely consumed, or they became so highly passivated
that the anode to electrolyte resistance increased substantially. When properly operating,
the current density from silverized lead anodes is typically 10 amperes per square foot.
Because of the environmental concerns with lead, these anodes are no longer used.
11
Electrical TP 16
March 2017
1.6 Platinum. Pure platinum wire is sometimes used for impressed current
cathodic protection anodes where space is limited. Platinum is essentially immune to
deterioration in most applications. In seawater its consumption rate at current densities
as high as 500 amperes per square foot is 0.00001 pound per ampere year. Due to the
high cost of platinum, this material is more commonly used as a thin coating on other
metals.
1.7.1 Types. Platinized anodes are available in a wide variety of sizes and shapes
as shown below. Table 8 provides examples of platinized niobium wire anode
configurations used for impressed current anodes in water storage and processing
vessels. Manufacturers can provide material catalogs with detailed anode information
and also provide the same information on their company Internet websites. An example
of a platinized anode configuration is shown in Figure 6.
* Note for Table 8: Refer to manufacturers’ brochures for more specific information.
Metric sizes are soft metric conversions from U.S. standard SI units. Actual metric sizes
for materials available in foreign countries may differ.
Platinized niobium/titanium probe type anodes are also available for use in steel vessels
such as condenser water boxes and heat exchangers where the interior is difficult to
access and its space limited. Such anodes are often mounted through the vessel shell,
with the anode part of the probe extending into the vessel, and wire connections made to
the probe on the exterior of the vessel. Table 9 provides examples of platinized niobium
wire anode configurations used for impressed current anodes in water storage and
12
Electrical TP 16
March 2017
processing vessels. Manufacturers can provide material catalogs with detailed anode
information and also provide the same information on their company internet websites.
Figure 6
Example platinized anode configuration
* Note for Table 9: Refer to manufacturers’ brochures for more specific information.
Metric sizes are soft metric conversions from U.S. standard SI units. Actual metric sizes
for materials available in foreign countries may differ.
13
Electrical TP 16
March 2017
1.7.2 Operation. Platinized anodes can be operated at very high current densities.
100 Amperes per square foot are typical. All of the current flows from the platinum coated
portion of the anode surface. However, if this coating is damaged, current may also flow
from the substrate material resulting in its premature failure. The primary limitation of
platinized anodes is that the oxide film on the substrate can break down if excessive
anode-to-electrolyte voltages are encountered. The practical limit for platinized titanium is
12 volts. Platinized niobium can be used at potentials as high as 100 volts.
1.8.1 Types. Mixed metal oxide (MMO) and ceramic anodes are available in a
variety of substrate configurations:
• Solid rod
• Tubular substrates
• Wire
• Ribbon
• Expanded mesh
• Probe
For DOD applications, Solid rod, tubular, and wire type anodes are commonly used
where bulk anodes such as HSCBCI and graphite are used. As the cost of these anodes
have decreased, these anodes are now preferred in many applications over their bulk
anode predecessors. Their smaller dimensions and lower weights can reduce and
simplify CP system installation. There generally higher current density capacities can
often result in installation of less anodes that their bulk anode counterparts. Probe
anodes are used in water storage and processing vessels. Wire, ribbon, and mesh
anodes are used in CP systems installed to protect the exterior bottoms of on-grade
storage tanks with a secondary containment liner because of limited space between the
tank bottom and the containment liner. Ribbon and mesh anodes are most often the
anode configurations of choice for CP systems installed to protect the reinforcing steel in
concrete.
14
Electrical TP 16
March 2017
15
Electrical TP 16
March 2017
16
Electrical TP 16
March 2017
Figure 7
Roll of MMO Ribbon Anode (left). MMO Ribbon installed (right). Thinner metal
strip is the MMO anode.
Figure 8
Mixed Metal Oxide Mesh Anode installed on a concrete beam.
17
Electrical TP 16
March 2017
Figure 9
Mixed Metal Oxide tubular anode.
1.9 Anode Backfill. For nearly all underground installations, a special carbon
backfill, referred to in the industry as coke breeze, is provided in the anode hole or well.
Some of the reasons for using this special backfill include
18
Electrical TP 16
March 2017
1.9.1 Specifying the Type of Backfill. Ensure that the appropriate type of backfill
is specified and provided. Generally, calcined petroleum coke, or coke that has been
heated to remove high resistivity petroleum by-products, should be specified. The
calcined petroleum coke has a lower total bulk resistivity, and its more spherical
particles aids in the compaction of the backfill (Figure 10). Also, specify backfill that has
a carbon content greater than 92%, preferably greater than 99%, for greater anode
system life.
Figure 10
Petroleum coke backfill
19
Electrical TP 16
March 2017
2.2 Selection of Power Supply Type. Any source of direct current of appropriate
voltage and current can be used as a source of power for impressed current cathodic
protection systems. The selection of the power supply depends upon local conditions at
the site and should be evaluated based upon economics, availability of AC power or fuel,
and the availability of maintenance.
2.2.2 Thermoelectric generators. These power supplies convert heat directly into
direct current electricity. This is accomplished through a series of thermocouples that is
heated at one end by burning a fuel and cooled at the other, usually by cooling fins.
Thermoelectric generators are highly reliable as they have few, if any moving parts. They
are available in sizes from 5 to 500 watts. They are very expensive and should only be
considered for remote locations where electrical power is not available and fuel is
available. They are used as a power supply for impressed current cathodic protection on
remote pipelines where the product in the pipeline can be used as a fuel.
2.2.3 Solar Power. For solar powered systems, solar cells convert sunlight directly
into direct current electricity. Their cost per watt is high but is decreasing as solar cell
technology is improved. Solar panels are used for cathodic protection power supplies at
remote sites where neither electrical power nor fuel is available. In order to supply
current continuously, solar cells are used in a system that both supplies power to the CP
system and also recharges a set of batteries when sunlight is received (Figure 11). When
sunlight is not being received, the batteries supply the required current. Security must be
considered with solar power systems as many of the solar powered systems have been
damaged by vandalism and theft. Environmental and safety considerations must include
procurement, maintenance and disposal of battery electrolytes, usually acids.
2.2.4 Batteries. When current requirements are low, storage batteries can be used
to supply power for impressed current cathodic protection systems at remote sites. They
must be periodically recharged and maintained. Again, environmental and safety
considerations must include procurement, maintenance and disposal of battery
electrolytes, usually acids.
20
Electrical TP 16
March 2017
Figure 11
Solar powered CP system. Solar panels shown in picture on the left. Battery bank
and control center shown in picture on the right.
2.2.5 Generators. Engine or wind driven generators can also be used to supply
direct current power for impressed current cathodic protection systems at sites where AC
power is not available.
Since most CP systems are powered by rectifiers, the rest of this section will
concentrate on the procedures for selecting rectifiers. The rectifier selected for a specific
impressed current cathodic protection application must be matched to both the electrical
requirements and the environmental conditions at the site. Rectifiers are available in
many electrical types and specifically designed for use in impressed current cathodic
protection systems in many environments.
3.1 Rectifier Components. Figure 1-12 is a circuit diagram for a typical single
phase full wave bridge type rectifier having the components found in most standard
rectifiers of this type. The diagram also shows an external switch and circuit protection
device that is recommended for all rectifier installations to conform with the requirements
of the National Electrical Code.
21
Electrical TP 16
March 2017
Figure 12
Single Phase, Full-Wave Bridge Rectifier
windings can be varied by changing the effective number of secondary windings through
a system of connecting bars or “taps”. Two sets of taps are normally present, one for
coarse adjustments and one for fine adjustments. By manipulation of these taps, the
rectifier direct current (DC) output voltage can be adjusted from zero to its maximum
capacity in even steps of not more than 5 percent of the maximum output voltage.
3.1.2 Rectifying Elements. The alternating current (AC) from the secondary
windings of the transformer element is converted to direct current (DC) by the rectifying
elements or “stacks”. The stack is an assembly of plates or diodes and may be in several
configurations. The most common rectifying elements are selenium plate stacks and
silicon diodes. Each has advantages and disadvantages as discussed below. The most
common configurations of rectifying elements are the single-phase bridge, single-phase
center tap, three-phase bridge and three phase wye. These arrangements are described
in detail in section 3.2. The rectifying elements allow current to flow in one direction only
and produce a pulsating direct current. The rectifying elements do allow a small amount
of alternating current to pass. This “ripple”" is undesirable and should be held to low
levels. Rectifiers are not 100% efficient in converting alternating current to direct current.
This is due to the presence of alternating current and to inherent losses in the rectifying
elements that result in heating of the stacks. Silicon elements are more efficient than
selenium elements at high output voltages but are more susceptible to failure due to
voltage overloads or surges. The efficiency of a rectifying element is calculated by the
following equation:
Typical efficiencies of single phase rectifying elements are in the order of 60 to 75 % but
can be increased by filtering the output or by using a three-phase circuit. Selection of
appropriate circuit type is discussed in section 3.3. Selection of silicon versus selenium
rectifying elements is discussed in detail in section 3.3.8.
3.1.4 Meters. In order to conveniently measure the output current and potential, the
rectifier should be furnished with meters for reading these values. The meter should not
be continuously operating but should be switched into the circuit as required. This not
only protects the meter from electrical damage from surges but, when the meter is read,
its movements from zero to a value on the meter can be used to help detect defective
meters. Often, one meter and a two-position switch are used to measure both potential
23
Electrical TP 16
March 2017
and current. Current is usually measured using a millivolt meter connected to an external
current shunt. Output voltage and current can also be conveniently measured by the use
of portable meters used across the rectifier output and the current shunt.
3.2.1 Single Phase - Bridge. The circuit for this type of rectifier is shown in Figure
12. This type of rectifier is the most commonly used type of rectifier up to an output
power of about 1,000 watts. Above 1,000 watts, the extra cost of three phase types is
often justified by the increased electrical efficiency of the three phase units. The rectifying
unit consists of four elements. If any one of the rectifying elements fails or changes
resistance, the other elements usually also fail. Current passes through pairs of the
rectifying elements through the external load (structure and anode circuit). The active
pair of elements alternates as the polarity of the alternating current reverses while the
other pair blocks the flow of current. The result is full wave rectified current as shown in
Figure 13.
3.2.2 Single Phase - Center Tap. The circuit of a single-phase center tap rectifier is
shown in Figure 14. This type of rectifier has only two rectifying elements but produces
full wave rectified output. However, as only one-half of the transformer output is applied
to the load, the transformer required is considerably heavier and more costly than in
single-phase bridge type units. This type of unit is also less sensitive to adjustment than
the single-phase bridge type, however it is electrically more efficient.
3.2.3 Three Phase - Bridge. The circuit for a three-phase bridge rectifier is shown
in Figure 15. The circuit operates like three combined single-phase bridge circuits that
share a pair of diodes with one of the other three bridges. There are three secondary
windings in the transformer that produce out of phase alternating current that is supplied
to each pair of rectifying elements. This out of phase relationship produces a direct
current output with less alternating current “ripple” than the single-phase type, typically,
only 4.5%. Due to the reduction in alternating current ripple, three-phase bridge rectifiers
are more electrically efficient than the single-phase types, and the extra initial cost of the
unit is often justified by savings in supplied power, particularly for units of over 1000 watts
capacity.
24
Electrical TP 16
March 2017
Figure 13
Full-Wave Rectified Current
Figure 14
Single-Phase Center-Tap Circuit
25
Electrical TP 16
March 2017
Figure 15
Three-Phase Bridge Circuit
3.2.4 Three Phase - Wye. The circuit for a three-phase wye rectifier is shown in
Figure 16. This type of rectifier supplies half-wave rectified current as shown in
Figure 17. The power to the rectifier unit is supplied by three separate windings on a
transformer but only three rectifying elements, each in series with the output, are
provided. This type of rectifier unit is practical only for systems requiring low output
voltages.
3.2.5.1 Constant Current Type. A block diagram of one type of constant current
rectifier is shown in Figure 18. A DC input signal to the power amplifier is supplied from
an adjustable resistor in the output circuit. The power amplifier uses this “feedback”
signal to adjust the voltage supplied to the stack so that a constant input signal and
therefore a constant output current are supplied. The power amplifier may either be of an
electronic (silicon controlled rectifier) or saturable reactor type.
26
Electrical TP 16
March 2017
Figure 16
Three-Phase Wye Circuit Schematic
Figure 17
Half-wave rectifier output
27
Electrical TP 16
March 2017
Figure 18
Constant Current Rectifier Block Diagram
Figure 19
Constant Potential Rectifier Block Diagram
28
Electrical TP 16
March 2017
3.2.5.3 Other Special Types. Several standardized rectifiers have been developed
for commercial applications such as natural gas and electrical distribution system
protection. The use of a standardized unit allows for economy of production and
reduction in overall cost of the unit as well as the installation and maintenance of the unit.
Where a large number of similar capacity units are to be used, consider the selection of a
standardized type of rectifier.
29
Electrical TP 16
March 2017
3.3.2 Air Cooled vs. Oil Immersed. Rectifiers can be supplied as either entirely air-
cooled, entirely oil-immersed or with the stacks only oil-immersed (Figures 20 through
22). Air-cooled units are lowest in cost and easiest to install and repair. However, specify
oil-cooled units in marine environments, where corrosive or dirty atmospheric conditions
are encountered, or where explosive gasses may be present. Air cooled units require
more frequent maintenance to clean the air screens and other components and are also
susceptible to damage by insects and other pests. Older oil-cooled units were supplied
with oils containing Poly-Chlorinated Bisphenyls (PCBs) which have been determined to
be carcinogenic and are no longer supplied with new units. Treat units containing PCB's
according to current policy regarding PCB's.
Figure 20
Typical Air-cooled Rectifier.
30
Electrical TP 16
March 2017
Figure 21
Typical entirely immersed oil-cooled rectifier.
Figure 22
Typical oil-cooled rectifier with only the stacks and transformer immersed.
31
Electrical TP 16
March 2017
3.3.4 DC Voltage And Current Output. Direct current voltage outputs from 8 to 120
volts and current outputs from 4 amperes to 200 amperes are common in any
combination. Almost any current can be provided but it is generally best to select a
standard size of rectifier unit and use multiple units if very large amounts of current are
required.
3.3.5 Filters. Electrical filters are used to both increase the efficiency of the rectifier
by reducing alternating current ripple and to reduce interference with communications
equipment. Efficiency filters can increase the efficiency of single-phase bridge type
rectifiers by from 10 to 14 percent and their use should be based upon a first cost versus
operating (power) cost basis. Efficiency filters are not commonly used with three-phase
rectifiers, as the alternating current ripple in these types of units is inherently low. Use
noise interference filters when a large unit is to be installed in the vicinity of
communications lines or can be retrofitted when noise problems are encountered and are
significantly affected by turning the unit on and off.
