BURNDY

Grounding

TABLE OF CONTENTS
HYGROUND™ IRREVERSIBLE COMPRESSION GROUNDING
AND INSTALLATION TOOLING

HYGROUND™ Features
and Benefits .....................D-3 - D-4 Type YGIB .....................D-18 - D-19

Type YGL-C ................................D-5 Type GSTUD-HY .......................D-20

D-1
Type YGLR-C ..............................D-6 Types YGT & YTTAG ................D-21

Type YGHP-C .............................D-7 Type YG-B..................................D-22

Type YGHP-C .............................D-8 MECHANICAL GROUNDING


Types KC, K2C .........................D-23
Type YGHC-C .............................D-9
Types KC22J12T13,
EQC632C ................................D-24
Type YGC ..................................D-10

Types KS-DB, GKA,


Type YSHG ................................D-11
KPB, CL50-1 ................D-25 - D-26

Type YGHR-C .......................... D-12


Type GAR ......................D-27 - D-28

Type YGHR-C ..........................D-13


Types GAR-BU & GAR
3900 Series & GAR-RB .........D-29

Type YGHA ...............................D-14


Type GAR-TC ...........................D-30

Type YGHS ...............................D-14


LIGHTNING PROTECTION INFO.
Basic rules for selection are:
Type YGA ..................................D-15 1. Must be like material to the conductor.
2. Two bolts to ground rod –– minimum, for mechanical.
3. Cable to cable connections can be anything –– one bolt,
two bolt, compression, etc.
Type YGS ..................................D-16 4. Cable to steel structure must have 8 in.2 contact with steel.
5. Heavy duty stacks –– mechanical only.
6. On all connectors with heavy duty stack rating, we must
offer 1/16" thick lead plating as an option. Reason is closest
Type YGF ..................................D-17 25 ft. to stack opening must use lead coated product.
7. UL 96 Listing.
BURNDY
Grounding

TABLE OF CONTENTS
MECHANICAL GROUNDING (Continued)

Type GD ....................................D-31 Types GC, GCM ........................D-43

Type GP ....................................D-32 Type GL ....................................D-44

D-2
Type GK ....................................D-32 Type GZ ....................................D-44

Water Pipe Grounding ..D-33 - D-36 Type GC-CT ..............................D-45

Type GC-A ................................D-37 Type GIE-G ...............................D-46

Type GG ....................................D-38 Rail Connector ..........................D-47

Type GQ ....................................D-39 Type QGFL ...............................D-48

Type GX ....................................D-40 Type GA-H ................................D-48

Type GRC .................................D-40 Type GRF ..................................D-49


Raised Floor Grounding

Type B ............................D-41 - D-42


Types GP-G1, GPRT..................D-50
Raised Floor Grounding
Types GB, GBM ........................D-43
BURNDY
Grounding

THE HYGROUND™
IRREVERSIBLE
COMPRESSION
SYSTEM
BURNDY® has developed an irreversible
compression ground system which meets the
most stringent safety and performance
requirements, including those of OSHA and
nuclear power plant design. Performance
excellence and long life expectancy are the
system’s basic design guidelines. It is a com-
plete system which consists of connectors for
grid cross connections, taps, splices, cable to D-3
ground rod, ground plates and terminations.

Our irreversible compression ground connec-


tors employ well-proven design principles
and technology that have been in existence
for over 60 years.

Connectors are just one component of our


Irreversible Compression Ground System.
Installation tooling is also an integral part of
this system. BURNDY® pioneered the com-
pression connector principle and continues
today to be the leader in compression tech-
nology. Our tooling package is the most
extensive in the industry and affords the user
many options.
BURNDY
Grounding

THE HYGROUND™ Features and Benefits


IRREVERSIBLE • Irreversible compression.
◊ Meets 1999 NEC code, section 250-50
• Inspection ports are provided to assure
proper insertion of the conductor.
COMPRESSION and 250-64. ◊ Built-in quality assurance.
• Material-pure wrought copper extrusions, • The die index number is embossed on the
SYSTEM rod and seamless tubing––identical connector after completion of the crimp.
(Continued) material to the conductor.
◊ Completely eliminates the possibility of
◊ Facilitates speedy inspection of installed
connectors to insure consistently reliable
corrosion due to dissimilar metals. and sound connections.
• Heavy duty connector design. • Most HYGROUND™ irreversible compres-
◊ All connectors will carry the equivalent sion elements are prefilled with
or greater current carrying capacity PENETROX® and individually sealed
of the conductor while maintaining in clear polyethylene sheet.
high mechanical strength and ◊ Ensures that all contact surfaces are in
D-4 electrical integrity. the proper condition for installation.
• Range taking design––minimum number of ◊ Ensures the electrical integrity of the
connector combinations required to install finished connection by inhibiting moisture
a conductor range of #6 solid to 500 kcmil and contaminates from entering the
plus 1/2, 5/8, 3/4, and 1 ground rods contact area.
and rebar. • All HYGROUND™ irreversible compres-
◊ Inventories are kept to a minimum and sion connectors are Listed in conformance
product selection is simplified. with Underwriters Laboratories Standard
• System engineered tooling. UL467 and conform to applicable sections
◊ Each tooling recommendation has of the National Electrical Code.
been designed to ensure reliability ◊ May be used in direct burial or concrete
of the connection. embedded grounding applications.
• Irreversible compression connectors • All HYGROUND™ irreversible connectors
can be installed in all kinds of weather. (with the exception of type YGA and YGS)
◊ Eliminates costly construction delays have been tested successfully according
and enables the installer to better to requirements of Standard IEEE 837
schedule his job. latest revision.
• May be installed without special training ◊ Meets tough industry performance
or special tools. Y750 crimps entire range. requirements.
◊ Low installed cost. ◊ UPRECRIMP™ dies give added
Simplified installation. mechanical strength. UPRECRIMP™ 34
• Each connection can be made in less than for 3/4" rod, UPRECRIMP™ 12 for 1/2"
3 minutes. rod, and UPRECRIMP™ 58 for 5/8" rod
◊ Low installed cost. (now includes undersized U.S. market
Simplified installation. place rods).
• Non-hazardous process installation. Does • Allows connection to most sizes of
not produce heat or dangerous particles. structural steel with no drilling, tapping,
◊ Safe. or welding.
No need for special protective equipment ◊ Safely installed at low cost. Hot work
or clothing. permits are not required to install in
• Each connector is clearly marked with hazardous areas
catalog number, conductor size and
installation die information.
◊ Easy and accurate identification.
BURNDY
Grounding

TYPE YGL-C
HYGRID CROSS CONNECTOR

An irreversable compression ground grid


cross connector which allows adjustment of
the compression elements prior to installa-
tion. Only six connectors and four dies are
required to install all combinations from #6
solid through 500 kcmil. UL467 Listed. MEETS ALL
Acceptable for direct burial in earth and con-
crete. Prefilled with PENETROX® compound
and strip sealed.
IEEE
837 REQUIREMENTS
467 96
D-5
CATALOG
NUMBER B B-B C C-C D L R
YGL2C2 1.09
1.09 .313 .31
YGL29C2
1.66
YGL29C29 .75 .75 1.66 .500 .50 UL96 Listed for Lightning Protection.
2.50
YGL34C2 1.09 .313 .31
2.09
YGL34C29 1.66 .500 .50
YGL34C34 1.10 1.10 2.28 2.28 .750 .75

ORDERING INFORMATION
CATALOG CABLE TO CABLE CABLE TO GROUND ROD TO REBAR
NUMBER ELEMENT “A” ELEMENT “B” ELEMENT “A” ELEMENT “B” ELEMENT “A”
#6 SOL. (.162) – #2 STR. (.292)
YGL2C2
{59500} – {59500} #6 SOL. (.162) – #2 STR. (.292)
#1 STR. (.332) – 250 kcmil (.575) {59500} – {59500}
YGL29C2 #6 SOL. (.162) – #2 STR. (.292) 3/8" – 1/2"
{98500} – {131500}
1/2" – 5/8" Rod
#2 STR. (.292) – 250 kcmil (.575) #2 STR. (.292) – 250 kcmil (.575)
YGL29C29 #2 STR. (.292) – 250 kcmil (.575) #3 – 4 Rebar
{65500} – {131500} {65500} – {131500}
YGL34C2 #6 SOL. (.162) – #2 STR. (.292) #6 SOL. (.162) – #2 STR. (.292)
5/8" – 3/4"
YGL34C29 250 kcmil (.575) – 500 kcmil (.813) #2 STR. (.292) – 250 kcmil (.575) 5/8" – 3/4" Rod #2 STR. (.292) – 250 kcmil (.575)
#5 – 6 Rebar
YGL34C34 250 kcmil (.575) – 500 kcmil (.813) 250 kcmil (.575) – 500 kcmil (.813)
Dimensions in brackets { } represent lightning
protection conductors.

INSTALLATION TOOLS, DIE SET CAT. NO. (NUMBER OF CRIMPS)


CATALOG Y750/735/Y39 HYPRESS PAT750-18V Y45 HYPRESS Y46 HYPRESS
NUMBER ELEMENT “A” ELEMENT “B” ELEMENT “A” ELEMENT “B” ELEMENT “A” ELEMENT “B” ELEMENT “A” ELEMENT “B”
YGL2C2 U-0 (1) U-0 (1) U-0 (1) U-0 (1) U-0 (1) U-0 (1) U-0 (1) U-0 (1)
YGL29C2 U997 (1) U-0 (1) ➂ U997P (1) U-0 (1) U997 (1) U-0 (1) U997 (1) U-0 (1)
YGL29C29 U997 (1) U997 (1) ➂ U997P (1) ➂ U997P (1) U997 (1) U997 (1) U997 (1) U997 (1)
S998 or P998 or
YGL34C2* PU998 (1) U-0 (1) PU998 (1) U-0 (1) U-0 (1) U-0 (1)
PU998 (1) PU998 (1)
S998 or PU998 or
YGL34C29* PU998 (1) U997 (1) PU998 (1) ➂ U997P (1) U997 (1) U997 (1)
PU998 (1) PU998 (1)
YGL34C34* U1011 (3) U1011 (3) U1011 (3) U1011 (3) S1011 (3) S1011 (3) P1011 (3) P1011 (3)
1. Where a "U" or "PU" die is recommended with Y45 * These connectors can only be installed using the Y750,
HYPRESS™, a PT6515 adapter must be used. Y45, or Y46 HYPRESS™ with the recommended dies.
2. Where a "U" or "PU" die is recommended with the Y46 These connectors CANNOT be installed with the Y35 and
HYPRESS™, a PUADP-1 adapter must be used. Y39 HYPRESS™.
➂ Polarized die for the PAT750-18V.

NOTES: GROUND ROD


• Before crimping, both connector elements can • When attaching connector to ground rod, ground
be turned on rod diameter "D" to any desired rod must be embossed with appropriate PRE- DIA. PRECRIMP DIES
position. CRIMP™ die. For connections that must meet 1/2 UPRECRIMP 12
• Clean rust and/or protective coatings from rebar IEEE 837 requirements UPRECRIMP™ - type
5/8 UPRECRIMP 58 U2CABT
prior to installation. PRE crimp dies must be used for maximum
clamping retention. 3/4 UPRECRIMP 34
BURNDY
Grounding

TYPE YGLR-C
GRIDLOK Element A

High Strength
Irreversible
Compression Ground Rod to Element B
Grid Connector
Ground grid connector for a wide range of
copper cable to ground rod. Provides high
torque strength on ground rod. UL467 MEETS ALL

D-6
Listed. Acceptable for direct burial in earth
and concrete. Prefilled with PENETROX®
compound and strip sealed.
IEEE
837 REQUIREMENTS

COMMERCIAL INSTALLATION TOOLS, DIE SET CAT. NO., (NUMBER OF CRIMPS)


COPPER METRIC COPPER COPPER WELD GROUND ROD Y35/Y39 HYPRESS™ Y750 HYPRESS™ Y45 HYPRESS™ Y46 HYPRESS™
CATALOG CABLE RANGE CABLE RANGE CABLE RANGE DIA. ELEMENT ELEMENT ELEMENT ELEMENT ELEMENT ELEMENT ELEMENT ELEMENT
NUMBER ELEMENT “A” ELEMENT “A” ELEMENT “A” ELEMENT “B” B B-B D L “A” “B” “A” “B” “A” “B” “A” “B”
#2 Str. (.292 Dia.) 35mm2 (7.62mm Dia.) 91.65 kcmil (.343 Dia.)
YGLR29C12 thru thru thru U997 (1) PU998 (1) U997 (1) U997 (1) U997 (1)
250 kcmil (.575 Dia.) 120 mm2 (14.40mm Dia.) 248.8 kcmil (.572 Dia.) 1/2
250 kcmil (.575 Dia.) 120 mm2 (14.40mm Dia.) 248.8 kcmil (.572 Dia.) [12.7] U1011 S998 P998
YGLR34C12 thru thru thru — or or or
500 kcmil (.813 Dia.) 240 mm2 (20.35mm Dia.) 498.8 kcmil (.810 Dia.) .313 2.53 PU998 (1) PU998 (1) PU998 (1)
#2 Str. (.292 Dia.) 35 mm2 (7.62mm Dia.) 91.65 kcmil (.343 Dia.) [7.9] [64.3]
YGLR29C58 thru thru thru U997 (1) PU998 (1) U997 (1) U997 (1) U997 (1)
250 kcmil (.575 Dia.) 120 mm2 (14.40mm Dia.) 248.8 kcmil (.572 Dia.) 5/8
250 kcmil (.575 Dia.) 120 mm2 (14.40mm Dia.) 248.8 kcmil (.572 Dia.) [15.9] U1011 S998 P998
YGLR34C58 thru thru thru — or U1011 (2) or S1012 (2) or P1011(2)
500 kcmil (.813 Dia.) 240 mm2 (20.35mm Dia.) 498.8 kcmil (.810 Dia.) .75 .88 PU998 (1) or PU998 (1) or PU998 (1) or
#2 Str. (.292 Dia.) 35 mm2 (7.62mm Dia.) 91.65 kcmil (.343 Dia.) [19.1] [22.4] PU998 (1) PU998 (1) PU998 (1)
YGLR29C34 thru thru thru U997 (1) PU998 (1) U997 (1) U997 (1) U997 (1)
250 kcmil (.575 Dia.) 120 mm2 (14.40mm Dia.) 248.8 kcmil (.572 Dia.) 3/4
250 kcmil (.575 Dia.) 120 mm2 (14.40mm Dia.) 248.8 kcmil (.572 Dia.) [19.1] U1011 (2) U1011 (2) U1011 (2)
YGLR34C34 thru thru thru or or or
500 kcmil (.813 Dia.) 240 mm2 (20.35mm Dia.) 496.8 kcmil (.810 Dia.) .500 2.63 PU998 PU998 PU998
#2 Str. (.292 Dia.) 35 mm2 (7.62mm Dia.) 91.65 kcmil (.343 Dia.) [12.7] [66.8]
1
YGLR29C100 thru thru thru — U997 (1) U997 (1) U997 (1)
[25.4]
250 kcmil (.575 Dia.) 120 mm2 (14.40mm Dia.) 248.8 kcmil (.572 Dia.)

