Sellos Remotos
Sellos Remotos
Introduction
In 1983, Honeywell introduced the first Smart Pressure
Transmitter― the ST 3000®. In 1989, Honeywell launched
the first all digital, bi-directional protocol for smart field
devices. Today, its ST 3000 Series 900 Remote Seal
Transmitters continue to bring proven “smart” technology to
a wide spectrum of pressure measurement applications.
For applications in which the transmitter must be mounted
remotely from the process, Honeywell offers the remote
seal line of gauge, absolute and differential pressure
transmitters. Typical applications include level
measurement in pressurized vessels in the chemical and
hydrocarbon processing industries. A second application is
flow measurement for slurries and high viscosity fluids in
the chemical industry. Honeywell remote seal transmitters
are available with secondary fill fluids for corrosive or high
Figure 1—Series 900 Remote Seal Pressure Transmitters feature
temperature process fluids. proven piezoresistive sensors and advanced seal technology with
standard weld connections.
Models
All ST 3000 transmitters can provide a 4-20 mA output,
STR93D 0 to 100 psid 0 to 7 bar
®
Honeywell Digitally Enhanced (DE) output, HART output,
STR94G 0 to 500 psig 0 to 35 bar or FOUNDATION™ Fieldbus output. When digitally integrated
All ST 3000 transmitters can be ordered to provide one of with Honeywell’s Process Knowledge System™,
the following output communication options. EXPERION PKS™ ST 3000 instruments provide a more
accurate process variable as well as advanced diagnostics.
Communications options
Honeywell’s cost-effective ST3000 S900 transmitters lead
4-20 mA
the industry in reliability and stability:
Honeywell Digitally Enhanced (DE)
• Stability
HART® (versions 5.x or 6.x)
• Reliability
FOUNDATION™ Fieldbus
The devices provide comprehensive self-diagnostics to help ST3000 S900 Transmitter Benefits
users maintain high uptime, meet regulatory requirements,
and attain high quality standards. S900 transmitters allow Stability = ±0.01% per year
smart performance at analog prices. Accurate, reliable and Reliability = 470 years MTBF
stable, Series 900 transmitters offer greater turndown ratio
than conventional transmitters.
2 ST 3000 Smart Pressure Transmitter
Figure 7— Sanitary Seals Figure 10— Stainless Steel Armor and PVC Coated Stainless
Steel Armor Capillaries
Saddle Seals can be used with differential, gauge and 2” Stainless Steel Nipples are available for Close-Coupled
absolute pressure transmitters and are available with 3” and remote seal solutions.
4” (6 bolt or 8 bolt designs) process connections.
Microprocessor-based electronics provide higher span- • Comprehensive list of on-board diagnostics (Ref. ST
turndown ratio, improved temperature and pressure 3000 User manual with HART® 6, 34-ST-25-17 Rev: June
compensation, and improved accuracy. 09 and FoundationTM Fieldbus option manual 34-ST-25-
15 Rev: June 09)
The transmitter’s meter body and electronics housing resist
shock, vibration, corrosion, and moisture. The electronics
housing contains a compartment for the single-board
electronics, which is isolated from an integral junction box.
The single-board electronics is replaceable and
interchangeable with any other ST 3000 Series 100 or
Series 900 model transmitters.
Features
• Choice of linear or square root output conformity is a
simple configuration selection.
Figure 13—ST 3000 Remote Seals operable limits for pressure versus temperature
ST 3000 Smart Pressure Transmitter 7
1440
1200
250
= Operating Area
* Performance specifications are based on reference conditions of 25°C (77°F), zero (0) static pressure, 10 to 55% RH, and
316L Stainless Steel barrier diaphragm.