3.3.6 Explosion Proof Rectifiers. Rectifiers and other system components such as
switches and circuit breakers are available in explosion proof enclosures conforming to
National Electrical Code (NEC) Safety Standards for Class I, Group D hazardous
conditions such as may be encountered in fuel or natural gas storage or distribution
systems. Specify such enclosures where required by the NEC or whenever explosive
hazards may exist.
3.3.8 Selenium vs. Silicon Stacks. While some old installations used copper oxide
rectifying elements, modern units use only either silicon or selenium rectifying elements.
In general, silicon units are used for larger units where their higher efficiency is more
important than their lower reliability.
3.3.8.1 Selenium Stacks. Ordinary selenium stacks deteriorate with time. This
“aging” can be reduced by variations in plate composition, and “non-aging” stacks are
available. Aging rates are determined by operating temperatures that are a function of
current flow; thus the selection of a unit using selenium rectifying elements which has a
somewhat greater capacity than required will increase stack life. The efficiency of
selenium rectifying elements is a function of operating voltage versus rated voltage as
shown in Figure 23.
3.3.8.2 Silicon Diodes. Silicon diodes are mounted in metal cases that are mounted
on either aluminum or copper plates to dissipate the heat generated during operation.
Silicon diodes do not age as do selenium stacks and, as shown in Figure 24, is more
efficient than selenium elements, particularly at higher voltage ratings. Silicon rectifying
elements are more subject to failure from voltage surges that would only cause increased
aging of selenium stacks. Surge protection should always be used on both the AC input
and DC output of rectifiers using silicon diode rectifying elements.
3.3.9 Other Options. Select other available features such as listed in Section 3.3.1
as appropriate. In remote off-base areas, small arms proof enclosures may be required
based upon local experience.
Edc x Idc
Iac =
F x Eac
where:
Iac = Alternating Current Requirement (Amps)
Edc = Direct Current Output Voltage
Idc = Direct Current Output Amperage
F = Rectifier Efficiency %
Eac = Alternating Current Voltage (per phase to ground)
33
Electrical TP 16
March 2017
Figure 23
Efficiency versus voltage for selenium stacks
34
Electrical TP 16
March 2017
Figure 24
Efficiency versus voltage for silicon stacks
Edc x Idc
Iac =
3 x F x Eac
where:
Iac = Alternating Current Requirement (Amps)
Edc = Direct Current Output Voltage
Idc = Direct Current Output Amperage
F = Rectifier Efficiency %
Eac = Alternating Current Voltage (per phase to ground)
35
Electrical TP 16
March 2017
Figure 25
CP for Building Underground Heat and Water Lines
36
Electrical TP 16
March 2017
Figure 26
Impressed Current Type CP System for Aircraft Hydrant Refueling System
37
Electrical TP 16
March 2017
Figure 27
Cathodic Protection of Foundation Piles
Figure 28
Impressed Current CP for Existing On-Grade Storage Tank
38
Electrical TP 16
March 2017
Figure 29
Impressed Current CP with Horizontal Anodes for On-Grade Storage Tank
39
Electrical TP 16
March 2017
Figure 30
Impressed Current CP for Small Water Tank
Figure 31
Deep Well Anode Impressed Current CP for Steel Sheet Pile Bulkhead
40
Electrical TP 16
March 2017
Figure 32
Impressed Current CP with Distributed Anodes for Water Side
of a Steel Sheet Pile Bulkhead Wall
Figure 33
Suspended Anode Impressed Current CP for H-Piling in Seawater
41
Electrical TP 16
March 2017
Figure 34
Impressed Current CP Sled Anode for H-Piling in Seawater
42
Electrical TP 16
March 2017
Figure 35
Impressed Current CP for Cellular Earth Fill Pier Supports
43
Electrical TP 16
March 2017
Figure 36
Impressed Current CP for Elevated Water Storage Tank Interior
44
Electrical TP 16
March 2017
Figure 37
Typical Distributed Anode Impressed Current CP for Underground Storage
Tank Farm
45
Electrical TP 16
March 2017
Figure 38
Impressed Current CP System for a Gasoline Service Station
46
Electrical TP 16
March 2017
Figure 39
Impressed Current CP System for an Industrial Hot Water Storage Tank Interior,
with Separate Galvanic Anode for the Electrically Isolated Manway Cover.
47
Electrical TP 16
March 2017
The following examples illustrate the application of the design principles outlined in this
Technical Paper as well as UFC 3-570-01 Chapters 3 and 4. They are intended to
illustrate the design methods to be used, but are NOT standard designs. The
examples are also not considered to be mandatory DOD policy and procedures.
The policy is described in UFC 3-570-01. Project engineers may use these examples
as guides when technically reviewing project design submissions.
When the system is installed, it will require adjustment and possible modification in order
for effective protection to be achieved. In congested areas, interference problems are
often difficult to correct and optimum levels of protection may not be practically achieved.
In such cases, cathodic protection will reduce the incidence and degree of corrosion
damage but corrosion may not be entirely eliminated.
48
Electrical TP 16
March 2017
5.1.2 Calculations.
AP = π DP LP
where
A = Surface area of piping (ft²)
DP = Diameter of pipe
LP = Length of piping
A. Zone 1:
= 2,969 ft²
49
Electrical TP 16
March 2017
B. Zone 2:
= 10,927 ft²
AT = A1 + A2
AT = 2,969 + 10,927
= 13,896 ft²
where
I = Current requirement (amps)
A = Surface area of piping
I’ = Assumed current density = 2 mA/ft²
CE = Pipe coating efficiency
A. Zone 1:
I1 = 2979 x 2 x (1 – 0.5)
B. Zone 2:
I2 = 10927 x 2 x (1 – 0.95)
50
Electrical TP 16
March 2017
gp = (G) (A)
where
gp = pipe specific conductance (Siemens)
G = coating conductance (Siemens/ft2) = 1 x 10-4
A = Surface area of piping = 13,896 ft2
= 1.39 Siemens
gp
g =
Lp/1000
1.39
g =
15,611/1000
α = (r x g)1/2
where
α = attenuation constant
r = pipe resistance (ohms/1000 ft) = 0.021 ohms/1000 ft (schedule 80 pipe)
g = pipe unit specific conductance (Siemens/1000ft) = 0.089 S/1000 ft
α = [(.021ohm)(0.089 S)]1/2
= 0.043
51
Electrical TP 16
March 2017
RG = (r/g)1/2
= 0.486 ohm
where
RSO = resistance on opposite end of pipe from rectifier (ohm)
RG = pipe characteristic resistance (ohm) = 0.486 ohm
x = length of pipe (1000 ft) = 15,611/1000 ft = 15.611
= 0.83 ohm
IS = VS/RSO
where
IS = current required to cause voltage shift of 1 volt at source (Amps)
VS = Source voltage (volt) = 1.0 volt
RSO = resistance on opposite end of pipe from rectifier (ohm) = 0.83 ohm
= 1.21 Amp
where
52
Electrical TP 16
March 2017
= 1.234 - 0.425
= 0.809 volt
This indicates that a single power source at the lower tank farm end of the
pipeline could protect the entire line without greatly over protecting the end near the
power source. This represents a decrease of 19.1%. Generally anything less than 25%
is considered acceptable.
h. Calculate voltage shift at the mid-point along the distance of the pipe
assuming rectifier and anode groundbed are located at the bottom of the
hill near the lower tank farm.
where
E = potential at the opposite end of pipe from rectifier (volt)
ES = potential of the pipe at the rectifier (volt) = 1.0 volt
IS = current req’d to cause voltage shift of 1 volt at source = 1.21 Amp
x = length of pipe to midpoint (1000 ft) = 7,805/1000 ft = 7.81
= 1.06 - 0.20
Again this indicates that a single power source at the end of the pipeline
could protect the both segments of the line without greatly over protecting the end near
the power source.
Although a single rectifier could protect this entire fuel pipeline, the
cathodic protection designer expressed concerns over this system for the following
reasons:
53
Electrical TP 16
March 2017
The two zones will be electrically isolated from each other with a dielectric insulation
flange. Provisions for bonding will be included to give versatility to the system.
End of Example
5.2.2 Calculations.
54
Electrical TP 16
March 2017
1. Arbitrarily select a 2-21/32" dia. X 42" long, 31 Lb. tubular high silicon
chromium bearing cast iron anode in a 10" dia. X 66" long backfill column.
Try to design for a 2 ohm ground bed resistance.
where
2. Calculate current output per anode to ensure it does not exceed the
maximum recommended by the manufacturer. The maximum
recommended output for the 2-21/32" X 42" high silicon cast iron anode is
3.5 Amps
I
IA =
N
where
55
Electrical TP 16
March 2017
0.7 Amp
IA =
8 Anodes
0.09 Amps/anode
NWu
L =
SI
where,
(8 anodes)(31 lb/anode)(0.85)
L =
(1.0 lb/amp-yr)(0.7 amps)
= 300 years
5.2.2.4 Determine Wire Size And Resistance (Rw) For Positive And Negative
Header Cables.
Assume that the rectifier will be near the tank. Therefore, the wire resistance is
negligible.
RT = Ra + Rw + Rx
where,
56
Electrical TP 16
March 2017
RT = 17 + 0 + 0
= 17 ohms
where,
= 25.5 Volts
Vr x I
PA =
e
where,
PA = AC power (VA)
Vr = Rectifier voltage = 28 volts
I = Rectifier current = 4 amps
E = Rectifier efficiency = 85%
28 Volts x 4 amps
PA =
0.85
131 VA
57
Electrical TP 16
March 2017
PA
IAC =
VA
131 VA
IAC =
120 V
= 1.09 amps AC
End of Example
58
Electrical TP 16
March 2017
5.3 Multiple Underground Storage Tanks. The service station shown in Figure
40 has three existing underground tanks and associated pipe. The quality of the
coating is unknown and it is not feasible to install dielectric insulation to isolate the UST
system. Because of the anticipated large current requirement, an impressed current
protection system is chosen. To distribute the current evenly around the tanks and
piping, and to minimize interference effects on other structures, a distributed anode
surface bed using vertical anodes is selected. Vertical anodes can be installed with
relative ease in holes cored through the paving around the UST system. Wiring can be
installed several inches below the paving by cutting and hand excavating narrow
slots/trenches through the paving.
B. Pipe is 2 in., nominal size. Total length of all buried piping is 750 ft.
H. The cathodic protection system circuit resistance should not exceed 2.5
ohms.
J. Current requirement test indicates that 8.2 amperes are needed for
cathodic protection.
5.3.2 Calculations.
5.3.2.1 Find the External Surface Area (A) of the Storage Tanks and Piping.
A. Storage Tanks
AT = 2 π rT 2 + π DT LT
59
Electrical TP 16
March 2017
Figure 40
Cathodic Protection of Multiple Underground Storage Tanks
60
Electrical TP 16
March 2017
where
AT = 3 x 635 ft²
= 1905 ft²
B. Piping
AP = π DP LP
where
AP = Surface area of piping (ft²)
DP = Diameter of pipe = 2.375 in. or 0.198 ft for 2 in. nominal size pipe
LP = Length of piping = 750 ft
= 467 ft²
AP = AT + AP
A = 1905 + 467
= 2372 ft²
61
Electrical TP 16
March 2017
5.3.2.2 Verify the Current Requirement (I).
where
I = 2372 x 2 x (1 – 0)
The 4.7 amp would be reasonable for the facility if it were electrically isolated
from other buried metals such as the building ground system. The actual
current requirement of 8.2 amp occurs because of current loss to these other
buried metal structures and is also reasonable in relation to that calculated for
an isolated facility.
5.3.2.3 Select An Anode and Calculate the Number of Anodes Required (NL) to
Meet the Design Life Requirements.
Calculations can be run on several size anodes, but in this case 2-in. by 60-
in. packaged ceramic rod anodes (rod size = 0.125 in x 4 ft long) are chosen
for ease of construction. Using the following equation, the number of anodes
required to meet the cathodic protection system design life can be calculated:
I
NL =
IA
where
I = Current requirement = 8.2 amps
IA = Ceramic rod anode current rating = 1.0 amps/anode
NL = Quantity of anodes to meet design life
8.2
N =
1.0
62
Electrical TP 16
March 2017
5.3.2.4 Calculate the Quantity of Anodes to Meet the Maximum Anode Bed
Resistance of 2.5 Ohms (NR).
where
Initially, try 9 anodes, the quantity required to meet the design life
= 3.26 ohms
Of the above-calculated quantities for the anodes, 9 to meet the design life
and 14 to meet the maximum anode bed resistance requirement, the larger
quantity of the two must be used to ensure all conditions are satisfied.
Therefore, use 14 each 0.125 in x 4 ft long ceramic rod anodes pre-packaged
in backfill in 2-in. by 60-in. canisters.
RT = RA + Rw + RC
63
Electrical TP 16
March 2017
where,
LW x RMFT
RW =
1000 ft
where,
LW = Effective cable length. The loop circuit makes calculating effective wire
resistance complex. Since current is discharged from anodes spaced
all along the cable, one-half the total cable length may be used to
approximate the cable resistance. Total cable length = 300 ft. Effective
cable length = ½ x 300 ft = 150 ft.)
RMFT = Resistance per 1000 lineal feet of No. 4 AWG cable that has been
selected for ease of handling = 0.254 ohms/1000 LF.
Since the tanks and piping are essentially bare and are not electrically
isolated, structure-to-earth resistance may be considered negligible.
Therefore, RC = 0
64
Electrical TP 16
March 2017
D. Calculate total resistance (RT):
RT = RA + Rw + RC
= 2.26 + 0.04 + 0
= 2.30 ohms
Since the design requirements call for a maximum ground bed resistance
of 2.5 ohms and RT = 2.30 ohms, the design using fourteen 2-in. by 60-in.
packaged ceramic anodes will work.
where,
VREC = Rectifier Voltage (volts)
RT = Total circuit resistance = 2.30 ohms
I = System current requirement = 8.2 amps
120% = Rectifier voltage capacity design safety factor
= 22.6 Volts
Based on the design requirement of 22.6 V and 8.2 amp, a rectifier can be
chosen. A 12-amp, 24-V unit is selected because this is the nearest standard
commercial size available.
End of Example
65
Electrical TP 16
March 2017
5.4 Elevated Steel Water Tank. This impressed current CP design is for an
elevated steel water tank that has not been built. Hence, it is not possible to determine
the current requirements, etc., by actual measurements. Calculated estimates have been
used.
