Manual Pro Mass 300
Manual Pro Mass 300
                                 Special Documentation
                                 Proline Promass 300
                                 Functional Safety Manual
Coriolis flowmeter
Application                                                   Your benefits
Monitoring of the maximum and/or minimum flow or density      • Use for flow monitoring up to SIL 2 (single-channel
in systems which are required to comply with the particular     architecture) or SIL 3 (multi-channel architecture with
functional safety requirements of IEC 61508.                    homogeneous redundancy) - independently assessed and
                                                                certified by TÜV in accordance with IEC 61508
The measuring device fulfills the requirements concerning:
                                                              • Alternatively also suitable for density monitoring
• Functional safety as per IEC 61508
                                                              • Measurement is virtually independent of the process
• Explosion protection (depending on the version)
                                                                properties
• Electromagnetic compatibility as per IEC 61326-3-2 and
                                                              • Permanent self-monitoring
  NAMUR recommendation NE 21
                                                              • Easy installation and commissioning
• Electrical safety as per IEC 61010-1
                                                              • Integrated proof-testing
                                                              • Heartbeat verification for the documentation of diagnostic
                                                                checks in accordance with IEC 61511
                                                                                      Proline Promass 300
Table of contents
Manufacturer's Declaration . . . . . . . . . . . . . . . . . . .                  3
Safety-related characteristic values . . . . . . . . . . . . . . . . . . 4
Useful lifetime of electric components . . . . . . . . . . . . . . . . 6
Document information . . . . . . . . . . . . . . . . . . . . . . . 6
Document function . . . . . . . . . . . . . . . . . . . . . . . . . . . .         6
Using this document . . . . . . . . . . . . . . . . . . . . . . . . . . .         6
Symbols used . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .      6
Supplementary device documentation . . . . . . . . . . . . . . . .                7
Safety function . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Definition of the safety function . . . . . . . . . . . . . . . . . . . 10
Restrictions for use in safety-related applications . . . . . . . 10
Life cycle . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Requirements for the personnel . . . . . . . . . . . . . . . . . . .             23
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .   23
Commissioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .        24
Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .      24
Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .        24
Repairs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .    24
Modification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .     24
Decommissioning . . . . . . . . . . . . . . . . . . . . . . . . . . . .          24
Appendix . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .         25
Structure of the measuring system . . . . . . . . . . . . . . . . .              25
Verification or calibration . . . . . . . . . . . . . . . . . . . . . . .        26
Notes on the redundant use of multiple sensors . . . . . . . .                   26
Version history . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .      26
2                                                                                         Endress+Hauser
Proline Promass 300
Manufacturer's Declaration
A0031602-EN
Endress+Hauser                                             3
                                                                                                                        Proline Promass 300
Safety-related characteristic
values
General
Operating mode  Low Demand Mode  High Demand Mode  Continuous Mode 1)
Valid hardware version (main electronics) From delivery date August 2, 2016
Valid firmware version 01.00.zz and higher (HART; from delivery date August 2, 2016)
Type of assessment                            Complete HW/SW assessment in the context of development including FMEDA and change
(only 1 version can be selected)              process according to 61508-2, 3
                                               Assessment of evidence for proven-in-use HW/SW including FMEDA and change process
                                              according to 61508-2, 3
 Analysis of HW/SW field data for evidence of "prior use" according to IEC 61511
Assessment by (including Report No. + FMEDA   TÜV Rheinland Industrie Service GmbH – Certificate No. 968/FSP 1306.00/16
data source)
SIL integrity
Hardware safety integrity Single-channel service (HFT = 0)  SIL 2 capable  SIL 3 capable
FMEDA
4                                                                                                                               Endress+Hauser
Proline Promass 300
PTC 4)                                                                                              Up to 98 %
             5)
MTBFtot                                                                     66 years                                           55 years
                               6)
Diagnostic test interval                                                                              30 min
                         7)
Fault response time                                                                                    30 s
                        8)
Process safety time                                                                                    50 h
Note
The measuring device has been developed for use in "Low Demand" and "High Demand" mode.
Explanation
Our in-house quality management system saves information on safety-related systematic errors that will become known in the future.
Endress+Hauser                                                                                                                                 5
                                                                                                                     Proline Promass 300
Useful lifetime of electric   The established failure rates of electrical components apply for a useful lifetime of 12 years as per
components                    IEC 61508-2: 2010, Section 7.4.9.5, Note 3.
                              The device's year of manufacture is coded in the first character of the serial number (→ table below).