250 kcmil (.575 Dia.) 120 mm2 (14.40mm Dia.) 248.8 kcmil (.572 Dia.) U1011 (2) U1011 (2) U1011 (2)
1
YGLR34C100 thru thru thru or or or
[25.4]
500 kcmil (.813 Dia.) 240 mm2 (20.35mm Dia.) 498.8 kcmil (.810 Dia.) PU998 (1) PU998 PU998

NOTES:
1. Before crimping, both connector elements can be 5. Ground rod must be pre-crimped with die GROUND ROD
turned on rod diameter 'D' to any desired position. U2CABT (Index No. 348) when crimping the
2. Grooves are filled with PENETROX®. ground rod element (Element “B”) with the PU998 DIA. PRECRIMP DIES
dies in the Y750, Y35, Y39, Y45, or Y46 tools. Pre- 1/2 UPRECRIMP 12
3. Suitable for direct burial in earth or concrete.
crimping is not required when the S1012, P1011 5/8 UPRECRIMP 58 U2CABT
4. The catalog numbers shown are for unplated or U1011 dies are used. See precrimp die chart.
copper connectors for use on copper clad or 3/4 UPRECRIMP 34
6. Where a 'U' or 'PU' die is recommended with the
stainless steel ground rod. To order electro-tin
Y45 HYPRESS™, a PT6515 adapter must be When attaching connector to ground rod, ground
plated connectors for use on galvanized steel
used. rod must be embossed with appropriate PRE-
ground rod add suffix "TN" to the catalog number,
only if the Figure 8 connector (Element “B”) is tin 7. Where a 'U' or 'PU' die is recommended with the CRIMP™ die. For connections that must meet IEEE
plated, the Figure 6 connector (Element “A”) is Y46 HYPRESS™, a PUADP-1 adapter must be 837 requirements UPRECRIMP™ - type PRE crimp
unplated. Note: The ground rod hole diameter is used. dies must be used for maximum clamping retention.
larger for galvanized steel ground rod in the tin
plated connector. 8. Dimensions in bracket [ ] are in millimeters.
9. Die "1011" appears on Element "B" of the
connector only.
BURNDY
Grounding

TYPE YGHP-C
HYTAP™ CONNECTOR

Irreversible compression ground tap figure 6


can be used as a tap connector or as a tap
splice connector. Four die sets and eight con-
nectors can accommodate a conductor range
from #8 solid through 500 kcmil plus 1/2",
5/8", and 3/4" copper bonded ground rods.
UL467 Listed. Acceptable for direct burial in
UL96 Listed for Lightning Protection.
earth and concrete. Prefilled with PENE-
TROX® compound and strip sealed.
MEETS ALL
D-7
IEEE
837 REQUIREMENTS
467 96 Fig. 1 Fig. 2

INSTALLATION DATA
➄ DIE Y750/Y35 ➂ ➃
CATALOG FIG. ACCOMMODATES CABLE TO REBAR INDEX Y39 Y45 Y46 NO. OF
NUMBER NO. RUN TAP RUN TAP B NO. HYPRESS™ PAT750-18V HYPRESS™ HYPRESS™ CRIMPS
#6 SOL. (0.162) {59500} – ➀ #6 SOL. (0.162) {#2 STR.} –
YGHP2C2 1 — —
#2 STR. (0.292) {59500} #2 STR. (0.292) {#2 STR.}
0 U0 U0 U0 U0 1
#6 SOL. (0.162) – #8 SIK. (0.128) –
YGHP2C6W6W➇ 2 — —
#2 STR. (0.292) 6 STR. (0.184) QTY. 2
#8 SOL. (0.128) –
YGHP29C6W6W➇ 2 #8 SOL. – 6 STR.
6 STR. (0.184) QTY. 2 #3 REBAR
#4 SOL. (0.204) {#4 SOL.} – 3/8
YGHP29C2 1 1/0 STR. (0.372) {98500} – #2 STR.
#2 STR. (0.292) {#2 STR.}
250 kcmil (0.575) {131500} THRU 997 U997 ➆ U997P U997 U997 1
1/0 STR. (0.372) {98500} – .75
YGHP29C26 1 1/2" – 5/8" ROD 1/0 STR. – 2/0 STR.
2/0 STR. (0.419) {98500} 1/2 [19]
3/0 STR. (0.470) {131500} – #4 REBAR
YGHP29C29 ➁ 1 3/0 STR. – 250 kcmil
250 kcmil (0.575) {211500}
#4 SOL. (0.204) –
YGHP34C2 ➅ 1 #5 REBAR —
#2 STR. (0.292)
250 kcmil (0.575) {250 kcmil} – 5/8
1/0 STR. (0.372) {98500} – PU998 or PU998 or
YGHP34C26 ➅ 1 500 kcmil (0.813) {500 kcmil} 1/0 STR. – 2/0 STR. 998 PU998 PU998 1
2/0 STR. (0.419) {98500} S998 P998
5/8" – 3/4" ROD THRU
3/0 STR. (0.470) {131500} –
YGHP34C29 ➅ 1 3/0 STR. – 250 kcmil
250 kcmil (0.575) {211500}
3/4
250 kcmil (0.575) –
350 kcmil (0.681) – 1.10
YGHP34C34 ➅ 1 500 kcmil (0.813) #6 REBAR 350 kcmil – 500 kcmil 1011 ➅U1011 U1011 S1011 P1011 3
500 kcmil (0.843) [28]
5/8" – 3/4" ROD
Dimensions in brackets { } represent lightning protection
conductors.

NOTES: GROUND ROD


➀ When using #6 Sol. in tap, fold conductor double to improve ➄ Clean rust and protective coatings from rebar before con- DIA. PRECRIMP DIES
fill in YGHP2C2. nector installation to provide a proper ground connection.
➁ For YGHP29C29 when using 3/0 in tap, minimum run 1/2 UPRECRIMP 12
Precrimping is not required.
conductor is 2/0 STR. ➅ These connectors can only be installed using the Y750, Y45 5/8 UPRECRIMP 58 U2CABT
➂ Where a 'U' or 'PU' die is recommended with the Y45 or Y46 HYPRESS™ with the recommended dies. These 3/4 UPRECRIMP 34
HYPRESS™, a PT6515 adapter must be used. connectors can not be installed with the Y35 and Y39
➃ Where a 'U' or 'PU' die is recommended with the Y45 HYPRESS™.
HYPRESS™, a P-UADP-1 adapter must be used. ➆ Polarized die for the PAT750-18V. For increased rotational resistance on ground rods,
pre-crimp ground rod with U2CABT die Index 348 or
➇ Not UL96/CSA.
uprecrimp dies may be used for even greater rota-
tion and vibration resistance on ground rods.
CABLE TO GROUND ROD
CABLE TO REBAR
CABLE TO CABLE
FOR CONCRETE ENCASED
ELECTRODE GROUNDING
APPLICATIONS
BURNDY
Grounding

TYPE YGHP-C PREFILLED WITH


“THIRD HAND”

PENETROX-E

HYTAP™ CONNECTOR TAP (B)

High Strength
Copper Irreversible
Compression
DIE INDEX
Ground Rod Tap AND CONDUCTOR
INFORMATION TAP (A)
Connector
PATENTED
Type YGHP-C irreversible compression
ground tap figure 6 can be used as a ground Features and Benefits
D-8 rod tap connector for both continuous run and
tapping applications. An open groove allows • Tap (A) accepts a continuous run on • Prefilled with PENETROX® and individually
ground rod to be connected to a continuous tap conductor sealed in clear polyethylene sheet.
run or tap. The second groove is for a tap Tap (B) accepts a tap conductor only. ◊ Ensures the electrical integrity of the
only. Prefilled with PENETROX-E® and strip ◊ One connector style can be used for finished connection by inhibiting moisture
sealed. UL467 Listed for direct burial in earth many applications, reducing number and contaminates from entering the
or concrete. of connectors in inventory. contact area. Maintains long-term
• Material is high conductivity wrought high-conductivity.
MEETS ALL copper extrusion, identical material to • UL467 Listed.

IEEE
837 REQUIREMENTS
the conductor.
◊ High-conductivity copper minimizes
resistance and voltage drop. Eliminates
◊ May be used in direct burial or concrete
embedded grounding applications.
Provides quality assurance to recognized
the possibility of corrosion due to industry NEC standards from an
dissimiliar metals. independent party.
• System engineered tooling. • “Third Hand” constrains conductors while
◊ The tooling recommendation has been installer completes crimp. Included with
designed to ensure a reliable, depend- each connector.
able connection every time. ◊ Simplifies installation, reducing
• The die index number is embossed on installed cost.
conductor after completion of crimp.
◊ Faciliates speedy inspection of installed
connectors to insure consistently reliable
and dependable connections.

SINGLE TAP CONTINUOUS RUN CONTINUOUS RUN AND TAP

▲ INSTALLATION TOOLING
Y35/Y750 Y46 •
CATALOG GROUND DIMENSIONS DIE NO. OF DIE NO. OF DIE
NUMBER ROD DIA. ■ TAP CONDUCTOR + H B W NO. CRIMPS NO. CRIMPS INDEX
YGHP58C2W-2 #2 Sol. - #6 Sol. Copper
1/2 - 5/8 (1) Continuous run and (1) Tap or 1.90 .75 .94 U997 (1) U997 (1) 997
YGHP58C2W-2TN
up to (2) taps may be connected.
NOTE: A 12" bend radius is recommended for the conductor. ■ Ground rod must be precrimped with die U2CABT (Index
• Use PUADP-1 with ‘U’-dies in Y46. No. 348).
▲ See tooling section in Master Catalog for complete tool and For even greater rotational resistance use U-PRECRIMP
die listing. die.
+ Either tap position may be left void when fewer than (2) For Galvanized Steel Rods order YGHP58C2W-2TN.
conductors are used.
BURNDY
Grounding

TYPE YGHC-C
HYTAP™ CONNECTOR

Irreversible compression ground tap figure


"C" connectors. Accomodates all cable
combinations from #6 solid through 500
kcmil. "C"- shaped opening permits placing
two continuous parallel cables into conductor
groove. UL 467 Listed. Acceptable for direct
burial in earth or concrete. Prefilled with
PENETROX® compound and strip sealed. MEETS ALL

UL96 Listed for Lightning Protection.


IEEE
837 REQUIREMENTS D-9
467 96

INSTALLATION DATA
COMMERCIAL COPPER STRANDED COPPER DIE Y750/Y35 ➀ ➁
CATALOG CABLE RANGE CABLE RANGE INDEX Y39 Y45 Y46 NO. OF
NUMBER RUN TAP RUN TAP A B NO. HYPRESS™ HYPRESS™ HYPRESS™ CRIMPS
#6 SOL. (0.162) #6 SOL. (0.162) 10 mm2 (4.12 mm) 10 mm2 (4.12 mm) 1.16 0.75
YGHC2C2 C U-C U-C U-C 1
#2 STR. (0.292) #2 STR. (0.292) 35 mm2 (7.62 mm) 35 mm2 (7.62 mm) [30] [19]
1 STR. (0.328) #6 SOL. (0.162)
35 mm2 (7.62 mm) 10 mm2 (4.12 mm)
{98500} {#6 SOL.} 1.41 0.75
YGHC26C2 0 U-O U-O U-O 1
2/0 STR. (0.419) #2 STR. (0.292) [36] [19]
70 mm2 (10.9 mm) 35 mm2 (7.62 mm)
{98500} {#2 STR.}
1 STR. (0.328) 1 STR. (0.328)
35 mm2 (7.62 mm) 35 mm2 (7.62 mm)
{98500} {98500} 1.54 0.75
YGHC26C26 0 U-O U-O U-O 1
2/0 STR. (0.419) 2/0 STR. (0.419) [39] [19]
70 mm2 (10.9 mm) 70 mm2 (10.9 mm)
{98500} {98500}
3/0 STR. (0.470) 6 SOL. (0.419)
95 mm2 (12.5 mm) 10 mm2 (4.12 mm)
{3/0 STR.} {59500} 1.97 0.75
YGHC29C26 997 U997 U997 U997 1
250 kcmil (0.575) 2/0 STR. (0.419) [50] [19]
120 mm2 (14.4 mm) 70 mm2 (10.9 mm)
{250 kcmil} {98500}
3/0 STR. (0.470) 3/0 STR. (0.470) 95 mm2 (12.5 mm) 95 mm2 (12.5 mm) 2.06 0.88
YGHC29C29 997 U997 U997 U997 1
250 kcmil (0.575) 250 kcmil (0.575) 120 mm2 (14.4 mm) 120 mm2 (14.4 mm) [52] [22]
300 kcmil (0.630) #6 SOL. (0.162)
150 mm2 (16 mm) 10 mm2 (4.12 mm)
{300 kcmil} {59500} 2.42 0.88
YGHC34C26 ➅ 1011 U1011 S1011 P1011 2
500 kcmil (0.813) 2/0 STR. (0.419) [62] [22]
240 mm2 (20.35 mm) 70 mm2 (10.9 mm)
{500 kcmil} {98500}
300 kcmil (0.630) 3/0 STR. (0.470) 150 mm2 (16 mm) 95 mm2 (12.5 mm) 2.67 0.88
YGHC34C29 ➅ 1011 U1011 S1011 P1011 2
500 kcmil (0.813) 250 kcmil (0.575) 240 mm2 (20.35 mm) 120 mm2 (14.4 mm) [66] [22]
300 kcmil (0.630) 300 kcmil (0.630) 150 mm2 (16 mm) 150 mm2 (16 mm) 2.91 1.1
YGHC34C34 ➅ 1011 U1011 S1011 P1011 3
500 kcmil (0.813) 500 kcmil (0.813) 240 mm2 (20.35 mm) 240 mm2 (20.35 mm) [74] [28]
Dimensions in brackets { } represent lightning protection conductors.

NOTES:
➀ Where a "U" or "PU" die is recommended with 5. In referencing connectors without PENETROX®
the Y45 HYPRESS™, PT6515 adapter must be oxide inhibitor add suffix "NP" to the end of the
used. Catalog Number.
➁ Where a "U" or "PU" die is recommended with ➅ These connectors can only be installed using
the Y46 HYPRESS™, a PUADP-1 adapter must the Y750, Y45 or Y46 HYPRESS™ with the
be used. recommended dies.
3. Listed under UL486A for copper wire connec- These connectors cannot be installed with the
tors Y35 and Y39 HYPRESS™.
4. Dimensions in brackets [ ] are in millimeters.
BURNDY
Grounding

TYPE YGC
COPPER CRIMPIT™

UL 467 Listed for direct burial in earth or


concrete. Prefilled with PENETROX® E2
oxide inhibitor.