Minimum recommended span for STR93D DP Transmitter with two Remote Seals
Diaphragm Capillary Capillary Length
Size 5' 10' 15' 20' 25' 30' 35' maximum
2.0 15 psig 20 psig 25 psig - - - - 15'
2.4 150 iwc 200 iwc 250 iwc 300 iwc 350 iwc 400 iwc 450 iwc 35'
2.9 50 iwc 75 iwc 100 iwc 125 iwc 150 iwc 175 iwc 200 iwc 35'
3.5 25 iwc 25 iwc 25 iwc 28 iwc 32 iwc 36 iwc 40 iwc 35'
4.1 25 iwc 25 iwc 25 iwc 25 iwc 25 iwc 27 iwc 30 iwc 35'
Minimum recommended span for STR94G or STR93D DP Transmitter with one Remote Seal
Diaphragm Direct Capillary Capillary Length
Size Mount 5' 10' 15' 20' 30' 35' maximum
2.0 25 psi 30 psi 40 psi 50 psi - - - 15'
2.4 10 psi 15 psi 20 psi 25 psi 30 psi 40 psi 50 psi 35'
2.9 8 psi 9 psi 10 psi 11 psi 12 psi 14 psi 15 psi 35'
3.5 2 psi 2 psi 3 psi 4 psi 5 psi 7 psi 8 psi 35'
4.1 0.9 psi 0.9 psi 1 psi 2 psi 3 psi 4 psi 5 psi 35'
Minimum span is the higher of the value from the table above or the value defined under Performance Conditions for the range transmitter
*
See Figure 13 for Fill Fluid temperature limits.
**
2-inch Sanitary Seals are limited to 15 ft. (4.6 m) capillary length.
NOTE: Pressure transmitters that are part of safety equipment for the protection of piping (systems) or vessel(s) from
exceeding allowable pressure limits, (equipment with safety functions in accordance with Pressure Equipment Directive
97/23/EC article 1, 2.1.3), require separate examination.
1
Vent/Drains are sealed with Teflon® or PTFE
2
Hastelloy® C-276 or UNS N10276
3
Monel 400® or UNS N04400
4
Supplied as 316 SS or as Grade CF8M, the casting equivalent of 316 SS.
5
Carbon Steel heads are zinc-plated and not recommended for water service due to hydrogen migration. For that service, use 316 stainless steel wetted
Process Heads.
6
Hastelloy® C-276 or UNS N10276. Supplied as indicated or as Grade CW12MW, the casting equivalent of Hastelloy® C-276
7
Monel 400® or UNS N04400. Supplied as indicated or as Grade M30C, the casting equivalent of Monel 400®
10 ST 3000 Smart Pressure Transmitter
Certifications
Temperature
Type of Protection Comm. Option Field Parameters
Codes
Explosionproof:
Class I, Division 1, Groups A, B, C, D
locations
All All T5 Ta = 93ºC
Dust Ignition Proof:
Class II, III, Division 1, Groups E, F,
G locations,
Enclosure Type 4X
Vmax = 42.4V
Imax = 225mA
4-20 mA / DE Ci = 4.2nF T4 Ta = 93ºC
Intrinsically Safe: Li = *
Pi =1.2W
Class I, II, III, Division 1, Groups A,
B, C, D, E, F, G locations, Enclosure Vmax = 30V
Imax = 225mA
Type 4X 4-20 mA / HART
®
Ci = 4.2nF T4 Ta = 93ºC
Li = *
Pi =1.2W
Vmax = 32V
Imax = 120mA
Fieldbus – Entity T4 Ta = 40ºC
Ci = 4.2nF
(Not FISCO) T3 Ta = 93ºC
Li = 0
Intrinsically Safe: Pi =0.84W
Vmax = 24V
Class I, II, III, Division 1, Groups A, Imax = 250mA
Fieldbus – Entity T4 Ta = 40ºC
B, C, D, E, F, G locations; (Not FISCO)
Ci = 4.2nF
T3 Ta = 93ºC
Li = 0
FM Class 1, Zone 0, AEx ia Group IIC, Pi =1.2W
SM
Approvals Enclosure Type 4X / IP 66/67 Vmax = 17.5V
Imax = 380mA
T4 Ta = 40ºC
FISCO Ci = 4.2nF
T3 Ta = 93ºC
Li = 0
Pi =5.32W
Vmax = 42.4V
Imax = 225mA
4-20 mA / DE Ci = 4.2nF T4 Ta = 93ºC
Nonincendive: Li = *
Pi =1.2W
Class I, Division 2, Groups A, B, C, D Vmax = 30V
locations, Enclosure Type 4X Imax = 225mA
4-20 mA / HART Ci = 4.2nF T4 Ta = 93ºC
Li = *
Pi =1.2W
Vmax = 32V
Imax = 120mA
Nonincendive: Fieldbus – Entity T4 Ta = 40ºC
Ci = 4.2nF
(Not FNICO) T3 Ta = 93ºC
Li = 0
Class I, Division 2, Groups A, B, C, Pi =0.84W
D;
Vmax = 24V
Imax = 250mA
Suitable for: Fieldbus – Entity T4 Ta = 40ºC
Ci = 4.2nF
Class II, Division 2, Groups F&G; (Not FNICO) T3 Ta = 93ºC
Li = 0
Class III, Division 2; Pi =1.2W
Class I, Zone 2, Group IIC,
Vmax = 32V
Enclosure Type 4X / IP 66/67 FNICO Ci = 4.2nF
T4 Ta = 40ºC
T3 Ta = 93ºC
Li = 0
* Li = 0 except Li = 150µH when Option ME, Analog Meter, is selected.