5.4.2 Calculations.
AT = 2 π r x (approximate)
where
66
Electrical TP 16
March 2017
Figure 41
Segmented Elevated Tank for Area Calculations
Ac = 2πrh
where
67
Electrical TP 16
March 2017
AB = √2 x 3.1416 x 28 √14² + 28²
AB = 3,894 ft²
ATB = AT + AC + AB
= 1,759 + 1,935 + 3,894
= 7,588 ft²
A = 2 π rR h R
where
W = YSI/E
where
68
Electrical TP 16
March 2017
10 x 1.0 x 15.2
W =
0.50
= 304 pounds
W = YSI/E
where
Y = 10 years
S = 1.0 lbs/A yr
I = 3.62 A
E = 0.50
W = 10 x 1.0 x 3.62/0.50
= 72.4 pounds
DN
W =
2 (π + N)
where
D = 56 feet
N = Assumed number of anodes = 10
56 x 10
W =
2 (3.1416 + 10)
5.4.2.8 Spacing of Main Anodes. Generally the distance from the anode to the tank
wall and tank bottom is about equal; this distance should be about one-half
the circumferential distance between anodes.
A. Circumferential spacing:
2πr
C =
N
69
Electrical TP 16
March 2017
where
2 x 3.1416 x 22
C =
10
Figure 42
Anode Spacing for Elevated Water Tank
A. Size of anode units selected is 1-1/8 inch outer diameter by ¾ inch inside
diameter by 9 inches long. This is a standard sausage type anode that
weighs one pound, and has an effective surface area of 0.25 ft2.
70
Electrical TP 16
March 2017
304
Number of units =
10 x 1
15.2 Amps
Number of units =
10 x 0.025
This quantity of anode units per string is not practical for the tank bowl
since the distance between the anode hanger and the bottom of the bowl
is only 28 feet. Table 15 shows the maximum recommended discharge
current rate per anode for various types of anodes to ensure a minimum
10-year life. Using the type B anode, only three anode units per string are
required. The manufacturer does not recommend the use of more than
two type B anodes units per anode string assembly because of their
fragile nature. Therefore, the best anode unit choices for the main anode
strings are the type C or type CDD. Type CDD is recommended because
the lead wire connection is protected longer by the thicker wall of the
enlarged ends. Two type CDD anodes per string provide a current
capacity of 2 A x 10 strings = 20 A. These anodes are spaced as shown
in Figure 43.
71
Electrical TP 16
March 2017
15.2 Amps
Anode current density =
2 x 10 x 2
= 0.38 A/ft2
72
Electrical TP 16
March 2017
where
ρ = 4,000 ohm-cm
D = 56 feet
L = 2 x 5 feet = 10 feet
a = 44 x 0.275 = 12.1 feet (0.275-equivalent diameter factor from curve - see
Figure 8-61)
= 3.19 ohms
A. However, the L/d ratio of two 1-1/2-inch diameter by 60-inch long anodes
in tandem is less than 100 and thus the fringe factor must be used.
2 x 60
L/d =
1.5
= 80 < 100
B. The fringe factor from the curve in Figure TP16-45 corresponding to the
L/d ratio is 0.95.
73
Electrical TP 16
March 2017
Figure 43
Anode Suspension Arrangement for Elevated Steel Water Tank
74
Electrical TP 16
March 2017
Figure 44
Equivalent Diameter for Anodes in a Circle in a Water Tank
A. In the design of an elevated water tank, the need for stub anodes must be
justified. The main anode radius has been calculated to b 22 feet. The
main anodes are spaced to provide approximately the same distance from
the sides and the bottom of the tank. The main anodes will protect a
length along the tank bottom equal to 1-1/2 times the spacing o the anode
from the bottom.
75
Electrical TP 16
March 2017
Figure 45
Fringe Factor for Stub Anodes
As = π (r22 – r12)
where
r = radius of protected segment (13 feet)
2
r = radius of riser (2.5 feet)
1
76
Electrical TP 16
March 2017
Im = 15.2 - 1.02
= 14.2 A
200
R =
1000 x 0.159
= 0.032 ohm
E = IR
where
I = 14.2 A
R = 0.032 ohm
E = 14.2 x 0.032
= 0.45 V
E = IR
where
I = 14.2 A
R = 3.03 ohms
E = 14.2 x 3.03
= 43.0 V
77
Electrical TP 16
March 2017
D. Total voltage drop in main anode circuit:
ET = 0.45 + 43.0
= 43.45 or 45.0 V
1.02
Output =
10 x 0.03
= 0.34 A/ft²
where
ρ = 4,000 ohm-cm
D = 56 feet
L = 5 feet
a = 16 x 0.275 = 4.4 feet (factor from Figure 44)
= 10.6 ohms
78
Electrical TP 16
March 2017
60
L/d =
1
= 60 < 100
The fringe factor from the curve in Figure 45 corresponding to the L/d ratio
is 0.9.
200
R =
1000 x 0.159
= 0.032 ohm
E = IR
where
I = 1.02 A
R = 0.032 ohm
E = 1.02 x 0.032
= 0.033 V
50
R =
1000 x 0.159
= 0.008 ohm
79
Electrical TP 16
March 2017
E = IR
where
I = 1.02/10 = 0.102 A
R = 0.008 ohm
E = negligible
E = IR
where
I = 1.02 A
R = 9.54 ohms
E = 1.02 x 9.54
= 9.73 V
ET = 0.033 + 9.73
= 9.73 V
F. Since the stub anode voltage is below the 45 V calculated for the main
tank anode circuit, the necessary current adjustment can be accomplished
through a variable resistor in the stub anode circuit.
Rectifier output = 80 V
Anode current = 1.02 A
Anode resistance = 9.54 ohms
80
Electrical TP 16
March 2017
C. Variable resistor rating:
R = E/I
where
E = 80 V
I = 1.02/2 or 0.51 A
R = 80/0.51
= 156.9 ohms
5.4.2.18 Resistance of Riser Anodes. In order to get the maximum desired current
in the riser (3.62 A), the resistance limit is calculated as follows:
R = E/I
where
E = 43.45 V
I = 3.62 A
R = 43.5/3.62
= 12.0 ohms
81
Electrical TP 16
March 2017
B. Number of units required:
where
ρ = 4,000 ohm-cm
D = 5 feet
D = 2 inches or 0.166 feet
R = 12 ohms
= 5.92 feet
In order to get proper current distribution in the riser pipe, the anode units
should not be placed too far apart. It is generally considered that each
anode unit protects a length along the riser pipe equal to 1-1/2 times the
spacing of the anode from the riser pipe wall.
82
Electrical TP 16
March 2017
where
r = 4,000 ohm-cm
D = 5 feet
D = 2 inches or 0.166 feet
L = 36 x 9 inches = 324 inches or 27 feet
= 2.63 ohms
L/d ratio for the riser anode string is 324/2 or 162; thus no fringe factor
correction is applied.
200
R =
1000 x 0.159
= 0.032 ohms
E = IR
where
I = 3.62 A
R = 0.032 ohm
E = 3.62 x 0.032
= 0.116 V
C. Voltage drop in riser anode suspension cables. Wire size No. 2 AWG,
0.159 ohm/1,000 feet, estimated length 130 feet:
83
Electrical TP 16
March 2017
E = IR
where
I = 3.62/2
= 1.81 A average (single current does not flow the full length of the anode
string)
R = 0.02 ohm
E = 1.81 x 0.02
= 0.04 V
E = IR
where
I = 3.62 A
R = 2.63 ohms
E = 3.62 x 2.63
= 9.52 V
A Criteria for the variable resistor are the same as given for the stub anode
resistor.
Rectifier output = 80 V
Anode current = 3.62 A
Anode resistance = 2.63 + 0.032 + 0.02 = 2.68 ohms
84
Electrical TP 16
March 2017
C. Variable resistor rating:
R = E/I
where
E = 80 V
I = 3.62/2 = 1.81 A
R = 80/1.81
= 44.2 ohms
The resistor should reduce anode current by one-half when full rectifier
voltage is applied. The nearest commercially available resistor size that
meets the above requirements is a 750-W, 50-ohm, 3.87-A resistor
(rheostat). This rheostat is 10 inches in diameter and 3 inches in depth,
and fairly expensive. This rheostat will not fit into most rectifier cases. In
addition, the power consumed by the rheostat is considerable. This power
creates substantial heat that may damage components within the rectifier
case unless adequate ventilation is provided. The problems associated
with using a large rheostat can be eliminated by using a separate rectifier
for the riser anodes. Although initial cost may be slightly high, power
savings will be substantial and damage by heat will be avoided.
A. Requirements:
B. Rectifier rating. Standard ratings for a rectifier in this size class are 18
Volts, 4 Amps.
5.4.2.24 Wire Sizes and Types. All positive feeder and suspension cables (rectifier to
anodes) must be No. 2 AWG, HMWPE insulated copper cable. To avoid complication,
the negative rectifier cable (rectifier to structure) must be the same size and type (see
Figure 46).
85
Electrical TP 16
March 2017
5.4.2.25 Discussion of the Design.
C. The HSCBCI anodes were selected for this particular design purely for
illustrative purposes. It does not mean that this material is superior to
other types of anode material. Other acceptable anode materials include
platinized titanium or niobium and mixed metal oxide (ceramic) anodes.
With the advent of newer tubular center connected anodes, the designer
should choose these anodes over the end connected in most cases
because of their higher current capability and longer life.
D. For this design, silicon stacks should be specified for the rectifier that
protects the bowl and selenium stacks should be specified for the rectifier
that protects the riser. Silicon stacks operate more efficiently at high DC
output voltages than selenium stacks do but require elaborate surge and
overload protection. This protection is not economical in the low power
consuming units. A guide for selection of rectifying cells is as follows:
86
Electrical TP 16
March 2017
Figure 46
Elevated Steel Water Tank Showing Rectifier and Anode Arrangement
87
Electrical TP 16
March 2017
Figure 47
Hand Hole and Anode Suspension Detail for Elevated Water Tank
Figure 48
Riser Anode Suspension Detail for Elevated water Tank
End of Example
88
Electrical TP 16
March 2017
5.5 Elevated Steel Water Tank Where Ice Is Expected.
Impressed current cathodic protection is designed for an elevated steel water tank (Figure
49). The tank is already built and current requirement tests have been conducted.
Anodes cannot be suspended from the tank roof because heavy ice (up to two feet thick)
covers the water service during the winter. The anode cables could not tolerate this
weight; so another type of support must be used. An internally supported hoop shaped
wire anode system is selected.
a. The water tank is a pedestal spheroid with a ten-inch riser pipe. Only the
bowl will be protected because the riser pipe is less than 30 inches in
diameter.
5.5.2 Calculations.
5.5.2.1 Calculate the Length of Wire in Feet (LB) Needed for the Current
Required.
89
Electrical TP 16
March 2017
I
LB =
IA
where
Select the 0.0625 in. diameter copper cored anode wire based on the
current requirement of 25 amps and design life of 15 years.
25
LB =
0.31
= 81 feet
5.5.2.2 Calculate the Desired Diameter of the Anode Wire Ring (DR). Experience
shows that the diameter of the anode wire ring should be between 40 and 70 percent of
the bowl diameter.
Check to determine if the length is adequate for the desired anode life.
For an anode ring diameter of 20.5 feet the circumference (anode wire
length) is
CR = π x DR
= 64.4 feet
This length is inadequate for 0.0625 in. wire anode (which requires a
minimum of 81 feet to meet the desired anode life). Therefore, increase
the wire ring (hoop) diameter to 50 percent of the tank diameter.
and
90
Electrical TP 16
March 2017
CR = π x 25.75
= 80.9 feet
This diameter yields an anode length that is still slightly less than that
required for a 15-year anode life. Therefore, use a hoop diameter that is
about 55 percent of the tank bowl diameter.
and
CR = π x 29.0
= 91 feet
5.5.2.3 Calculate the Anode-to-Water Resistance (RA) for the 0.0625 in. Diameter
Anode Wire.
0.0016 r 8 DR 2 DR
RA = ( ln + ln )
DR DA H
where,
H = 35 Ft x 60% = 21 Ft
0.0016 x 2000 8 x 29 2 x 29
RA = ( ln + ln )
29 0.00521 21
RA = 1.29 ohms
91
Electrical TP 16
March 2017
5.5.2.4 Determine the Total Circuit Resistance (RT).
RT = RN + RW + RC
where,
RN = Anode-to-water resistance
RW = Wire resistance
RC = Tank-to-water resistance
LW x RMFT
RW =
1000 Ft
where,
LW = 115 Ft (Effective wire length. The positive wires from the rectifier to
each end of the anode ring will be about 115 feet long.
RMFT = 0.57 Ohm (Effective wire resistance per 1000 lineal feet. Since there
are positive wires from the rectifier to each end of the anode ring, each
wire will carry about one half of the current [12.5 amp]. The wires
selected are No. 10 AWG. Since the two wires are in parallel, the
effective resistance is one half the single wire resistance [1.02 ohms per
1000 lineal feet/2 = 0.51 ohm])
= 0.06 ohm
The negative wire is connected to the tank structure near the rectifier, so its
resistance is negligible. The tank-to-water resistance is also negligible
because the coating is very deteriorated.
D. Calculate (RT):
= 1.35 ohm
92
Electrical TP 16
March 2017
5.5.2.4 Calculate the Rectifier Voltage (VREC).
VREC = I x RT x 120%
where,
= 40.5 Volts
5.5.4 Installation.
End of Example
93
Electrical TP 16
March 2017
Figure 49
Elevated Pedestal tank with ceramic anode wire ring for icing conditions.
94
Electrical TP 16
March 2017
Figure 50
Pressure entrance fitting for underwater power and reference electrode wire penetrations in water storage tanks.
95
Electrical TP 16
March 2017
5.6 Steel Gas Main. Design an impressed current cathodic protection system for
the 6-inch welded steel gas main shown in Figure 51. The pipeline has not yet been
constructed, so current requirement tests cannot be conducted.
Figure 51
Cathodic Protection System for Gas Main
96
Electrical TP 16
March 2017
5.6.1 Design Data.
G. The pipeline must be isolated from the pump house with a dielectric
insulating flange on the main line inside the pump house.
I. The pipe is coated with hot-applied coal-tar enamel and holiday checked
before installation.
5.6.2 Calculations.
AP = π D L
where
AP = Outside surface area of the pipe
D = Outer pipe diameter = 6.625 inches for a 6-inch nominal diameter pipe
= 6.625 in/12 in/ft = 0.552 feet
L = Pipe length = 6,800 feet
= 11,792 ft²
97
Electrical TP 16
March 2017
5.6.2.2 Area of Bare Pipe to Be Cathodically Protected Based on 90 Percent
Coating Efficiency.