COPPER
D-10
CATALOG CONDUCTOR
NUMBER RUN TAP H L INDEX OUR840 MD6/MD7 CRIMPS
#8 SOL. #8 SOL.
YGC8C8 .46 .52 162 W162 W162 2
#8 STR. #8 STR.
#6 SOL. #8 SOL.
YGC6C8 .73 .62 BG XBG WBG 2
#6 STR. #8 STR.
#6 SOL. #6 SOL.
YGC6C6 .76 .62 BG XBG WBG 2
#6 STR. #6 STR.
BURNDY
Grounding

TYPE YSHG
HIGH STRENGTH
COPPER IRREVERSIBLE
COMPRESSION
Double H-Tap Connector

Type YSHG Double H-Tap grounding series is


comprised of five connectors designed to
accommodate wire range sizes #14 through
500 kcmil, including ground rod sizes: 3/4",
1", and rebar sizes: #6, #8 and #9. Prefilled
with PENETROX® E2 and strip sealed. Features and Benefits D-11
• UL467 Listed. • Grooves are prefilled with PENETROX® E2
◊ Suitable for direct burial in earth oxide inhibitor and individually sealed.
or concrete. ◊ Inhibits moisture and contaminants
• Material is high conductivity ensuring electrical integrity.
copper extrusion.
◊ Minimizes resistance, eliminates
corrosion due to dissimilar metals.

Fig. 1 Fig. 2 Fig. 3

TOOLING INDEX
CATALOG FIG. CONDUCTOR SIZES (*NUMBER OF CRIMPS) EMBOSS- W T L
NUMBER NO. MAIN TAP 1 TAP 2 TAP 3 Y750 * Y46 * MENT .06 .04 .06
#9 & #8 REBAR, 1 [25] GROUND 3.22 1.70 2.44
YSHG4429 250 - 2 PYFR 2 K-R
3 ROD [82] [43] [62]
1 [25] Cu CLAD GROUND ROD 2.97 1.50 2.94
* YSHG3939 500 - 350 PYFR 2 K-R
1 500 kcmil COPPER [75] [38] [75]
#6 REBAR, 1 [25] Cu CLAD
2.97 1.50 2.34
* YSHG3931 2 GROUND ROD, 3/4 GROUND ROD 4/0 - 1/0 1-6 2 - 14 PYFR 2 K-R
[75] [38] [59]
500 - 350 kcmil COPPER
#6 REBAR, 3/4 [19] GROUND ROD P1104 2 2.43 1.15 2.44
YSHG3434 400 - 4/0 U1104 4 1104
1 400 - 250 kcmil COPPER †U1104 4 [62] [29] [62]
#6 REBAR, 3/4 [19] GROUND ROD P1104 2 2.23 1.31 2.44
YSHG3429 3/0 - 1/0 1-4 8 - 14 U1104 4 1104
2 400 - 4/0 kcmil COPPER †U1104 4 [57] [33] [62]

* NOTE: Not for use on 1 steel ground rod.


† Use PUADP-1 adapter.
BURNDY
Grounding

TYPE YGHR-C
HYTAIL™
High Strength
Irreversible
Compression Ground Rod Tap
Connectors

High torque strength ground rod connectors.


Accommodates a wide range of copper MEETS ALL
conductors to ground rod. UL467 Listed.
Acceptable for direct burial in earth or con-
D-12 crete. Prefilled with PENETROX® compound
IEEE
837 REQUIREMENTS
and strip sealed.
CATALOG
NUMBER H B
YGHR26C12 1.94 [49.3]
YGHR26C58 1.97 [50.0]
YGHR26C34 2.19 [55.6]
YGHR26C100 2.55 [56.2]
YGHR29C12 1.94 [49.3]
.88
YGHR29C58 2.14 [54.4]
[22.4]
YGHR29C34 2.19 [55.6]
YGHR29C100 2.45 [62.2]
YGHR34C58 2.14 [54.4]
YGHR34C34 2.44 [62.0]
YGHR34C100 2.70 [68.6]

CATALOG COMMERCIAL COPPER NOMINAL GROUND INSTALLATION TOOLS, DIE SET CAT. NO. (NUMBER OF CRIMPS)
NUMBER CABLE RANGE ROD DIA. Y750/Y35/Y39 ① Y45 HYPRESS ① Y46 HYPRESS ①
YGHR26C12 1/2 [12.7] S1012 (2)
YGHR26C58 #2 STR. (.292 DIA.) 5/8 [15.9] ➃
YGHR26C34 thru 3/4 [19.0] PU998 (1) ②
2/0 STR. (.419 DIA.) S1011 (2) S1012 (2)
YGHR26C100* 1 [25.4]
PU998 (1)
YGHR29C12 1/2 [12.7] U1011 (2) S1012 (2) P1011 (2)
YGHR29C58 #4/0 STR. (.528 DIA.) 5/8 [15.9] ➃ ➃ ➃
YGHR29C34 thru 3/4 [19.0] PU998 (1) PU998 (1) ② PU998 (1)
250 kcmil (.575 DIA.) S1011 (2) S1012 (2) ③
YGHR29C100* 1 [25.4]
➃ PU998 (1)
YGHR34C58 300 kcmil (.630 DIA.) 5/8 [15.9] S1012 (2)

YGHR34C34* thru 3/4 [19.0] PU998 (1) ②
YGHR34C100* 500 kcmil (.813 DIA.) 1 [25.4] S1011 (2) P1011 (2)

NOTES: ➁ Where a PU998 die is recommended with the Y45


• The catalog numbers shown are for unplated copper HYPRESS™, a PT6515 adapter must be used.
connectors for use on copper clad or stainless steel ground ➂ Where a PU998 die is recommended with the Y46
rod. To order electro-tin plated connectors for use on HYPRESS™, a PUADP-1 adapter must be used.
galvanized steel ground rod add suffix "TN" to the catalog ➃ These die numbers do not appear on the connector.
number. Note: The ground rod hole diameter is larger for * These connectors can only be installed using the Y750, Y45
galvanized steel ground rod in the tin plated connector. or the Y46 HYPRESS™ with the recommended dies. These
① Ground rod must be pre-crimped with die U2CABT (Index connectors CAN NOT be installed with the Y35 and Y39
No. 348) when the PU998 dies are used in the Y750, Y35, HYPRESS™. When attaching connector to ground rod,
Y39, Y45, or Y46 tools. Pre-crimping is not required when ground rod must be embossed with appropriate PRE-
the P1011, S1011, S1012 or U1011 dies are used. UPRE- CRIMP™ die. For connections that must meet IEEE 837
CRIMP™ dies may be used for additional mechanical resis- requirements UPRECRIMP™ - type PRE crimp dies must
tance on ground rods. be used for maximum clamping retention.
BURNDY
Grounding

TYPE YGHR-C
HYTAIL™
High Strength
Irreversible
Compression Ground Rod Tap
Connectors

Type YGHR-C irreversible compression


grounding connector is engineered specifical- Features and Benefits
ly for the Telecommunications Industry for
(1, 2 or 3) #2 solid, tinned or bare conductor • Tap side 1, 2 or 3 conductors. • The die index number is embossed on
taps. UL467 Listed. Acceptable for direct burial ◊ One connector style can be used for connector after completion of crimp. D-13
in earth or concrete. BURNDY® has designed many applications. ◊ Facilitates speedy inspection of installed
this connector to meet the stringent require- • Material is high conductivity wrought connectors to ensure consistently
ments of OSHA, the National Electric Code copper extrusion, identical material to reliable and dependable connections.
(NEC), UL, and the Telecommunications the conductor. • Prefilled with PENETROX® and individually
Industry. Performance and long life are this ◊ High-conductivity copper minimizes sealed in clear polyethylene sheet.
connector’s basic design guidelines. resistance and voltage drop. Eliminates ◊ Ensures the electrical integrity of the
the possibility of corrosion due to finished connection by inhibiting moisture
dissimilar metals. and contaminates from entering the
• System engineered tooling. contact area. Maintains long-term
◊ Each tooling recommendation has high-conductivity.
been designed to provide a reliable, • UL 467 Listed. Acceptable for direct burial.
dependable connection. ◊ May be used in direct burial or concrete
embedded grounding applications.
Provides quality assurance to recognized
industry NEC standards from an
independent party.

TAP RUN
TAP RUN AND

INSTALLATION TOOLING
Y35/Y750** Y46*
CATALOG GROUND ROD DIE NO. OF DIE NO. OF DIE
NUMBER+ DIAMETER • TAP CONDUCTOR ▲ NO. CRIMPS NO. CRIMPS INDEX
PU998† (1)
PU998† (1)
#2 Sol. Copper 1, 2, or 3 U1011 (2) 998 or
YGHR58C2W-3 5/8
may be connected P998 (1) 1011
U1011 (2)
P1011 (2)

• Contact BURNDY® for other ground rod diameters. † Ground rod must be precrimped with die U2CABT (Index
* PU998 and U1011 die sets require PUADP-1 adapter for No. 348) when PU998 die set is used in the Y35, Y750 or
use in the Y46 HYPRESS™. Y46
Tap positions may be left void when fewer than (3) conduc- ▲ HYPRESS™ tools. For even greater mechanical resistance
tors are used. use UPRECRIMP™ 58 dies.
+ To order electro-tin plated connector for use on galvanized ** The Y750 utilizes PU dies and the U1011 die. The Y35 only
steel ground rod add suffix -“TN” to the catalog number. uses PU998 die set.
NOTE: The ground rod hole diameter is larger for galvanized NOTE: A 12" bend radius is recommended for the conductor.
steel ground rod in the tin plated connector.
BURNDY
Grounding

TYPE YGHA
HYLUG™
Heavy Duty Irreversible
Compression Terminals
Heavy duty HYLUG™ irreversible compres-
sion terminals designed not only to carry
short circuit load, but to also withstand high
mechanical stress. Each conductor element
has an inspection probe hole to insure proper MEETS ALL
cable insertion. UL467 Listed. Acceptable for
direct burial in earth or concrete. UL486A
®
D-14 Listed. Prefilled with PENETROX compound
IEEE
837 REQUIREMENTS
and strip sealed.

INSTALLATION TOOLS, DIE SET CAT. NO.,


CATALOG AND (NUMBER OF CRIMPS)
NUMBER COPPER CONDUCTOR SIZE HYPRESS™ Y35/Y39/Y45 ① /Y46 ② /Y750 B C L T
YGHA2C-2N 2 str. U1CRT (1) .75 .97 4.21 .26
YGHA25-2N 1/0 str. U27RT (1) .83 .91 4.60 .19
YGHA26-2N 2/0 str. U28RT (1) .83 .97 4.38 .26
YGHA27-2N 3/0 str. U29RT (1) 1.18 1.08 4.94 .29
YGHA28-2N 4/0 str. U30RT (2) 1.18 1.22 4.94 .30
YGHA29-2N 250 kcmil U31RT (2) 1.18 1.28 4.94 .34
YGHA31-2N 350 kcmil U34RT (2) 1.18 1.62 5.00 .43
YGHA34-2N 500 kcmil U36RT (3) 1.48 1.72 5.42 .40
① Where a “U” or “PU” die is recommended with the Y45
HYPRESS™, a PT6515 adapter must be used.
➁ Where a “U” or “PU” die is recommended with the Y46
HYPRESS™, a PUADP-1 adapter must be used.

TYPE YGHS
HYLINK™
Heavy Duty Irreversible
Compression Terminals
KNURLED
RINGS
Heavy duty HYLINK™ ground splice
INSPECTION PROBE HOLES
designed not only to carry short circuit load, FOR CABLE STOP
but to also withstand high mechanical stress.
Each conductor element has an inspection
probe hole and a center stop to ensure MEETS ALL
proper cable insertion. UL467 Listed.
Acceptable for direct burial in earth or
concrete. UL486A Listed. Prefilled with
IEEE
837 REQUIREMENTS
PENETROX® compound and strip sealed.
INSTALLATION TOOLS, DIE SET CAT. NO.,
CATALOG AND (NUMBER OF CRIMPS)
NUMBER COPPER CONDUCTOR SIZE HYPRESS™ Y35/Y39/Y45 ① /Y46 ② /Y750 B L
YGHS2C 2 str. U1CRT (1) .75 1.73
YGHS25 1/0 str. U27RT (1) .83 1.89
YGHS26 2/0 str. U28RT (1) .83 1.89
YGHS27 3/0 str. U29RT (1) 1.18 2.59
YGHS28 4/0 str. U30RT (2) 1.18 2.59
YGHS29 250 kcmil U31RT (2) 1.18 2.59
YGHS31 350 kcmil U34RT (2) 1.18 2.59
YGHS34 500 kcmil U36RT (3) 1.48 3.19
① Where a “U” or “PU” die is recommended with the Y45
HYPRESS™, a PT6515 adapter must be used.
➁ Where a “U” or “PU” die is recommended with the Y46
HYPRESS™, a PUADP-1 adapter must be used.
BURNDY
Grounding

TYPE YGA
HYLUG™
Grounding Irreversible
Compression Terminals

Irreversible compression HYLUG™ Ground


terminal specifically designed for grounding
applications. Each connector has an inspec-
tion probe hole to insure proper cable inser-
tion. UL467 Listed. Acceptable for direct
burial in earth or concrete. UL486A Listed.
Prefilled with PENETROX® compound and
D-15
strip sealed.

Fig. 1 Fig. 2

INSTALLATION TOOLS, DIE SET CAT. NO., AND


(NUMBER OF CRIMPS)
MECHANICAL HYDRAULIC
Y35/Y39/Y45 ①
COPPER Y2MR MD7-34R OUR840 /Y46 ② /Y750
CATALOG FIG. CONDUCTOR DIE # (# OF DIE # (# OF DIE # (# OF DIE # (# OF STUD
NUMBER NO. SIZE CRIMPS) CRIMPS) CRIMPS) CRIMPS) SIZE B C L T E
W8CVT (2)
YGA8C-TC10 2 8 sol./8 str. Red (4) U8CRT (2) #10 .81 .41 1.57 .08 —
X8CRT (2)
W8CVT (2)
YGA8C-TC14 2 8 sol./8 str. Red (4) U8CRT (2) 1/4 .81 .44 1.69 .08 —
X8CRT (2)
W8CVT (2)
YGA8C-TC516 2 8 sol./8 str. Red (4) U8CRT (2) 5/16 .81 .51 1.75 .06 —
X8CRT (2)
W8CVT (2)
YGA8C-2N 1 8 sol./8 str. Red (4) U8CRT (2) 1/2 .81 .71 4.09 .05 —
X8CRT (2)
W5CVT (2)
YGA6C-TC10 2 6 sol./6 str. Blue (4) U5CRT (2) #10 1.12 .42 1.89 .09 —
X5CRT (2)
W5CVT (2)
YGA6C-TC14 2 6 sol./6 str. Blue (4) U5CRT (2) 1/4 1.12 .45 2.02 .08 —
X5CRT (2)
W5CVT (2)
YGA6C-TC516 2 6 sol./6 str. Blue (4) U5CRT (2) 5/16 1.12 .51 2.08 .07 —
X5CRT (2)
W5CVT (2)
YGA6C-2TC38E2G1 1 6 sol./6 str. Blue (4) U5CRT (2) 3/8 1.12 .58 3.42 .06 .75
X5CRT (2)
W5CVT (2)
YGA6C-2N 1 6 sol./6 str. Blue (4) U5CRT (2) 1/2 1.12 .83 4.40 .12 1.75
X5CRT (2)
W2CVT (2)
YGA2C-2TC38 1 2 sol./2 str. Brown (4) U2CRT (2) 3/8 1.25 .60 3.48 .12 1.00
X2CRT (2)
W2CVT (2)
YGA2C-2TC38E2G1 1 2 sol./2 str. Brown (4) U2CRT (2) 3/8 1.25 .60 3.66 .12 .75
X2CRT (2)
W2CVT (2)
YGA2C-2N 1 2 str. Brown (4) U2CRT (2) 1/2 1.22 .81 4.71 .12 1.75
X2CRT (2)
W25VT (4)
YGA25-2N 1 1/0 str. — U25RT (2) 1/2 1.35 .81 4.91 .12 1.75
X25RT (4)
W26VT (4)
YGA26-2N 1 2/0 str. — U26RT (2) 1/2 1.45 .81 4.89 .12 1.75
X26RT (4)
W28VT (4)
YGA28-2N 1 4/0 str. — U28RT (2) 1/2 1.57 1.00 5.06 .14 1.75
X28RT (4)
YGA29-2N 1 250 kcmil — W29VT (4) U29RT (2) 1/2 1.57 1.09 5.16 .16 1.75
YGA34-2N 1 500 kcmil — W34VT (4) U34RT (4) 1/2 2.20 1.52 5.94 .23 1.75

① Where a “U” or “PU” die is recommended with the Y45 ➁ Where a “U” or “PU” die is recommended with the Y46
HYPRESS™, a PT6515 adapter must be used. HYPRESS™, a PUADP-1 adapter must be used.
BURNDY
Grounding

TYPE YGS
HYLINK™
Grounding Irreversible
Compression Splices

Irreversible compression HYLINK™ ground


splices specifically designed for grounding
applications. Each conductor element has an
inspection probe hole and a center stop to
ensure proper cable insertion. UL467 Listed.
Acceptable for direct burial in earth or
concrete. UL486A Listed. Prefilled with
D-16
PENETROX® compound and strip sealed.