This certificate defines the certifications covered for the ST 3000 Pressure Transmitter family of
products, including the SMV 3000 Smart Multivariable Transmitter. It represents the compilation of
the five certificates Honeywell currently has covering the certification of these products into marine
applications.
For ST 3000 Smart Pressure Transmitter and SMV 3000 Smart Multivarible Transmitter
American Bureau of Shipping (ABS) - 2009 Steel Vessel Rules 1-1-4/3.7, 4-6-2/5.15, 4-8-3/13 &
ST 3000 Pressure 13.5, 4-8-4/27.5.1, 4-9-7/13. Certificate number: 04-HS417416-PDA
Transmitter Marine
Certificate Bureau Veritas (BV) - Product Code: 389:1H. Certificate number: 12660/B0 BV
(MT Option)
Det Norske Veritas (DNV) - Location Classes: Temperature D, Humidity B, Vibration A, EMC B,
Enclosure C. For salt spray exposure; enclosure of 316 SST or 2-part epoxy protection with 316
SST bolts to be applied. Certificate number: A-11476
The ST 3000 Smart Pressure Transmitters are in conformity with the essential requirements of the Pressure
Equipment Directive.
Honeywell ST 3000 Smart Pressure Transmitters are designed and manufactured in accordance with the
applicable portions of Annex I, Essential Safety Requirements, and sound engineering practices. These
transmitters have no pressurized internal volume, or have a pressurized internal volume rated less than 200 bar
(2,900 psig), and/or have a maximum volume of less than 0.1 liter (Article 3, 1.1.(a) first indent, Group 1 fluids).
Therefore, these transmitters are not subject to the essential requirements of the directive 97/23/EC (PED,
Annex I) and shall not have the CE mark applied.
European
Pressure
For transmitters rated > 200 bar (2,900 psig) < 1,000 bar (14,500 psig) Honeywell maintains a technical file in
Equipment
accordance with Annex III, Module A, (internal production control) when the CE mark is required. Transmitter
Directive (PED)
Attachments: Diaphragm Seals, Process Flanges and Manifolds comply with Sound Engineering Practice.
(97/23/EC)
NOTE: Pressure transmitters that are part of safety equipment for the protection of piping (systems) or
vessel(s) from exceeding allowable pressure limits, (equipment with safety functions in accordance with
Pressure Equipment Directive 97/23/EC article 1, 2.1.3), require separate examination.
A formal statement from TÜV Industry Service Group of TÜV America, Inc., a division of TÜV Süddeutschland,
a Notified Body regarding the Pressure Equipment Directive, can be found at www.honeywell.com. A hard
copy may be obtained by contacting a Honeywell representative.
Dual Seal Dual Seal Certification based on ANSI/NFPA 70-202 and ANSI/ISA 12.27.01 requirements without the use of
Certification additional seal protection elements.
Recommended
Frequency of Honeywell recommends verifying the calibration of these devices once every four years.
Calibration
Approved Honeywell Process Solutions - York, PA USA
Manufacturing Honeywell (Tianjin) Limited – Tianjin, P.R. China
Locations Honeywell Automation India Ltd – Pune 411013 India
FoundationTM Fieldbus is a trademark of the Fieldbus Foundation. Viton® is a registered trademark of DuPont
HART® is a registered trademark of HART Communications Foundation. Teflon® is a registered trademark of DuPont.