A = AP x (1 – CE)
where
A = Area of bare pipe to be cathodically protected
AP = Outside surface area of the pipe = 11,792 ft²
CE = Pipe coating efficiency = 90% or 0.9
= 1,179 ft²
I = A x CD
where
A = Area of bare pipe to be cathodically protected = 1,179 ft²
I = Current required for cathodic protection
CD = Current density = 2 mA/ft²
= 2,358 mA or 2.36 A
r
RV = K
L
98
Electrical TP 16
March 2017
where
r = Soil resistivity = 2,000 ohm-cm
K = Shape function (refer to para. 6.2.1.4a) = 0.0167
L = Backfilled anode length = 7.0 feet
L/D = 84 inches/10 inches backfill size
2,000
RV = x 0.167
7.0
= 4.77 ohms
One of the design requirements is that the anode bed resistance is not to
exceed 2 ohms. Anode size used is 2-inch diameter x 60 inches long with
carbonaceous backfill having overall dimensions of 10-inch diameter x 84
inches long and spaced 20 feet apart:
1 p
Rn = RV + rs
n s
where
Rn = Anode bed resistance = 2 ohms
n = number of anodes
RV = Single anode resistance = 4.77 ohms
rs = Earth resistivity with pin spacing equal to S = 2,000 ohm-cm
p = paralleling factor (refer to para. 6.2.1.4b)
s = spacing between adjacent anodes = 20 feet
RV
n = p
Rn - ( rs )
s
4.77
n = p
2 - ( 2000 )
20
4.77
n =
2 – 100p
99
Electrical TP 16
March 2017
Try n = 4 anodes, p = 0.00283 (refer to para. 6.2.1.4b)
4.77
4 =
2 – (100 x 0.00283)
4.77
3 =
2 – (100 x 0.00289)
3 = 2.79
This is the closest possible. In order to keep total resistance below 2.0
ohms, use 3 anodes.
1 0.00289
R3 = ( 4.77 ) + ( 2000 )
3 20
I
ND =
AA x IA
where:
2.36
ND =
2.6 x 1
100
Electrical TP 16
March 2017
Only one anode is required to stay within the maximum anode current
discharge limit. However, use the 3 anodes required to meet the 2-ohm
ground bed resistance design requirement.
YSI
W =
E
WE
Y =
SI
where
Y = Theoretical anode bed life
W = Total anode bed weight = 180 pounds
S = Anode consumption rate = 1.0 lb/A yr
E = Anode efficiency = 0.50
I = Current required for cathodic protection = 2.36 A
180 x 0.50
Y =
1.0 x 2.36
= 38.1 years
It should be noted that the expected ground bed life greatly exceeds the
design requirement of 15 years. This is brought about by the additional
anode material required to establish a 2-ohm ground bed. The lower
ground bed resistance saves energy (power, P = I² R).
101
Electrical TP 16
March 2017
= 0.080 ohms
RT = 2.0 + 0.080
= 2.08 ohms
E = IR
where
I = 2.36 A
R = 2.08 ohms
To allow for rectifier aging, film formation, and seasonal changes in the
soil resistivity, it is considered good practice to use a multiplying factor of
1.5 to establish the rectifier voltage rating.
End of Example
102
Electrical TP 16
March 2017
5.7 Hot Water Storage Tank. Design impressed current cathodic protection for
the interior of the industrial hot water storage tank shown in Figure 52.
Figure 52
Cathodic Protection for an Industrial Hot Water Storage Tank
103
Electrical TP 16
March 2017
5.7.2 Computations.
AT = 2 π r² + π d L
where
= 167.5 ft²
A = AP x (1 – CE)
where
A = Area of bare pipe to be cathodically protected
AP = Outside surface area of the pipe = 11,792 ft²
CE = Pipe coating efficiency = 0% or 0
A = 167.5 ft² x (1 – 0)
= 167.5 ft²
I = A x CD
where
A = Area of bare tank surface be cathodically protected = 167.5 ft²
I = Current required for cathodic protection
CD = Current density = 5 mA/ft²
= 838 mA or 0.84 A
104
Electrical TP 16
March 2017
5.7.2.3 Minimum Weight of Anode Material for 5-Year Life.
YSI
W =
E
where
Y = Anode design life = 5 years
S = Anode consumption rate = 1.0 lb/A yr
E = Anode efficiency = 0.50
I = Current required for cathodic protection = 0.84 A
5 x 1.0 x 0.84
W =
E
= 8.4 pounds
W
NL =
WA
where
8.4 lbs
NI =
4 lbs
105
Electrical TP 16
March 2017
where
= 204.5 ohms
This resistance must be corrected by the fringe factor because they are short
anodes. The fringe factor is 0.48 from the curve in Figure 45 for an L/d =
9/1.5 = 6.
1 p
RT = RV + rs
n s
where
RT = Total anode-to-electrolyte resistance
n = number of anodes
RV = resistance-to-electrolyte of a single anode = 98.2 ohms
rs = electrolyte resistivity = 8,600 ohm-cm
p = paralleling factor
s = spacing between adjacent anodes = 4 feet
1 0.00289
RT = 98.2 + 8,600
3 4
= 38.94 ohms
106
Electrical TP 16
March 2017
E = IR
where
I = Protection current required = 0.84 A
R = Anode group resistance = 38.94 ohms
= 32.7 V
5.7.2.6 Rectifier Location. Locate the rectifier adjacent to tank for the following
reasons:
End of Example
107
Electrical TP 16
March 2017
5.8 Steam Heat Distribution System. Provide cathodic protection for a pre-
engineered steam conduit distribution system. Galvanic CP had been previously installed
on the outer conduit of some sections of the steam distribution lines. The system was
ineffective because of high soil resistivity, lack of adequate electrical isolation from
adjacent buried metallic structures (e.g. building H-piles, copper grounding systems,
water lines, electrical conduits, etc). The CP systems included in this design will be
impressed current type. Existing PVC condensate return lines will be replaced with steel
conduits in the near future.
C. Coating Efficiency: 85% for existing steam conduits and 95% for new
condensate lines.
D. Conventional shallow anode beds were considered, but have a high failure
rate due to third party damage. Deep well anode beds require less space
than shallow anode beds, and are not as likely to cause stray current
interference to nearby metallic structures. A number of small
rectifier/deep well systems are anticipated with each system electrically
isolated from all other systems to minimize the possibility of interference
and facilitate troubleshooting of system shorts that may occur. The deep
well will utilize mixed metal oxide tubular anodes in carbonaceous backfill.
F. The steam lines will have insulating flanges and unions at the building tie-
ins. It is anticipated that the electrical isolation will be 90% effective.
Dielectric insulation will be provided at critical locations to electrically
segregate rectifier systems.
5.9.2 Calculations.
AP = π D L
where
AC = Outside surface area of the conduit
108
Electrical TP 16
March 2017
D = Outer steam conduit diameter = 8.625 inches average = 0.72 ft
Outer steam condensate diameter = 6.625 inches average = 0.55 ft
L = Pipe length
A = AC x (1 – CE)
where
A = Area of bare conduit to be cathodically protected
AC = Outside surface area of the conduit
CE = Conduit coating efficiency = 85% or 0.85
Condenstate coating efficiency = 95% or 0.95
109
Electrical TP 16
March 2017
5.9.2.3 Protective Current Required Based on 3 mA/ft² of Bare Metal.
I = A x CD
where
A = Area of bare pipe to be cathodically protected
I = Current required for cathodic protection
CD = Current density = 3 mA/ft²
In order to keep the systems small, limit the size of each system to 15 amps.
The number of systems is
Use mixed metal oxide (MMO) tubular anodes in carbonaceous backfill. The
quantity of MMO anodes must be calculated to meet two different parameters:
design life based on anode maximum current discharge, and anode bed
resistance. The required quantity of anodes will be the larger of the two
calculated quantities.
Y IR
NL =
AA S
where:
IR = Current required = 8.9 amps
NL = Number of anodes to meet design life
S = Manufacturer’s MMO anode life rating (years)
AA = Manufacturer’s MMO anode current rating (amps)
Y = CP system design life = 20 years
110
Electrical TP 16
March 2017
Example Manufacturer’s MMO Anode Ratings
Rated Output (Amperes)
Anode Size
10 years 15 years 20 years
1” x 45” 5.5 – 6.0 4.0 – 4.5 3.0 – 3.5
1” x 60” 7.0 – 8.0 5.0 – 6.0 4.0 – 5.0
1” x 90” 11.0 – 12.0 8.0 – 9.0 6.0 – 7.0
20 x 15
NL =
3.25 x 20
= 5 anodes
The anodes will be installed in a vertical deep well. The resistance of the
anode well can be approximated by the following equation:
0.0052 r 8L
RS = [ ln ( )-1]
L d
where
111
Electrical TP 16
March 2017
0.0052 x 22,700 8 x 100
RS = [ ln ( )-1]
100 0.67
Several iterations using several different backfill column lengths yield the
following:
A 2-ohm deep well ground bed is not economically feasible, therefore, select
a 200 ft backfill column with 4.0 ohms resistance. Although 5 anodes are
required to meet the design life, use 8 anodes to ensure anode current
attenuation along the backfill column is minimized. Install the anodes so that
the bottom of the anode is about ten feet above the bottom of the hole. Use
an anode spacing of twenty feet. Provide anodes with factory connected lead
wires of sufficient length to reach the anode junction box without splicing.
E = I R + 2 Volts
where
I = 15 A
R = 4 ohms
112
Electrical TP 16
March 2017
E = 15 A x 4.0 + 2 V
= 62 V
To allow for rectifier aging, film formation, and seasonal changes in the soil
resistivity, use a multiplying factor of 1.25 to establish the rectifier voltage and
current ratings ratings.
V IR
IL =
240
where:
IL = Full output AC line current (amps).
IR = Rectifier rated output current = 22 amps
VR = Rectifier rated output current = 80 volts
80 x 22
IL =
240
IL = 8 Amps
The circuit overcurrent protection device shall not be less than 125 percent of
the continuous load. The rectifier is a continuous load, therefore,
End of Example
113
Electrical TP 16
March 2017
5.9 Aircraft Multiple Hydrant Refueling System. Cathodic protection will be
provided to new underground 18-inch diameter stainless steel hydrant refueling supply
and return lines, 12-inch/10-inch diameter stainless steel lines supplying the direct
refueling stations, and 32 single point and 17 dual point hydrant outlets with 4-inch/6-inch
risers. The stainless steel lines will be coated with extruded polyethylene. Dielectric
Isolating flanges will be provided to electrically isolate the buried pipelines. Bare
galvanized steel grounding rods will be provided at the hydrant refueling pits. Also
intermittent current loads will be imposed on the CP system where copper clad tie
downs embedded in the concrete apron are connected to one or more aircraft that are
refueling. Tie downs are bonded together by a bare copper conductor encased in the
concrete apron.
B. Current Density: 0.5 mA/ft² for soil, 5 mA/ft² for structures embedded in
concrete.
C. Coating Efficiency: 90% for the extruded polyethylene coating. Bare (0%)
for the hydrant outlet risers.
G. A conventional anode bed with high silicon cast iron tubular anodes
installed horizontally is planned. Due to the soft sand environment, use
ten-inch diameter pre-packaged anodes to simplify installation.
5.9.2 Calculations.
AP = π D L
where
AP = Outside surface area of the pipe
D = Outer pipe diameter
L = Pipe length
114
Electrical TP 16
March 2017
Stainless Steel Distribution Pipe
Diameter (in) Length (ft) Area (ft²)
18 9,000 42,412
12 830 2,770
10 180 507
Total pipe surface area 45,689
There are 32 single point and 17 dual point hydrant outlet pits for a total of
66 hydrant outlet risers.
5.9.2.2 Surface Area of Hydrant Pit Ground Rods. There are32 single point and
17 dual point hydrant outlet pits for a total of 49 pits and therefore, 49 ground rods.
AR = π D L NR
where
AR = Surface area of the ground rod
D = Ground rod diameter = ¾ inch = 0.0625 ft
L = Ground rod length = 10 ft
NR = Quantity of Ground Rods = 49
AP = 3.1416 x 0.0625 x 10 x 49
= 96.2 ft²
A = πDL
where
A = Surface area
D = Ground rod/wire diameter
L = Ground rod/wire length
A = AS x (1 – CE)
where
A = Area of bare structure to be cathodically protected
AS = Surface area of the structure
CE = Structure coating efficiency
I = A x CD
where
A = Area of bare pipe to be cathodically protected
I = Current required for cathodic protection
CD = Current density = 0.5 mA/ft² for pipe and ground rods in soil
= 5 mA/ft² for grounding encased in concrete
116
Electrical TP 16
March 2017
Area of Bare Structure to be Protected
Structure Surface Area (ft²) CD (mA/ft²) I (mA)
SS Distribution Pipe 4,569.0 0.5 2,285
SS Hydrant Risers 242.0 0.5 121
Hydrant Pit Ground Rods 96.2 0.5 48
Tiedown/Ground System 896 5 4,480
6,934
Total pipe surface area
Say 6.9 Amps
Use high silicon chromium bearing cast iron (HSCBCI) tubular anodes. The
quantity of anodes must be calculated to meet three different parameters,
design life, anode bed resistance, and anode maximum current discharge.
The required quantity of anodes will be the largest of the three calculated
quantities.
Y S IR
NL =
WU
where:
IR = Current required = 8.9 amps
NL = Number of anodes to meet design life
S = Anode consumption rate = 1 lb/amp-yr)
U = Anode utilization factor = 0.8
W = Weight of one anode (lb)
Y = CP system design life = 25 years
I
ND =
AA x IA
117
Electrical TP 16
March 2017
where:
I = Current required = 8.9 amps)
AA = Anode surface area (SF)
IA = Max. recommended anode discharge current density (1 amp/SF)
1.64 ρ
RS = x [ln (48L/d) + ln (L/h) - 2 + (2h/L)]
πL
where
d = diameter of anode backfill column = 10 inches
L = length of the anode backfill column (feet)
RS = anode bed design resistance = 2 ohms
ρ = soil resistivity = 86 ohm-m
h = anode depth = 10 feet
Assume one foot of backfill column beyond the ends of each anode.
118
Electrical TP 16
March 2017
CALCULATED ANODE QUANTITIES
Weight Area Backfill Backfill
Anode Size NL ND NR
(LB) (SF) Length (LF) Dia. (ft)
2.66" x 42" 31 2.4 5.42 0.833 9 4 32
2.66" x 60" 46 3.5 9.0 0.833 7 3 20
2.66" x 84" 63 4.9 9.0 0.833 5 2 20
3.75" x 84" 85 6.9 9.0 0.833 4 2 20
= 0.024 ohms
= 0.208 ohms
119
Electrical TP 16
March 2017
RT = RS + Rn + Rp
= 2.23 ohms
E = I R + 2 Volts
where
I = 12 A
R = 2.23 ohms
E = 12 A x 2.23 + 2 V
= 28.8 V
End of Example
120
Electrical TP 16
March 2017
5.10 On-Grade Fuel Storage Tanks. Provide impressed current cathodic
protection for the exterior bottoms of five existing on-grade fuel storage tanks:
Review of historical records indicates that the tanks have not had cathodic protection in
the past.
