Bur Grounding Cat PDF
Bur Grounding Cat PDF
Grounding
TABLE OF CONTENTS
HYGROUND™ IRREVERSIBLE COMPRESSION GROUNDING
AND INSTALLATION TOOLING
HYGROUND™ Features
and Benefits .....................D-3 - D-4 Type YGIB .....................D-18 - D-19
D-1
Type YGLR-C ..............................D-6 Types YGT & YTTAG ................D-21
TABLE OF CONTENTS
MECHANICAL GROUNDING (Continued)
D-2
Type GK ....................................D-32 Type GZ ....................................D-44
THE HYGROUND™
IRREVERSIBLE
COMPRESSION
SYSTEM
BURNDY® has developed an irreversible
compression ground system which meets the
most stringent safety and performance
requirements, including those of OSHA and
nuclear power plant design. Performance
excellence and long life expectancy are the
system’s basic design guidelines. It is a com-
plete system which consists of connectors for
grid cross connections, taps, splices, cable to D-3
ground rod, ground plates and terminations.
TYPE YGL-C
HYGRID CROSS CONNECTOR
ORDERING INFORMATION
CATALOG CABLE TO CABLE CABLE TO GROUND ROD TO REBAR
NUMBER ELEMENT “A” ELEMENT “B” ELEMENT “A” ELEMENT “B” ELEMENT “A”
#6 SOL. (.162) – #2 STR. (.292)
YGL2C2
{59500} – {59500} #6 SOL. (.162) – #2 STR. (.292)
#1 STR. (.332) – 250 kcmil (.575) {59500} – {59500}
YGL29C2 #6 SOL. (.162) – #2 STR. (.292) 3/8" – 1/2"
{98500} – {131500}
1/2" – 5/8" Rod
#2 STR. (.292) – 250 kcmil (.575) #2 STR. (.292) – 250 kcmil (.575)
YGL29C29 #2 STR. (.292) – 250 kcmil (.575) #3 – 4 Rebar
{65500} – {131500} {65500} – {131500}
YGL34C2 #6 SOL. (.162) – #2 STR. (.292) #6 SOL. (.162) – #2 STR. (.292)
5/8" – 3/4"
YGL34C29 250 kcmil (.575) – 500 kcmil (.813) #2 STR. (.292) – 250 kcmil (.575) 5/8" – 3/4" Rod #2 STR. (.292) – 250 kcmil (.575)
#5 – 6 Rebar
YGL34C34 250 kcmil (.575) – 500 kcmil (.813) 250 kcmil (.575) – 500 kcmil (.813)
Dimensions in brackets { } represent lightning
protection conductors.
TYPE YGLR-C
GRIDLOK Element A
High Strength
Irreversible
Compression Ground Rod to Element B
Grid Connector
Ground grid connector for a wide range of
copper cable to ground rod. Provides high
torque strength on ground rod. UL467 MEETS ALL
D-6
Listed. Acceptable for direct burial in earth
and concrete. Prefilled with PENETROX®
compound and strip sealed.
IEEE
837 REQUIREMENTS
NOTES:
1. Before crimping, both connector elements can be 5. Ground rod must be pre-crimped with die GROUND ROD
turned on rod diameter 'D' to any desired position. U2CABT (Index No. 348) when crimping the
2. Grooves are filled with PENETROX®. ground rod element (Element “B”) with the PU998 DIA. PRECRIMP DIES
dies in the Y750, Y35, Y39, Y45, or Y46 tools. Pre- 1/2 UPRECRIMP 12
3. Suitable for direct burial in earth or concrete.
crimping is not required when the S1012, P1011 5/8 UPRECRIMP 58 U2CABT
4. The catalog numbers shown are for unplated or U1011 dies are used. See precrimp die chart.
copper connectors for use on copper clad or 3/4 UPRECRIMP 34
6. Where a 'U' or 'PU' die is recommended with the
stainless steel ground rod. To order electro-tin
Y45 HYPRESS™, a PT6515 adapter must be When attaching connector to ground rod, ground
plated connectors for use on galvanized steel
used. rod must be embossed with appropriate PRE-
ground rod add suffix "TN" to the catalog number,
only if the Figure 8 connector (Element “B”) is tin 7. Where a 'U' or 'PU' die is recommended with the CRIMP™ die. For connections that must meet IEEE
plated, the Figure 6 connector (Element “A”) is Y46 HYPRESS™, a PUADP-1 adapter must be 837 requirements UPRECRIMP™ - type PRE crimp
unplated. Note: The ground rod hole diameter is used. dies must be used for maximum clamping retention.
larger for galvanized steel ground rod in the tin
plated connector. 8. Dimensions in bracket [ ] are in millimeters.
9. Die "1011" appears on Element "B" of the
connector only.
BURNDY
Grounding
TYPE YGHP-C
HYTAP™ CONNECTOR
INSTALLATION DATA
➄ DIE Y750/Y35 ➂ ➃
CATALOG FIG. ACCOMMODATES CABLE TO REBAR INDEX Y39 Y45 Y46 NO. OF
NUMBER NO. RUN TAP RUN TAP B NO. HYPRESS™ PAT750-18V HYPRESS™ HYPRESS™ CRIMPS
#6 SOL. (0.162) {59500} – ➀ #6 SOL. (0.162) {#2 STR.} –
YGHP2C2 1 — —
#2 STR. (0.292) {59500} #2 STR. (0.292) {#2 STR.}
0 U0 U0 U0 U0 1
#6 SOL. (0.162) – #8 SIK. (0.128) –
YGHP2C6W6W➇ 2 — —
#2 STR. (0.292) 6 STR. (0.184) QTY. 2
#8 SOL. (0.128) –
YGHP29C6W6W➇ 2 #8 SOL. – 6 STR.
6 STR. (0.184) QTY. 2 #3 REBAR
#4 SOL. (0.204) {#4 SOL.} – 3/8
YGHP29C2 1 1/0 STR. (0.372) {98500} – #2 STR.
#2 STR. (0.292) {#2 STR.}
250 kcmil (0.575) {131500} THRU 997 U997 ➆ U997P U997 U997 1
1/0 STR. (0.372) {98500} – .75
YGHP29C26 1 1/2" – 5/8" ROD 1/0 STR. – 2/0 STR.
2/0 STR. (0.419) {98500} 1/2 [19]
3/0 STR. (0.470) {131500} – #4 REBAR
YGHP29C29 ➁ 1 3/0 STR. – 250 kcmil
250 kcmil (0.575) {211500}
#4 SOL. (0.204) –
YGHP34C2 ➅ 1 #5 REBAR —
#2 STR. (0.292)
250 kcmil (0.575) {250 kcmil} – 5/8
1/0 STR. (0.372) {98500} – PU998 or PU998 or
YGHP34C26 ➅ 1 500 kcmil (0.813) {500 kcmil} 1/0 STR. – 2/0 STR. 998 PU998 PU998 1
2/0 STR. (0.419) {98500} S998 P998
5/8" – 3/4" ROD THRU
3/0 STR. (0.470) {131500} –
YGHP34C29 ➅ 1 3/0 STR. – 250 kcmil
250 kcmil (0.575) {211500}
3/4
250 kcmil (0.575) –
350 kcmil (0.681) – 1.10
YGHP34C34 ➅ 1 500 kcmil (0.813) #6 REBAR 350 kcmil – 500 kcmil 1011 ➅U1011 U1011 S1011 P1011 3
500 kcmil (0.843) [28]
5/8" – 3/4" ROD
Dimensions in brackets { } represent lightning protection
conductors.