Hastelloy® C-276 is a registered trademark of Haynes International. DC® 200 is a registered trademark of Dow Corning.
Monel® 400 is a registered trademark of Special Metals Corporation. FM ApprovalsSM is a service mark of FM Global
ST 3000 and Experion are registered trademarks of Honeywell International Inc.
16 ST 3000 Smart Pressure Transmitter
Mounting
LP Side
Maximum level
H2
Fixed
ref. leg Variable
Head
H1
Minimum level
.
HP Side
NOTE: Lower flange seal should not be mounted over 22 feet below the
transmitter for silicone fill fluid (11 feet for CTFE fill fluid) with tank at one
atmosphere. The combination of tank vacuum and high pressure capillary
head effect should not exceed 9 psi vacuum (300 mmHg absolute).
Consult Honeywell for installation of STR93D
Figure 16 – Typical mounting arrangement for ST 3000 Transmitter with Remote Diaphragm Seals
ST 3000 Smart Pressure Transmitter 17
Application Data
Min
SGf = Specific Gravity of capillary HP
a
fill fluid (See Page 9 for values.) Level
Max LP
Level
Min
a HP
Level
24253
Figure 17—Closed tank liquid level measurement distance
18 ST 3000 Smart Pressure Transmitter
Density or Interface
Calculate the minimum and maximum pressure
differentials to be measured (Figure 18).
LP
Pmin = (SGmin – SGf) x (d);
minimum density, 4mA output
Where:
HP
d = distance between the taps
24257
SGmax = maximum Specific Gravity
Reference Dimensions
millimeters
inches
With
82.9 94.9 Removal
Smart 3.6
3.26 3.74 Clearance Plug
meter 0.14
53.1 65.1 for All Caps
2.09 2.56 135
45.7 with meter
Without Without 5.32
1.8 meter meter
55.3
2.18
23.5
.925
Optional
Optional Meters
external Rotational
ground Lock
LP seal
omitted for
clarity
67
2.64
93.6
3.69
STR93D DP/I Remote Seal with Horizontal Pipe Mount
55.3
2.18
23.5
.925
Optional
Seal
Meters Optional omitted for
Rotational external clarity
Lock ground
Dimensions are for reference only and may be subject to change. For specific information contact Honeywell customer
service per the contact information located with in this document.
20 ST 3000 Smart Pressure Transmitter
Reference Dimensions
millimeters
inches
With
82.9 94.9 Removal
Smart
3.26 3.74 Clearance 3.6
meter Plug
53.1 65.1 for All Caps 0.14
2.09 2.56 with meter 135
45.7 Without Without 5.32
1.8 meter meter
55.3
Seal 2.18
omitted for
23.5 clarity
.925 LP seal
Rotational
Lock
Optional omitted for
Optional Meters clarity
external
ground
67
2.64
93.6
STR93D DP/I Remote Seal with Vertical Pipe Mount 3.69
With
Smart meter 82.9 94.9 Removal
3.6 Plug 135 3.26 3.74 Clearance
0.14 5.32
53.1 65.1 for All Caps
2.09 2.56 with meter
45.7 Without
55.3 Without
1.8 meter meter
2.18
Rotational
Optional 23.5
Lock
Meters .925
Optional
external
ground
Seal
omitted for
clarity
Dimensions are for reference only and may be subject to change. For specific information contact Honeywell customer
service per the contact information located with in this document.
ST 3000 Smart Pressure Transmitter 21
Flush Flanged Seal with Lower Flush Flanged Seal with Lower
Note: 0.90 dimension is 0.70 for 4.1” Dia.
Diaphragm
ST 3000 Smart Pressure Transmitter 25
Pancake Seal
Sanitary Seal
Sanitary Seal
ST 3000 Smart Pressure Transmitter 27
Saddle Seal
3” Saddle Seal
4” Saddle Seal
Calibration Rings
Calibration Ring
28 ST 3000 Smart Pressure Transmitter
Options
• High Accuracy (Option HA)
Extends applicable S100 models to ±0.025% analog • Lightning Protection (Option LP)
reference accuracy. A terminal block is available with circuitry that protects
• Angle Mounting Bracket (Options MB, MX, SB, SX, the transmitter from transient surges induced by nearby
FB) lightning strikes.