INSTALLATION TOOLS, DIE SET CAT. NO., AND


(NUMBER OF CRIMPS)
MECHANICAL HYDRAULIC
COPPER Y2MR MD7-34R OUR840 Y35/Y39/Y45①
CATALOG CONDUCTOR DIE # (# OF DIE # (# OF DIE # (# OF /Y46② /Y750
NUMBER SIZE CRIMPS) CRIMPS) CRIMPS) DIE # (# OF CRIMPS) B L
W2CVT (2)
YGS2C 2 str. Brown (4) U2CRT (2) 1.22 2.67
X2CRT (2)
YGS8C #8 sol./str. — X8CRT, W8CRT, W8CVT ➂ U8CRT (2) .78 1.75
YGS6C #6 sol./str. — X5CRT, W5CRT, W5CVT ➂ U6CRT (2) 1.09 2.38
W25VT (4)
YGS25 1/0 str. — U25RT (2) 1.35 2.97
X25RT (4)
W26VT (4)
YGS26 2/0 str. — U26RT (2) 1.45 3.13
X26RT (4)
W28VT (4)
YGS28 4/0 str. — U28RT (2) 1.57 3.37
X28RT (4)
YGS29 250 kcmil — W29VT (4) U29RT (2) 1.57 3.37
YGS34 500 kcmil — W34VT (4) — U34RT (4) 2.20 4.63
① Where a “U” or “PU” die is recommended with the Y45
HYPRESS™, a PT6515 adapter must be used.
➁ Where a “U” or “PU” die is recommended with the Y46
HYPRESS™, a PUADP-1 adapter must be used.
③ Use "X" with OUR840, "W" with MD6/MD7.
BURNDY
Grounding

TYPE YGF
GROUNDING PLATE

The irreversible compression ground plate is


designed to withstand the rigors of concrete
construction. The ground plates are made of
high strength, high-conductivity cast copper
alloy body with a pure wrought copper
compression element. In addition to the
Fig. 1
tapped NEMA size holes and spacing on the
face, the plate comes with a tapped hole on MEETS ALL
the underside for ease of positioning prior to
pouring the concrete. UL467 Listed.
Acceptable for direct burial in earth or
IEEE
837 REQUIREMENTS D-17
concrete. Prefilled with PENETROX®
compound and strip sealed.

Fig. 2

CATALOG
NUMBER FIG. NO. C D H L T Y
YGF29-2N 1 2.00 3.25 3.62 5.78 1.31 2.00
YGF29-4N 2 3.25 3.25 3.62 5.78 1.31 2.00
YGF34-2N 1 2.00 3.25 4.62 5.40 1.31 2.19
YGF34-4N 2 3.75 3.75 4.62 5.90 1.31 2.19
NOTES:
① This tapped hole may be used to position the grounding ① 3/8-16 thread with 1.00 EFF. Thread is standard. If other ② Plastic plugs are provided to keep dirt out of the threaded
plate on a threaded rod prior to placement of the concrete. thread is required, add appropriate Code No. to Catalog No. holes until the attachment of grounding terminals.
for desired thread.
-50 (1/2 -13, .94 EFF. Thread), -62 (5/8 -11, .94 EFF.
Thread) and -75 (3/4 -10, .81 EFF. Thread)
Example: YGF34-4N-50 is YGF34-4N with 1/2 -13 Thread

INSTALLATION TOOLS,
DIE SET CAT. NO., AND
(NUMBER OF CRIMPS)
CATALOG COPPER TAPPED HOLES HYPRESS™
NUMBER CONDUCTOR RANGE SIZE HOLE CENTERS Y750/Y35/Y39 Y45 ① Y46 ②
YGF29-2N 2 - 250 kcmil 1/2 - 13 1-3/4 U997 (1) U997 (1) U997 (1)
YGF29-4N 2 - 250 kcmil 1/2 - 13 1-3/4 U997 (1) U997 (1) U997 (1)
YGF34-2N* 250 - 500 kcmil 1/2 - 13 1-3/4 U1011 (3) S1011 (2) P1011 (2)
YGF34-4N* 250 - 500 kcmil 1/2 - 13 1-3/4 U1011 (3) S1011 (2) P1011 (2)

ORDERING INFORMATION
① Where a “U” or “PU” die is recommended ➁ Where a “U” or “PU” die is recommended * These connectors can only be installed
with the Y45 HYPRESS™, a PT6515 with the Y46 HYPRESS™, a PUADP-1 using the Y750, Y45 or Y46 HYPRESS™
adapter must be used. adapter must be used. with recommended dies. These connec-
tors CAN NOT be installed with the Y35 or
Y39 HYPRESS™.
BURNDY
Grounding

TYPE YGIB MEETS ALL

GROUNDLINK™ CONNECTOR
IEEE
837 REQUIREMENTS

An irreversible compression ground connec-


tion which allows attachment to a structural
steel standard (angled) or wide flange
(parallel) beam. Installed with a required
5-piece die set, Catalog PIBEAMKIT or
UIBEAMKIT. Die index 1105. Connector shipped with thread protection studs only. Order
GROUNDLINK™ connectors are made of TMHG kits separately.
high-conductivity wrought copper and come
pre-filled with PENETROX® E compound and
strip sealed. Order terminal mounting hard-
D-18 ware separately.

1.84 IN. Minimum flange depth.


➃ 3.06 IN. Minimum flange width. ➃ Fig. 1

Y46 SERIES Y750 SERIES STANDARD BEAMS


USE PIBEAMKIT USE UIBEAMKIT (FLANGE ANGLED) USE YGIBS)

Fig. 2 TERMINAL
“T” REF MAXIMUM
TERMINAL PAD MOUNTING HARDWARE
THICKNESS CATALOG NUMBER “T”

TMHG-42 .42

TMHG-92 .92
NOTE: Use TMHG-D92 to double stack lugs.
2 HOLE NEMA
SPACING WIDE FLANGE BEAMS
(FLANGE PARALLEL) USE YGIBW

NOTES:
1. Terminal conector to be ordered separately. When I-beam ➃ Dimensions shown reflect the minimum dimensions
connector is used with type "YGHA" terminal, the connec- required on a beam to properly install the I-beam
tion meets IEEE 837-1989 requirements. YGA-2N, YA-2N connector.
and other BURNDY® 2-hole NEMA copper terminals are
5. To correctly determine the appropriate YGIB connector to
suitable.
use based on flange thickness, order either
2. Order "TMHG" Terminal Mounting Hardware Kit separate- YGIBGAUGE1 or YGIBKIT1 (KIT1 contains wiremike).
ly. Kit consists of 2 studs, 2 flat washers, 2 lockwashers
and 2 hex nuts.
3. Using the 1/4 hex key wrench, screw the stud into the
connector until stud bottoms out in connector. Install a
"YGHA" terminal, flat washer, lockwasher and hex nut
onto stud. Tighten and torque to 480 pound-inches.
BURNDY
Grounding

TYPE YGIB
(Continued)

GROUNDLINK™ CONNECTOR

COPPER iBEAM
CONDUCTOR FIG. FLANGE SUGGESTED TERMINALS
RANGE CATALOG NUMBER NO. “L” “J” THICKNESS COPPER CONDUCTOR TERMINAL “T” REF.
#2 STR. AWG YGHA2C-2N .26
YGIBS28-338-2N 1 3.00
1/0 STR. AWG YGHA25-2N .19
2 - 4/0 AWG .250
2/0 STR. AWG YGHA26-2N .26
YGIBW28-338-2M 2 3.00 to
4/0 STR. AWG YGHA28-2N .30
.338
YGIBS34-338-2N 1 250 kcmil YGHA29-2N .34 D-19
250 - 500 kcmil 6.00
YGIBW34-338-2N 2 500 kcmil YGHA34-2N .40
#2 STR. AWG YGHA2C-2N .26
YGIBS28-400-2N 1 3.00
1/0 STR. AWG YGHA25-2N .19
2 - 4/0 AWG .338
2/0 STR. AWG YGHA26-2N .26
YGIBW28-400-2N 2 3.00 to
4/0 STR. AWG YGHA28-2N .30
.400
YGIBS34-400-2N 1 250 kcmil YGHA29-2N .34
250 - 500 kcmil 6.00
YGIBW34-400-2N 2 500 kcmil YGHA34-2N .40
#2 STR. AWG YGHA2C-2N .26
YGIBS28-462-2N 1 3.00
1/0 STR. AWG YGHA25-2N .19
.400
2 - 4/0 AWG 2/0 STR. AWG YGHA26-2N .26
YGIBW28-462-2N 2 3.00 to
4/0 STR. AWG YGHA28-2N .30
.462
YGIBS34-462-2N 1 250 kcmil YGHA29-2N .34
250 - 500 kcmil 6.00
YGIBW34-462-2N 2 500 kcmil YGHA34-2N .40
1/2 - 13
#2 STR. AWG YGHA2C-2N .26
YGIBS28-550-2N 1 3.00
1/0 STR. AWG YGHA25-2N .19
2 - 4/0 AWG 4.62
2/0 STR. AWG YGHA26-2N .26
YGIBW28-550-2N 2 3.00 to
4/0 STR. AWG YGHA28-2N .30
.550
YGIBS34-550-2N 1 250 kcmil YGHA29-2N .34
250 - 500 kcmil 6.00
YGIBW34-550-2N 2 500 kcmil YGHA34-2N .40
#2 STR AWG YGHA2C-2N .26
YGIBS28-613-2N 1 3.00
1/0 STR. AWG YGHA25-2N .19
2 - 4/0 AWG .550
2/0 STR. AWG YGHA26-2N .26
YGIBW28-613-2N 2 3.00 to
4/0 STR. AWG YGHA28-2N .30
.613
YGIBS34-613-2N 1 250 kcmil YGHA29-2N .34
250 - 500 kcmil 6.00
YGIBW34-613-2N 2 500 kcmil YGHA34-2N .40
#2 STR. AWG YGHA2C-2N .26
YGIBS28-675-2N 1 3.00
1/0 STR. AWG YGHA25-2N .19
2 - 4/0 AWG .613
2/0 STR. AWG YGHA26-2N .26
YGIBW28-675-2N 2 3.00 to
4/0 STR. AWG YGHA28-2N .30
.675
YGIBS34-675-2N 1 250 kcmil YGHA29-2N .34
250 - 500 kcmil 6.00
YGIBW34-675-2N 2 500 kcmil YGHA34-2N .40
BURNDY
Grounding

TYPE GSTUD-HY
VERSITAIL™
Structural Steel Grounding
Connector
INSTALLATION

1. Weld the VERSITAIL™ to the steel


member.
2. Select the proper connector for your FEATURES SPECIFICATIONS
specific application. • The VERSITAIL™ may be welded to steel • Low Carbon, hot rolled steel.
D-20 a. FOR COMPRESSION CONNECTORS surfaces quickly and easily with normal • Pure copper plated finish.
Select the proper BURNDY® type construction equipment.
“YGHP,” “YGHC,” or ‘YGHR” connector. • The VERSITAIL™ eliminates costly disk
Clean the conductor, join the VERSI- grinding and the need to expose virgin
TAIL™ and the grounding conductor metal. The welding process burns through (FLATTENING
together with the recommended tool and the oxidation and “scale” to establish RESULTANT)
die set, then crimp the connector over excellent electrical grounding continuity.
the knurled area of the VERSITAIL™. • The VERSITAIL™ may be installed by the T
b. FOR MECHANICAL CONNECTORS welder in the field or at the steel fabricator
based on customer preference. 45°
Select the properly sized BURNDY®
connector. Clean the conductor, then • The VERSITAIL™’s pure copper coating
apply PENETROX E® oxide inhibiting over low carbon, hot rolled steel is compat-
1.25
compound on the contact area for ible with standard welding processes. [32]
increased effectiveness and service life. No toxic gasses are generated.
Put the connector over the knurled area • The VERSITAIL™’s knurled surface is
of the VERSITAIL™ and apply the copper plated and specifically designed to TYPICAL
ensure excellent mechanical gripping and LETTERING
recommended torque value for correct
installation. electrical integrity for BURNDY® compres-
sion and mechanical connectors in all L A (STOCK
DIA.)
grounding applications.
• The VERSITAIL™ may be installed during
adverse weather conditions thus eliminating
costly construction delays. KNURLED 2.19
END [56]
BENEFITS
Low installation cost.
• No drilling . . . No cleaning . . . B (DIA. OVER KNURL)
• No special preparation

ELECTRICAL
EQUIVALENT
NOM. DIMENSIONS COPPER
CATALOG ROD A B L T CONDUCTOR SIZE
NUMBER SIZE IN. [MM] IN. [MM] IN. [MM] IN. [MM] (AWG.)*
GSTUD14HY 1/4 .25 [6.3] .26 [6.6] 4.81 [122.2] .19 [4.8] #6
GSTUD38HY 3/8 .38 [9.7] .39 [9.9] 5.81 [147.6] .25 [6.4] #3
GSTUD916HY 5/8 .56 [14.2] .57 [14.5] 5.68 [144.3] .38 [9.7] 1/0
GSTUD34HY 3/4 .75 [19.0] .76 [19.3] 5.81 [147.6] .51 [13.0] 4/0
* This is the equivalent rating for continuous service. Larger
conductors may be connected using both compression and
bolted connectors in potential ground fault applications.
BURNDY
Grounding

TYPES YGT & YTTAG Type YGT Static Type YTTAG Combination
Grounding Receptacle Static Grounding Receptacle
with Cover and Aircraft Tie Down Bar
STATIC GROUNDING
RECEPTACLE

Type YGT static grounding receptacles are


designed for static grounding of equipment.
The receptacle is connected to the ground
grid with HYGROUND™ compression
connectors and finished flush with surface to
provide a permanent corrosion proof ground-
ing point.