                              Example: serial number L5ABBF02000 → year of manufacture 2016
                              Document information
Document function             The document is part of the Operating Instructions and serves as a reference for application-specific
                              parameters and notes.
                                    • General information about functional safety: SIL
                                    • General information about SIL is available:
                                      In the Download Area of the Endress+Hauser Internet site: www.de.endress.com/SIL
Symbol Meaning
                                                      DANGER!
                                       DANGER         This symbol alerts you to a dangerous situation. Failure to avoid this situation will
                                                      result in serious or fatal injury.
                                                      WARNING!
                                       WARNING        This symbol alerts you to a dangerous situation. Failure to avoid this situation can
                                                      result in serious or fatal injury.
                                                      CAUTION!
                                       CAUTION        This symbol alerts you to a dangerous situation. Failure to avoid this situation can
                                                      result in minor or medium injury.
                                                      NOTE!
                                       NOTICE         This symbol contains information on procedures and other facts which do not result in
                                                      personal injury.
Symbol Meaning
                                           Tip
                                           Indicates additional information.
Reference to documentation
A Reference to page
6                                                                                                                           Endress+Hauser
Proline Promass 300
Symbol Meaning
Reference to graphic
1. , 2. , 3. … Series of steps
Result of a step
Write-protected parameter
Symbols in graphics
Symbol Meaning
A, B, C, ... Views
Supplementary device         For an overview of the scope of the associated Technical Documentation, refer to the following:
documentation                • The W@M Device Viewer : Enter the serial number from the nameplate
                               (www.endress.com/deviceviewer)
                             • The Endress+Hauser Operations App: Enter the serial number from the nameplate or scan the
                               2-D matrix code (QR code) on the nameplate.
Standard documentation
Operating Instructions
Endress+Hauser                                                                                                            7
                                                                               Proline Promass 300
Technical Information
Safety Instructions
ATEX/IECEx Ex ec XA01514D
cCSAus XP XA01515D
cCSAus Ex d/ Ex de XA01516D
cCSAus Ex nA XA01517D
INMETRO Ex ec XA01519D
NEPSI Ex nA XA01521D
ATEX/IECEx Ex i XA01494D
ATEX/IECEx Ex ec XA01498D
cCSAus IS XA01499D
cCSAus Ex nA XA01513D
INMETRO Ex i XA01500D
INMETRO Ex ec XA01501D
NEPSI Ex i XA01502D
NEPSI Ex nA XA01503D
Special Documentation
8                                                                                   Endress+Hauser
Proline Promass 300
Installation Instructions
                      Installation Instructions for spare   For an overview of the accessories available for order, see the Operating
                      part sets                             Instructions for the device
Endress+Hauser                                                                                                                          9
                                                                                                                            Proline Promass 300
850 Firmware version Firmware with SIL capability, e.g. 01.00.zz (HART)
                                  1)     In devices with several outputs, only current output 1 (terminals 26 and 27) is suitable for safety functions.
                                         The other outputs can, if necessary, be connected for non-safety-oriented purposes.
                                  2)     Only for devices with approval for custody transfer
                                  3)     Additional selection of further approvals is possible.
                                                             Order code:
                                                             Ser. no.:
                                                             Ext. ord. cd.:
i i
Date:
                                                                                                         1
                                                                                                                                                 A0031473
1 SIL logo
                                  Safety function
Definition of the safety          The measuring device's permitted safety functions are:
function                          • Monitoring of a maximum or minimum mass flow or a mass flow range for liquid or gaseous
                                    media
                                  • Monitoring of a maximum or minimum volume flow or a volume flow range for liquid media
                                  • Monitoring of a maximum or minimum density or a density range for liquid media
                                  The safety functions are based on the simultaneous, continuous measurement of the mass flow and
                                  the density of a liquid.
Restrictions for use in safety-   Do not exceed the specifications indicated in the device documentation: →  7.
related applications
                                  Dangerous undetected failures in this scenario
                                  An incorrect output signal that deviates from the value specified in the Operating Instructions but is
                                  still in the range of 4 to 20 mA, is considered a dangerous, undetected failure.
10                                                                                                                                Endress+Hauser
Proline Promass 300
                      NOTICE
                      Use the measuring device according to the specifications.
                      ‣ Pay attention to the medium properties and the environmental conditions.
                      ‣ Carefully follow instructions pertaining to critical process situations and installation conditions.