B. Current Density: Record drawings and field inspection indicates the tanks
have been constructed on an “impermeable layer” of compacted coral with
a minimum thickness of 12 inches. The compacted coral may affect the
even distribution of current and higher than normal current densities may
be necessary to ensure the entire tank bottom is adequately protected.
Usually, 1 - 1.5 ma/sf of current is sufficient to protect a tank bottom if the
current is evenly distributed. With the compacted coral layer beneath the
tanks, a current of 2 ma/sf will be used.
E. A deep well anode will be specified to: (1) improve current distribution of
current to the entire tank bottom because of the compacted coral bed;
(2) minimize excavation (historic preservation laws require an
archaeologist to monitor all excavations full time which would add
significant cost; (3) minimize disruption of on-going operations; and (4)
minimize cathodic interference on other buried metallic structures in the
tank farm.
The surface area of the tank bottoms can be calculated using the following
equation:
AT = π r2
where
AT = Surface area of a tank bottom (ft2)
r = tank bottom radius (ft)
IR = AT x (1 - CE) x CD
where
IR = Current requirement/rectifier output current
AT = Surface area of a tank bottom = 2,640 (ft2)
CE = Coating efficiency = 0 for bare surfaces
CD = Current density = 2 ma/ ft2
122
Electrical TP 16
March 2017
The following tables summarize the current requirements.
Use high silicon chromium bearing cast iron (HSCBCI) tubular anodes.
Y S IR
NL =
WU
where:
NL = Number of anodes to meet design life
Y = CP system design life = 25 years
S = Anode consumption rate = 1 lb/amp-yr)
IR = Current required (amps) = 40 amps
W = Weight of one anode (lb)
U = Anode utilization factor (0.85)
IR
ND =
AA X IA
123
Electrical TP 16
March 2017
where:
IR = Current required (amps) = 40
AA = Anode surface area (ft2)
IA = Max. recommended anode discharge current density (1 amp/ ft2)
Weight Area
Anode Size NL ND
(LB) (SF)
2.19" x 84" (TA2) 46 4.0 25 10
2.66" x 84" (TA3) 63 4.9 19 9
3.75" x 84" (TA4) 85 6.9 14 6
The anodes will be installed in a vertical deep well. The resistance of the
anode well can be approximated by the following equation:
0.0052 r 8L
RS = [ ln ( )-1]
L d
where
Based on the above a minimum anode well active depth of about 55 feet
minimum is required.
Considering the number of anodes required and backfill life, use two wells
of 101 feet active depth with seven anodes in each well. Install the
anodes so that the bottom of the anode is about five feet above the bottom
of the hole. Use an anode spacing of seven feet. Provide anodes with
factory connected lead wires of sufficient length to reach the anode
junction box without splicing. Calculate the anode bed circuit resistance of
each well using the appropriate numbers from the above table:
124
Electrical TP 16
March 2017
A. Anode bed resistance (RA) is the equivalent resistance of the two wells in
parallel. Calculate the equivalent resistance of the two wells:
1 1
RA = +
R1 R2
where,
RA = Equivalent anode well circuit resistance
R1 = Circuit resistance of the first anode well
R2 = Circuit resistance of the second anode well
1 1
RA = +
0.61 0.61
= 0.31 ohm
Anode Well Cable Resistance (RAW). Use No. 8 copper wire for the anode
leads. Each of the anode leads will run directly back to the anode junction
box, so the parallel cable resistance is estimated as follows:
1 1 1 1
= + +····+
RAW RA1 RA2 RAn
where,
125
Electrical TP 16
March 2017
1 1 1 1
= + +····+
RAW RA1 RA2 RA7
1 1 1 1
= + +····+
RAW RA1 RA2 RAn
Anode Header Cable Resistance(RHC). Use No. 2 copper wire for the
anode header cable runs. After a 100 ft run of cable to a junction box,
there are two parallel runs of 200 ft and 450 ft. The equivalent resistance
is 0.053 ohm.
Structure Header Cable Resistance. Use No. 2 copper wire for the
structure leads. After a 450 ft run of cable to anode junction box no. 1,
there are two parallel runs of 100 ft to (tanks 3, 4 and truck stand piping)
and 225 ft (tank 5 piping and tanks 1 and 2). The equivalent resistance for
all of these cable runs is 0.11 ohm.
VR = Irect x RT x 150%
= 30 volts
126
Electrical TP 16
March 2017
5.10.2.5 Calculate Rectifier Input Power.
Available power is 120 volts. For rectifiers of the size specified above, use
single phase 120 volt AC input voltage. Rectifier input power is calculated as
follows:
VR x IR
P =
rectifier efficiency
30 volts x 42 amps
=
0.85
= 1,500 VA
P
IAC =
VAC
1,500 VA
=
120
= 12.5 amperes
5.10.2.6 Summary.
A. Anodes: 14 each high silicon chromium bearing cast iron tubular anodes,
with dimensions of 3.75 inches in diameter x 84 inches long, and weighing
85 LB. Anodes to be installed in two 130 foot deep well, seven anodes
per well, with an active depth of 101 feet. Locate the first anode so that
the bottom anode is 5 feet above the bottom of the well. Install remaining
anodes with a 14 foot spacing on center between the anodes. Anode
supplied by manufacturer with #8 AWG lead wire with HMWPE insulation.
One end is factory connected to the anode. The anode leads should be
long enough to extend to the junction box without splicing.
B. Rectifier:
Type: Air cooled
AC Input: 120 volt, 60 Hz, single phase
DC Output: 30 volts, 42 amperes
Efficiency: 85% minimum
End of Example
127
Electrical TP 16
March 2017
5.11 On-Grade Storage Tanks with Impermeable Containment Liner. Two
each 27,000 barrel on-grade vertical fuel storage tanks are protected by an existing
impressed current CP system. However, a project proposes to install a new tank
bottom above the existing tank bottom, creating a double tank bottom. A high-density
polyethylene containment liner will be installed over the existing tank bottom. The
existing tank bottom and new polyethylene liner will prevent the existing CP system
from providing protection to the new tank bottom. Galvanic corrosion between the new
and old tank bottoms can result in rapid corrosion of the new tank bottom. Therefore, a
new CP system will be installed between the two tank bottoms to provide corrosion
protection to the new tank bottom. The space between the new and existing tank
bottoms will be 4 inches minimum; therefore, the new CP anode system must be
installable in this small space.
E. Slope of the new tank bottom will result in only 4 inches clearance
between the existing and new tank bottom at its lowest point. Therefore,
the proposed new CP system will be an impressed current system
consisting of mixed metal oxide coated titanium ribbon anodes.
F. Each tank will have its own independent system to allow independent
system adjustment for each tank. The rectifier will have two independent
DC output circuits, one for each tank, contained in one enclosure.
5.11.2 Calculations.
The tank bottom is a circular surface for which its surface area can be
calculated from the following equation:
A = π x r2
128
Electrical TP 16
March 2017
The area of each tank bottom is
The current requirement for each tank is calculated using the equation:
Allow an additional 25% to account for unknown factors in the sand backfill
that will be used, for rectifier aging and other long term additional requirement:
Use the next nominal size rectifier circuit of 8 amperes for each tank.
Commonly used mixed metal oxide coated titanium ribbon anodes are 0.25
inch wide by 0.025 inch thick. Manufacturer's literature indicates this material to have a
current rating of 5 ma/LF for 50 year life.
The quantity of anode ribbon required for a 25+ year life for each tank is
N = 3850 ma x 5 ma/LF
= 770 LF
The ribbons will be spaced in evenly spaced parallel strips to ensure uniform
distribution of CP current. This will result in 14 strips of ribbon spaced 5 feet on center.
129
Electrical TP 16
March 2017
5.11.2.3 Circuit Resistance of Anode Ribbons
The strips are of different lengths due to the circular perimeter of the tank
bottom. The theoretical resistance of a strip of metal can be calculated using the
following equation from reference (c):
ρ 2
RS = (ln 4L + a - πab2 + ln 4L - 1)
4πL a 2(a+b) S
where
The rectifier output voltage is calculated by Ohm's Law. Use the resistance
for 45,000 ohm-cm sand to ensure proper operation when sand is dry:
VR = Ireq x Rs
= 3.85 amps x 5.7 Ω
= 21.9 volts
130
Electrical TP 16
March 2017
Use the next highest nominal size rectifier of 24 volts to account for rectifier back
voltage, circuit resistance for the power feed leads and conductor bars, and
compensation for system aging.
VA = VR x IR
rectifier efficiency
= 24 volts x 8 amps
0.65
The total power for the two circuits is 800 VA or 0.8 KVA. For rectifiers of this
size, use single phase 120 volt AC input voltage. AC input current is calculated to be:
IAC = VA/VAC
= 800 VA/120 volts
= 6.67 say 7 amps
5.11.3 Summary
Anode material: Mixed metal oxide coated titanium ribbon, 0.25" wide x
0.025" thick. The anode grid requires 770 LF per tank
placed in 14 parallel rows spaced at 5 FT on center.
Conductor bar: Conductor bars are uncoated titanium ribbons, 0.5" wide x
0.04" thick. Estimated quantity is 320 LF per tank.
Rectifier:
Type: Oil cooled, enclosure suitable for class I, division 2.
AC Input: 120 volt, 7 amps, 60 Hz, single phase
DC Output: Two independent circuits, each circuit rated at 24 volts, 8
amperes
Efficiency: 65% minimum
131
Electrical TP 16
March 2017
Reference
electrodes: Combination cell of copper copper-sulfate and zinc, each
component having a #14 AWG lead wire long enough to
reach the junction box without splicing. 5 each
combination cells per tank are required.
Due to the proximity of the tank bottom to the anode, especially at its lowest
point, dielectric mesh will be installed between the anode and new tank bottom to
prevent electrical short circuits.
End of Example
132
Electrical TP 16
March 2017
5.12 Land Side of Steel Sheet Piling (Impressed Current).
5.12.2 Calculations.
The lengths of the bulkhead and deadman anchor wall are 660 LF and
625 LF respectively. The following table summarizes the number of piles
in each wall.
133
Electrical TP 16
March 2017
The surface area for the bulkhead can be calculated using the following
equation:
The following table summarizes the surface areas for each zone.
2. Tie Rods. There are 153 tie rods, coated, wrapped, and installed in PVC
sleeves. Only the portions of the tie rod at the turnbuckle and on the
back side of the anchor wall are exposed to the soil. An estimated length
of two LF will account for the exposed tie rod and turnbuckle. The tie
rods are 2.5 inches in diameter. Since the tie rods are threaded at the
turnbuckle and anchor wall, assume that the steel is bare. Calculate the
surface area as follows.
3. Anchor Wall. Both sides of the anchor wall are coated and exposed to
the soil. The surface area for both sides of the pile is 5 SF/LF. The
134
Electrical TP 16
March 2017
length of each anchor wall pile is 8 LF. The total anchor wall surface
area is:
5.12.2.2 Calculate the Current Required for Protection of the Sheet Pile.
The current requirement is calculated using the equation:
where
IR = Cathodic protection current required
CE = coating efficiency
J = current density
LAND SIDE
Structures/Zones Surface J Current
CE
area (SF) (ma/SF) Req'd (ma)
Bare 8,800 0 1 8,800
Concrete Coated 2,200 0.9 1 220
Sheet pile
25% of above for concrete cap rebar 2,255
Bulkhead
Bare 8,800 0 2 17,600
Soil
Coated 33,000 0.7 2 19,800
Tie Rods Soil Bare 200 0 2 400
Sheet pile
Soil Coated 16,680 0.7 2 10,008
Anchor Wall
Total Land Side Current Required 59,083
or 59.1 amps
Use an 80 ampere rectifier. The extra current capacity will allow for additional
coating deterioration, system aging, and current loss to the water side of the sheet pile.
135
Electrical TP 16
March 2017
5.12.2.3 Calculate the Quantity of Anodes.
Use high silicon chromium bearing cast iron (HSCBCI) tubular anodes. The
quantity of anodes must be calculated to meet three different parameters,
design life, anode bed resistance, and anode maximum current discharge.
The required quantity of anodes will be the largest of the three calculated
quantities.
Y S IR
NL =
WU
where:
IR = Current required = 59.1 amps
NL = Number of anodes to meet design life
S = Anode consumption rate = 1 lb/amp-yr)
U = Anode utilization factor = 0.8
W = Weight of one anode (lb)
Y = CP system design life = 20 years
I
ND =
AA x IA
where:
I = Current required (59.1 amps)
AA = Anode surface area (SF)
IA = Max. recommended anode discharge current density (1 amp/SF)
136
Electrical TP 16
March 2017
0.0052 ρ
NR = x [ ln (8L/d) - 1 ]
RS x L
where
d = diameter of anode backfill column (1 FT)
L = length of the anode backfill column (LF)
NR = quantity of anodes to meet the anode bed design resistance
RS = anode bed design resistance (1 ohm)
ρ = soil resistivity (6,000 ohm-cm)
137
Electrical TP 16
March 2017
5.12.2.4 Calculate the Total Circuit Resistance (RT).
1. Calculate the anode bed circuit resistance (Rs) using the appropriate
numbers from the above table:
0.0052 ρ
RS = x [ ln (8L/d) - 1 ]
N x L
= 0.56 ohm
Each anode lead will run directly back to the anode junction box, so the
parallel cable resistance is estimated to be equivalent to a 230 LF length
of cable. Use No. 4 copper wire for the anode leads. The cable
resistance is estimated as follows:
The total circuit resistance is 0.56 ohm + 0.06 ohm = 0.62 ohm
5.12.2.5 Calculate the Rectifier Output Voltage (VR) Using Ohm's Law.
VR = Irect x RT x 125%
= 59.1 amps x 0.62 Ω x 1.25
= 45.8 volts
Use the next highest nominal size rectifier rated for 50 volts DC.
Available power is 480/277 volts. For rectifiers of the size specified above,
use three phase 480 volt AC input voltage. Three phase rectifiers are more
efficient and long term power costs outweigh the higher initial costs for the
rectifier. Rectifier input power is calculated as follows:
138
Electrical TP 16
March 2017
VR x IR
P =
rectifier efficiency
50 volts x 80 amps
=
0.85
P
IAC =
VAC x 1.732
5,000 VA
=
480 volts x 1.732
= 6 amps
The sheet pile bulkhead is not located near a building where an electrical
panel can be used. Therefore, the rectifier will be located adjacent to a three
phase, 480 volt transformer station.
VA
IFL =
VAC x √3
500,000 VA
=
480 volts x 1.732
= 601 amps
IFL
ISC =
%ZT/100
601
=
4.5/100
139
Electrical TP 16
March 2017
= 13,356 Amps
5.12.2.7 Summary
Rectifier:
Type: Oil cooled, enclosure suitable for outdoors use.