D-21

Fig. 1 Fig. 2

Catalog Figure Dimensions


Number Number * HYGROUND Connector H D Y Dia. Z Dia. “TD”
YGT275 1 Select suitable YGHR or 5.5 2.75 .75 .56 —
YGLR for 3/4 ground rod and
YTTAG388 2 sized to ground conductor. 6.5 4.75 .75 .56 4.3
* When using U or PU dies with Y46 HYPRESS™, a PUADP-1
adapter is required.

NOTES:
1. Ground rod must be pre-crimped with U2CABT die set when
PU998 die is used or for even higher mechanical resistance
use special UPRECRIMP™ dies on ground rods.
2. Pre-crimping of ground is not necessary when P1011 die is
used. Install YGHR or YGLR on hub Y. Hub Z is inserted into
1/2" rigid conduit. The conduit is driven into earth to provide
support and provide correct level of receptacle prior to
cement pour.
BURNDY
Grounding

TYPE YG-B
BUS BAR CONNECTOR

BURNDY’s YG14B2TC2C6C Compression


Bus Bar Connector is ideally suited for cellu-
lar tower applicatons and is easier to use than
exothermic connections. This high conduc-
tivity wrought copper connector allows
attachment of the ground conductor to the
Fig. 1 Fig. 2
ground bus with just one crimp using the
BURNDY® Y750 HYPRESS™ Hydraulic
Compression tool and the U1105 die set. This
exclusive patent pending design allows the
D-22 user to attach #2 AWG sol./str. and/or #6
sol./str. copper conductor to 1/4" thick copper
bus bar. This connection is suitable using (1)
or (2) conductors for power, grounding and
bonding applictions. UL Listed to both UL486
and UL467 (suitable for direct burial) ensures
that this connector will meet the rigors of Fig. 3
either application. Prefilled with PENETROX®
E compound and strip sealed.

GROUND BAR BUS BAR INSTALLATION


CATALOG NUMBER FIG NO. THICKNESS TAP CONDUCTORS TOOLING DIE NO. NO. OF CRIMPS
#2 SOL/and/or STR COPPER
YG14B2TC2C6C 1 1/4" Y750 U1105 1
#6 SOL/and/or STR COPPER
#2
YG14B2TC2C2C* 2 1/4" Y750 U1105 1
#2
#1 FLEX CABLE
YG14BTC26 3 1/4" through Y750 U1105 1
2/0 FLEX CABLE
4/0 AWG STR to 1/0
YG14BTC28 3 1/4” Y750 U1105 1
AWG STR COPPER
NOTE: Suitable for use with either (1) or (2) conductors
(excluding YG14BTC26 and YG14BTC28).
* For continuous uncut conductor applications.
BURNDY
Grounding

MECHANICAL
GROUNDING
CONNECTORS
More than 60 years of technological innova- problem that this diversified line cannot help high copper alloys are used in their manufac-
tion has made BURNDY® mechanical solve. ture, ensuring top performance under the
grounding connectors one of the most widely most extreme environmental conditions.
All BURNDY® mechanical grounding connec-
used, highly respected lines in the industry. tors have been designed for easy installation UL467 Listed for direct burial applications in
There is virtually no grounding application and for outstanding durability. Only the finest earth or concrete.

TYPES KC, K2C


D-23
SERVIT™ POST
For Copper Cable to Flat

SERVIT™ POST used to ground one or two


cables to steel structures, fence posts, trans-
formers. Also used to tap one or two cables
from bus bar. One-wrench installation.

KC K2C

CATALOG NUMBER CONDUCTOR STUD


TYPE KC TYPE K2C STRANDED SOLID DIAMETER B CFx CFy D H HH
KC15 K2C15 3/8 1/2
12 - 9 12 - 8 1/4 - 20 1/2 3/8 5/8 7/8
KC15B1 K2C15B1 7/8 1
KC17 K2C17 3/8 1/2
10 - 7 10 - 6 1/4 - 20 5/8 7/16 7/8 1
KC17B1 K2C17B1 7/8 1
KC20 K2C20 13/32 5/8
10 - 5 10 - 4 5/16 - 18 11/16 1/2 7/8 1-1/8
KC20B1 K2C20B1 27/32 1
KC22 K2C22 15/32 5/8
10 - 3 10 - 2 3/8 - 16 3/4 5/8 1 1-1/4
KC22B1 K2C22B1 31/32 1-1/8
KC23 K2C23 15/32 5/8
8-2 10 - 1 3/8 - 16 13/16 5/8 1 1-3/8
KC23B1 K2C23B1 31/32 1-1/8
KC25 K2C25 9/16 3/4
2 - 1/0 2 - 2/0 1/2 - 13 15/16 3/4 1-1/8 1-5/8
KC25B1 K2C25B1 1-1/16 1-1/4
KC26 K2C26 17/32 3/4
2 - 2/0 2 - 3/0 1/2 - 13 1 7/8 1-3/8 1-7/8
KC26B1 K2C26B1 1-1/16 1-1/4
KC28 K2C28 3/4 1
1 - 4/0 1 - 4/0 5/8 - 11 1-1/2 1-3/16 1-3/4 2-1/4
KC28B1 K2C28B1 1-1/4 1-1/2
KC31 K2C31 3/4 1
1 - 350 — 5/8 - 11 1-11/16 1-3/8 2-1/4 2-7/8
KC31B1 K2C31B1 1-1/4 1-1/2
KC34 K2C34 1 1-1/4
3/0 - 500 — 3/4 - 10 2 1-5/8 2-3/8 3-1/4
KC34B1 K2C34B1 1-1/2 1-3/4
Add “NSP” suffix to have connector supplied w/split lockwasher
and nut.
BURNDY
Grounding

TYPES KC22J12T13,
EQC632C
TRANSFORMER GROUND
CONNECTORS
.6
For Copper
Stud Size = 1⁄2” - 13 Type EQC632C Type KC22J12T13
Fits all standard EEI NEMA distribution
transformers as a tank grounding terminal.
CATALOG NUMBER RANGES
KC22J12T13 8 Sol. - 2 Sol.
KC26 2 Sol. - 2/0 Str.
D-24 KC34J12T13 3/0 - 500 Str.
EQC632C 8 Sol. - 2 Str.
Both, one-wrench installation.
BURNDY
Grounding

TYPE KS-DB
SERVIT™
For Copper

UL467 Listed for direct burial applications in


earth or concrete. Compact, high-strength,
high copper alloy SERVIT™ split-bolt has
free-running threads and easy to grip wrench
flats. Highly resistant to cracking and
corrosion.

D-25

Catalog Copper Conductor Range Rebar w/ (1) Recommended


Number Cross Flats L W (Sol. - Str.) No. 8 Sol. Cu Torque In. Lb.
KS15-DB .50 .85 .38 12 AWG - 8 AWG N/A 80
KS17-DB .63 1.14 .45 8 AWG - 6 AWG N/A 165
KS20-DB .69 1.20 .51 8 AWG - 4 AWG N/A 165
KS22-DB .75 1.50 .60 6 AWG - 3 AWG N/A 275
KS23-DB .82 1.54 .62 6 AWG - 2 AWG N/A 275
KS25-DB .94 1.77 .73 4 AWG - 1/0 N/A 385
2 AWG - 2/0 #3
KS26-DB 1.05 1.94 .82 385
6 AWG - 8 AWG Str./Sol. (3/8)
KS27-DB 1.36 1.86 1.17 1 AWG - 3/0 N/A 500
1 AWG - 250 kcmil #4
KS29-DB 1.36 2.07 1.17 650
6 AWG - 8 AWG Str./Sol. (1/2)
1/0 AWG - 350 kcmil #5
KS31-DB 1.70 2.51 1.41 650
6 AWG - 8 AWG Str./Sol. (5/8)
2/0 AWG - 500 kcmil #6
KS34-DB 1.82 2.79 1.48 825
6 AWG - 8 AWG Str./Sol. (3/4)
BURNDY
Grounding

TYPE GKA
For Copper

UL467 Listed for direct burial applications in


earth or concrete. One-piece forged body
construction insures mechanical integrity in
an underground environment. Supplied with a
stainless steel headless screw.

CATALOG NUMBER CABLE RANGE B C H J K L


GKA8C 1 #10 SOL. - #8 STR. .31 .38 .58 #10 - 32 .21 .81
D-26 GKA4C 2 #14 SOL. - #4 STR. .46 .54 .71 5/16 - 24 .28 1.13
1. To be assembled with TMH322 stainless steel hardware kit. 2. To be assembled with TMH 323 stainless steel hardware kit.
Ordered separately. Ordered separately.

TYPE KPB
For Copper

UL467 Listed for direct burial in earth or con-


crete. UL 486 listed. This exclusive BURNDY®
design accommodates #10 - #4 copper
where continuous conductor runs are
preferable.

CATALOG
NUMBER RANGE STUD HOLE
KPB4CG1 #10 - #4 CU #10 1
1. To be assembled with TMH322 stainless steel hardware kit.
Ordered separately.

TYPE CL50-1 Stainless Steel Screw

COPPER LAY-IN QIKLUG™


For Copper

The Lay-In QIKLUG™ is manufactured from


high strength pure electrolytic copper to
ensure maximum strength and conductivity.
UL467 Listed for direct burial in earth or con-
crete. The open-faced design allows for fast
lay-in of the conductor without the need for
cutting or breaking.

CATALOG WIRE RANGE


NUMBER COPPER STUD HOLE
CL50-1 #14 - #4 CU #10
BURNDY
Grounding

TYPE GAR
FENCE POST GROUNDING
CONNECTOR
For Parallel or 90°
Copper Cable
Connection
To Rod or Pipe with
the Same Connector
High copper alloy ground connector for join-
ing a range of cable, parallel or at right angles D-27
to rod or tube. Especially good for fence
posts. High copper alloy cast body with
DURIUM™ U-bolts, nuts and lockwashers,
permit entire connection to be buried in
ground or concrete without danger of
corrosion.
• One-wrench installation.
• UL467 Listed.
• Acceptable for direct burial.

Catalog Conductor
Number Tube I.P.S. Rod Cable H J W
GAR114C 8 Sol. - 4 Str.
GAR1126 1/4 1/2 4 Sol. - 2/0 Str. 2-1/2 1-7/8
GAR1129 2/0 Sol. - 250
3/8
GAR644C 8 Sol. - 4 Str.
GAR6426 4 Sol. - 2/0 Str. 2-7/8 2-1/8
3/8 5/8 - 3/4
GAR6429 2/0 Sol. - 250
GAR6434 300 - 500 3-1/2 1/2 2-1/2
GAR144C 8 Sol. - 4 Str. 2-3/4
GAR1426 4 Sol. - 2/0 Str. 3/8 2-3/8
1/2 - 3/4 7/8 - 1 3
GAR1429 2/0 Sol. - 250
GAR1434 300 - 500 3-3/4 1/2 2-3/4
GAR154C 8 Sol. - 4 Str.
2-7/8
GAR1526 4 Sol. - 2/0 Str. 3/8 2-5/8
1 1-1/8 - 1-1/4
GAR1529 2/0 Sol. - 250 3-3/8
GAR1534 300 - 500 4-1/2 1/2
GAR164C 8 Sol. - 4 Str.
GAR1626 4 Sol. - 2/0 Str. 3-1/2 3/8 3
1-1/4 1-3/8 - 1-1/2
GAR1629 2/0 Sol. - 250
GAR1634 300 - 500 4-1/4 1/2 3-3/8
GAR174C 8 Sol. - 4 Str.
GAR1726 4 Sol. - 2/0 Str. 4 3/8 3-1/4
1-1/2 1-5/8 - 1-7/8
GAR1729 2/0 Sol. - 250
GAR1734 300 - 500 4-5/8 1/2 2-5/8
GAR184C 8 Sol. - 4 Str.
4-1/4
GAR1826 4 Sol. - 2/0 Str. 3/8 3-3/4
2 2 - 2-3/8
GAR1829 2/0 Sol. - 250 4-1/2
GAR1834 300 - 500 5-1/4 1/2 4-1/8
GAR194C 8 Sol. - 4 Str.
GAR1926 4 Sol. - 2/0 Str. 5 3/8 4-1/4
2-1/2 2-1/2 - 7/8
GAR1929 2/0 Sol. - 250
GAR1934 300 - 500 5-5/8 1/2 4-5/8
BURNDY
Grounding

TYPE GAR
(Continued)
FENCE POST GROUNDING
CONNECTOR

Catalog Conductor
Number Tube I.P.S. Rod Cable H J W
GAR204C 8 Sol. - 4 Str. 5-5/8 3/8 4-3/4
GAR2026 4 Sol. - 2/0 Str.
3 3 - 3-1/2
GAR2029 2/0 Sol. - 250
GAR2034 300 - 500 6-3/8 1/2 5-1/4
D-28 GAR214C 8 Sol. - 4 Str.
GAR2126 4 Sol. - 2/0 Str. 6-1/4 3/8 5-3/8
3-1/2 3-1/2 - 4
GAR2129 2/0 Sol. - 250
GAR2134 300 - 500 6-3/4 1/2 5-3/4
GAR224C 8 Sol. - 4 Str.
GAR2226 4 Sol. - 2/0 Str. 6-3/8 3/8 5-7/8
4 4 - 4-1/2
GAR2229 2/0 Sol. - 250
GAR2234 300 - 500 6-7/8 1/2 6-1/4
GAR244C 8 Sol. - 4 Str.
3/8 6-7/8
GAR2426 4 Sol. - 2/0 Str. 7-3/4
5 —
GAR2429 2/0 Sol. - 250
1/2 7-1/4
GAR2434 300 - 500 8-5/8
GAR8629 6 — 2/0 Sol. - 250 8-13/16 1/2 8-3/8
Contact BURNDY® for additional pipe and wire size
combinations not shown.
BURNDY
Grounding

TYPES GAR-BU AND


GAR3902 SERIES
GROUND CONNECTORS

Type GAR-BU is a high-conductivity copper


ground connector for connecting a small to
medium range copper ground conductor to
water pipe as well as structural and reinforc-
ing rod shapes. Universal acceptance of
several sizes of cylindrical shapes makes this Features and benefits
suitable for industrial construction and main-
tenance work as well as cathodic protection. • Cable clamp swivels at 90°.
Cable clamp swivels to permit parallel ◊ Permits parallel grounding of one pipe D-29
grounding of one pipe or 90° degree cable or a 90° cable run for grounding several
run for grounding several parallel pipes. parallel pipes.
Single wrench installation. UL467 Listed and • One-wrench installation.
CSA certified. ◊ Simplified installation.
• DURIUM™ silicon bronze hardware (-BU
Series)*.
◊ Long lasting corrosion resistance and
* acceptable for direct burial in earth
or concrete.
• UL467 Listed.
◊ Provides quality assurance to recognized
industry NEC standards from an
independent party.