                            Detailed information on:
                            • Installation
                            • Electrical connection
                            • Medium properties
                            • Environment
                            • Process
                            Operating Instructions and Technical Information for the device →  7
                       LCAUTION
                      Pay particular attention to the following:
                      ‣ It is essential to avoid the occurrence of entrained air, cavitation or two-phase mixtures in the
                         measuring tube which can result in a higher measuring uncertainty.
                      ‣ In the case of liquids with a low boiling point or liquids in suction lines, it is important to ensure
                         that the pressure does not drop below the vapor pressure and that the liquid does not start to
                         boil.
                      ‣ Please ensure that there is never any outgassing of the gases naturally contained in many liquids.
                         Sufficiently high system pressure prevents the occurrence of these effects.
                      ‣ Make sure that cavitation does not occur as it can affect the operating life of the measuring
                         tubes.
                      ‣ If gaseous media are used, turbulences can occur at high flow velocity rates, e.g. if valves are
                         half-closed. This can cause the measured values to fluctuate.
                      ‣ Avoid applications that cause buildup, corrosion or abrasion in the measuring tube.
                      No special measures need to be taken into consideration for single-phase, liquid media with
                      properties similar to water.
                            Detailed information on the suitability of the measuring device for safety-related operation is
                            available from your Endress+Hauser sales center.
Endress+Hauser                                                                                                                11
                                                                                                          Proline Promass 300
                         ‣ Use a 4–20 mA power supply unit with either voltage limitation or voltage monitoring.
                          NOTICE
                         The safety-related connection values depend on the Ex approval.
                         ‣ Pay attention to the safety-related connection values.
                               For detailed information on the connection values, see the "Safety Instructions" documentation
                               → 8
                         HART communication
                         The measuring device also communicates via HART or WirelessHART in the SIL mode. This
                         comprises all the HART features with additional device information.
                          NOTICE
                         The measuring device's safety-related signal is the 4–20 mA analog output signal (output;
                         input 1).
                         All safety measures refer to this signal exclusively.
                         ‣ Please note the following: →  10.
                          NOTICE
                         When the SIL locking code is entered, the device parameters that affect the safety-related
                         output signal are locked and write-protected. It is still possible to read the parameters.
                         When SIL locking is enabled, restrictions apply on all communication options, such as the service
                         interface (CDI-RJ45), HART protocol and WirelessHART protocol, local display and WLAN.
                         ‣ Deactivation of the SIL mode →  19.
12                                                                                                             Endress+Hauser
Proline Promass 300
                                 NOTICE
                                When SIL mode is activated, additional diagnostics are activated.
                                If a diagnostic event occurs and the locked SIL mode is deactivated, the error message remains while
                                the error persists, even if the diagnostic event is no longer active in the unlocked state.
                                ‣ In this case, the device must be disconnected briefly from the power supply .
                                ‣ When the device is then restarted, a self-check is carried out, and the diagnostics event is reset
                                     where applicable.
1) www.endress.com/deviceviewer
Endress+Hauser                                                                                                                          13
                                                                                    Proline Promass 300
14                                                                                        Endress+Hauser
Proline Promass 300
                       NOTICE
                      Once the SIL device has been locked, the process-related parameters are write protected, and
                      thereby locked, for security reasons.
                      It is still possible to read the parameters. When SIL locking is enabled, restrictions apply on all
                      communication options, such as the service interface, HART protocol and WirelessHART protocol,
                      local display and WLAN.
                      ‣ Follow the specified locking sequence.
                       1.   Check preconditions.
                            
                                                                                               Setup
                                       Pressure                    Assign
                                                                                           Current span          Failure mode
                                     compensation             current output 1
                                               Assign                     Assign
                                           process variable           process variable
                                           = Off       or            = Off     or
                                           = Mass flow or            = Density
                                           = Vol. flow
A0015325-EN
                       2.   In the Setup menu → Advanced setup submenu, select the SIL confirmation wizard.
                       3.   Select Set write protection parameter.
                       4.   Enter the SIL locking code 7452.
                             The device first checks the preconditions listed under item 1.
                       NOTICE
                      If these preconditions are not met, the message "SIL preparation = failed" appears on the
                      display along with the parameter that failed to meet the preconditions under 1.
                      The SIL confirmation sequence is not continued.
                      ‣ Check preconditions.
                      If the conditions are met, the message "SIL preparation = finished" appears on the display.