The angle mounting bracket is available in either zinc- • NAMUR NE43 Compliance (Option NE)
plated carbon steel or stainless steel and is suitable for This option provides software the meets the NAMUR
horizontal or vertical mounting on a two inch (50 NE43 requirements for failsafe software. Transmitter
millimeter) pipe, as well as wall mounting. An optional failure information is generated when the measuring
flat mounting bracket is also available in carbon steel information is no longer valid.
for two inch (50 millimeter) pipe mounting. An option Transmitter failure values are ≤ 3.6 mA and ≥ 21.0 mA.
also exists for Marine approved mounting brackets
The normal ST 3000 ranges are ≤ 3.8 mA and ≥ 20.8
used with Marine certification options.
mA.
• Indicating Meter (Options ME and SM)
• Write Protection (Options WP and WX)
Two integral meter options are available. An analog
Provides the capability to hardwire write-protect
meter (option ME) is available with a dual 0 to 10
installed transmitter configurations.
square root and 0 to 100% linear scale. The Smart
Meter (option SM) provides an LCD display for both • Stainless Steel Tagging (Option TG)
analog and digital output and can be configured to Up to 30 characters can be added on the stainless
display pressure in selected engineering units. steel nameplate mounted on the transmitter’s
electronics housing at no extra cost. A stainless steel
• HART® Output Protocol (Options HC and H6)
wired on tag with additional data of up to 4 lines of 28
Optional electronic modules for the ST 3000 provide
characters is also available. The number of characters
HART® Protocol compatibility in either HART® 5.x or
for tagging includes spaces.
6.x formats. Transmitters with a HART® Option are
compatible with any HART® enabled system that • Transmitter Configuration (Options TC and FC)
provides 5.x or 6.x format support. With Option TC, the factory can configure the analog,
DE or HART® transmitter’s linear/square root
• FoundationTM Fieldbus Output (Option FF)
extraction, damping time, LRV, URV and mode
Equips transmitter with FF protocol for use in 31.25
(analog/digital) and enter an ID tag of up to eight
kbit/s FF networks. See document 34-ST-03-72 for
characters and scratchpad information as specified.
additional information on ST 3000 Fieldbus
transmitters. With Option FC, the Device ID, Transmitter Tag, Unit
Level Node Address, Output Mode and Damping Time
• SIL2/SIL3 Certification (Option SL)
Constants can be specified.
This ST 3000 product is available for use with safety
systems. With the SL option, we are fully certified to • Custom Calibration and ID in Memory (Option CC)
SIL 2 capability for single transmitters and SIL 3 The factory can calibrate any range within the scope of
capability for multiple transmitter use through TÜV the transmitter’s range and enter an ID tag of up to
Nord Sys Tec GmbH & Co. KG. We are in compliance eight characters in the transmitter’s memory.
with the following SIL standards: • Indicator Configuration (Option CI)
IEC 61508-1: 1998 Provides custom configuration of Smart Meters.
Model Selection Guides are subject to change and are inserted into the specifications as guidance only.
Prior to specifying or ordering a model check for the latest revision Model Selection Guides which are published at:
http://hpsweb.honeywell.com/Cultures/en-US/Products/Instrumentation/ProductModelSelectionGuides/default.htm
Model Selection Guide
34-ST-16U-34
Issue 47
Page 1 of 11
Instructions
● Select the desired Key Number. The arrow to the right marks the selection available.
● Make selections from each Table (I, II and IV), using the column below the proper arrow.
● Select as many Table III options as desired plus a communications option selection.
● A () denotes unrestricted availability. A letter denotes restricted availability.
● Restrictions follow Table IV.
KEY NUMBER
Description Selection Avail.
0-25" to 0-2,700" H2O / 0-62.2 to 0-7,000 mbar
STR93D
Body Rating*: 750 psi (51.7 bar) Compound Characterized
0-5 to 0-500 psig / 0-0.35 to 0-35 bar
STR94G
Body Rating*: 500 psi (35 bar)
* Remote seal system pressure rating is body rating or seal rating, whichever is less.