PENETROX-E
High Strength
Copper Irreversible
Compression
DIE INDEX
Ground Rod Tap AND CONDUCTOR
INFORMATION TAP (A)
Connector
PATENTED
Type YGHP-C irreversible compression
ground tap figure 6 can be used as a ground Features and Benefits
D-8 rod tap connector for both continuous run and
tapping applications. An open groove allows • Tap (A) accepts a continuous run on • Prefilled with PENETROX® and individually
ground rod to be connected to a continuous tap conductor sealed in clear polyethylene sheet.
run or tap. The second groove is for a tap Tap (B) accepts a tap conductor only. ◊ Ensures the electrical integrity of the
only. Prefilled with PENETROX-E® and strip ◊ One connector style can be used for finished connection by inhibiting moisture
sealed. UL467 Listed for direct burial in earth many applications, reducing number and contaminates from entering the
or concrete. of connectors in inventory. contact area. Maintains long-term
• Material is high conductivity wrought high-conductivity.
MEETS ALL copper extrusion, identical material to • UL467 Listed.
IEEE
837 REQUIREMENTS
the conductor.
◊ High-conductivity copper minimizes
resistance and voltage drop. Eliminates
◊ May be used in direct burial or concrete
embedded grounding applications.
Provides quality assurance to recognized
the possibility of corrosion due to industry NEC standards from an
dissimiliar metals. independent party.
• System engineered tooling. • “Third Hand” constrains conductors while
◊ The tooling recommendation has been installer completes crimp. Included with
designed to ensure a reliable, depend- each connector.
able connection every time. ◊ Simplifies installation, reducing
• The die index number is embossed on installed cost.
conductor after completion of crimp.
◊ Faciliates speedy inspection of installed
connectors to insure consistently reliable
and dependable connections.
▲ INSTALLATION TOOLING
Y35/Y750 Y46 •
CATALOG GROUND DIMENSIONS DIE NO. OF DIE NO. OF DIE
NUMBER ROD DIA. ■ TAP CONDUCTOR + H B W NO. CRIMPS NO. CRIMPS INDEX
YGHP58C2W-2 #2 Sol. - #6 Sol. Copper
1/2 - 5/8 (1) Continuous run and (1) Tap or 1.90 .75 .94 U997 (1) U997 (1) 997
YGHP58C2W-2TN
up to (2) taps may be connected.
NOTE: A 12" bend radius is recommended for the conductor. ■ Ground rod must be precrimped with die U2CABT (Index
• Use PUADP-1 with ‘U’-dies in Y46. No. 348).
▲ See tooling section in Master Catalog for complete tool and For even greater rotational resistance use U-PRECRIMP
die listing. die.
+ Either tap position may be left void when fewer than (2) For Galvanized Steel Rods order YGHP58C2W-2TN.
conductors are used.
BURNDY
Grounding
TYPE YGHC-C
HYTAP™ CONNECTOR
INSTALLATION DATA
COMMERCIAL COPPER STRANDED COPPER DIE Y750/Y35 ➀ ➁
CATALOG CABLE RANGE CABLE RANGE INDEX Y39 Y45 Y46 NO. OF
NUMBER RUN TAP RUN TAP A B NO. HYPRESS™ HYPRESS™ HYPRESS™ CRIMPS
#6 SOL. (0.162) #6 SOL. (0.162) 10 mm2 (4.12 mm) 10 mm2 (4.12 mm) 1.16 0.75
YGHC2C2 C U-C U-C U-C 1
#2 STR. (0.292) #2 STR. (0.292) 35 mm2 (7.62 mm) 35 mm2 (7.62 mm) [30] [19]
1 STR. (0.328) #6 SOL. (0.162)
35 mm2 (7.62 mm) 10 mm2 (4.12 mm)
{98500} {#6 SOL.} 1.41 0.75
YGHC26C2 0 U-O U-O U-O 1
2/0 STR. (0.419) #2 STR. (0.292) [36] [19]
70 mm2 (10.9 mm) 35 mm2 (7.62 mm)
{98500} {#2 STR.}
1 STR. (0.328) 1 STR. (0.328)
35 mm2 (7.62 mm) 35 mm2 (7.62 mm)
{98500} {98500} 1.54 0.75
YGHC26C26 0 U-O U-O U-O 1
2/0 STR. (0.419) 2/0 STR. (0.419) [39] [19]
70 mm2 (10.9 mm) 70 mm2 (10.9 mm)
{98500} {98500}
3/0 STR. (0.470) 6 SOL. (0.419)
95 mm2 (12.5 mm) 10 mm2 (4.12 mm)
{3/0 STR.} {59500} 1.97 0.75
YGHC29C26 997 U997 U997 U997 1
250 kcmil (0.575) 2/0 STR. (0.419) [50] [19]
120 mm2 (14.4 mm) 70 mm2 (10.9 mm)
{250 kcmil} {98500}
3/0 STR. (0.470) 3/0 STR. (0.470) 95 mm2 (12.5 mm) 95 mm2 (12.5 mm) 2.06 0.88
YGHC29C29 997 U997 U997 U997 1
250 kcmil (0.575) 250 kcmil (0.575) 120 mm2 (14.4 mm) 120 mm2 (14.4 mm) [52] [22]
300 kcmil (0.630) #6 SOL. (0.162)
150 mm2 (16 mm) 10 mm2 (4.12 mm)
{300 kcmil} {59500} 2.42 0.88
YGHC34C26 ➅ 1011 U1011 S1011 P1011 2
500 kcmil (0.813) 2/0 STR. (0.419) [62] [22]
240 mm2 (20.35 mm) 70 mm2 (10.9 mm)
{500 kcmil} {98500}
300 kcmil (0.630) 3/0 STR. (0.470) 150 mm2 (16 mm) 95 mm2 (12.5 mm) 2.67 0.88
YGHC34C29 ➅ 1011 U1011 S1011 P1011 2
500 kcmil (0.813) 250 kcmil (0.575) 240 mm2 (20.35 mm) 120 mm2 (14.4 mm) [66] [22]
300 kcmil (0.630) 300 kcmil (0.630) 150 mm2 (16 mm) 150 mm2 (16 mm) 2.91 1.1
YGHC34C34 ➅ 1011 U1011 S1011 P1011 3
500 kcmil (0.813) 500 kcmil (0.813) 240 mm2 (20.35 mm) 240 mm2 (20.35 mm) [74] [28]
Dimensions in brackets { } represent lightning protection conductors.
NOTES:
➀ Where a "U" or "PU" die is recommended with 5. In referencing connectors without PENETROX®
the Y45 HYPRESS™, PT6515 adapter must be oxide inhibitor add suffix "NP" to the end of the
used. Catalog Number.
➁ Where a "U" or "PU" die is recommended with ➅ These connectors can only be installed using
the Y46 HYPRESS™, a PUADP-1 adapter must the Y750, Y45 or Y46 HYPRESS™ with the
be used. recommended dies.
3. Listed under UL486A for copper wire connec- These connectors cannot be installed with the
tors Y35 and Y39 HYPRESS™.
4. Dimensions in brackets [ ] are in millimeters.
BURNDY
Grounding
TYPE YGC
COPPER CRIMPIT™
COPPER
D-10
CATALOG CONDUCTOR
NUMBER RUN TAP H L INDEX OUR840 MD6/MD7 CRIMPS
#8 SOL. #8 SOL.
YGC8C8 .46 .52 162 W162 W162 2
#8 STR. #8 STR.
#6 SOL. #8 SOL.
YGC6C8 .73 .62 BG XBG WBG 2
#6 STR. #8 STR.
#6 SOL. #6 SOL.