                      Once the preconditions have been met, the device automatically switches the following parameters
                      to safety-oriented settings:
Endress+Hauser                                                                                                                        15
                                                                                                Proline Promass 300
Setup
                                                                     Partial filled
                                           Current output 1
                                                                    pipe detection
                                                 =                        =
                                            Forward flow                  0
A0015326-EN
Diagnostics
Simulation
                                                  =                       =
                                                 Off                     Off
A0015327-EN
     The diagnostic behavior is set in such a way that the measuring device is set to the safe state when
     an error occurs. This means that the diagnostic messages listed in the graphic are set to alarm and
     the current output adopts the configured failsafe mode →  12.
Expert
System
                                                        Diagnostic
                                                         handling
                                                        Diagnostic
                                                         behavior
         Diagnostic no.   Diagnostic no.     Diagnostic no.    Diagnostic no.         Diagnostic no.    Diagnostic no.
             046            140, 274             374             830, 831               834, 835            913
                                                             =
                                                           Alarm
A0031622-EN
16                                                                                                     Endress+Hauser
Proline Promass 300
Expert
Sensor
                                                              Process
                                                             parameter
                                              =                   =                    =
                                              0                   0                   Off
A0031474-EN
Expert
Sensor
                                                               Sensor
                                                             adjustment
                                                              Variable
                                                             adjustment
                      Mass flow   Mass flow         Volume flow       Volume flow      Density offset   Density factor
                       offset      factor              offset            factor
                         =           =                  =                  =                   =              =
                         0           1                  0                  1                   0              1
A0023070-EN
Expert
Sensor
                                                              External
                                                            compensation
                                                             Temperture
                                                               mode
                                                                 =
                                                             Internal
                                                             measured
                                                               value
A0031477-EN
Endress+Hauser                                                                                                                 17
                                                                                              Proline Promass 300
Expert
Output Communication
                                                    Current                HART
                                                    output 1            configuration
                                                    Start-up               HART
                                                     mode                 address
                                                      =                       =
                                                     Min.                     0
A0015328-EN
     To check that values are displayed correctly, the following string appears on the device display or
     operating tool: 0123456789+-.
      5.   The user must confirm that the values are displayed correctly.
            The device displays the current settings for the following parameters one after another for
               the user to confirm each of them:
                               Installation                          Assign
                                                                                               Current span
                                direction                        current output
A0031475-EN
1) This parameter is only displayed if the "Gas" option is selected in the "Medium" parameter.
           For detailed information on the parameters in the graphic, see the Operating Instructions for
           the device →  7
18                                                                                                    Endress+Hauser
Proline Promass 300
                       6.   At the end of the verification, the SIL locking code 7452 must be entered in the Set write
                            protection parameter again to confirm that all the parameter values have been defined
                            correctly.
                             If the SIL locking code has been entered correctly, the message "End of sequence" appears
                                on the display.
                       7.   Press the  key to confirm.
                      The SIL mode is now activated.
Recommendation:
                                                                                                 OFF ON
                                                                                            1
                                                                                            2
                                                                                            3
                                                                                            4
A0029630
                       NOTICE
                      If the SIL confirmation sequence is aborted before the "End of sequence" message is displayed,
                      the SIL device is not locked. The safety-oriented parameter settings have been made but the SIL
                      device has not been locked.
                      ‣ Perform SIL device locking again.
                      Unlocking a SIL device
                      A device in the locked SIL mode is protected against unauthorized operation by means of a SIL
                      locking code and, where applicable, by means of a user-specific release code and a hardware write
                      protection switch. The device must be unlocked in order to change parameters, for proof-tests as well
                      as to reset self-holding diagnostic messages.
                       NOTICE
                      Unlocking the device deactivates diagnostic functions, and the device may not be able to carry
                      out its safety function in the unlocked SIL mode.
                      ‣ Therefore, independent measures must be taken to ensure that there is no risk of danger while
                         the SIL device is unlocked.
                      Unlocking procedure:
                       1.   Check the write protection switch (WP) in the connection compartment.
                       2.   Set this switch to the OFF position where necessary.
                             Hardware write protection disabled.
                       3.   Enter the user-specific release code if necessary.
                       4.   In the Setup menu → Advanced setup submenu, select the Deactivate SIL wizard.
                       5.   Select Reset write protection parameter.
                       6.   Enter the SIL locking code 7452.
                             If the SIL locking code has been entered correctly, the message "End of sequence" appears
                                on the display.
                       7.   Press the  key to confirm.
                      The SIL mode is now deactivated.
Endress+Hauser                                                                                                           19
                                                                                                  Proline Promass 300
Proof-testing    NOTICE
                The safety function is not guaranteed during a proof test.
