0 ratings0% found this document useful (0 votes) 135 views34 pagesGenerator Protection
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content,
claim it here.
Available Formats
Download as PDF or read online on Scribd
GENERATOR
PROTECTION
@ MULTILIN
GE Power Management
Tecnology Center
Haver, BA USAGenerator Protection
General Considerations
* Severe faults
* Can cause damage to:
— Insulation
— Windings
— Core
* Can cause mechanical shock to:
— Shatts
— Couplings
Generator Protection
Topics
« Stator Windings
— Phase Faults
— Tum-to-Tum Faults
— Ground Faults
* Rotor
— Ground Fa
© System Back-up
— Phase Faults
— Ground Faults
‘+ Abnormal Operating Conditions
— Loss of Excitation
— Unbalanced Stator Current
— Overexcitation
— Abnormal Frequency
— Reverse Power
Pe+ References
+ IEEE Guide for AC Generator Protection - C37.102
+ IEEE Guide for Generator Ground Protection - C37.101
+ IEEE Guide for Abnormal Frequency Protection for
Power Generating Plant - C37.106
+ IEEE Tutorial on the Protection of Synchronous
Generators - 95 TP 102
+ Generator Protection - GEK-75512
+ Generating Station Protection - GET-6497
+ Art and Science of Protective Relaying - Chapter 10
+ Loss of Excitation - GER-3183
+ Negative Sequence - GER-3181
+ Out of Step - GER-3179
+ HSR - System and Machine Considerations - GER-3224
+ Performance Assessment of a New Digital Subsystem
for Generator Protection - (Paper)
ital Protection System
PRO's CON's
+ Economy - Material and Labor + Redundancy
+ Enhanced Protections + Field Experience
- Frequency Tracking
= Configurable Inputs / Outputs
+ Peripheral Functions
- Self Tests
- Present Values
- Communications
- Sequence of Events Recording
= Fault Report / Oscillography
+ Physical Size
Pa) aus
CONTROL
PACKAGE
@
(9) oe
crs
(PTs 3€
600 VOLTS & BELOW
OTHER TYPES OF
GROUNDING MAY
BE APPLICABLE
RECOMMENDED MINIMUM PROTECTION FOR SMALL GENEATOR
1. 0-600 kVA, BELOW 5 kV
2 500-1000 kVA, BELOW 24kV
Time Overcurrent Relay With Voltage
Restraint (Type IFCV)
51G Time Overcurrent Ground Relay
(Type 1FC53)O
DISTRIBUTION
‘TRANSFORMER
OVERVOLTAGE
RELAY
OVERVOLTAGE
RELAYU
Device
SIV
51g
32
87
86
Bus
GROUNDING MAY
BE APPLICABLE
RECOMMENDED PROTECTION FOR SMALL GENERATOR
1, 0-800 kVA, BELOW 8 KV
2. 600-1000 KVA, BELOW 24 kV
Time Overcurrent Relay With Voltage
Restraint (Type IFCV)
Time Overcurrent Ground Relay
(Type 1FC53)
Phase Balance Relay (Type SGC)
‘Anti-Motoring Relay (Type ICW or GGP)
Differential Relay (Type 1JD or CFD)
Auxiliary Lockout Relay (Type HSA)
PsSELF BALANCE DIFFERENTIAL,MINIMUM PROTECTOR FOR LARGE GENERATOR
1. 0-600 kVA, ABOVE 5 kV
2, 600-1000 kVA, ABOVE 2.4KV
3, ABOVE 1000 kVA, ANY VOLTAGE
Device
51V__ Time Overcurrent Relay With Voltage
Restraint (Type IFCV)
51G Time Overcurrent Ground Relay
(Type IFC53)
| 48 Phase Balance Relay (Type SGC)
40 Loss of Excitation Relay (Type DS2820A100
or CEH)
87 Differential Relay (Type IUD or CFD)
> 86 Auxiliary Lockout Relay (Type HSA)
PBRECOMMEND GENERATOR PACKAGE
Device
51V_ Time Overcurrent Relay With Voltage Restraint
(Type IFCV)
51G Time Overcurrent Ground Relay-Generator Neutral
Grounded (Type IFC53)
50GS _Instantaneous Overcurrent Ground Relay-Generator
Neutral Ungrounded (Type HFC)
32 Anti-Motoring Relay (Type ICW or GGP)
40 Loss of Field Relay (Type DS2820A100 or CEH)
46 Phase Balance Relay (Type SGC)
64F Field Ground Relay (Type PUG)
60V Loss of Potential Relay (Type CFVB)
59 ‘Overspeed Relay (Type IFV71)
87 Differential Relay (Type WWD or CFO)
87G _ Sensitive Ground Differential Relay (Type FD)
86 Auxiliary Lockout Relay (Type HSA)
PaPhase Fault Stator Winding Protection
Variable Slope % Diff Relay
Generator Stator C2
‘Winging
) Phase Fault Stator Winding Protection
~ Variable Slope % Diff Relay
* Variable slope minimizes chance of misoperation
during external fault
* Use identical CT's
* Consequences of phase faults severe, but are very rare;
Isolated phase bus
* Detects all phase and some ground faults
* High R grounded fault currents too low!