YGC6C6 .76 .62 BG XBG WBG 2
#6 STR. #6 STR.
BURNDY
Grounding
TYPE YSHG
HIGH STRENGTH
COPPER IRREVERSIBLE
COMPRESSION
Double H-Tap Connector
TOOLING INDEX
CATALOG FIG. CONDUCTOR SIZES (*NUMBER OF CRIMPS) EMBOSS- W T L
NUMBER NO. MAIN TAP 1 TAP 2 TAP 3 Y750 * Y46 * MENT .06 .04 .06
#9 & #8 REBAR, 1 [25] GROUND 3.22 1.70 2.44
YSHG4429 250 - 2 PYFR 2 K-R
3 ROD [82] [43] [62]
1 [25] Cu CLAD GROUND ROD 2.97 1.50 2.94
* YSHG3939 500 - 350 PYFR 2 K-R
1 500 kcmil COPPER [75] [38] [75]
#6 REBAR, 1 [25] Cu CLAD
2.97 1.50 2.34
* YSHG3931 2 GROUND ROD, 3/4 GROUND ROD 4/0 - 1/0 1-6 2 - 14 PYFR 2 K-R
[75] [38] [59]
500 - 350 kcmil COPPER
#6 REBAR, 3/4 [19] GROUND ROD P1104 2 2.43 1.15 2.44
YSHG3434 400 - 4/0 U1104 4 1104
1 400 - 250 kcmil COPPER †U1104 4 [62] [29] [62]
#6 REBAR, 3/4 [19] GROUND ROD P1104 2 2.23 1.31 2.44
YSHG3429 3/0 - 1/0 1-4 8 - 14 U1104 4 1104
2 400 - 4/0 kcmil COPPER †U1104 4 [57] [33] [62]
TYPE YGHR-C
HYTAIL™
High Strength
Irreversible
Compression Ground Rod Tap
Connectors
CATALOG COMMERCIAL COPPER NOMINAL GROUND INSTALLATION TOOLS, DIE SET CAT. NO. (NUMBER OF CRIMPS)
NUMBER CABLE RANGE ROD DIA. Y750/Y35/Y39 ① Y45 HYPRESS ① Y46 HYPRESS ①
YGHR26C12 1/2 [12.7] S1012 (2)
YGHR26C58 #2 STR. (.292 DIA.) 5/8 [15.9] ➃
YGHR26C34 thru 3/4 [19.0] PU998 (1) ②
2/0 STR. (.419 DIA.) S1011 (2) S1012 (2)
YGHR26C100* 1 [25.4]
PU998 (1)
YGHR29C12 1/2 [12.7] U1011 (2) S1012 (2) P1011 (2)
YGHR29C58 #4/0 STR. (.528 DIA.) 5/8 [15.9] ➃ ➃ ➃
YGHR29C34 thru 3/4 [19.0] PU998 (1) PU998 (1) ② PU998 (1)
250 kcmil (.575 DIA.) S1011 (2) S1012 (2) ③
YGHR29C100* 1 [25.4]
➃ PU998 (1)
YGHR34C58 300 kcmil (.630 DIA.) 5/8 [15.9] S1012 (2)
➃
YGHR34C34* thru 3/4 [19.0] PU998 (1) ②
YGHR34C100* 500 kcmil (.813 DIA.) 1 [25.4] S1011 (2) P1011 (2)
TYPE YGHR-C
HYTAIL™
High Strength
Irreversible
Compression Ground Rod Tap
Connectors
TAP RUN
TAP RUN AND
INSTALLATION TOOLING
Y35/Y750** Y46*
CATALOG GROUND ROD DIE NO. OF DIE NO. OF DIE
NUMBER+ DIAMETER • TAP CONDUCTOR ▲ NO. CRIMPS NO. CRIMPS INDEX
PU998† (1)
PU998† (1)
#2 Sol. Copper 1, 2, or 3 U1011 (2) 998 or
YGHR58C2W-3 5/8
may be connected P998 (1) 1011
U1011 (2)
P1011 (2)
• Contact BURNDY® for other ground rod diameters. † Ground rod must be precrimped with die U2CABT (Index
* PU998 and U1011 die sets require PUADP-1 adapter for No. 348) when PU998 die set is used in the Y35, Y750 or
use in the Y46 HYPRESS™. Y46
Tap positions may be left void when fewer than (3) conduc- ▲ HYPRESS™ tools. For even greater mechanical resistance
tors are used. use UPRECRIMP™ 58 dies.
+ To order electro-tin plated connector for use on galvanized ** The Y750 utilizes PU dies and the U1011 die. The Y35 only
steel ground rod add suffix -“TN” to the catalog number. uses PU998 die set.
NOTE: The ground rod hole diameter is larger for galvanized NOTE: A 12" bend radius is recommended for the conductor.
steel ground rod in the tin plated connector.
BURNDY
Grounding
TYPE YGHA
HYLUG™
Heavy Duty Irreversible
Compression Terminals
Heavy duty HYLUG™ irreversible compres-
sion terminals designed not only to carry
short circuit load, but to also withstand high
mechanical stress. Each conductor element
has an inspection probe hole to insure proper MEETS ALL
cable insertion. UL467 Listed. Acceptable for
direct burial in earth or concrete. UL486A
®
D-14 Listed. Prefilled with PENETROX compound
IEEE
837 REQUIREMENTS
and strip sealed.
TYPE YGHS
HYLINK™
Heavy Duty Irreversible
Compression Terminals
KNURLED
RINGS
Heavy duty HYLINK™ ground splice
INSPECTION PROBE HOLES
designed not only to carry short circuit load, FOR CABLE STOP
but to also withstand high mechanical stress.
Each conductor element has an inspection
probe hole and a center stop to ensure MEETS ALL
proper cable insertion. UL467 Listed.
Acceptable for direct burial in earth or
concrete. UL486A Listed. Prefilled with
IEEE
837 REQUIREMENTS
PENETROX® compound and strip sealed.
INSTALLATION TOOLS, DIE SET CAT. NO.,
CATALOG AND (NUMBER OF CRIMPS)
NUMBER COPPER CONDUCTOR SIZE HYPRESS™ Y35/Y39/Y45 ① /Y46 ② /Y750 B L
YGHS2C 2 str. U1CRT (1) .75 1.73
YGHS25 1/0 str. U27RT (1) .83 1.89
YGHS26 2/0 str. U28RT (1) .83 1.89
YGHS27 3/0 str. U29RT (1) 1.18 2.59
YGHS28 4/0 str. U30RT (2) 1.18 2.59
YGHS29 250 kcmil U31RT (2) 1.18 2.59
YGHS31 350 kcmil U34RT (2) 1.18 2.59
YGHS34 500 kcmil U36RT (3) 1.48 3.19
① Where a “U” or “PU” die is recommended with the Y45
HYPRESS™, a PT6515 adapter must be used.
➁ Where a “U” or “PU” die is recommended with the Y46
HYPRESS™, a PUADP-1 adapter must be used.
BURNDY
Grounding
TYPE YGA
HYLUG™
Grounding Irreversible
Compression Terminals
Fig. 1 Fig. 2
① Where a “U” or “PU” die is recommended with the Y45 ➁ Where a “U” or “PU” die is recommended with the Y46
HYPRESS™, a PT6515 adapter must be used. HYPRESS™, a PUADP-1 adapter must be used.