                Nevertheless, process safety must be guaranteed during proof testing.
                ‣ The safety-related output signal 4 to 20 mA (output; input 1) may not be used for the protective
                   system.
                ‣ Take alternative monitoring measures if necessary.
                Proof testing the safety function of the entire system
                 1.   Check the functional integrity of the safety function at appropriate intervals.
                 2.   The operator specifies the testing interval and this must be taken into account when
                      determining the probability of failure PFDavg of the sensor system.
                       In the case of a single-channel system architecture, the average probability of failure (PFD
                        avg) of the sensor is derived from the proof-test interval Ti, the failure rate for dangerous
                        undetected failures λ du, the proof test coverage PTC and the assumed mission time by
                        close approximation as follows:
                          MT Mission time
                          PTC Proof test coverage
                          Ti Test interval
                 3.   The operator also specifies the procedure for proof-testing.
                       NOTE!
                          In accordance with IEC 61511, as an alternative to testing the safety function of the entire
                          system an independent proof test of the subsystems, →  21 e.g. the sensor, is
                          permitted.
20                                                                                                      Endress+Hauser
Proline Promass 300
SIL2 - 1oo1
                                            PFDa!"
                                   0.003
0.0025 2
0.002
0.0015
                                   0.001
                                                                                                                            1
                                   0.0005
                                   0                                                                                    t
                                             0              2              4             6            8            10
                                                                                                                                       A0031604
                                            PFDa!"
                                   0.003
0.0025 2
0.002
0.0015
                                   0.001
                                                                                                                            1
                                   0.0005
                                   0                                                                                    t
                                             0              2              4             6            8            10
                                                                                                                                       A0031605
                                   I. Test sequence:
                                   The measured values (3 to 5 measuring points) are checked with a secondary standard on an
                                   installed device (mobile calibration rig or calibrated reference device) or on a factory calibration rig
                                   following device removal.
                                   The measured values of the secondary standard and the device under test (DUT) are compared using
                                   one of the following methods:
2) Under IEC 61508 the sensor is synonymous with the entire flowmeter.
Endress+Hauser                                                                                                                             21
                                                                                    Proline Promass 300
     I. Test sequence:
     Check the measured values with a reference value (secondary standard or value from the literature)
     when the device is installed, or check on a factory calibration rig once the device has been removed.
     The density measured values determined in each case are compared against the real density of the
     media.
     The reference values are compared against the measured values of the device under test (DUT) using
     one of the following methods:
     a. Comparison by reading off the digital measured value
     Compare the digital measured value of the secondary standard against the measured value display of
     the DUT at the logic subsystem (process control system or safety-related PLC).
     b. Comparison of the measured value by measuring the current
      1.     Measure the current at the DUT using an external, traceably-calibrated ammeter.
              Note: measuring equipment requirements:
                • DC current measuring uncertainty ±0.2 %
                • DC current resolution 10 μA
      2.     Measure the current of the DUT at the logic subsystem (process control system or safety-
             related PLC).
Other recommendations
22                                                                                       Endress+Hauser
Proline Promass 300
                        NOTICE
                       At least 98 % of dangerous, undetected failures are detected using these test sequences (PTC =
                       0.98). The influence of systematic errors on the safety function is not fully covered by the test.
                       Systematic faults can be caused, for example, by medium properties, operating conditions,
                       build-up or corrosion.
                       ‣ If one of the test criteria from the test sequences described above is not fulfilled, the device may
                           no longer be used as part of a protective system.
                       ‣ Take measures to reduce systematic errors.
                            Detailed information on:
                            • Orientation
                            • Medium properties
                            • Operating conditions
                            Operating Instructions for the device →  7
                       Heartbeat Technology
                       Heartbeat Technology continuously diagnoses whether failures have occurred. The scope of the
                       diagnostics in the SIL mode corresponds to the SFF.
                       Heartbeat Technology also allows operators to create documented proof that diagnostic checks have
                       been carried out and thereby supports the documentation of proof testing in accordance with IEC
                       61511-1, Section 16.3.3, "Documentation of proof testing and inspections".
                        NOTICE
                       The SIL mode needs to be disabled temporarily in order to perform heartbeat verification.
                       ‣ On completion of the verification, the SIL mode must be enabled again .
                            The Heartbeat Verification application package is available as an order option and can be
                            retrofitted on all measuring devices.
                            Please contact your Endress+Hauser service or sales organization to retrofit the device.