* Simultaneous tripPhase Fault Backup
Stator Windings
Overall differential
Primary protection for transformer and buswork
Backup for generator
Less sensitive and slower than generator differential (CFD)
Simultaneous trip
panStator Winding Turn-Turn Faults
Split Phase Protection Using Separate Bushing CT’s
+ Hydro machines have
— Multiple turns per slot
— Multiple circuits per phase
* Differentially connected 50/51 relay “compares” current In each circuit
* Difference indicates tum-to-tumn fault
+ 50 must be set insensitively due to
— Normal unbalance
— CT mismatch
Stator Winding Turn-Turn Faults
Split Phase Protection Using Single Window CT
* Single CT per phase eliminates CT mismatch problems
* Differential current caused by differential flux
«50 can be set more sensitively
‘ Detects some phase and ground faults
+ Simultaneous tripGenerator Grounding
St
re
Ts
eg * Zee Sequence Capacv Retctnce
wal} El}e PERERA ci
yd Generator Grounding
* ho Vug = Vig: Veu = 5.4V, #10 TD =>4 sec
#10 TD (4 sec) coordinates with system relays.
+ Vo = >0 for fault at N
‘+ Relay protects 95-97% of winding
* Simultaneous tripping
Stator Winding Ground Fault Protection
(cont'd)
Also Ip = 0 for fault at N
Need to clear in case another occurs;
then machine is solidly grounded!
Normally Ves # 0
* Fault at N= >Vyo:
‘ould use third harmenic undervoltage relay
to protect remaining 3-5%
* Many other methods used
PasG
Coordination - Stator Ground Relay
Capacitance Between Wingings 4
sk ‘SLG
a
je
Te) TT
Fw
* SLG fault on system causes zero sequence voltage
* Voltage can couple to generator side through capacitance
between GSU windings
‘* 1AV must coordinate with system ground fault protection
(if system relaying is overcurrent)
P16Coordination - Stator Ground Relay
Coordination - Stator Ground Relay
PT secondary fault may be detected before fuse can blow
Could remove generator for PT fault — very bad!
Solution: Ground one phase instead of neutral
Line-line voltage across fuse during phase A or phase C fault
Then fuse and IAV probably coordinate
patRotor
ield Ground Protection
Exciter
mt
Rotor Field Ground Protection
* Ifinsulation between field and rotor breaks down,
ground fault occurs
© Shorts part of windings = > unbalanced flux
* Detect with instantaneous DC relay with timer
© Timer prevents operation due to transients caused
by fast excitation response
‘+ Recommend simultaneous trip — sequential
sometimes used, some alarm
PagLoss of Excitation Protection
* Loss of field — short or open
* No magnetic field
* Rotor still driven; so power produced
* Generator derives excitation from system
— Induction generator
* Problems!
— Rotor overspeeds
— Draws Vars, --Voltage pulsates
— Current pulsates (2¥2x Normal)
* Z looking into generator varies!
pagLoss of Excitation Protection
Loss of Excitation Characteristics
for a Tandem Compound Generator
er Unit impedance
Loss of Excitation Protection
Stable Transient Swing-Generator
Initially Operating at 0.95 Leading Power Factor
i un Feu an
ar el
t Oat 1
a C ln
Max Time ¥
wd bee —f
Per Unit Impedance
P20“) Generator Protection Using
Two Loss of Excitation Relays,
One CEH52A Relay
x
I
2
Diameter =
10PU
LL (No Times
Delay)
Diameter =
(Ys sec Time]
x | Delay)
‘ Utilizes 2 offset MHO characteristics
‘¢ Results in simultaneous or generator tripUnbalanced Stator Current Protection
8B ee at
po
—|
le
Lemna te
Leh #le
* Unbalanced currents caused by:
- = Yreymmetrical faults
+ Result in Ig and lp
Unbalanced Stator Current Protection
Rotor End Section of Generator
Including Retaining Ring
Retaining Ring
‘* Generators hate lp
* Icauses:
= 120H2 rotor currents
— Excessive heating in retaining ring,
slot wedges and field windingoO
Unbalanced Stator Current Protection
‘Table |
ANSI Requirements for Unbalanced
Faults on Synchronous Machines
Permissible 17t
‘Types of Synchronous Machine (lz in Per Unit)
Sallent pole generator" 40
‘Synchronous condenser* 30
Cylindrical rotor generators**
Indirectly cooled 30
Directly cooled (0-800 MVA) 10
Directly cooled (801-1600 MVA) See Next Slide
ANSI C-s0:12
ANSI C50:
Negative-Sequence Fault Current Capability
for Directly Cooled Generators
(per ANSI C50.13)
eta
ft 10, -(00625)(MVA - 800)
tin Per Unit
“400 00 7200 7600
Generator MVA RatingUnbalanced Stator Current Protection
Table I!