AC Input: 480 volt, 6 amps, 60 Hz, three phase
DC Output: 50 volts, 80 amps
Efficiency: 85% minimum
End of Example
140
Electrical TP 16
March 2017
Figure 40
Cathodic Protection of Multiple Underground Storage Tanks
60
Electrical TP 16
March 2017
where
AT = 3 x 635 ft²
= 1905 ft²
B. Piping
AP = π DP LP
where
AP = Surface area of piping (ft²)
DP = Diameter of pipe = 2.375 in. or 0.198 ft for 2 in. nominal size pipe
LP = Length of piping = 750 ft
= 467 ft²
AP = AT + AP
A = 1905 + 467
= 2372 ft²
61
Electrical TP 16
March 2017
where
I = 2372 x 2 x (1 – 0)
The 4.7 amp would be reasonable for the facility if it were electrically isolated
from other buried metals such as the building ground system. The actual
current requirement of 8.2 amp occurs because of current loss to these other
buried metal structures and is also reasonable in relation to that calculated for
an isolated facility.
5.3.2.3 Select An Anode and Calculate the Number of Anodes Required (NL) to
Meet the Design Life Requirements.
Calculations can be run on several size anodes, but in this case 2-in. by 60-
in. packaged ceramic rod anodes (rod size = 0.125 in x 4 ft long) are chosen
for ease of construction. Using the following equation, the number of anodes
required to meet the cathodic protection system design life can be calculated:
I
NL =
IA
where
I = Current requirement = 8.2 amps
IA = Ceramic rod anode current rating = 1.0 amps/anode
NL = Quantity of anodes to meet design life
8.2
N =
1.0
62
Electrical TP 16
March 2017
5.3.2.4 Calculate the Quantity of Anodes to Meet the Maximum Anode Bed
Resistance of 2.5 Ohms (NR).
where
Initially, try 9 anodes, the quantity required to meet the design life
= 3.26 ohms
Of the above-calculated quantities for the anodes, 9 to meet the design life
and 14 to meet the maximum anode bed resistance requirement, the larger
quantity of the two must be used to ensure all conditions are satisfied.
Therefore, use 14 each 0.125 in x 4 ft long ceramic rod anodes pre-packaged
in backfill in 2-in. by 60-in. canisters.
RT = RA + Rw + RC
63
Electrical TP 16
March 2017
where,
LW x RMFT
RW =
1000 ft
where,
LW = Effective cable length. The loop circuit makes calculating effective wire
resistance complex. Since current is discharged from anodes spaced
all along the cable, one-half the total cable length may be used to
approximate the cable resistance. Total cable length = 300 ft. Effective
cable length = ½ x 300 ft = 150 ft.)
RMFT = Resistance per 1000 lineal feet of No. 4 AWG cable that has been
selected for ease of handling = 0.254 ohms/1000 LF.
Since the tanks and piping are essentially bare and are not electrically
isolated, structure-to-earth resistance may be considered negligible.
Therefore, RC = 0
64
Electrical TP 16
March 2017
RT = RA + Rw + RC
= 2.26 + 0.04 + 0
= 2.30 ohms
Since the design requirements call for a maximum ground bed resistance
of 2.5 ohms and RT = 2.30 ohms, the design using fourteen 2-in. by 60-in.
packaged ceramic anodes will work.
where,
VREC = Rectifier Voltage (volts)
RT = Total circuit resistance = 2.30 ohms
I = System current requirement = 8.2 amps
120% = Rectifier voltage capacity design safety factor
= 22.6 Volts
Based on the design requirement of 22.6 V and 8.2 amp, a rectifier can be
chosen. A 12-amp, 24-V unit is selected because this is the nearest standard
commercial size available.
End of Example
65
Electrical TP 16
March 2017
5.4 Elevated Steel Water Tank. This impressed current CP design is for an
elevated steel water tank that has not been built. Hence, it is not possible to determine
the current requirements, etc., by actual measurements. Calculated estimates have been
used.
5.4.2 Calculations.
AT = 2 π r x (approximate)
where
66
Electrical TP 16
March 2017
Figure 41
Segmented Elevated Tank for Area Calculations
Ac = 2πrh
where
67
Electrical TP 16
March 2017
ATB = AT + AC + AB
= 1,759 + 1,935 + 3,894
= 7,588 ft²
A = 2 π rR h R
where
W = YSI/E
where
68
Electrical TP 16
March 2017
10 x 1.0 x 15.2
W =
0.50
= 304 pounds
W = YSI/E
where
Y = 10 years
S = 1.0 lbs/A yr
I = 3.62 A
E = 0.50
W = 10 x 1.0 x 3.62/0.50
= 72.4 pounds
DN
W =
2 (π + N)
where
D = 56 feet
N = Assumed number of anodes = 10
56 x 10
W =
2 (3.1416 + 10)
5.4.2.8 Spacing of Main Anodes. Generally the distance from the anode to the tank
wall and tank bottom is about equal; this distance should be about one-half
the circumferential distance between anodes.
A. Circumferential spacing:
2πr
C =
N
69
Electrical TP 16
March 2017
where
2 x 3.1416 x 22
C =
10
Figure 42
Anode Spacing for Elevated Water Tank
A. Size of anode units selected is 1-1/8 inch outer diameter by ¾ inch inside
diameter by 9 inches long. This is a standard sausage type anode that
weighs one pound, and has an effective surface area of 0.25 ft2.
70
Electrical TP 16
March 2017
304
Number of units =
10 x 1
15.2 Amps
Number of units =
10 x 0.025
This quantity of anode units per string is not practical for the tank bowl
since the distance between the anode hanger and the bottom of the bowl
is only 28 feet. Table 15 shows the maximum recommended discharge
current rate per anode for various types of anodes to ensure a minimum
10-year life. Using the type B anode, only three anode units per string are
required. The manufacturer does not recommend the use of more than
two type B anodes units per anode string assembly because of their
fragile nature. Therefore, the best anode unit choices for the main anode
strings are the type C or type CDD. Type CDD is recommended because
the lead wire connection is protected longer by the thicker wall of the
enlarged ends. Two type CDD anodes per string provide a current
capacity of 2 A x 10 strings = 20 A. These anodes are spaced as shown
in Figure 43.
71
Electrical TP 16
March 2017
15.2 Amps
Anode current density =
2 x 10 x 2
= 0.38 A/ft2
72
Electrical TP 16
March 2017
where
ρ = 4,000 ohm-cm
D = 56 feet
L = 2 x 5 feet = 10 feet
a = 44 x 0.275 = 12.1 feet (0.275-equivalent diameter factor from curve - see
Figure 8-61)
= 3.19 ohms
A. However, the L/d ratio of two 1-1/2-inch diameter by 60-inch long anodes
in tandem is less than 100 and thus the fringe factor must be used.
2 x 60
L/d =
1.5
= 80 < 100
B. The fringe factor from the curve in Figure TP16-45 corresponding to the
L/d ratio is 0.95.
73
Electrical TP 16
March 2017
Figure 43
Anode Suspension Arrangement for Elevated Steel Water Tank
74
Electrical TP 16
March 2017
Figure 44
Equivalent Diameter for Anodes in a Circle in a Water Tank
A. In the design of an elevated water tank, the need for stub anodes must be
justified. The main anode radius has been calculated to b 22 feet. The
main anodes are spaced to provide approximately the same distance from
the sides and the bottom of the tank. The main anodes will protect a
length along the tank bottom equal to 1-1/2 times the spacing o the anode
from the bottom.
75
Electrical TP 16
March 2017
Figure 45
Fringe Factor for Stub Anodes
As = π (r22 – r12)
where
r = radius of protected segment (13 feet)
2
r = radius of riser (2.5 feet)
1
76
Electrical TP 16
March 2017
Im = 15.2 - 1.02
= 14.2 A
200
R =
1000 x 0.159
= 0.032 ohm
E = IR
where
I = 14.2 A
R = 0.032 ohm
E = 14.2 x 0.032
= 0.45 V
E = IR
where
I = 14.2 A
R = 3.03 ohms
E = 14.2 x 3.03
= 43.0 V
77
Electrical TP 16
March 2017
ET = 0.45 + 43.0
= 43.45 or 45.0 V
1.02
Output =
10 x 0.03
= 0.34 A/ft²
where
ρ = 4,000 ohm-cm
D = 56 feet
L = 5 feet
a = 16 x 0.275 = 4.4 feet (factor from Figure 44)
= 10.6 ohms
78
Electrical TP 16
March 2017
60
L/d =
1
= 60 < 100
The fringe factor from the curve in Figure 45 corresponding to the L/d ratio
is 0.9.
200
R =
1000 x 0.159
= 0.032 ohm
E = IR
where
I = 1.02 A
R = 0.032 ohm
E = 1.02 x 0.032
= 0.033 V
50
R =
1000 x 0.159
= 0.008 ohm
79
Electrical TP 16
March 2017
E = IR
where
I = 1.02/10 = 0.102 A
R = 0.008 ohm
E = negligible
E = IR
where
I = 1.02 A
R = 9.54 ohms
E = 1.02 x 9.54
= 9.73 V
ET = 0.033 + 9.73
= 9.73 V
F. Since the stub anode voltage is below the 45 V calculated for the main
tank anode circuit, the necessary current adjustment can be accomplished
through a variable resistor in the stub anode circuit.
Rectifier output = 80 V
Anode current = 1.02 A
Anode resistance = 9.54 ohms
80
Electrical TP 16
March 2017
R = E/I
where
E = 80 V
I = 1.02/2 or 0.51 A
R = 80/0.51
= 156.9 ohms
5.4.2.18 Resistance of Riser Anodes. In order to get the maximum desired current
in the riser (3.62 A), the resistance limit is calculated as follows:
R = E/I
where
E = 43.45 V
I = 3.62 A
R = 43.5/3.62
= 12.0 ohms
81
Electrical TP 16
March 2017
where
ρ = 4,000 ohm-cm
D = 5 feet
D = 2 inches or 0.166 feet
R = 12 ohms
= 5.92 feet
In order to get proper current distribution in the riser pipe, the anode units
should not be placed too far apart. It is generally considered that each
anode unit protects a length along the riser pipe equal to 1-1/2 times the
spacing of the anode from the riser pipe wall.
82
Electrical TP 16
March 2017
where
r = 4,000 ohm-cm
D = 5 feet
D = 2 inches or 0.166 feet
L = 36 x 9 inches = 324 inches or 27 feet
= 2.63 ohms
L/d ratio for the riser anode string is 324/2 or 162; thus no fringe factor
correction is applied.
200
R =
1000 x 0.159
= 0.032 ohms
E = IR
where
I = 3.62 A
R = 0.032 ohm
E = 3.62 x 0.032
= 0.116 V
C. Voltage drop in riser anode suspension cables. Wire size No. 2 AWG,
0.159 ohm/1,000 feet, estimated length 130 feet:
83
Electrical TP 16
March 2017
E = IR
where
I = 3.62/2
= 1.81 A average (single current does not flow the full length of the anode
string)
R = 0.02 ohm
E = 1.81 x 0.02
= 0.04 V
E = IR
where
I = 3.62 A
R = 2.63 ohms
E = 3.62 x 2.63
= 9.52 V
A Criteria for the variable resistor are the same as given for the stub anode
resistor.
Rectifier output = 80 V
Anode current = 3.62 A
Anode resistance = 2.63 + 0.032 + 0.02 = 2.68 ohms
84
Electrical TP 16
March 2017
R = E/I
where
E = 80 V
I = 3.62/2 = 1.81 A
R = 80/1.81
= 44.2 ohms
The resistor should reduce anode current by one-half when full rectifier
voltage is applied. The nearest commercially available resistor size that
meets the above requirements is a 750-W, 50-ohm, 3.87-A resistor
(rheostat). This rheostat is 10 inches in diameter and 3 inches in depth,
and fairly expensive. This rheostat will not fit into most rectifier cases. In
addition, the power consumed by the rheostat is considerable. This power
creates substantial heat that may damage components within the rectifier
case unless adequate ventilation is provided. The problems associated
with using a large rheostat can be eliminated by using a separate rectifier
for the riser anodes. Although initial cost may be slightly high, power
savings will be substantial and damage by heat will be avoided.
A. Requirements:
B. Rectifier rating. Standard ratings for a rectifier in this size class are 18
Volts, 4 Amps.
5.4.2.24 Wire Sizes and Types. All positive feeder and suspension cables (rectifier to
anodes) must be No. 2 AWG, HMWPE insulated copper cable. To avoid complication,
the negative rectifier cable (rectifier to structure) must be the same size and type (see
Figure 46).
85
Electrical TP 16
March 2017
C. The HSCBCI anodes were selected for this particular design purely for
illustrative purposes. It does not mean that this material is superior to
other types of anode material. Other acceptable anode materials include
platinized titanium or niobium and mixed metal oxide (ceramic) anodes.
With the advent of newer tubular center connected anodes, the designer
should choose these anodes over the end connected in most cases
because of their higher current capability and longer life.
D. For this design, silicon stacks should be specified for the rectifier that
protects the bowl and selenium stacks should be specified for the rectifier
that protects the riser. Silicon stacks operate more efficiently at high DC
output voltages than selenium stacks do but require elaborate surge and
overload protection. This protection is not economical in the low power
consuming units. A guide for selection of rectifying cells is as follows:
86
Electrical TP 16
March 2017
Figure 46
Elevated Steel Water Tank Showing Rectifier and Anode Arrangement
87
Electrical TP 16
March 2017
Figure 47
Hand Hole and Anode Suspension Detail for Elevated Water Tank
Figure 48
Riser Anode Suspension Detail for Elevated water Tank
End of Example
88
Electrical TP 16
March 2017
Impressed current cathodic protection is designed for an elevated steel water tank (Figure
49). The tank is already built and current requirement tests have been conducted.
Anodes cannot be suspended from the tank roof because heavy ice (up to two feet thick)
covers the water service during the winter. The anode cables could not tolerate this
weight; so another type of support must be used. An internally supported hoop shaped
wire anode system is selected.
a. The water tank is a pedestal spheroid with a ten-inch riser pipe. Only the
bowl will be protected because the riser pipe is less than 30 inches in
diameter.
5.5.2 Calculations.
5.5.2.1 Calculate the Length of Wire in Feet (LB) Needed for the Current
Required.
89
Electrical TP 16
March 2017
I
LB =
IA
where
Select the 0.0625 in. diameter copper cored anode wire based on the
current requirement of 25 amps and design life of 15 years.
25
LB =
0.31
= 81 feet
5.5.2.2 Calculate the Desired Diameter of the Anode Wire Ring (DR). Experience
shows that the diameter of the anode wire ring should be between 40 and 70 percent of
the bowl diameter.