                            For detailed information on the verification of the measuring device with Heartbeat
                            Verification,application package, refer to the Special Documentation for the device →  8
                       Life cycle
Requirements for the   The personnel for installation, commissioning, diagnostics and maintenance must fulfill the
personnel              following requirements:
                       ‣ Trained, qualified specialists must have a relevant qualification for this specific function and task.
                       ‣ Are authorized by the plant owner/operator.
                       ‣ Are familiar with federal/national regulations.
                       ‣ Before starting work, read and understand the instructions in the manual and supplementary
                           documentation as well as the certificates (depending on the application).
                       ‣ Follow instructions and comply with basic conditions.
                       The operating personnel must fulfill the following requirements:
                       ‣ Are instructed and authorized according to the requirements of the task by the facility's owner-
                          operator.
                       ‣ Follow the instructions in this manual.
Endress+Hauser                                                                                                             23
                                                                                                  Proline Promass 300
                  Orientation
                       For detailed information on the orientation, see the Operating Instructions for the device
                       → 7
Commissioning          For detailed information on commissioning, see the Operating Instructions for the device
                       → 7
Operation              For detailed information on operation options, see the Operating Instructions for the device
                       → 7
Maintenance For detailed information on maintenance, see the Operating Instructions for the device →  7
                       Alternative monitoring measures must be taken to ensure process safety during configuration,
                       proof-testing and maintenance work on the device.
Repairs                Repair means restoring functional integrity by replacing defective components. Components of
                       the same type must be used for this purpose. It is recommended to document the repair. This
                       includes specifying the device serial number, the repair date, the type of repair and the
                       individual who performed the repair.
                       For detailed information on device returns, see the Operating Instructions for the device →  7
Modification      Modifications are changes to devices with SIL capability already delivered or installed.
                  ‣ Modifications to devices with SIL capability are usually performed in the Endress+Hauser
                    manufacturing center.
                  ‣ Modifications to devices with SIL capability onsite at the user's plant are possible following
                    approval by the Endress+Hauser manufacturing center. In this case, the modifications must be
                    performed and documented by an Endress+Hauser service technician.
                  ‣ Modifications to devices with SIL capability by the user are not permitted.
Decommissioning        For detailed information on decommissioning, see the Operating Instructions for the device
                       → 7
24                                                                                                     Endress+Hauser
Proline Promass 300
                             Appendix
Structure of the measuring   System components
system
                                                                  1              2               3
                                                                                                                            A0015443
                             3      System components
                             1    Pump
                             2    Measuring device
                             3    Valve
                             4    Automation system
                             An analog signal (4–20 mA) proportional to the flow or density is generated in the transmitter. This
                             is sent to a downstream automation system where it is monitored to determine whether it falls
                             below or exceeds a specified limit value. The safety function (mass flow, volume flow or density
                             monitoring) is implemented in this way.
Endress+Hauser                                                                                                                 25
                                                                                                                        Proline Promass 300
                               NOTICE
                              The device must be correctly mounted to guarantee safe operation.
                              ‣ Observe the mounting instructions.
                                    For detailed information on mounting, see the Operating Instructions for the device →  7
Verification or calibration   The SIL mode must be disabled in order to verify the measuring point with Heartbeat Technology or
                              calibrate the measuring point.
                               NOTICE
                              To use the device in a safety function again following a verification or calibration, the
                              configuration of the measuring point must be checked and the SIL mode must be enabled
                              again.
                              ‣ Activation of the SIL mode →  14.
Notes on the redundant use    This section provides additional information regarding the use of homogeneously redundant sensors
of multiple sensors           e.g. 1oo2 or 2oo3 architectures.
                              The common cause factors β and βD indicated below are minimum values for the device. These must
                              be used when designing the sensor subsystem:
                              • Minimum value β for homogeneously redundant use: 2 %
                              • Minimum value βD for homogeneously redundant use: 1 %
                              The device meets the requirements for SIL 3 in homogeneously redundant applications. When
                              installing identical sensors, i.e. the same type and nominal diameter, the sensors must not be
                              connected directly flange to flange but at different locations in the pipe. This is to prevent the
                              sensors from affecting each other acoustically.
                               NOTICE
                              Note the following if a fault is detected in one of the redundantly operated devices during the
                              proof test:
                              ‣ Check the other devices to see if the same fault occurs there.
SD01727D/06/xx/01.16 First version 01.00.zz (HART; from delivery date August 2, 2016)
26                                                                                                                          Endress+Hauser