BURNDY
Grounding
TYPE YGS
HYLINK™
Grounding Irreversible
Compression Splices
TYPE YGF
GROUNDING PLATE
Fig. 2
CATALOG
NUMBER FIG. NO. C D H L T Y
YGF29-2N 1 2.00 3.25 3.62 5.78 1.31 2.00
YGF29-4N 2 3.25 3.25 3.62 5.78 1.31 2.00
YGF34-2N 1 2.00 3.25 4.62 5.40 1.31 2.19
YGF34-4N 2 3.75 3.75 4.62 5.90 1.31 2.19
NOTES:
① This tapped hole may be used to position the grounding ① 3/8-16 thread with 1.00 EFF. Thread is standard. If other ② Plastic plugs are provided to keep dirt out of the threaded
plate on a threaded rod prior to placement of the concrete. thread is required, add appropriate Code No. to Catalog No. holes until the attachment of grounding terminals.
for desired thread.
-50 (1/2 -13, .94 EFF. Thread), -62 (5/8 -11, .94 EFF.
Thread) and -75 (3/4 -10, .81 EFF. Thread)
Example: YGF34-4N-50 is YGF34-4N with 1/2 -13 Thread
INSTALLATION TOOLS,
DIE SET CAT. NO., AND
(NUMBER OF CRIMPS)
CATALOG COPPER TAPPED HOLES HYPRESS™
NUMBER CONDUCTOR RANGE SIZE HOLE CENTERS Y750/Y35/Y39 Y45 ① Y46 ②
YGF29-2N 2 - 250 kcmil 1/2 - 13 1-3/4 U997 (1) U997 (1) U997 (1)
YGF29-4N 2 - 250 kcmil 1/2 - 13 1-3/4 U997 (1) U997 (1) U997 (1)
YGF34-2N* 250 - 500 kcmil 1/2 - 13 1-3/4 U1011 (3) S1011 (2) P1011 (2)
YGF34-4N* 250 - 500 kcmil 1/2 - 13 1-3/4 U1011 (3) S1011 (2) P1011 (2)
ORDERING INFORMATION
① Where a “U” or “PU” die is recommended ➁ Where a “U” or “PU” die is recommended * These connectors can only be installed
with the Y45 HYPRESS™, a PT6515 with the Y46 HYPRESS™, a PUADP-1 using the Y750, Y45 or Y46 HYPRESS™
adapter must be used. adapter must be used. with recommended dies. These connec-
tors CAN NOT be installed with the Y35 or
Y39 HYPRESS™.
BURNDY
Grounding
GROUNDLINK™ CONNECTOR
IEEE
837 REQUIREMENTS
Fig. 2 TERMINAL
“T” REF MAXIMUM
TERMINAL PAD MOUNTING HARDWARE
THICKNESS CATALOG NUMBER “T”
TMHG-42 .42
TMHG-92 .92
NOTE: Use TMHG-D92 to double stack lugs.
2 HOLE NEMA
SPACING WIDE FLANGE BEAMS
(FLANGE PARALLEL) USE YGIBW
NOTES:
1. Terminal conector to be ordered separately. When I-beam ➃ Dimensions shown reflect the minimum dimensions
connector is used with type "YGHA" terminal, the connec- required on a beam to properly install the I-beam
tion meets IEEE 837-1989 requirements. YGA-2N, YA-2N connector.
and other BURNDY® 2-hole NEMA copper terminals are
5. To correctly determine the appropriate YGIB connector to
suitable.
use based on flange thickness, order either
2. Order "TMHG" Terminal Mounting Hardware Kit separate- YGIBGAUGE1 or YGIBKIT1 (KIT1 contains wiremike).
ly. Kit consists of 2 studs, 2 flat washers, 2 lockwashers
and 2 hex nuts.
3. Using the 1/4 hex key wrench, screw the stud into the
connector until stud bottoms out in connector. Install a
"YGHA" terminal, flat washer, lockwasher and hex nut
onto stud. Tighten and torque to 480 pound-inches.
BURNDY
Grounding
TYPE YGIB
(Continued)
GROUNDLINK™ CONNECTOR
COPPER iBEAM
CONDUCTOR FIG. FLANGE SUGGESTED TERMINALS
RANGE CATALOG NUMBER NO. “L” “J” THICKNESS COPPER CONDUCTOR TERMINAL “T” REF.
#2 STR. AWG YGHA2C-2N .26
YGIBS28-338-2N 1 3.00
1/0 STR. AWG YGHA25-2N .19
2 - 4/0 AWG .250
2/0 STR. AWG YGHA26-2N .26
YGIBW28-338-2M 2 3.00 to
4/0 STR. AWG YGHA28-2N .30
.338
YGIBS34-338-2N 1 250 kcmil YGHA29-2N .34 D-19
250 - 500 kcmil 6.00
YGIBW34-338-2N 2 500 kcmil YGHA34-2N .40
#2 STR. AWG YGHA2C-2N .26
YGIBS28-400-2N 1 3.00
1/0 STR. AWG YGHA25-2N .19
2 - 4/0 AWG .338
2/0 STR. AWG YGHA26-2N .26
YGIBW28-400-2N 2 3.00 to
4/0 STR. AWG YGHA28-2N .30
.400
YGIBS34-400-2N 1 250 kcmil YGHA29-2N .34
250 - 500 kcmil 6.00
YGIBW34-400-2N 2 500 kcmil YGHA34-2N .40
#2 STR. AWG YGHA2C-2N .26
YGIBS28-462-2N 1 3.00
1/0 STR. AWG YGHA25-2N .19
.400
2 - 4/0 AWG 2/0 STR. AWG YGHA26-2N .26
YGIBW28-462-2N 2 3.00 to
4/0 STR. AWG YGHA28-2N .30
.462
YGIBS34-462-2N 1 250 kcmil YGHA29-2N .34
250 - 500 kcmil 6.00
YGIBW34-462-2N 2 500 kcmil YGHA34-2N .40
1/2 - 13
#2 STR. AWG YGHA2C-2N .26
YGIBS28-550-2N 1 3.00
1/0 STR. AWG YGHA25-2N .19
2 - 4/0 AWG 4.62
2/0 STR. AWG YGHA26-2N .26
YGIBW28-550-2N 2 3.00 to
4/0 STR. AWG YGHA28-2N .30
.550
YGIBS34-550-2N 1 250 kcmil YGHA29-2N .34
250 - 500 kcmil 6.00
YGIBW34-550-2N 2 500 kcmil YGHA34-2N .40
#2 STR AWG YGHA2C-2N .26
YGIBS28-613-2N 1 3.00
1/0 STR. AWG YGHA25-2N .19
2 - 4/0 AWG .550
2/0 STR. AWG YGHA26-2N .26
YGIBW28-613-2N 2 3.00 to
4/0 STR. AWG YGHA28-2N .30
.613
YGIBS34-613-2N 1 250 kcmil YGHA29-2N .34
250 - 500 kcmil 6.00
YGIBW34-613-2N 2 500 kcmil YGHA34-2N .40
#2 STR. AWG YGHA2C-2N .26
YGIBS28-675-2N 1 3.00
1/0 STR. AWG YGHA25-2N .19
2 - 4/0 AWG .613
2/0 STR. AWG YGHA26-2N .26
YGIBW28-675-2N 2 3.00 to
4/0 STR. AWG YGHA28-2N .30
.675
YGIBS34-675-2N 1 250 kcmil YGHA29-2N .34
250 - 500 kcmil 6.00
YGIBW34-675-2N 2 500 kcmil YGHA34-2N .40
BURNDY
Grounding
TYPE GSTUD-HY
VERSITAIL™
Structural Steel Grounding
Connector
INSTALLATION
ELECTRICAL
EQUIVALENT
NOM. DIMENSIONS COPPER
CATALOG ROD A B L T CONDUCTOR SIZE
NUMBER SIZE IN. [MM] IN. [MM] IN. [MM] IN. [MM] (AWG.)*
GSTUD14HY 1/4 .25 [6.3] .26 [6.6] 4.81 [122.2] .19 [4.8] #6
GSTUD38HY 3/8 .38 [9.7] .39 [9.9] 5.81 [147.6] .25 [6.4] #3
GSTUD916HY 5/8 .56 [14.2] .57 [14.5] 5.68 [144.3] .38 [9.7] 1/0
GSTUD34HY 3/4 .75 [19.0] .76 [19.3] 5.81 [147.6] .51 [13.0] 4/0
* This is the equivalent rating for continuous service. Larger
conductors may be connected using both compression and
bolted connectors in potential ground fault applications.