Check to determine if the length is adequate for the desired anode life.
For an anode ring diameter of 20.5 feet the circumference (anode wire
length) is
CR = π x DR
= 64.4 feet
This length is inadequate for 0.0625 in. wire anode (which requires a
minimum of 81 feet to meet the desired anode life). Therefore, increase
the wire ring (hoop) diameter to 50 percent of the tank diameter.
and
90
Electrical TP 16
March 2017
CR = π x 25.75
= 80.9 feet
This diameter yields an anode length that is still slightly less than that
required for a 15-year anode life. Therefore, use a hoop diameter that is
about 55 percent of the tank bowl diameter.
and
CR = π x 29.0
= 91 feet
5.5.2.3 Calculate the Anode-to-Water Resistance (RA) for the 0.0625 in. Diameter
Anode Wire.
0.0016 r 8 DR 2 DR
RA = ( ln + ln )
DR DA H
where,
H = 35 Ft x 60% = 21 Ft
0.0016 x 2000 8 x 29 2 x 29
RA = ( ln + ln )
29 0.00521 21
RA = 1.29 ohms
91
Electrical TP 16
March 2017
RT = RN + RW + RC
where,
RN = Anode-to-water resistance
RW = Wire resistance
RC = Tank-to-water resistance
LW x RMFT
RW =
1000 Ft
where,
LW = 115 Ft (Effective wire length. The positive wires from the rectifier to
each end of the anode ring will be about 115 feet long.
RMFT = 0.57 Ohm (Effective wire resistance per 1000 lineal feet. Since there
are positive wires from the rectifier to each end of the anode ring, each
wire will carry about one half of the current [12.5 amp]. The wires
selected are No. 10 AWG. Since the two wires are in parallel, the
effective resistance is one half the single wire resistance [1.02 ohms per
1000 lineal feet/2 = 0.51 ohm])
= 0.06 ohm
The negative wire is connected to the tank structure near the rectifier, so its
resistance is negligible. The tank-to-water resistance is also negligible
because the coating is very deteriorated.
D. Calculate (RT):
= 1.35 ohm
92
Electrical TP 16
March 2017
VREC = I x RT x 120%
where,
= 40.5 Volts
5.5.4 Installation.
End of Example
93
Electrical TP 16
March 2017
Figure 49
Elevated Pedestal tank with ceramic anode wire ring for icing conditions.
94
Electrical TP 16
March 2017
Figure 50
Pressure entrance fitting for underwater power and reference electrode wire penetrations in water storage tanks.
95
Electrical TP 16
March 2017
5.6 Steel Gas Main. Design an impressed current cathodic protection system for
the 6-inch welded steel gas main shown in Figure 51. The pipeline has not yet been
constructed, so current requirement tests cannot be conducted.
Figure 51
Cathodic Protection System for Gas Main
96
Electrical TP 16
March 2017
G. The pipeline must be isolated from the pump house with a dielectric
insulating flange on the main line inside the pump house.
I. The pipe is coated with hot-applied coal-tar enamel and holiday checked
before installation.
5.6.2 Calculations.
AP = π D L
where
AP = Outside surface area of the pipe
D = Outer pipe diameter = 6.625 inches for a 6-inch nominal diameter pipe
= 6.625 in/12 in/ft = 0.552 feet
L = Pipe length = 6,800 feet
= 11,792 ft²
97
Electrical TP 16
March 2017
A = AP x (1 – CE)
where
A = Area of bare pipe to be cathodically protected
AP = Outside surface area of the pipe = 11,792 ft²
CE = Pipe coating efficiency = 90% or 0.9
= 1,179 ft²
I = A x CD
where
A = Area of bare pipe to be cathodically protected = 1,179 ft²
I = Current required for cathodic protection
CD = Current density = 2 mA/ft²
= 2,358 mA or 2.36 A
r
RV = K
L
98
Electrical TP 16
March 2017
where
r = Soil resistivity = 2,000 ohm-cm
K = Shape function (refer to para. 6.2.1.4a) = 0.0167
L = Backfilled anode length = 7.0 feet
L/D = 84 inches/10 inches backfill size
2,000
RV = x 0.167
7.0
= 4.77 ohms
One of the design requirements is that the anode bed resistance is not to
exceed 2 ohms. Anode size used is 2-inch diameter x 60 inches long with
carbonaceous backfill having overall dimensions of 10-inch diameter x 84
inches long and spaced 20 feet apart:
1 p
Rn = RV + rs
n s
where
Rn = Anode bed resistance = 2 ohms
n = number of anodes
RV = Single anode resistance = 4.77 ohms
rs = Earth resistivity with pin spacing equal to S = 2,000 ohm-cm
p = paralleling factor (refer to para. 6.2.1.4b)
s = spacing between adjacent anodes = 20 feet
RV
n = p
Rn - ( rs )
s
4.77
n = p
2 - ( 2000 )
20
4.77
n =
2 – 100p
99
Electrical TP 16
March 2017
4.77
4 =
2 – (100 x 0.00283)
4.77
3 =
2 – (100 x 0.00289)
3 = 2.79
This is the closest possible. In order to keep total resistance below 2.0
ohms, use 3 anodes.
1 0.00289
R3 = ( 4.77 ) + ( 2000 )
3 20
I
ND =
AA x IA
where:
2.36
ND =
2.6 x 1
100
Electrical TP 16
March 2017
Only one anode is required to stay within the maximum anode current
discharge limit. However, use the 3 anodes required to meet the 2-ohm
ground bed resistance design requirement.
YSI
W =
E
WE
Y =
SI
where
Y = Theoretical anode bed life
W = Total anode bed weight = 180 pounds
S = Anode consumption rate = 1.0 lb/A yr
E = Anode efficiency = 0.50
I = Current required for cathodic protection = 2.36 A
180 x 0.50
Y =
1.0 x 2.36
= 38.1 years
It should be noted that the expected ground bed life greatly exceeds the
design requirement of 15 years. This is brought about by the additional
anode material required to establish a 2-ohm ground bed. The lower
ground bed resistance saves energy (power, P = I² R).
101
Electrical TP 16
March 2017
= 0.080 ohms
RT = 2.0 + 0.080
= 2.08 ohms
E = IR
where
I = 2.36 A
R = 2.08 ohms
To allow for rectifier aging, film formation, and seasonal changes in the
soil resistivity, it is considered good practice to use a multiplying factor of
1.5 to establish the rectifier voltage rating.
End of Example
102
Electrical TP 16
March 2017
5.7 Hot Water Storage Tank. Design impressed current cathodic protection for
the interior of the industrial hot water storage tank shown in Figure 52.
Figure 52
Cathodic Protection for an Industrial Hot Water Storage Tank
103
Electrical TP 16
March 2017
5.7.2 Computations.
AT = 2 π r² + π d L
where
= 167.5 ft²
A = AP x (1 – CE)
where
A = Area of bare pipe to be cathodically protected
AP = Outside surface area of the pipe = 11,792 ft²
CE = Pipe coating efficiency = 0% or 0
A = 167.5 ft² x (1 – 0)
= 167.5 ft²
I = A x CD
where
A = Area of bare tank surface be cathodically protected = 167.5 ft²
I = Current required for cathodic protection
CD = Current density = 5 mA/ft²
= 838 mA or 0.84 A
104
Electrical TP 16
March 2017
YSI
W =
E
where
Y = Anode design life = 5 years
S = Anode consumption rate = 1.0 lb/A yr
E = Anode efficiency = 0.50
I = Current required for cathodic protection = 0.84 A
5 x 1.0 x 0.84
W =
E
= 8.4 pounds
W
NL =
WA
where
8.4 lbs
NI =
4 lbs
105
Electrical TP 16
March 2017
where
= 204.5 ohms
This resistance must be corrected by the fringe factor because they are short
anodes. The fringe factor is 0.48 from the curve in Figure 45 for an L/d =
9/1.5 = 6.
1 p
RT = RV + rs
n s
where
RT = Total anode-to-electrolyte resistance
n = number of anodes
RV = resistance-to-electrolyte of a single anode = 98.2 ohms
rs = electrolyte resistivity = 8,600 ohm-cm
p = paralleling factor
s = spacing between adjacent anodes = 4 feet
1 0.00289
RT = 98.2 + 8,600
3 4
= 38.94 ohms
106
Electrical TP 16
March 2017
E = IR
where
I = Protection current required = 0.84 A
R = Anode group resistance = 38.94 ohms
= 32.7 V
5.7.2.6 Rectifier Location. Locate the rectifier adjacent to tank for the following
reasons:
End of Example
107
Electrical TP 16
March 2017
5.8 Steam Heat Distribution System. Provide cathodic protection for a pre-
engineered steam conduit distribution system. Galvanic CP had been previously installed
on the outer conduit of some sections of the steam distribution lines. The system was
ineffective because of high soil resistivity, lack of adequate electrical isolation from
adjacent buried metallic structures (e.g. building H-piles, copper grounding systems,
water lines, electrical conduits, etc). The CP systems included in this design will be
impressed current type. Existing PVC condensate return lines will be replaced with steel
conduits in the near future.
C. Coating Efficiency: 85% for existing steam conduits and 95% for new
condensate lines.
D. Conventional shallow anode beds were considered, but have a high failure
rate due to third party damage. Deep well anode beds require less space
than shallow anode beds, and are not as likely to cause stray current
interference to nearby metallic structures. A number of small
rectifier/deep well systems are anticipated with each system electrically
isolated from all other systems to minimize the possibility of interference
and facilitate troubleshooting of system shorts that may occur. The deep
well will utilize mixed metal oxide tubular anodes in carbonaceous backfill.
F. The steam lines will have insulating flanges and unions at the building tie-
ins. It is anticipated that the electrical isolation will be 90% effective.
Dielectric insulation will be provided at critical locations to electrically
segregate rectifier systems.
5.9.2 Calculations.
AP = π D L
where
108
Electrical TP 16
March 2017
A = AC x (1 – CE)
where
A = Area of bare conduit to be cathodically protected
AC = Outside surface area of the conduit
CE = Conduit coating efficiency = 85% or 0.85
Condenstate coating efficiency = 95% or 0.95
109
Electrical TP 16
March 2017
I = A x CD
where
A = Area of bare pipe to be cathodically protected
I = Current required for cathodic protection
CD = Current density = 3 mA/ft²
In order to keep the systems small, limit the size of each system to 15 amps.
The number of systems is
Use mixed metal oxide (MMO) tubular anodes in carbonaceous backfill. The
quantity of MMO anodes must be calculated to meet two different parameters:
design life based on anode maximum current discharge, and anode bed
resistance. The required quantity of anodes will be the larger of the two
calculated quantities.
Y IR
NL =
AA S
where:
IR = Current required = 8.9 amps
NL = Number of anodes to meet design life
S = Manufacturer’s MMO anode life rating (years)
AA = Manufacturer’s MMO anode current rating (amps)
Y = CP system design life = 20 years
110
Electrical TP 16
March 2017
20 x 15
NL =
3.25 x 20
= 5 anodes
The anodes will be installed in a vertical deep well. The resistance of the
anode well can be approximated by the following equation:
0.0052 r 8L
RS = [ ln ( )-1]
L d
where
111
Electrical TP 16
March 2017
Several iterations using several different backfill column lengths yield the
following:
A 2-ohm deep well ground bed is not economically feasible, therefore, select
a 200 ft backfill column with 4.0 ohms resistance. Although 5 anodes are
required to meet the design life, use 8 anodes to ensure anode current
attenuation along the backfill column is minimized. Install the anodes so that
the bottom of the anode is about ten feet above the bottom of the hole. Use
an anode spacing of twenty feet. Provide anodes with factory connected lead
wires of sufficient length to reach the anode junction box without splicing.
E = I R + 2 Volts
where
I = 15 A
R = 4 ohms
112
Electrical TP 16
March 2017
E = 15 A x 4.0 + 2 V
= 62 V
To allow for rectifier aging, film formation, and seasonal changes in the soil
resistivity, use a multiplying factor of 1.25 to establish the rectifier voltage and
current ratings ratings.
V IR
IL =
240
where:
IL = Full output AC line current (amps).
IR = Rectifier rated output current = 22 amps
VR = Rectifier rated output current = 80 volts
80 x 22
IL =
240
IL = 8 Amps
The circuit overcurrent protection device shall not be less than 125 percent of
the continuous load. The rectifier is a continuous load, therefore,
End of Example
113
Electrical TP 16
March 2017
B. Current Density: 0.5 mA/ft² for soil, 5 mA/ft² for structures embedded in
concrete.
C. Coating Efficiency: 90% for the extruded polyethylene coating. Bare (0%)
for the hydrant outlet risers.
G. A conventional anode bed with high silicon cast iron tubular anodes
installed horizontally is planned. Due to the soft sand environment, use
ten-inch diameter pre-packaged anodes to simplify installation.
5.9.2 Calculations.
AP = π D L
where
AP = Outside surface area of the pipe
D = Outer pipe diameter
L = Pipe length
114
Electrical TP 16
March 2017
There are 32 single point and 17 dual point hydrant outlet pits for a total of
66 hydrant outlet risers.
5.9.2.2 Surface Area of Hydrant Pit Ground Rods. There are32 single point and
17 dual point hydrant outlet pits for a total of 49 pits and therefore, 49 ground rods.
AR = π D L NR
where
AR = Surface area of the ground rod
D = Ground rod diameter = ¾ inch = 0.0625 ft
L = Ground rod length = 10 ft
NR = Quantity of Ground Rods = 49
AP = 3.1416 x 0.0625 x 10 x 49
= 96.2 ft²
A = πDL
where
A = Surface area
D = Ground rod/wire diameter
L = Ground rod/wire length
115
Electrical TP 16
March 2017
A = AS x (1 – CE)
where
A = Area of bare structure to be cathodically protected
AS = Surface area of the structure
CE = Structure coating efficiency
I = A x CD
where
A = Area of bare pipe to be cathodically protected
I = Current required for cathodic protection
CD = Current density = 0.5 mA/ft² for pipe and ground rods in soil
= 5 mA/ft² for grounding encased in concrete
116
Electrical TP 16
March 2017
Use high silicon chromium bearing cast iron (HSCBCI) tubular anodes. The
quantity of anodes must be calculated to meet three different parameters,
design life, anode bed resistance, and anode maximum current discharge.
The required quantity of anodes will be the largest of the three calculated
quantities.