Continuous Unbalanced Current Capability
Permissible lp
‘Type of Generator and Rating (percent)
Salient Pole
With connected amortisseur windings 10
With non-connected amortisseur windings 5
Cylindrical Rotor
Indirectly cooled 10
Directly cooled
to 960 MVA 8
961 to 1200 MVA 6
1201 to 1500 MVA 5Unbalanced Stator Current Protection
<$
Negatve sequence
ET) Tee orcaeey
= ‘Compare Electromechanical (INC)
‘and Static (SGC)
Unbalanced Stator Current Protection
Typical Time-Current Curve
for Electromechanical INC Relay
121 Generate Capadites
— Relay Charactratics for
Aanous Time Olt Setings
+ Minimum sensitivity
~0.6 PU
B88 88
‘© Relay curves cross
generator capability curves
* Designed to detect
unbalanced, uncleared
system faults
“Time (seconde)
£88.
e7a1otsa0 2456 810
eu)
P25,Unbalanced Stator Current Protection
Generator Negative Sequence Currents
with Open Conductor
‘Open
Conductor
X=02PU.
Number of Lines (PU)
1 06
2 0.09
3 0.05
* INC sensitivity inadequate for open conductor
* Coordination with capability curves difficult
Unbalanced Stator Current Protection
Characteristics of the SGC Static Negative
‘Sequence Time Overcurrent Relay
aes 3 888
“Time In Seconds
a
aos 1 228 1 295 0
er Unt
P26Unbalanced Stator Current Protection
oo) Application of the SGC Relay on an
800 MVA 2-Pole Directly Cooled Generator
“Time tn Second
&
ange oy —l
‘Open Conductor
Range oy
O2b tee systema
af
) ‘+ Generator trip if auxillaries permit
© Simultaneous trip, if notOverexcitation Protection
* Regulator left in service during startup and shutdown
© ITE constant and f |, then 1
+ Flux enters non-laminated parts of generator and transformer
magnetic core, :.Severe overheating
‘© Trip generator and field breakers
5 Overexcitation Protection
General Guide for Permissible Short-Time
Overexcitation of Generator Step-up Transformers
x TTS eodeo]
7 ree
ea Bas
7° een
a: Ath
sore,
15 L ui
" tf one Ton
1 2845 10 2345 10 20904050 100
‘Time (Minutes)
P20) Overexcitation Protection
STV Volts/Hz Relay
'
(s 7 p=
\_s™%) %
v=
T> damicR
© Simultaneous trip amicr > 1
v= kt
KSTurbine Abnormal Frequency Protection
)
+ Overspeed caused by load rejection
* Not a problem, operator or automatic control can
fore normal speed
Underspeed caused by loss of generation
Load shedding takes long time to restore normal speed
Possibility of turbine damage most critical
P30Turbine Abnormal Frequency Protection
‘Turbine Off-Frequency Limits 0.5 Hz Frequency Bands
* Vibrations caused — different modes for different frequencies
* Blade covers and tie wires can crack
+ Generator trip
Turbine Abnormal Frequency Protection
Failure modes are different for different bands.
Failure modes are dependent on cumulative
time within band
Detect cumulative time within bands using “N”
Generator trip or
PatTurbine Abnormal Frequency Protection
Three Step Under Frequency Protective Scheme
Using One Relay and One Timer Per Step
Fa
[
i
F,, Fyand F, — Frequency
el
Ty Tpand T — Timers
wtReverse Power Protection
Caused when energy supply to prime mover Is cut off
Generator drives turbine = >Motor!
Heating due to “windage” losses in turbine and slip
frequency currents
Heating causes abnormal contraction and expansion of parts,
Maximum time turbine can operate
Power directional relay (GGP 53C) set between 0.5 and 3.0%
(setting a function of load and turbine idling losses)
Time delay (30 sec)
‘Turbine trip
PasBackup Protection for System Faults
O
‘« I system relays are distance relays
— Use CEB, overeach longest fi
| simultaneous trip
* If system relays are overcurrent
— Use IFCY, voltage restrained overcurrent relay, generator trip
out of station, TD <1 sec,
Backup Protection for System Faults
Problem-Setting of CEB Backup Relay
ces
Prose
* Large CEB setting may result
‘* Danger of tripping on load or swing
* If false tripping possible, set to detect only bus fault
) and use redundant transmission line relaying
Pst