BURNDY
Grounding
TYPES YGT & YTTAG Type YGT Static Type YTTAG Combination
Grounding Receptacle Static Grounding Receptacle
with Cover and Aircraft Tie Down Bar
STATIC GROUNDING
RECEPTACLE
D-21
Fig. 1 Fig. 2
NOTES:
1. Ground rod must be pre-crimped with U2CABT die set when
PU998 die is used or for even higher mechanical resistance
use special UPRECRIMP™ dies on ground rods.
2. Pre-crimping of ground is not necessary when P1011 die is
used. Install YGHR or YGLR on hub Y. Hub Z is inserted into
1/2" rigid conduit. The conduit is driven into earth to provide
support and provide correct level of receptacle prior to
cement pour.
BURNDY
Grounding
TYPE YG-B
BUS BAR CONNECTOR
MECHANICAL
GROUNDING
CONNECTORS
More than 60 years of technological innova- problem that this diversified line cannot help high copper alloys are used in their manufac-
tion has made BURNDY® mechanical solve. ture, ensuring top performance under the
grounding connectors one of the most widely most extreme environmental conditions.
All BURNDY® mechanical grounding connec-
used, highly respected lines in the industry. tors have been designed for easy installation UL467 Listed for direct burial applications in
There is virtually no grounding application and for outstanding durability. Only the finest earth or concrete.
KC K2C
TYPES KC22J12T13,
EQC632C
TRANSFORMER GROUND
CONNECTORS
.6
For Copper
Stud Size = 1⁄2” - 13 Type EQC632C Type KC22J12T13
Fits all standard EEI NEMA distribution
transformers as a tank grounding terminal.
CATALOG NUMBER RANGES
KC22J12T13 8 Sol. - 2 Sol.
KC26 2 Sol. - 2/0 Str.
D-24 KC34J12T13 3/0 - 500 Str.
EQC632C 8 Sol. - 2 Str.
Both, one-wrench installation.
BURNDY
Grounding
TYPE KS-DB
SERVIT™
For Copper
D-25
TYPE GKA
For Copper
TYPE KPB
For Copper
CATALOG
NUMBER RANGE STUD HOLE
KPB4CG1 #10 - #4 CU #10 1
1. To be assembled with TMH322 stainless steel hardware kit.
Ordered separately.
TYPE GAR
FENCE POST GROUNDING
CONNECTOR
For Parallel or 90°
Copper Cable
Connection
To Rod or Pipe with
the Same Connector
High copper alloy ground connector for join-
ing a range of cable, parallel or at right angles D-27
to rod or tube. Especially good for fence
posts. High copper alloy cast body with
DURIUM™ U-bolts, nuts and lockwashers,
permit entire connection to be buried in
ground or concrete without danger of
corrosion.
• One-wrench installation.
• UL467 Listed.
• Acceptable for direct burial.
Catalog Conductor
Number Tube I.P.S. Rod Cable H J W
GAR114C 8 Sol. - 4 Str.
GAR1126 1/4 1/2 4 Sol. - 2/0 Str. 2-1/2 1-7/8
GAR1129 2/0 Sol. - 250
3/8
GAR644C 8 Sol. - 4 Str.
GAR6426 4 Sol. - 2/0 Str. 2-7/8 2-1/8
3/8 5/8 - 3/4
GAR6429 2/0 Sol. - 250
GAR6434 300 - 500 3-1/2 1/2 2-1/2
GAR144C 8 Sol. - 4 Str. 2-3/4
GAR1426 4 Sol. - 2/0 Str. 3/8 2-3/8
1/2 - 3/4 7/8 - 1 3
GAR1429 2/0 Sol. - 250
GAR1434 300 - 500 3-3/4 1/2 2-3/4
GAR154C 8 Sol. - 4 Str.
2-7/8
GAR1526 4 Sol. - 2/0 Str. 3/8 2-5/8
1 1-1/8 - 1-1/4
GAR1529 2/0 Sol. - 250 3-3/8
GAR1534 300 - 500 4-1/2 1/2
GAR164C 8 Sol. - 4 Str.
GAR1626 4 Sol. - 2/0 Str. 3-1/2 3/8 3
1-1/4 1-3/8 - 1-1/2
GAR1629 2/0 Sol. - 250
GAR1634 300 - 500 4-1/4 1/2 3-3/8
GAR174C 8 Sol. - 4 Str.
GAR1726 4 Sol. - 2/0 Str. 4 3/8 3-1/4
1-1/2 1-5/8 - 1-7/8
GAR1729 2/0 Sol. - 250
GAR1734 300 - 500 4-5/8 1/2 2-5/8
GAR184C 8 Sol. - 4 Str.
4-1/4
GAR1826 4 Sol. - 2/0 Str. 3/8 3-3/4
2 2 - 2-3/8
GAR1829 2/0 Sol. - 250 4-1/2
GAR1834 300 - 500 5-1/4 1/2 4-1/8
GAR194C 8 Sol. - 4 Str.
GAR1926 4 Sol. - 2/0 Str. 5 3/8 4-1/4
2-1/2 2-1/2 - 7/8
GAR1929 2/0 Sol. - 250
GAR1934 300 - 500 5-5/8 1/2 4-5/8
BURNDY
Grounding
TYPE GAR
(Continued)
FENCE POST GROUNDING
CONNECTOR
Catalog Conductor
Number Tube I.P.S. Rod Cable H J W
GAR204C 8 Sol. - 4 Str. 5-5/8 3/8 4-3/4
GAR2026 4 Sol. - 2/0 Str.
3 3 - 3-1/2
GAR2029 2/0 Sol. - 250
GAR2034 300 - 500 6-3/8 1/2 5-1/4
D-28 GAR214C 8 Sol. - 4 Str.
GAR2126 4 Sol. - 2/0 Str. 6-1/4 3/8 5-3/8
3-1/2 3-1/2 - 4
GAR2129 2/0 Sol. - 250
GAR2134 300 - 500 6-3/4 1/2 5-3/4
GAR224C 8 Sol. - 4 Str.
GAR2226 4 Sol. - 2/0 Str. 6-3/8 3/8 5-7/8
4 4 - 4-1/2
GAR2229 2/0 Sol. - 250
GAR2234 300 - 500 6-7/8 1/2 6-1/4
GAR244C 8 Sol. - 4 Str.
3/8 6-7/8
GAR2426 4 Sol. - 2/0 Str. 7-3/4
5 —
GAR2429 2/0 Sol. - 250
1/2 7-1/4
GAR2434 300 - 500 8-5/8
GAR8629 6 — 2/0 Sol. - 250 8-13/16 1/2 8-3/8
Contact BURNDY® for additional pipe and wire size
combinations not shown.