Y S IR
NL =
WU
where:
IR = Current required = 8.9 amps
NL = Number of anodes to meet design life
S = Anode consumption rate = 1 lb/amp-yr)
U = Anode utilization factor = 0.8
W = Weight of one anode (lb)
Y = CP system design life = 25 years
ND = I
117
Electrical TP 16
March 2017
AA x IA
where:
I = Current required = 8.9 amps)
AA = Anode surface area (SF)
IA = Max. recommended anode discharge current density (1 amp/SF)
1.64 ρ
RS = x [ln (48L/d) + ln (L/h) - 2 + (2h/L)]
πL
where
d = diameter of anode backfill column = 10 inches
L = length of the anode backfill column (feet)
RS = anode bed design resistance = 2 ohms
ρ = soil resistivity = 86 ohm-m
h = anode depth = 10 feet
Assume one foot of backfill column beyond the ends of each anode.
118
Electrical TP 16
March 2017
= 0.024 ohms
= 0.208 ohms
119
Electrical TP 16
March 2017
RT = RS + Rn + Rp
= 2.23 ohms
E = I R + 2 Volts
where
I = 12 A
R = 2.23 ohms
E = 12 A x 2.23 + 2 V
= 28.8 V
End of Example
120
Electrical TP 16
March 2017
Review of historical records indicates that the tanks have not had cathodic protection in
the past.
B. Current Density: Record drawings and field inspection indicates the tanks
have been constructed on an “impermeable layer” of compacted coral with
a minimum thickness of 12 inches. The compacted coral may affect the
even distribution of current and higher than normal current densities may
be necessary to ensure the entire tank bottom is adequately protected.
Usually, 1 - 1.5 ma/sf of current is sufficient to protect a tank bottom if the
current is evenly distributed. With the compacted coral layer beneath the
tanks, a current of 2 ma/sf will be used.
E. A deep well anode will be specified to: (1) improve current distribution of
current to the entire tank bottom because of the compacted coral bed;
(2) minimize excavation (historic preservation laws require an
archaeologist to monitor all excavations full time which would add
significant cost; (3) minimize disruption of on-going operations; and (4)
minimize cathodic interference on other buried metallic structures in the
tank farm.
121
Electrical TP 16
March 2017
The surface area of the tank bottoms can be calculated using the following
equation:
AT = π r2
where
AT = Surface area of a tank bottom (ft2)
r = tank bottom radius (ft)
IR = AT x (1 - CE) x CD
where
IR = Current requirement/rectifier output current
AT = Surface area of a tank bottom = 2,640 (ft2)
CE = Coating efficiency = 0 for bare surfaces
CD = Current density = 2 ma/ ft2
122
Electrical TP 16
March 2017
Use high silicon chromium bearing cast iron (HSCBCI) tubular anodes.
Y S IR
NL =
WU
where:
NL = Number of anodes to meet design life
Y = CP system design life = 25 years
S = Anode consumption rate = 1 lb/amp-yr)
IR = Current required (amps) = 40 amps
W = Weight of one anode (lb)
U = Anode utilization factor (0.85)
IR
ND =
AA X IA
123
Electrical TP 16
March 2017
where:
IR = Current required (amps) = 40
AA = Anode surface area (ft2)
IA = Max. recommended anode discharge current density (1 amp/ ft2)
Weight Area
Anode Size NL ND
(LB) (SF)
2.19" x 84" (TA2) 46 4.0 25 10
2.66" x 84" (TA3) 63 4.9 19 9
3.75" x 84" (TA4) 85 6.9 14 6
The anodes will be installed in a vertical deep well. The resistance of the
anode well can be approximated by the following equation:
0.0052 r 8L
RS = [ ln ( )-1]
L d
where
Based on the above a minimum anode well active depth of about 55 feet
minimum is required.
Considering the number of anodes required and backfill life, use two wells
of 101 feet active depth with seven anodes in each well. Install the
anodes so that the bottom of the anode is about five feet above the bottom
of the hole. Use an anode spacing of seven feet. Provide anodes with
factory connected lead wires of sufficient length to reach the anode
junction box without splicing. Calculate the anode bed circuit resistance of
each well using the appropriate numbers from the above table:
124
Electrical TP 16
March 2017
A. Anode bed resistance (RA) is the equivalent resistance of the two wells in
parallel. Calculate the equivalent resistance of the two wells:
1 1
RA = +
R1 R2
where,
RA = Equivalent anode well circuit resistance
R1 = Circuit resistance of the first anode well
R2 = Circuit resistance of the second anode well
1 1
RA = +
0.61 0.61
= 0.31 ohm
Anode Well Cable Resistance (RAW). Use No. 8 copper wire for the anode
leads. Each of the anode leads will run directly back to the anode junction
box, so the parallel cable resistance is estimated as follows:
1 1 1 1
= + +····+
RAW RA1 RA2 RAn
where,
125
Electrical TP 16
March 2017
1 1 1 1
= + +····+
RAW RA1 RA2 RA7
1 1 1 1
= + +····+
RAW RA1 RA2 RAn
Anode Header Cable Resistance(RHC). Use No. 2 copper wire for the
anode header cable runs. After a 100 ft run of cable to a junction box,
there are two parallel runs of 200 ft and 450 ft. The equivalent resistance
is 0.053 ohm.
Structure Header Cable Resistance. Use No. 2 copper wire for the
structure leads. After a 450 ft run of cable to anode junction box no. 1,
there are two parallel runs of 100 ft to (tanks 3, 4 and truck stand piping)
and 225 ft (tank 5 piping and tanks 1 and 2). The equivalent resistance for
all of these cable runs is 0.11 ohm.
VR = Irect x RT x 150%
= 30 volts
126
Electrical TP 16
March 2017
Available power is 120 volts. For rectifiers of the size specified above, use
single phase 120 volt AC input voltage. Rectifier input power is calculated as
follows:
VR x IR
P =
rectifier efficiency
30 volts x 42 amps
=
0.85
= 1,500 VA
P
IAC =
VAC
1,500 VA
=
120
= 12.5 amperes
5.10.2.6 Summary.
A. Anodes: 14 each high silicon chromium bearing cast iron tubular anodes,
with dimensions of 3.75 inches in diameter x 84 inches long, and weighing
85 LB. Anodes to be installed in two 130 foot deep well, seven anodes
per well, with an active depth of 101 feet. Locate the first anode so that
the bottom anode is 5 feet above the bottom of the well. Install remaining
anodes with a 14 foot spacing on center between the anodes. Anode
supplied by manufacturer with #8 AWG lead wire with HMWPE insulation.
One end is factory connected to the anode. The anode leads should be
long enough to extend to the junction box without splicing.
B. Rectifier:
Type: Air cooled
AC Input: 120 volt, 60 Hz, single phase
DC Output: 30 volts, 42 amperes
Efficiency: 85% minimum
End of Example
127
Electrical TP 16
March 2017
E. Slope of the new tank bottom will result in only 4 inches clearance
between the existing and new tank bottom at its lowest point. Therefore,
the proposed new CP system will be an impressed current system
consisting of mixed metal oxide coated titanium ribbon anodes.
F. Each tank will have its own independent system to allow independent
system adjustment for each tank. The rectifier will have two independent
DC output circuits, one for each tank, contained in one enclosure.
5.11.2 Calculations.
The tank bottom is a circular surface for which its surface area can be
calculated from the following equation:
A = π x r2
128
Electrical TP 16
March 2017
The current requirement for each tank is calculated using the equation:
Allow an additional 25% to account for unknown factors in the sand backfill
that will be used, for rectifier aging and other long term additional requirement:
Use the next nominal size rectifier circuit of 8 amperes for each tank.
Commonly used mixed metal oxide coated titanium ribbon anodes are 0.25
inch wide by 0.025 inch thick. Manufacturer's literature indicates this material to have a
current rating of 5 ma/LF for 50 year life.
The quantity of anode ribbon required for a 25+ year life for each tank is
N = 3850 ma x 5 ma/LF
= 770 LF
The ribbons will be spaced in evenly spaced parallel strips to ensure uniform
distribution of CP current. This will result in 14 strips of ribbon spaced 5 feet on center.
129
Electrical TP 16
March 2017
The strips are of different lengths due to the circular perimeter of the tank
bottom. The theoretical resistance of a strip of metal can be calculated using the
following equation from reference (c):
ρ 2
RS = (ln 4L + a - πab2 + ln 4L - 1)
4πL a 2(a+b) S
where
The rectifier output voltage is calculated by Ohm's Law. Use the resistance
for 45,000 ohm-cm sand to ensure proper operation when sand is dry:
VR = Ireq x Rs
= 3.85 amps x 5.7 Ω
= 21.9 volts
130
Electrical TP 16
March 2017
Use the next highest nominal size rectifier of 24 volts to account for rectifier back
voltage, circuit resistance for the power feed leads and conductor bars, and
compensation for system aging.
VA = VR x IR
rectifier efficiency
= 24 volts x 8 amps
0.65
The total power for the two circuits is 800 VA or 0.8 KVA. For rectifiers of this
size, use single phase 120 volt AC input voltage. AC input current is calculated to be:
IAC = VA/VAC
= 800 VA/120 volts
= 6.67 say 7 amps
5.11.3 Summary
Anode material: Mixed metal oxide coated titanium ribbon, 0.25" wide x
0.025" thick. The anode grid requires 770 LF per tank
placed in 14 parallel rows spaced at 5 FT on center.
Conductor bar: Conductor bars are uncoated titanium ribbons, 0.5" wide x
0.04" thick. Estimated quantity is 320 LF per tank.
Rectifier:
Type: Oil cooled, enclosure suitable for class I, division 2.
AC Input: 120 volt, 7 amps, 60 Hz, single phase
DC Output: Two independent circuits, each circuit rated at 24 volts, 8
amperes
Efficiency: 65% minimum
131
Electrical TP 16
March 2017
Reference
electrodes: Combination cell of copper copper-sulfate and zinc, each
component having a #14 AWG lead wire long enough to
reach the junction box without splicing. 5 each
combination cells per tank are required.
Due to the proximity of the tank bottom to the anode, especially at its lowest
point, dielectric mesh will be installed between the anode and new tank bottom to
prevent electrical short circuits.
End of Example
132
Electrical TP 16
March 2017
5.12.2 Calculations.
133
Electrical TP 16
March 2017
The lengths of the bulkhead and deadman anchor wall are 660 LF and
625 LF respectively. The following table summarizes the number of piles
in each wall.
The surface area for the bulkhead can be calculated using the following
equation:
The following table summarizes the surface areas for each zone.
2. Tie Rods. There are 153 tie rods, coated, wrapped, and installed in PVC
sleeves. Only the portions of the tie rod at the turnbuckle and on the
back side of the anchor wall are exposed to the soil. An estimated length
of two LF will account for the exposed tie rod and turnbuckle. The tie
rods are 2.5 inches in diameter. Since the tie rods are threaded at the
turnbuckle and anchor wall, assume that the steel is bare. Calculate the
surface area as follows.
134
Electrical TP 16
March 2017
3. Anchor Wall. Both sides of the anchor wall are coated and exposed to
the soil. The surface area for both sides of the pile is 5 SF/LF. The
length of each anchor wall pile is 8 LF. The total anchor wall surface
area is:
5.12.2.2 Calculate the Current Required for Protection of the Sheet Pile.
The current requirement is calculated using the equation:
where
IR = Cathodic protection current required
CE = coating efficiency
J = current density
LAND SIDE
Structures/Zones Surface J Current
CE
area (SF) (ma/SF) Req'd (ma)
Bare 8,800 0 1 8,800
Concrete Coated 2,200 0.9 1 220
Sheet pile
25% of above for concrete cap rebar 2,255
Bulkhead
Bare 8,800 0 2 17,600
Soil
Coated 33,000 0.7 2 19,800
Tie Rods Soil Bare 200 0 2 400
Sheet pile
Soil Coated 16,680 0.7 2 10,008
Anchor Wall
Total Land Side Current Required 59,083
or 59.1 amps
Use an 80 ampere rectifier. The extra current capacity will allow for additional
coating deterioration, system aging, and current loss to the water side of the sheet pile.
135
Electrical TP 16
March 2017
Use high silicon chromium bearing cast iron (HSCBCI) tubular anodes. The
quantity of anodes must be calculated to meet three different parameters,
design life, anode bed resistance, and anode maximum current discharge.
The required quantity of anodes will be the largest of the three calculated
quantities.
Y S IR
NL =
WU
where:
IR = Current required = 59.1 amps
NL = Number of anodes to meet design life
S = Anode consumption rate = 1 lb/amp-yr)
U = Anode utilization factor = 0.8
W = Weight of one anode (lb)
Y = CP system design life = 20 years
I
ND =
AA x IA
where:
I = Current required (59.1 amps)
AA = Anode surface area (SF)
IA = Max. recommended anode discharge current density (1 amp/SF)
136
Electrical TP 16
March 2017
0.0052 ρ
NR = x [ ln (8L/d) - 1 ]
RS x L
where
d = diameter of anode backfill column (1 FT)
L = length of the anode backfill column (LF)
NR = quantity of anodes to meet the anode bed design resistance
RS = anode bed design resistance (1 ohm)
ρ = soil resistivity (6,000 ohm-cm)
137
Electrical TP 16
March 2017
1. Calculate the anode bed circuit resistance (Rs) using the appropriate
numbers from the above table:
0.0052 ρ
RS = x [ ln (8L/d) - 1 ]
N x L
= 0.56 ohm
Each anode lead will run directly back to the anode junction box, so the
parallel cable resistance is estimated to be equivalent to a 230 LF length
of cable. Use No. 4 copper wire for the anode leads. The cable
resistance is estimated as follows:
The total circuit resistance is 0.56 ohm + 0.06 ohm = 0.62 ohm
5.12.2.5 Calculate the Rectifier Output Voltage (VR) Using Ohm's Law.
VR = Irect x RT x 125%
= 59.1 amps x 0.62 Ω x 1.25
= 45.8 volts
Use the next highest nominal size rectifier rated for 50 volts DC.
Available power is 480/277 volts. For rectifiers of the size specified above,
use three phase 480 volt AC input voltage. Three phase rectifiers are more
efficient and long term power costs outweigh the higher initial costs for the
rectifier. Rectifier input power is calculated as follows:
138
Electrical TP 16
March 2017
VR x IR
P =
rectifier efficiency
50 volts x 80 amps
=
0.85
P
IAC =
VAC x 1.732
5,000 VA
=
480 volts x 1.732
= 6 amps
The sheet pile bulkhead is not located near a building where an electrical
panel can be used. Therefore, the rectifier will be located adjacent to a three
phase, 480 volt transformer station.
VA
IFL =
VAC x √3
500,000 VA
=
480 volts x 1.732
= 601 amps
IFL
ISC =
%ZT/100
601
=
4.5/100
139
Electrical TP 16
March 2017
= 13,356 Amps
5.12.2.7 Summary
Rectifier:
Type: Oil cooled, enclosure suitable for outdoors use.
AC Input: 480 volt, 6 amps, 60 Hz, three phase
DC Output: 50 volts, 80 amps
Efficiency: 85% minimum
End of Example
140