CATALOG RECOMMENDED
NUMBER * CABLE RANGE IPS SIZE O.D. RANGE H J W TIGHTENING TORQUE
GAR3902-BU 1/2 - 1 .840 - 1.32 3.50 3.25
GAR3903-BU 1-1/4 - 2 1.66 - 2.38 4.00 4.25
GAR3904-BU 2-1/2 - 3-1/2 2.88 - 4.00 6.50 6.00
GAR3905-BU 4 - 5 4.50 - 5.56 7.50 7.50
#4 - 4/0 AWG 3/8 - 16 240 in. - lbs.
GAR3906-BU 6 6.62 8.50 8.62
GAR3907-BU 8 8.62 10.00 10.62
GAR3908-BU 10 10.75 12.00 12.75
GAR3909-BU 12 12.75 14.00 14.75
GAR3902 1/2 - 1 .840 - 1.32 3.50 3.25
GAR3903 1-1/4 - 2 1.66 - 2.38 4.00 4.25
GAR3904 2-1/2 - 3-1/2 2.88 - 4.00 6.50 6.00
GAR3905 4 - 5 4.50 - 5.56 7.50 7.50
#4 - 4/0 AWG 3/8 - 16 240 in. - lbs.
GAR3906 6 6.62 8.50 8.62
GAR3907 8 8.62 10.00 10.62
GAR3908 10 10.75 12.00 12.75
GAR3909 12 12.75 14.00 14.75
* Type GAR-BU is supplied with DURIUM™ silicon bronze
hardware and is listed for direct burial.

TYPE GAR-RB
For Reinforcement Bar

CATALOG COPPER CONDUCTOR


NUMBER REBAR IPS SIZE O.D. RANGE ROD MIN. MAX.
GAR644C-RB #3 - 6 (.375 - .750) 3/8 .625 - .75 5/8 - 3/4 8 Sol. 5 Str.
UL467 listed for direct burial in earth or concrete.
BURNDY
Grounding

TYPE GAR-TC
WATER PIPE GROUND
CONNECTOR

Type GAR-TC is a high-conductivity copper


ground connector that features a pre-drilled
pad, allowing a 2-hole compression terminal
to be directly connected to water pipe as well PATENTED
as structural and reinforcing rod shapes.
Universal acceptance of several sizes of
cylindrical shapes makes this suitable for
Features and Benefits
industrial construction and maintenance work • Large, smooth connector contact area • DURIUM™ silicon bronze hardware.
D-30 as well as telecommunications grounding. between pipe and ground clamp ◊ Provide long lasting corrosion resistance
Terminal may be mounted parallel, 45° or 90° ◊ Provides large surface contact area acceptable for direct burial in earth
degrees to the pipe. Acceptable for direct to maximize contact area between or concrete.
burial. connector and pipe. • One-wrench installation.
• The GAR-TC mounting pad permits ◊ Simplified installation.
parallel, 45° or 90° angle connections • UL467 Listed.
to the pipe. ◊ Provides quality assurance to recognized
◊ Provides maximum flexibility for industry NEC standards from an
field installation. independent party. Type GAR-TC is
• Pre-drilled pad for (2) 3/8 bolts on acceptable for direct burial
1 centers.
◊ Allows direct mounting of (2) hole
compression terminals up to 750 kcmil
to pipe.

MOUNTING PAD
FOR (2) 3/8"
Fig. 1 BOLTS - 1" L
COMPRESSION LUG WITH PAD
CAST HIGH COPPER ALLOY SADDLE FOR (2) 3/8" DIA. BOLTS
ON 1" CENTERS. 750 KCMIL MAX.

J
MOUNTING PAD
DURIUM 3/8"
SILICON BRONZE
PIPE DIA. HARDWARE

Fig. 2

CATALOG FIG. ACCOMMODATES RECOMMENDED


NUMBER NO. I.P.S. O.D. SIZE H J W TIGHTENING TORQUE
GAR3902TC 1 1/2 - 1 .840 - 1.32 3.50 3.75
GAR3903TC 1 1-1/4 - 2 1.66 - 2.38 4.00 4.75
GAR3904TC 1 2-1/2 - 3-1/2 2.88 - 4.00 6.50 3/8 - 16 6.50 240 in.-lbs.
GAR3905TC 1 4 - 5 4.50 - 5.56 7.50 8.00
GAR3906TC 1 6 6.62 8.50 9.12
GAR3907TC 2 8 8.62 10.00 11.25
GAR3908TC 2 10 10.75 12.00 3/8 - 16 13.25 240 in.-lbs.
GAR3909TC 2 12 12.75 14.00 15.25
① Add suffix “-TNET” for electro-tin plated connector and NOTE: Clean pipe surface beneath saddle until virgin metal is
electro-tin plated DURIUM™ silicon bronze hardware. Tin exposed, install GAR-TC ground connector and for
plated catalog number includes mounting hardware for maximum
second bolt hole. conductivity, apply PENETROX®-E oxide inhibiting
② TMH-289 includes (1) 38 x 125 HEB, (1) 38 CHEN, (1) 38 compound around perimeter of the saddle.
SW and (2) 38 FW. Order separately.
BURNDY
Grounding

TYPE GD
CABLE TO ROD/TUBE
GROUND CONNECTOR
For Two Copper Cables to Rod
or Tube

High copper alloy ground connector for join-


ing a range of two parallel cables to rod or
pipe. Especially good for grounding fence
posts. High copper alloy cast body with
DURIUM™ U-bolts, nuts, and lockwashers
make the GD suitable for burial in ground or D-31
concrete. One-wrench installation. UL467
Listed. Acceptable for direct burial in earth
or concrete.

Catalog Conductor
Number Tube I.P.S. Rod Cable H J W
GD1526 4 Sol. - 2/0 Str.
1 1-1/8 - 1-1/4 3-3/8 2-5/8
GD1529 2/0 Sol. - 250
GD1626 4 Sol. - 2/0 Str. 3
1-1/4 1-3/8 - 1-1/2 3-1/2
GD1629 2/0 Sol. - 250 3/8
GD174C 8 Sol. - 4 Str.
3-1/4
GD1726 4 Sol. - 2/0 Str. 4
1-1/2 1-5/8 - 1-7/8
GD1729 2/0 Sol. - 250
GD1734 300 - 500 4-5/8 1/2 3-5/8
GD184C 8 Sol. - 4 Str.
GD1826 4 Sol. - 2/0 Str. 4-3/8 3/8 3-3/4
2 2 - 2-3/8
GD1829 2/0 Sol. - 250
GD1834 300 - 500 5-3/8 1/2 4-1/8
GD194C 8 Sol. - 4 Str.
GD1926 4 Sol. - 2/0 Str. 3/8 4-1/4
2-1/2 2-1/2 - 2-7/8 5
GD1929 2/0 Sol. - 250
GD1934 300 - 500 1/2 4-5/8
GD204C 8 Sol. - 4 Str.
GD2026 4 Sol. - 2/0 Str. 5-5/8 3/8 4-7/8
3 3 - 3-1/2
GD2029 2/0 Sol. - 250
GD2034 300 - 500 6-3/8 1/2 5-1/4
GD214C 8 Sol. - 4 Str.
GD2126 4 Sol. - 2/0 Str. 6-1/4 3/8 5-3/8
3-1/2 3-1/2 - 4
GD2129 2/0 Sol. - 250
GD2134 300 - 500 6-7/8 1/2 5-3/4
GD224C 8 Sol. - 4 Str.
GD2226 4 Sol. - 2/0 Str. 6-3/8 3/8 5-7/8
4 4 - 4-1/2
GD2229 2/0 Sol. - 250
GD2234 300 - 500 6-7/8 1/2 6-1/4
Complies with NFPA 78-86 HEAVY DUTY stacks.
(Order: LD for lead plating for HEAVY DUTY stack
applications.)
BURNDY
Grounding

TYPE GP
GROUND CONNECTOR
For Two Copper Cables
to Rod or Pipe

High copper alloy ground connector for join-


ing a range of parallel cables perpendicular to Catalog Conductor
rod, pipe or column. Also used with one Number Tube I.P.S. Rod Cable H J W
groove for run, the other for tap to equipment.
GP114C 8 Sol. - 4 Str.
High copper alloy cast body and DURIUM™
GP1126 1/4 1/2 4 Sol. - 2/0 Str. 1-7/8
U-bolts, nuts, and lockwashers make the GP
GP1129 2/0 Sol. - 250 2-1/2
suitable for direct burial in the ground or 3/8
D-32 GP644C 8 Sol. - 4 Str.
concrete. One-wrench installation. UL467
GP6426 4 Sol. - 2/0 Str. 2-1/8
Listed. Acceptable for direct burial in earth 3/8 5/8 - 3/4
GP6429 2/0 Sol. - 250 2-7/8
or concrete.
GP6434 300 - 500 3-1/2 1/2 2-1/2
GP144C 8 Sol. - 4 Str. 2-3/4
GP1426 4 Sol. - 2/0 Str. 38 2-3/8
1/2 - 3/4 7/8 - 1 3
GP1429 2 Sol. - 250
GP1434 300 - 500 3-3/4 1/2 2-3/4
GP164C 8 Sol. - 4 Str.
1-1/4 1-5/8 3-1/2 3
GP1629 2 Sol. - 250
GP1726 1-1/2 1-7/8 4 Sol. - 2 Str. 4 3-1/4
GP184C 8 Sol. - 4 Str. 4-1/8 3/8
2 2-3/8 3-11/16
GP1826 4 Sol. - 2/0 Str. 4-3/8
GP2026 3 3-1/2 4 Sol. - 2/0 Str. 5-1/2 4-13/16
GP2226 4 4-1/2 4 Sol. - 2/0 Str. 6-3/8 5-13/16

TYPE GK
GROUND CONNECTOR
For Three Copper Cables to
Rod or Pipe

High copper alloy ground connector for join-


ing three equal cables to rod or tube. Cable Catalog Conductor
grooves take a wide range of cable. High Number Tube I.P.S. Rod Cable H J W
copper alloy cast body and DURIUM™ GK114C 8 Sol. - 4 Str. 2-1/2
U-bolts, nuts, and lockwashers make the GK 3/8
GK1126 1/4 1/2 4 Sol. - 2/0 Str. 2-1/2 2-3/4
suitable for direct burial in soil or concrete. GK1129 2/0 Sol. - 250 1/2 3-3/8
One-wrench installation. UL467 Listed. GK644C 8 Sol. - 4 Str. 2-5/8
Acceptable for direct burial in earth or 3/8
GK6426 4 Sol. - 2/0 Str. 2-7/8 3
concrete. 3/8 5/8 - 3/4
GK6429 2/0 Sol. - 250 3-1/2
1/2
GK6434 300 - 500 3-1/2 4
GK1426 4 Sol. - 2/0 Str. 2-3/4 38 3-1/4
GK1429 1/2 - 3/4 7/8 - 1 2 Sol. - 250 3-7/8
3-3/4 1/2
GK1434 300 - 500 4-3/8
GK1526 4 Sol. - 2/0 Str. 3-3/8 3/8 3-1/2
1 1-1/8 - 1-1/4
GK1529 2/0 Sol. - 250 3-3/4 1/2 4-1/8
GK1626 4 Sol. - 2/0 Str. 3-1/2 3/8 3-7/8
1-1/4 1-3/8 - 1-1/2
GK1629 2/0 Sol. - 250 4-1/4 1/2 4-1/2
GK1726 4 Sol. - 2/0 Str. 4 3/8 4-1/8
1-1/2 1-5/8 - 1-7/8
GK1729 2/0 Sol. - 250 4-5/8 1/2 4-3/4
GK1826 4 Sol. - 2/0 Str. 4-1/4 3/8 4-5/8
2 2 - 2-3/8
GK1829 2/0 Sol. - 250 4-3/8 1/2 5-1/8
GK1926 4 Sol. - 2/0 Str. 5 3/8 5-1/8
2-1/2 2-1/2 - 2-7/8
GK1929 2/0 Sol. - 250 5 1/2 5-5/8
BURNDY
Grounding

CAST BRONZE
CLAMPS FOR
CONDUIT
Pressure bar type conduit hub adjusts for
1/2, 3/4 EMT or 1/2 rigid conduit. Hub
swings 360° for easy alignment. Zinc plated
hardware.

RECOMMENDED
ACCOMMODATES REFERENCE SCREW TORQUE
CONDUCTOR RANGE DIMENSIONS “INCH POUNDS”
CATALOG WATER HUB PIPE WIRE
NUMBER PIPE GROUND SIZE H L W CLAMP CLAMP D-33
1/2 - 1 2.07 3.19
C-11JPT
[13 - 25] [53] [81]
1-1/4 - 2 10 - 6 1/2 2.70 3.83 2.70
C-22JPT 50 in.-lb. 50 in.-lb.
[32 - 51] Sol. [13] [69] [97] [69]
2-1/2 - 4 4.39 5.15
C-4JPT
[64 - 102] [112] [131]

CAST BRONZE
GROUND CLAMPS
For connecting grounding conductor to water
pipe or copper tube. "D" indicates UL467
Listed for direct burial in earth and concrete
and are supplied with silicon bronze hard-
ware. "B" indicates brass hardware.

RECOMMENDED
ACCOMMODATES SCREW TORQUE
CONDUCTOR RANGE “INCH POUNDS”
CATALOG WATER REFERENCE DIMENSIONS PIPE WIRE
NUMBER PIPE REBAR GROUND H L W C CLAMP CLAMP
C-11N —
1/2 - 1 10 - 2 1.81 2.25 .63 .63
C-11D #4 - #6
[13 - 25] Str. [46] [56] [16] [16]
C-11B
C-22
1-1/4 - 2 10 - 2 2.38 3.63 .75 1.00
C-22D
[32 - 51] Str. [60] [92] [19] [25] 50 in.-lb. 50 in.-lb.
C-22B

2-1/2 - 4 10 - 2 4.13 6.25 .96 1.88
C-4
[64 - 114] Str. [105] [159] [24] [48]
4-1/2 - 6 10 - 2 4.29 8.34 1.25 1.88
C-8
[114 - 165] Str. [109] [212] [32] [48]

BUDGET PRICE RECOMMENDED


ACCOMMODATES SCREW TORQUE
CAST BRONZE CONDUCTOR RANGE “INCH POUNDS”
GROUND CLAMP CATALOG WATER
NUMBER PIPE REBAR GROUND
REFERENCE DIMENSIONS
H L W C
PIPE WIRE
CLAMP CLAMP
Similar to above but lighter duty. C-5 1/2 - 1 10 - 2 1.56 2.25 .56 .50
— 50 in.-lb. 50 in.-lb.
(JUNIOR) [13 - 25] Str. [40] [56] [14] [13]
BURNDY
Grounding

DIE CAST CLAMPS


Die cast zinc with zinc plated screws.