BURNDY
Grounding
CATALOG RECOMMENDED
NUMBER * CABLE RANGE IPS SIZE O.D. RANGE H J W TIGHTENING TORQUE
GAR3902-BU 1/2 - 1 .840 - 1.32 3.50 3.25
GAR3903-BU 1-1/4 - 2 1.66 - 2.38 4.00 4.25
GAR3904-BU 2-1/2 - 3-1/2 2.88 - 4.00 6.50 6.00
GAR3905-BU 4 - 5 4.50 - 5.56 7.50 7.50
#4 - 4/0 AWG 3/8 - 16 240 in. - lbs.
GAR3906-BU 6 6.62 8.50 8.62
GAR3907-BU 8 8.62 10.00 10.62
GAR3908-BU 10 10.75 12.00 12.75
GAR3909-BU 12 12.75 14.00 14.75
GAR3902 1/2 - 1 .840 - 1.32 3.50 3.25
GAR3903 1-1/4 - 2 1.66 - 2.38 4.00 4.25
GAR3904 2-1/2 - 3-1/2 2.88 - 4.00 6.50 6.00
GAR3905 4 - 5 4.50 - 5.56 7.50 7.50
#4 - 4/0 AWG 3/8 - 16 240 in. - lbs.
GAR3906 6 6.62 8.50 8.62
GAR3907 8 8.62 10.00 10.62
GAR3908 10 10.75 12.00 12.75
GAR3909 12 12.75 14.00 14.75
* Type GAR-BU is supplied with DURIUM™ silicon bronze
hardware and is listed for direct burial.
TYPE GAR-RB
For Reinforcement Bar
TYPE GAR-TC
WATER PIPE GROUND
CONNECTOR
MOUNTING PAD
FOR (2) 3/8"
Fig. 1 BOLTS - 1" L
COMPRESSION LUG WITH PAD
CAST HIGH COPPER ALLOY SADDLE FOR (2) 3/8" DIA. BOLTS
ON 1" CENTERS. 750 KCMIL MAX.
J
MOUNTING PAD
DURIUM 3/8"
SILICON BRONZE
PIPE DIA. HARDWARE
Fig. 2
TYPE GD
CABLE TO ROD/TUBE
GROUND CONNECTOR
For Two Copper Cables to Rod
or Tube
Catalog Conductor
Number Tube I.P.S. Rod Cable H J W
GD1526 4 Sol. - 2/0 Str.
1 1-1/8 - 1-1/4 3-3/8 2-5/8
GD1529 2/0 Sol. - 250
GD1626 4 Sol. - 2/0 Str. 3
1-1/4 1-3/8 - 1-1/2 3-1/2
GD1629 2/0 Sol. - 250 3/8
GD174C 8 Sol. - 4 Str.
3-1/4
GD1726 4 Sol. - 2/0 Str. 4
1-1/2 1-5/8 - 1-7/8
GD1729 2/0 Sol. - 250
GD1734 300 - 500 4-5/8 1/2 3-5/8
GD184C 8 Sol. - 4 Str.
GD1826 4 Sol. - 2/0 Str. 4-3/8 3/8 3-3/4
2 2 - 2-3/8
GD1829 2/0 Sol. - 250
GD1834 300 - 500 5-3/8 1/2 4-1/8
GD194C 8 Sol. - 4 Str.
GD1926 4 Sol. - 2/0 Str. 3/8 4-1/4
2-1/2 2-1/2 - 2-7/8 5
GD1929 2/0 Sol. - 250
GD1934 300 - 500 1/2 4-5/8
GD204C 8 Sol. - 4 Str.
GD2026 4 Sol. - 2/0 Str. 5-5/8 3/8 4-7/8
3 3 - 3-1/2
GD2029 2/0 Sol. - 250
GD2034 300 - 500 6-3/8 1/2 5-1/4
GD214C 8 Sol. - 4 Str.
GD2126 4 Sol. - 2/0 Str. 6-1/4 3/8 5-3/8
3-1/2 3-1/2 - 4
GD2129 2/0 Sol. - 250
GD2134 300 - 500 6-7/8 1/2 5-3/4
GD224C 8 Sol. - 4 Str.
GD2226 4 Sol. - 2/0 Str. 6-3/8 3/8 5-7/8
4 4 - 4-1/2
GD2229 2/0 Sol. - 250
GD2234 300 - 500 6-7/8 1/2 6-1/4
Complies with NFPA 78-86 HEAVY DUTY stacks.
(Order: LD for lead plating for HEAVY DUTY stack
applications.)
BURNDY
Grounding
TYPE GP
GROUND CONNECTOR
For Two Copper Cables
to Rod or Pipe
TYPE GK
GROUND CONNECTOR
For Three Copper Cables to
Rod or Pipe
CAST BRONZE
CLAMPS FOR
CONDUIT
Pressure bar type conduit hub adjusts for
1/2, 3/4 EMT or 1/2 rigid conduit. Hub
swings 360° for easy alignment. Zinc plated
hardware.
RECOMMENDED
ACCOMMODATES REFERENCE SCREW TORQUE
CONDUCTOR RANGE DIMENSIONS “INCH POUNDS”
CATALOG WATER HUB PIPE WIRE
NUMBER PIPE GROUND SIZE H L W CLAMP CLAMP D-33
1/2 - 1 2.07 3.19
C-11JPT
[13 - 25] [53] [81]
1-1/4 - 2 10 - 6 1/2 2.70 3.83 2.70
C-22JPT 50 in.-lb. 50 in.-lb.
[32 - 51] Sol. [13] [69] [97] [69]
2-1/2 - 4 4.39 5.15
C-4JPT
[64 - 102] [112] [131]
CAST BRONZE
GROUND CLAMPS
For connecting grounding conductor to water
pipe or copper tube. "D" indicates UL467
Listed for direct burial in earth and concrete
and are supplied with silicon bronze hard-
ware. "B" indicates brass hardware.
RECOMMENDED
ACCOMMODATES SCREW TORQUE
CONDUCTOR RANGE “INCH POUNDS”
CATALOG WATER REFERENCE DIMENSIONS PIPE WIRE
NUMBER PIPE REBAR GROUND H L W C CLAMP CLAMP
C-11N —
1/2 - 1 10 - 2 1.81 2.25 .63 .63
C-11D #4 - #6
[13 - 25] Str. [46] [56] [16] [16]
C-11B
C-22
1-1/4 - 2 10 - 2 2.38 3.63 .75 1.00
C-22D
[32 - 51] Str. [60] [92] [19] [25] 50 in.-lb. 50 in.-lb.
C-22B
—
2-1/2 - 4 10 - 2 4.13 6.25 .96 1.88
C-4
[64 - 114] Str. [105] [159] [24] [48]
4-1/2 - 6 10 - 2 4.29 8.34 1.25 1.88
C-8
[114 - 165] Str. [109] [212] [32] [48]
RECOMMENDED
ACCOMMODATES SCREW TORQUE
CONDUCTOR RANGE “INCH POUNDS”
CATALOG WATER REFERENCE DIMENSIONS PIPE WIRE
NUMBER PIPE GROUND H L W C CLAMP CLAMP
D-34 1/2 - 1 10 - 2 1.56 2.25 .56 .50
CZ-11 50 in.-lb. 50 in.-lb.
[13 - 25] Str. [40] [56] [14] [13]
CAST BRONZE
CLAMPS
To connect armored cable to water pipe. Zinc
plated screws. Pressure bar grips armor or
outer cable insulation. 360° swing hub for
easy alignment.
RECOMMENDED
ACCOMMODATES REFERENCE SCREW TORQUE
CONDUCTOR RANGE DIMENSIONS “INCH POUNDS”
CATALOG WATER ARMORED PIPE WIRE
NUMBER PIPE CONDUCTOR H L W CLAMP CLAMP
1/2 - 1 1.38 3.05
C-11JA
[13 - 25] [35] [77]
1-1/4 - 2 10 - 6 2.60 3.69 1.41
C-22JA 50 in.-lb. 50 in.-lb.
[32 - 51] Sol. [66] [94] [36]
2-1/2 - 4 4.29 5.01
C-4JA [64 - 102] [109] [128]
CAST BRONZE
CLAMPS
For connecting armored cable to water pipe.
Zinc plated screws. "D" indicates UL467 for
direct burial in earth and concrete, supplied
with silicon bronze hardware.
RECOMMENDED
ACCOMMODATES SCREW TORQUE
CONDUCTOR RANGE “INCH POUNDS”
CATALOG WATER GROUND REFERENCE DIMENSIONS PIPE WIRE
NUMBER PIPE GROUND CLAMP H L W C CLAMP CLAMP
C-6 1/2 - 1 10 - 2 Bare Armored 1.60 2.34 1.06 .63
[13 - 25] Str. Unarmored [41] [59] [27] [16]
C-6D 50 in.-lb. 50 in.-lb.
Wire Cables
1-1/4 - 2 10 - 2 or Cords 2.38 3.62 .94 1.00
C-7 [32 - 51] Str. [60] [92] [24] [25]
BURNDY
Grounding
CAST BRONZE
CLAMP FOR
RIGID CONDUIT
For grounding rigid conduit systems.
Zinc plated screws.
RECOMMENDED
ACCOMMODATES SCREW TORQUE
CONDUCTOR RANGE “INCH POUNDS”
CATALOG WATER HUB REFERENCE DIMENSIONS PIPE WIRE
NUMBER PIPE GROUND SIZE H L W C CLAMP CLAMP D-35
1/2 - 1 2.07 2.34 1.34 1.06
C-61 [13 - 25] 10 - 2 1/2 [53] [59] [34] [27]
50 in.-lb. 50 in.-lb.
1-1/4 - 2 Str. [13] 2.69 3.62 1.34 1.40
C-66 [32 - 51] [68] [92] [34] [36]
CAST BRONZE
CLAMPS FOR
CONDUIT
For grounding rigid conduit systems.
Continuity from rigid conduit systems to
ground provided by cast bronze threaded
conduit hub. Zinc plated screws.
RECOMMENDED
ACCOMMODATES SCREW TORQUE
CONDUCTOR RANGE “INCH POUNDS”
CATALOG WATER HUB REFERENCE DIMENSIONS PIPE WIRE
NUMBER PIPE GROUND SIZE H L W C CLAMP CLAMP
1/2 - 1 2.25 3.23 .97
C-11LH-1 [13 - 25] [57] [83] [25]
1-1/4 - 2 10 Str. - 1/2 2.88 3.50 .69 1.34
C-22LH-1 [32 - 51] 6 Sol. [13] [73] [89] [18] [34]
2-1/2 - 4 4.56 4.82 2.44
C-4LH-1 [54 - 102] [116] [122] [62]
1/2 - 1 2.56 2.86 1.13
C-11LH-2 [13 - 25] [65] [73] [29]
1-1/4 - 2 2/0 - 10 3/4 3.19 3.50 1.00 1.50
C-22LH-2 50 in.-lb. 50 in.-lb.
[32 - 51] Str. [19] [65] [89] [25] [38]
2-1/2 - 4 4.88 4.82 2.38
C-4LH-2 [64 - 102] [124] [122] [60]
1/2 - 1 2.69 2.86 1.19
C-11LH-3 [13 - 25] [68] [73] [30]
1-1/4 - 2 3/0 - 10 1 3.32 3.50 1.13 1.56
C-22LH-3 [32 - 51] Str. [25] [59] [89] [29] [40]
2-1/2 - 4 5.01 4.82 2.44
C-4LH-3 [63 - 102] [127] [122] [62]
BURNDY
Grounding
CAST BRONZE
CLAMP WITH
COPPER STRAP
For grounding rigid conduit systems. Strap
helps protect conduit system from water
system vibrations. Zinc plated screws. Strap
ETP copper.
RECOMMENDED
ACCOMMODATES SCREW TORQUE
CONDUCTOR RANGE “INCH POUNDS”
D-36 CATALOG WATER HUB REFERENCE DIMENSIONS PIPE WIRE
NUMBER PIPE GROUND SIZE H L W C D CLAMP CLAMP
6 Sol. 1/2 1.06 1.06
C-11CSH-1 Max. [13] [27] [27]
1/2 - 1 3/4 1.75 8.50 1.25 1.50 6.12
C-11CSH-2 50 in.-lb. 50 in.-lb.
[13 - 25] 4/0 Str. [19] [44] [216] [32] [38] [155]
Max. 1 1.50 1.75
C-11CSH-3 [25] [38] [44]
GROUND STRAPS,
ADJUSTABLE
Burndy adjustable ground straps are made
from pure annealed copper. The heavy type is
.050 thick and 3/4 wide. The light type is
.025 thick and 3/4 wide. The bolts, nuts and
washers are plated steel. Four sizes cover a
ground pipe range of 3/8 to 4. Ground wire
connection can be soldered or solderless.
RECOMMENDED
CATALOG ACCOMMODATES REFERENCE DIMENSIONS SCREW TORQUE
NUMBER WATER PIPE H L W “INCH POUNDS”
.050
GS1T50 3/8 - 1 [1] 5.61
[10 - 25] .025 [142]
GS1T25 [1]
.050
GS2T50 3/8 - 2 [1] 9.38
[10 - 51] .025 [238]
GS2T25 [1] .75
50 in.-lb.
.050 [19]
GS3T50 3/8 - 3 [1] 13.20
[10 - 76] .025 [335]
GS3T25 [1]
.050
GS4T50 3/8 - 4 [1] 17.00
[10 - 102] .025 [432]
GS4T25 [1]
BURNDY
Grounding
TYPE GC-A
DUAL RATED
GROUND CLAMP
For Copper and
Aluminum Cable
TYPE GG
GROUND CONNECTOR
For Copper Bar, Strap, Braid or
Cable to Rod or Tube
TYPE GQ
GROUND CONNECTOR
For Copper Cable to Tube
D-39
Catalog Conductor
Number Tube I.P.S. Cable H J L W
GQ2626 6 Max. 4-1/2
4 Str. - 2/0 Str. 5 2-1/2
GQ26-1 Above 6 7-1/8
1/2
GQ2929 6 Max. 4-1/8
2/0 Str. - 250 6 2-3/4
GQ29-1 Above 6 7-1/2
BURNDY
Grounding
TYPE GX
GROUND CONNECTOR
For Copper Cables
D-40
Catalog Conductor
Number Groove A Groove B H J L W
GX4C4C 8 Sol. - 4 Str. 8 Sol. - 4 Str. 1-7/8 1-5/8 1-5/8
GX264C 8 Sol. - 4 Str.
4 Sol. - 2/0 Str. 2-1/2 1-3/4 1-3/4
GX2626 4 Sol. - 2/0 Str.
GX294C 8 Sol. - 4 Str.
GX2926 2/0 Sol. - 250 4 Sol. - 2/0 Str. 3/8 1-7/8
GX2929 2/0 Sol. - 250
2-3/4 1-7/8
GX344C 8 Sol. - 4 Str.