RECOMMENDED
ACCOMMODATES SCREW TORQUE
CONDUCTOR RANGE “INCH POUNDS”
CATALOG WATER REFERENCE DIMENSIONS PIPE WIRE
NUMBER PIPE GROUND H L W C CLAMP CLAMP
D-34 1/2 - 1 10 - 2 1.56 2.25 .56 .50
CZ-11 50 in.-lb. 50 in.-lb.
[13 - 25] Str. [40] [56] [14] [13]

CAST BRONZE
CLAMPS
To connect armored cable to water pipe. Zinc
plated screws. Pressure bar grips armor or
outer cable insulation. 360° swing hub for
easy alignment.

RECOMMENDED
ACCOMMODATES REFERENCE SCREW TORQUE
CONDUCTOR RANGE DIMENSIONS “INCH POUNDS”
CATALOG WATER ARMORED PIPE WIRE
NUMBER PIPE CONDUCTOR H L W CLAMP CLAMP
1/2 - 1 1.38 3.05
C-11JA
[13 - 25] [35] [77]
1-1/4 - 2 10 - 6 2.60 3.69 1.41
C-22JA 50 in.-lb. 50 in.-lb.
[32 - 51] Sol. [66] [94] [36]
2-1/2 - 4 4.29 5.01
C-4JA [64 - 102] [109] [128]

CAST BRONZE
CLAMPS
For connecting armored cable to water pipe.
Zinc plated screws. "D" indicates UL467 for
direct burial in earth and concrete, supplied
with silicon bronze hardware.

RECOMMENDED
ACCOMMODATES SCREW TORQUE
CONDUCTOR RANGE “INCH POUNDS”
CATALOG WATER GROUND REFERENCE DIMENSIONS PIPE WIRE
NUMBER PIPE GROUND CLAMP H L W C CLAMP CLAMP
C-6 1/2 - 1 10 - 2 Bare Armored 1.60 2.34 1.06 .63
[13 - 25] Str. Unarmored [41] [59] [27] [16]
C-6D 50 in.-lb. 50 in.-lb.
Wire Cables
1-1/4 - 2 10 - 2 or Cords 2.38 3.62 .94 1.00
C-7 [32 - 51] Str. [60] [92] [24] [25]
BURNDY
Grounding

CAST BRONZE
CLAMP FOR
RIGID CONDUIT
For grounding rigid conduit systems.
Zinc plated screws.

RECOMMENDED
ACCOMMODATES SCREW TORQUE
CONDUCTOR RANGE “INCH POUNDS”
CATALOG WATER HUB REFERENCE DIMENSIONS PIPE WIRE
NUMBER PIPE GROUND SIZE H L W C CLAMP CLAMP D-35
1/2 - 1 2.07 2.34 1.34 1.06
C-61 [13 - 25] 10 - 2 1/2 [53] [59] [34] [27]
50 in.-lb. 50 in.-lb.
1-1/4 - 2 Str. [13] 2.69 3.62 1.34 1.40
C-66 [32 - 51] [68] [92] [34] [36]

CAST BRONZE
CLAMPS FOR
CONDUIT
For grounding rigid conduit systems.
Continuity from rigid conduit systems to
ground provided by cast bronze threaded
conduit hub. Zinc plated screws.

RECOMMENDED
ACCOMMODATES SCREW TORQUE
CONDUCTOR RANGE “INCH POUNDS”
CATALOG WATER HUB REFERENCE DIMENSIONS PIPE WIRE
NUMBER PIPE GROUND SIZE H L W C CLAMP CLAMP
1/2 - 1 2.25 3.23 .97
C-11LH-1 [13 - 25] [57] [83] [25]
1-1/4 - 2 10 Str. - 1/2 2.88 3.50 .69 1.34
C-22LH-1 [32 - 51] 6 Sol. [13] [73] [89] [18] [34]
2-1/2 - 4 4.56 4.82 2.44
C-4LH-1 [54 - 102] [116] [122] [62]
1/2 - 1 2.56 2.86 1.13
C-11LH-2 [13 - 25] [65] [73] [29]
1-1/4 - 2 2/0 - 10 3/4 3.19 3.50 1.00 1.50
C-22LH-2 50 in.-lb. 50 in.-lb.
[32 - 51] Str. [19] [65] [89] [25] [38]
2-1/2 - 4 4.88 4.82 2.38
C-4LH-2 [64 - 102] [124] [122] [60]
1/2 - 1 2.69 2.86 1.19
C-11LH-3 [13 - 25] [68] [73] [30]
1-1/4 - 2 3/0 - 10 1 3.32 3.50 1.13 1.56
C-22LH-3 [32 - 51] Str. [25] [59] [89] [29] [40]
2-1/2 - 4 5.01 4.82 2.44
C-4LH-3 [63 - 102] [127] [122] [62]
BURNDY
Grounding

CAST BRONZE
CLAMP WITH
COPPER STRAP
For grounding rigid conduit systems. Strap
helps protect conduit system from water
system vibrations. Zinc plated screws. Strap
ETP copper.

RECOMMENDED
ACCOMMODATES SCREW TORQUE
CONDUCTOR RANGE “INCH POUNDS”
D-36 CATALOG WATER HUB REFERENCE DIMENSIONS PIPE WIRE
NUMBER PIPE GROUND SIZE H L W C D CLAMP CLAMP
6 Sol. 1/2 1.06 1.06
C-11CSH-1 Max. [13] [27] [27]
1/2 - 1 3/4 1.75 8.50 1.25 1.50 6.12
C-11CSH-2 50 in.-lb. 50 in.-lb.
[13 - 25] 4/0 Str. [19] [44] [216] [32] [38] [155]
Max. 1 1.50 1.75
C-11CSH-3 [25] [38] [44]

GROUND STRAPS,
ADJUSTABLE
Burndy adjustable ground straps are made
from pure annealed copper. The heavy type is
.050 thick and 3/4 wide. The light type is
.025 thick and 3/4 wide. The bolts, nuts and
washers are plated steel. Four sizes cover a
ground pipe range of 3/8 to 4. Ground wire
connection can be soldered or solderless.

RECOMMENDED
CATALOG ACCOMMODATES REFERENCE DIMENSIONS SCREW TORQUE
NUMBER WATER PIPE H L W “INCH POUNDS”
.050
GS1T50 3/8 - 1 [1] 5.61
[10 - 25] .025 [142]
GS1T25 [1]
.050
GS2T50 3/8 - 2 [1] 9.38
[10 - 51] .025 [238]
GS2T25 [1] .75
50 in.-lb.
.050 [19]
GS3T50 3/8 - 3 [1] 13.20
[10 - 76] .025 [335]
GS3T25 [1]
.050
GS4T50 3/8 - 4 [1] 17.00
[10 - 102] .025 [432]
GS4T25 [1]
BURNDY
Grounding

TYPE GC-A
DUAL RATED
GROUND CLAMP
For Copper and
Aluminum Cable

GC-A ground clamps are UL Listed for use


with either copper or aluminum conductors to
copper water pipe, galvanized pipe or steel
conduit. All clamps are constructed from tin
plated high-strength extruded aluminum alloy.
PENETROX® oxide inhibiting joint com- D-37
pounds are recommended for all aluminum
applications. Features and Benefits
• Clamps are dual rated for both copper
and aluminum conductors.
◊ Maximum flexibility of application.
• All connectors are tin plated.
◊ Provide low contact resistance and
prevents galvanic corrosion.
• All clamps are range taking.
◊ Only 3 catalog numbers covers complete
range of applications from 1/2 - 4 inches.

Catalog Conduit, Pipe, or Wire Screw Hex


Number Water Tube Size Range Type W L Size
GC15A 1/2 - 3/4 - 1 1/0 - 14 Slotted 11/16 2-1/4 S
GC18A 1-1/4 - 1-1/2 - 2 250 MCM - 6 Hex Socket 13/16 3-3/4 5/16
GC22A 2-1/2 - 3 - 3-1/2 - 4 250 MCM - 6 Hex Socket 1 6-5/16 5/16
BURNDY
Grounding

TYPE GG
GROUND CONNECTOR
For Copper Bar, Strap, Braid or
Cable to Rod or Tube

High copper alloy ground connector for join-


ing bar, strap, braid or cable to rod or tube.
High copper alloy cast body, DURIUM™
U-bolts, nuts and lockwashers make the GG
particularly effective for use with braid for
ground rods, switch handles, fence posts and
gates. One-wrench installation.
D-38
Catalog Conductor
Number Tube I.P.S. Rod A H J W
GG15-1 1 1-1/8 - 1-1/4 3-3/8 2-5/8
GG16-1 1-1/4 1-3/8 - 1-1/2 1 3
GG17-1 3-1/2
1-1/2 1-5/8 - 1-7/8 3/8 3-1/4
GG17-15 1-1/2
GG18-1 1
4-1/4 3-3/4
GG18-15 2 2 - 2-3/8 1-1/2
GG18-2 4-3/8 4-1/8
2
GG19-2
2-1/2 2-1/2 - 2-7/8 5 4-5/8
GG19-25 2-1/2
GG20-2 2
GG20-25 3 3 - 3-1/2 2-1/2 6-3/8 5-1/4
GG20-3 3
GG21-2 2
GG21-25 2-1/2
3-1/2 3-1/2 - 4 5-7/8 1/2 5-3/4
GG21-3 3
GG21-35 3-1/2
GG22-2 2
GG22-25 2-1/2
GG22-3 4 4 - 4-1/2 3 6-1/2 6-1/4
GG22-35 3-1/2
GG22-4 4
GG24-2 5 — 2 7-5/8 7-1/4

See note page D-1


BURNDY
Grounding

TYPE GQ
GROUND CONNECTOR
For Copper Cable to Tube

High copper alloy ground connector for cross


connecting a wide range of cable. High
copper alloy, cast body, DURIUM™ U-bolts,
nuts, and lockwashers make the GQ suitable
for burial in soil or concrete. One-wrench
installation. UL467 Listed. Acceptable for
direct burial in earth or concrete.

D-39

Catalog Conductor
Number Tube I.P.S. Cable H J L W
GQ2626 6 Max. 4-1/2
4 Str. - 2/0 Str. 5 2-1/2
GQ26-1 Above 6 7-1/8
1/2
GQ2929 6 Max. 4-1/8
2/0 Str. - 250 6 2-3/4
GQ29-1 Above 6 7-1/2
BURNDY
Grounding

TYPE GX
GROUND CONNECTOR
For Copper Cables

High copper alloy ground connector for cross


connecting a wide range of cable. The high
copper alloy cast body, DURIUM™ U-bolts,
nuts, and lockwashers make the GX suitable
for burial in soil or concrete. One-wrench
installation. UL467 Listed. Acceptable for
direct burial in earth or concrete.

D-40

Catalog Conductor
Number Groove A Groove B H J L W
GX4C4C 8 Sol. - 4 Str. 8 Sol. - 4 Str. 1-7/8 1-5/8 1-5/8
GX264C 8 Sol. - 4 Str.
4 Sol. - 2/0 Str. 2-1/2 1-3/4 1-3/4
GX2626 4 Sol. - 2/0 Str.
GX294C 8 Sol. - 4 Str.
GX2926 2/0 Sol. - 250 4 Sol. - 2/0 Str. 3/8 1-7/8
GX2929 2/0 Sol. - 250
2-3/4 1-7/8
GX344C 8 Sol. - 4 Str.
GX3426 4 Sol. - 2/0 Str. 2-1/8
300 - 500
GX3429 2/0 Sol. - 250
GX3434 300 - 500 4-1/4 1/2 2-5/8 2-5/8

TYPE GRC
HIGH STRENGTH
GROUND ROD CLAMP
For Copper Cable to Rod

High copper alloy ground connector for


joining a range of cable to copper clad,
galvanized steel, and stainless steel ground
rods. Slips over end of rod, one-wrench
installation. UL467 Listed for direct burial in REA LISTED
earth and concrete.

Catalog Drive Conductor Range


Number Rod Min. Max. H W L J
GRC12 1/2 2 Str. 2.00 .89 .63
10 Sol.
GRC58 5/8 1 Str. 2.19 .95 .63 3/8
GRC34 3/4 8 Sol. 1/0 Str. 2.47 1.09 .65
BURNDY
Grounding

TYPE B
FLEXIBLE COPPER BRAID

Flexible copper braid jumpers designed to


take up linear expansion and contraction,
compensate for misalignment and absorb
vibratory movement of electrical equipment
and devices.

Made of flat extra flexible, tinned, pure copper


braid, with unplated, seamless, pure copper
ferrules formed into a rectangular shape on
each end.
D-41
Last two numbers in catalog number indicate
total length of braid in inches (e.g., BD12N or
BD12 is 12 long braid jumper).

Other lengths, plating and drilling are


available. Refer to factory or Section G
(Substation).

NUMBER OF
CATALOG BRAIDS IN APPROXIMATE AMP
NUMBER FERRULES C D E K L N T INDOOR OUTDOOR
BD12 2.50 1.25 .44 12
BD12N** 3.00 1.75 .56 12
BD18 2.50 1.25 .44 18
1 .94 .62 .13 190 225
BD18N** 3.00 1.75 .56 18
BD24 2.50 1.25 .44 24
BD24N** 3.00 1.75 .56 24
BE12 1.50 .44 12 .75
BE12N** 1.75 .56 12 .62
BE18 1.50 .44 18 .75
1 1.50 3.00 .17 340 405
BE18N** 1.75 .56 18 .62
BE24 1.50 .44 24 .75
BE24N** 1.75 .56 24 .62
BF12 1.50 .44 12 .75
BF12N** 1.75 .56 12 .62
BF18 1.50 .44 18 .75
1 1.19 3.00 .25 360 430
BF18N** 1.75 .56 18 .62
BF24 1.50 .44 24 .75
BF24N** 1.75 .56 24 .62
BG12 1.50 .44 12 .75
BG12N** 1.75 .56 12 .62
BG18 1.50 .44 18 .75
1 1.50 3.00 .25 415 495
BG18N** 1.75 .56 18 .62
BG24 1.50 .44 24 .75
BG24N** 1.75 .56 24 .62
* This rating may vary with ambient conditions, orientation of
the braid and other service conditions.
** Tongue drilled per (2) hole NEMA standard.
BURNDY
Grounding

FLEXIBLE COPPER
BRAID
(Continued)

TYPE B

NUMBER OF
CATALOG BRAIDS IN APPROXIMATE AMP
NUMBER FERRULES C D E K L N T INDOOR OUTDOOR
B2D12 2.50 1.25 .44 12 .62
.94 .25 380 455
B2D12N** 3.00 1.75 .56 12 .62
B2E12 3.00 1.50 .44 12 .75
1.62 .25 530 635
D-42 B2E12N** 3.00 1.75 .56 12 .62
2
B2F12 3.00 1.50 .44 12 .75
1.38 .38 600 720
B2F12N** 3.00 1.75 .56 12 .62
B2G12 3.00 1.50 .44 12 .75
1.50 .50 700 840
B2G12N** 3.00 1.75 .56 12 .62
B3D12 2.50 1.25 .44 12 .62
1.19 .25 470 560
B3D12N** 3.00 1.75 .56 12 .62
B3E12 3.00 1.50 .44 12 .75
1.64 .31 700 840
B3E12N** 3.00 1.75 .56 12 .62
3
B3F12 3.00 1.50 .44 12 .75
1.44 .56 820 980
B3F12N** 3.00 1.75 .56 12 .62
B3G12 3.00 1.50 .44 12 .75
1.69 .69 960 1150
B3G12N** 3.00 1.75 .56 12 .62
B4D12 2.50 1.25 .44 12 .62
1.19 .32 600 720
B4D12N** 3.00 1.75 .56 12 .62
B4E12 3.00 1.50 .44 12 .75
1.64 .36 850 1020
B4E12N** 3.00 1.75 .56 12 .62
4
B4F12 3.00 1.50 .44 12 .75
1.50 .78 1000 1200
B4F12N** 3.00 1.75 .56 12 .62
B4G12 3.00 1.50 .44 12 .75
1.69 .94 1200 1440
B4G12N** 3.00 1.75 .56 12 .62
* This rating may vary with ambient conditions, orientation of
the braid and other service conditions.
** Tongue drilled per (2) hole NEMA standard.
BURNDY
Grounding

TYPES GB, GBM


Type
GROUND CONNECTOR GB

For Copper Cable to Bar


Type
High copper alloy ground connector for Type Type GBM
joining a range of cable to 1/4 thick bar.* GB GBM
Type GB separates cable from bar, GBM
clamps cable directly on bar surface.
One-wrench installation. UL467 Listed. The
high copper alloy cast body and DURIUM™
bolts, nuts, and lockwashers make the GB
and GBM suitable for direct burial in concrete
or ground. D-43
H H W W
Catalog Number Type Type Type Type
Type GB Type GBM Conductor GB/GBL GBM J GB/GBL GBM
GB4C GBM4C 8 Sol. - 4 Str. 1-1/2 1-1/4 1-1/4
1-1/2 3/8
GB26 GBM26 4 Sol. - 2/0 Str. 1-1/2 1-1/2
+GBL30 4 Sol. - 300 2 7/8 0
GB29 GBM29 2/0 Sol. - 250 2 1/2 2 2
GB34 GBM34 300 - 500 3 2-1/4 2-3/8 2-3/8
+ GBL30 is not UL listed.
Add "GS" suffix for galvanized steel hardware.
* For other bar thicknesses see note at bottom of page D-44.

TYPES GC, GCM


Type
GROUND CONNECTOR GC

For Two Copper


Cables to Bar
Type Type Type
High copper alloy ground connector for GC GCM GCM
joining a wide range of two parallel cables to
1/4 thick bar.* Type GC separates cable from
bar, GCM clamps cable to bar surface.
One-wrench installation. UL467 Listed. The
high copper alloy cast body and DURIUM™
bolts, nuts, and lockwashers make the GC
and GCM suitable for direct burial in concrete H H W W
or ground. Catalog Number Type Type Type Type
Type GC Type GCM Conductor GC/GCL GCM J GC/GCL GCM
GC4C4C GCM4C 8 Sol. - 4 Str. 1-1/2 1-3/8 1
1-1/2 3/8
GC2626 GCM26 4 Sol. - 2/0 Str. 2 1-3/4 1-3/8
GCL30 GCM30 4 Str. - 300 2 — — 1 —
GC2929 GCM29 2/0 Sol. - 250 2-1/4 2 — 2-1/4 2
GC3434 GCM34 300 - 500 2-7/8 2-1/4 1/2 2-7/8 2-5/8
Smooth oval-shank bolts are available upon request for cable-
tray applications (example: GC30G3). Also refer to type GC-CT.
Add "GS" suffix for galavanized steel hardware.
* For other bar thicknesses see note at bottom of page D-44.
BURNDY
Grounding

TYPE GL
GROUND CONNECTOR
For Two Copper
Cables to Bar

High copper alloy ground connector for join-


ing a wide range of two parallel cables to 1/4
thick bar.* Two-bolt design, separates cable
from bar. One-wrench installation. UL467
Listed. The high copper alloy cast body and Catalog
DURIUM™ bolts, nuts, and lockwashers Number* Conductor H J W
make them suitable for direct burial in GL4C4C 8 Sol. - 4 Str. 1-1/2 1-3/8
D-44 3/8
concrete or ground. GL2626 4 Sol. - 2/0 Str. 2 1-3/4
GL2929 2/0 Sol. - 250 2-1/4 2-1/4
1/2
GL3434 300 - 500 2-7/8 2-7/8
* For other bar thicknesses see note at bottom of page.

TYPE GZ
GROUND CONNECTOR
For Copper Cable to Bar

High copper alloy ground connector for


joining a wide range of cable to 1/4 thick
bar*. Cable is gripped by curving it around the
clamping bolt in connector groove. UL467
Listed. The high copper alloy cast body and
DURIUM™ bolts, nuts, and lockwashers
make them suitable for direct burial in Catalog
concrete or ground. Number* Conductor H J W
GZ4C-38 1-1/2 3/8 1-1/8
GZ4C-12 8 Str. - 4 Str. 1-7/8 1/2
1-3/4
GZ4C-58 5/8
2
GZ26-38 3/8 1-5/8
GZ26-12 3 Str. - 2/0 Str. 2-1/8 1/2
1-3/4
GZ26-58 5/8
2-1/4
GZ29-38 3/8
GZ29-12 3/0 Str. - 250 2-3/8 1/2 2-1/4
GZ29-58 2-1/2 5/8

NOTE:
* The GB, GBM, GC, GCM, GL and GZ are all
used for joining a range of cable to bar. The
catalog numbers in each table accommodate the
indicated cable range and up to 1/4 thick bar.
Optional bolt lengths are available to accommo-
date up to 1 thick bar. For bar thicknesses from
1/4 to 1/2, add the suffix “T4” to the catalog
number in the table. For bar thicknesses from
1/2 to 1, add the suffix “T8” to the catalog
number in the table.
BURNDY
Grounding

TYPE GC-CT
CABLETRAY
GROUND CLAMP

This unique connector incorporates features


which are unmatched. Made of tin-plated cast
copper alloy, it accommodates either one or
two conductors, copper or aluminum cable. In
addition to a low profile head with a deep
Phillips recess, the galvanized steel bolt has
a ribbed neck which prevents rotation during
installation when installed in a .44 diameter
hole. When used on aluminum conductor, the D-45
cable must be scratch brushed and
PENETROX® A joint compound must be used
on cable and connector.

ACCOMMODATES COPPER OR
CATALOG ALUMINUM CONDUCTOR
NUMBER IN EITHER GROOVE B CF H J W
#6 Sol. (.162 Dia.) -
GC2525CT 1.12 .56 1.95 3/8” - 16 1.45
1/0 Str. (.372 Dia.)
#2 Sol. (.258 Dia.) -
GC2626CT 1.12 .56 1.95 3/8” - 16 1.70
2/0 Str. (.419 Dia.)
2/0 Str. (.414 Dia.) -
GC2929CT 1.12 .56 2.20 3/8” - 16 1.98
250 kcmil (.575 Dia.)
NOTE:
The bolt head is mounted on the inside wall of cabletray to avoid
damage to the cable insulation.
May be used with aluminum or galvanized steel cable tray.
BURNDY
Grounding

TYPE GIE-G 8 1⁄8

GROUND CONNECTOR
For Vehicle Grounding
Heavy Duty Construction
1.2
High-strength copper alloy ground clamps for MAX.
grounding gasoline trucks, tank cars, aircraft OPENING
and other vehicles where danger of explosion
due to static electricity exists. Corrosion resis- Replaceable Contact Grip Screws
tant and supplied with nonsparking,
Catalog Number Catalog Number Material Point Configuration
adjustable, replaceable contact grip screws.
GIE4CG3P5 Cone Point
Automatic safety release disconnects should GIE4CG3 Beryllium Copper
D-46 GIE4CG3P7 Cup Point
a vehicle unexpectedly move from the
GIE4CG4P5 Cone Point
grounded area. Accommodates 4 Str. flexible GIE4CG4 Stainless Steel
GIE4CG4P7 Cup Point
copper cable.

TYPE GIE-G
GROUND CONNECTOR

Accommodates flexible rubber sheath cable


ranging from #6 to #2 conductor.

Catalog Number: GIE2CG3


BURNDY
Grounding

RAIL CONNECTOR
Mechanical clamp connectors designed for
use in power, contact or running rail appli-
cations. Connectors are cast of a high
conductivity copper alloy, tin-plated, and
assembled with high-strength DURIUM™
hardware. Connectors designed for extended
service life.

D-47

Fig. 1 Fig. 2

Fig. 3 Fig. 4

Catalog Fig.
Number No. Accomodates B H HH L W
J278 1 100 LBS. A.R.E.A. RUNNING RAIL 1.81 1.88 1.72 7.50 .88
J279 1 75 or 90 LBS. RUNNING RAIL 1.81 1.71 1.55 7.50 .88
J280 1 150 LBS. CONTACT RAIL 2.12 2.08 1.92 7.00 1.25
J295 2 150 LBS. THIRD RAIL 2.62 3.50 3.50 7.75 3.00
150 LBS. NMC CONTACT RAIL and
RGC44G1* 3 1.75 2.82 2.25 10.00 1.75
(1) 800-1000 kcmil CU CABLE
115 LBS. CONTACT or RUNNING RAIL and
RGC39G1* 4 2.75 2.00 4.78 8.32 1.25
(1) 500-750 kcmil CU CABLE
* Tin-plated.
BURNDY
Grounding

TYPE QGFL
BARTAP
For Copper Cable to
Flat Bar or Pad

High copper alloy BARTAP for joining a range


of cable to bar or pad. One-wrench instal-
lation. DURIUM™ nut and lockwasher.
Catalog T
Number Conductor B H J (Max.) W
QGFL1CB1 1-7/8 1/4
D-48 10 Sol. - 1 Str. 1-1/8 1
QGFL1CB1T6 2-3/8 3/4
3/8
QGFL26B1 2-1/8 1/4
QGFL26B1T6 1-1/4 2-5/8 3/4
8 Sol. - 2/0 Str. 1-1/8
QGFL26B2* 1-1/2 1/4
QGFL26B2T6* 1-1/2 2-7/8 3/4
QGFL29B1* 2-5/8 1/4
6 Str. - 250 1-5/8 1-3/8
QGFL29B1T6* 3-1/8 3/4
QGFL31B1* 2-7/8 1/4
2 Sol. - 350 1-3/4 1-5/8
QGFL31B1T6* 3-1/4 3/4
QGFL34B1 3-1/8 1/4
1/0 Sol. - 500 2 1-3/4
QGFL34B1T6 3-5/8 3/4
1/2
QGFL39B1 3-1/4 1/4
350 - 750 1-3/4
QGFL39B1T6 3-5/8 3/4
QGFL44B1 3-3/8 1/4
750 - 1000 2-1/8
QGFL44B1T6 4-1/8 3/4
2-1/4
QGFL46B1 4 1/4
1000 - 1500 2-1/2
QGFL46B1T6 4-1/2 3/4
QGFL48B1 4-3/4 1/4
1500 - 2000 3
QGFL48B1T6 5-1/4 3/4

* Can be installed side by side or in line on NEMA drilled bar.

TYPE GA-H
GROUND CONNECTOR
For Copper Cable
to “H” Beam

High copper alloy ground connector for join-


ing a wide range of cable parallel to “H”
beams or square tube. Hardware is
made from DURIUM™ for superior corrosion CATALOG CONDUCTOR
protection.
NUMBER “H” BEAM CABLE H J W
GA25H26 1-7/8  1-7/8 - 2-1/2  2-1/2 4 Sol. - 2/0 Str. 4-3/4 3/8 4
BURNDY
Grounding

TYPE GRF
UNIGROUND® RAISED FLOOR
GROUNDING CONNECTOR

The BURNDY® Uniground® is a universal


grounding clamp, specifically designed for all
raised flooring systems. It can be installed on
round or square pedestals and can
accommodate one or two grounding wires to
make an efficient grid. The underfloor signal
reference grid provides the low impedance Features and Benefits
ground path that attenuates high frequency • One connector fits all applications. • Grounds all pedestals (round or square).
static and 60 Hz transient noise for cleaner ◊ Ease of specification and installation. Will handle up to 7/8 square and 1 round. D-49
data output. UL467 Listed. • Single bolt design. ◊ Ease of installation. One connector
◊ Ease of installation: does it all
◊ — No need to disassemble. • Serves 3 needs:
◊ — Single wrench installation. 1. Signal Reference Grid.
• Accepts 1 or 2 ground conductors. 2. Static Ground.
◊ Requires less connectors to install 3. Fault Current Ground.
signal reference grid. ◊ Uniground solves all possible grounding
• Tin plated cast bronze construction. problems found in computer applications
◊ Resists corrosion and provides extended today.
life ground connection.

CATALOG NUMBER OF CONDUCTOR PEDESTAL TYPE


NUMBER CONDUCTORS SIZE SOL. & STR. ROUND SQUARE B H J W
GRF4C-3 1 or 2 #8 - #2 Up to 1 Up to 7/8 1.96 3.14 3/8 1.76
GRF4C-4 1 or 2 #8 - #2 Up to 3/4 Up to 5/8 1.79 3.13 3/8 1.40
BURNDY
Grounding

TYPES GP-G1, GP-RT


RAISED FLOOR
GROUNDING CLAMPS

High copper alloy ground connector for raised


floor computer grounding applications. These
connectors can be installed on round and
square pedestal applications and will accom- GP1726RT
modate one or two grounding wires to make
an efficient grid. The underfloor signal refer-
ence grid provides the low impedance ground
Features and Benefits
path that attenuates high frequency static and • Accepts 1 or 2 Ground Conductors
D-50 60 Hz transient noise for cleaner data output. ◊ Requires less connectors to install signal
UL467 Listed. reference grid.
In addition we offer the GP1726RT, which is • Made of copper alloy.
especially designed for penetrating epoxy • Durium U-Bolts, nuts and lockwashers.
paint on pedestals. This patented connector ◊ Provides a low impedance ground path
offers a low impedance, time saving connec- for maximum performance.
tion between conductors and the Pedestal. • Grounds all pedestals (round or square).
• Will handle from 3⁄4 to 1 round or square.
◊ Ease of installation.
• Serves 3 needs.
1. Signal Reference Grid.
2. Static Ground.
3. Fault Current Ground.
◊ Connectors solves all possible
grounding problems found in computer
applications today.

CATALOG NUMBER OF CONDUCTOR PEDESTAL TYPE


NUMBER CONDUCTORS SIZE SOL. & STR. ROUND OR SQUARE B J L W
GP654CG1 1 or 2 #8 Sol. - 4 Str. 3/4 - 1 Round 1.5 3/8 1.31 2.38
GP64526G1 1 or 2 #4 Sol. - 2/0 Str. 3/4 - 7/8 Square 1.5 3/8 1.69 2.38
GP1526G1 1 or 2 #4 Sol. - 2/0 Str. 1-1/4 Round 1.75 3/8 1.69 2.62
GP1726RT 1 or 2 #6 Sol. - 2/0 Str. 2 Round 2.12 3/8 1.50 3.22

You might also like