GX3426 4 Sol. - 2/0 Str. 2-1/8
300 - 500
GX3429 2/0 Sol. - 250
GX3434 300 - 500 4-1/4 1/2 2-5/8 2-5/8
TYPE GRC
HIGH STRENGTH
GROUND ROD CLAMP
For Copper Cable to Rod
TYPE B
FLEXIBLE COPPER BRAID
NUMBER OF
CATALOG BRAIDS IN APPROXIMATE AMP
NUMBER FERRULES C D E K L N T INDOOR OUTDOOR
BD12 2.50 1.25 .44 12
BD12N** 3.00 1.75 .56 12
BD18 2.50 1.25 .44 18
1 .94 .62 .13 190 225
BD18N** 3.00 1.75 .56 18
BD24 2.50 1.25 .44 24
BD24N** 3.00 1.75 .56 24
BE12 1.50 .44 12 .75
BE12N** 1.75 .56 12 .62
BE18 1.50 .44 18 .75
1 1.50 3.00 .17 340 405
BE18N** 1.75 .56 18 .62
BE24 1.50 .44 24 .75
BE24N** 1.75 .56 24 .62
BF12 1.50 .44 12 .75
BF12N** 1.75 .56 12 .62
BF18 1.50 .44 18 .75
1 1.19 3.00 .25 360 430
BF18N** 1.75 .56 18 .62
BF24 1.50 .44 24 .75
BF24N** 1.75 .56 24 .62
BG12 1.50 .44 12 .75
BG12N** 1.75 .56 12 .62
BG18 1.50 .44 18 .75
1 1.50 3.00 .25 415 495
BG18N** 1.75 .56 18 .62
BG24 1.50 .44 24 .75
BG24N** 1.75 .56 24 .62
* This rating may vary with ambient conditions, orientation of
the braid and other service conditions.
** Tongue drilled per (2) hole NEMA standard.
BURNDY
Grounding
FLEXIBLE COPPER
BRAID
(Continued)
TYPE B
NUMBER OF
CATALOG BRAIDS IN APPROXIMATE AMP
NUMBER FERRULES C D E K L N T INDOOR OUTDOOR
B2D12 2.50 1.25 .44 12 .62
.94 .25 380 455
B2D12N** 3.00 1.75 .56 12 .62
B2E12 3.00 1.50 .44 12 .75
1.62 .25 530 635
D-42 B2E12N** 3.00 1.75 .56 12 .62
2
B2F12 3.00 1.50 .44 12 .75
1.38 .38 600 720
B2F12N** 3.00 1.75 .56 12 .62
B2G12 3.00 1.50 .44 12 .75
1.50 .50 700 840
B2G12N** 3.00 1.75 .56 12 .62
B3D12 2.50 1.25 .44 12 .62
1.19 .25 470 560
B3D12N** 3.00 1.75 .56 12 .62
B3E12 3.00 1.50 .44 12 .75
1.64 .31 700 840
B3E12N** 3.00 1.75 .56 12 .62
3
B3F12 3.00 1.50 .44 12 .75
1.44 .56 820 980
B3F12N** 3.00 1.75 .56 12 .62
B3G12 3.00 1.50 .44 12 .75
1.69 .69 960 1150
B3G12N** 3.00 1.75 .56 12 .62
B4D12 2.50 1.25 .44 12 .62
1.19 .32 600 720
B4D12N** 3.00 1.75 .56 12 .62
B4E12 3.00 1.50 .44 12 .75
1.64 .36 850 1020
B4E12N** 3.00 1.75 .56 12 .62
4
B4F12 3.00 1.50 .44 12 .75
1.50 .78 1000 1200
B4F12N** 3.00 1.75 .56 12 .62
B4G12 3.00 1.50 .44 12 .75
1.69 .94 1200 1440
B4G12N** 3.00 1.75 .56 12 .62
* This rating may vary with ambient conditions, orientation of
the braid and other service conditions.
** Tongue drilled per (2) hole NEMA standard.
BURNDY
Grounding
TYPE GL
GROUND CONNECTOR
For Two Copper
Cables to Bar
TYPE GZ
GROUND CONNECTOR
For Copper Cable to Bar
NOTE:
* The GB, GBM, GC, GCM, GL and GZ are all
used for joining a range of cable to bar. The
catalog numbers in each table accommodate the
indicated cable range and up to 1/4 thick bar.
Optional bolt lengths are available to accommo-
date up to 1 thick bar. For bar thicknesses from
1/4 to 1/2, add the suffix “T4” to the catalog
number in the table. For bar thicknesses from
1/2 to 1, add the suffix “T8” to the catalog
number in the table.
BURNDY
Grounding
TYPE GC-CT
CABLETRAY
GROUND CLAMP
ACCOMMODATES COPPER OR
CATALOG ALUMINUM CONDUCTOR
NUMBER IN EITHER GROOVE B CF H J W
#6 Sol. (.162 Dia.) -
GC2525CT 1.12 .56 1.95 3/8” - 16 1.45
1/0 Str. (.372 Dia.)
#2 Sol. (.258 Dia.) -
GC2626CT 1.12 .56 1.95 3/8” - 16 1.70
2/0 Str. (.419 Dia.)
2/0 Str. (.414 Dia.) -
GC2929CT 1.12 .56 2.20 3/8” - 16 1.98
250 kcmil (.575 Dia.)
NOTE:
The bolt head is mounted on the inside wall of cabletray to avoid
damage to the cable insulation.
May be used with aluminum or galvanized steel cable tray.
BURNDY
Grounding
GROUND CONNECTOR
For Vehicle Grounding
Heavy Duty Construction
1.2
High-strength copper alloy ground clamps for MAX.
grounding gasoline trucks, tank cars, aircraft OPENING
and other vehicles where danger of explosion
due to static electricity exists. Corrosion resis- Replaceable Contact Grip Screws
tant and supplied with nonsparking,
Catalog Number Catalog Number Material Point Configuration
adjustable, replaceable contact grip screws.
GIE4CG3P5 Cone Point
Automatic safety release disconnects should GIE4CG3 Beryllium Copper
D-46 GIE4CG3P7 Cup Point
a vehicle unexpectedly move from the
GIE4CG4P5 Cone Point
grounded area. Accommodates 4 Str. flexible GIE4CG4 Stainless Steel
GIE4CG4P7 Cup Point
copper cable.
TYPE GIE-G
GROUND CONNECTOR
RAIL CONNECTOR
Mechanical clamp connectors designed for
use in power, contact or running rail appli-
cations. Connectors are cast of a high
conductivity copper alloy, tin-plated, and
assembled with high-strength DURIUM™
hardware. Connectors designed for extended
service life.
D-47
Fig. 1 Fig. 2
Fig. 3 Fig. 4
Catalog Fig.
Number No. Accomodates B H HH L W
J278 1 100 LBS. A.R.E.A. RUNNING RAIL 1.81 1.88 1.72 7.50 .88
J279 1 75 or 90 LBS. RUNNING RAIL 1.81 1.71 1.55 7.50 .88
J280 1 150 LBS. CONTACT RAIL 2.12 2.08 1.92 7.00 1.25
J295 2 150 LBS. THIRD RAIL 2.62 3.50 3.50 7.75 3.00
150 LBS. NMC CONTACT RAIL and
RGC44G1* 3 1.75 2.82 2.25 10.00 1.75
(1) 800-1000 kcmil CU CABLE
115 LBS. CONTACT or RUNNING RAIL and
RGC39G1* 4 2.75 2.00 4.78 8.32 1.25
(1) 500-750 kcmil CU CABLE
* Tin-plated.
BURNDY
Grounding
TYPE QGFL
BARTAP
For Copper Cable to
Flat Bar or Pad
TYPE GA-H
GROUND CONNECTOR
For Copper Cable
to “H” Beam
TYPE GRF
UNIGROUND® RAISED FLOOR
GROUNDING CONNECTOR