Base STR models no longer include a default communications option. All units now require the selection of a
Important Note:
communication option from Table III (AN, DE, HC, H6 or FF).
34-ST-16U-34
Issue 47
Page 2 of 11
TABLE II - SEALS
Format for Seal Selection:
Specify 12 characters ____________
Common Required Seal Availability
Note: The first 3 characters are common to all seals. STR9xx
When selecting required seal, you must specify
only the 9 selections within the required seal. Selection 3D 4G
No Fill Fluid 0___________ 3 3
®
Silicone DC 200 1___________ • •
CTFE 2___________ • •
Secondary Fill
Silicone Oil 704 3___________ • •
Neobee M20 2
® 4___________ • •
®
Syltherm 800 3 5___________ • •
No Capillary, No Nipple _0__________ 3 3
5 feet 1.5 m _A__________ • •
10 feet 3.0 m _B__________ • •
15 feet 4.5 m _C__________ • •
SS Armor
20 feet 6.1 m _D__________ • •
25 feet 7.5 m _E__________ • •
Capillary 35 feet 10.7 m _F__________ • •
Length 5 feet 1.5 m _G__________ • •
Connection of 10 feet 3.0 m _H__________ • •
Remote Seal 15 feet 4.5 m PVC Coated _J__________ • •
to Meter Body 20 feet 6.1 m SS Armor _K__________ • •
25 feet 7.5 m _L__________ • •
35 feet 10.7 m _M__________ • •
2 inch long SS nipple close-coupled _2__________ z z
No Selection __0_________ • •
No Seal Attached to Core Transmitter ___000000000 3 3
Diaphragm Flange Flange Pressure
1 Selection
Diameter Size Rating
ANSI Class 150 _ _ _ AFA _ _ _ _ _ _ • •
3"
3.5" ANSI Class 300 _ _ _ AFC _ _ _ _ _ _ • •
80mm DIN DN80-PN40 _ _ _ AFM _ _ _ _ _ _ • •
Diaphragm Upper Insert Selection
316L SS 316L SS _ _ _ _ _ _ AA _ _ _ _ • •
Hastelloy® C-276 316L SS _ _ _ _ _ _ AB _ _ _ _ • •
Wetted Material
Hastelloy® C-276 Hastelloy® C-276 _ _ _ _ _ _ AC _ _ _ _ • •
® ®
Monel 400 Monel 400 _ _ _ _ _ _ AE _ _ _ _ • •
5
Tantalum 316L SS _ _ _ _ _ _ AF _ _ _ _ 1 1
Flush Flanged
CS (Nickel Plated) ________1___ • •
Seal Flange Material
316L SS ________2___ • •
Seal-Capillary Center Seal _________1__ • •
Connection Side Seal _________2__ 9 9
Calibration Rings None __________A_ • •
316L SS __________B_ 5 5
®
Hastelloy C-276 __________C_ 5 5
®
Monel 400 __________D_ 5 5
34-ST-16U-34
Issue 47
Page 3 of 11
Availability
STR9xx
TABLE II - SEALS (continued)
Description Selection 3D 4G
Flushing None ___________0 • •
Flush Flanged Connections One 1/4" with plastic plug ___________H 6 6
Seal and Plugs4 One 1/4" with metal plug ___________J 6 6
Metal plug material Two 1/4" with plastic plugs ___________M 6 6
will be the same as Two 1/4" with metal plugs ___________N 6 6
Lower material, if One 1/2" with plastic plug ___________P 6 6
metal plug is chosen - One 1/2" with metal plug ___________Q 6 6
(SS Plug for CS Lower Two 1/2" with plastic plugs ___________R 6 6
and Tantalum Clad) Two 1/2" with metal plugs ___________S 6 6
Table II continued below
STR9xx
3D 4G
Const. - See Spec.
Diaphragm Flange Pressure
Flange Size Figure 34-ST-03- Selection
Diameter Rating 1
57
ANSI 150 22 _ _ _ BCA _ _ _ _ _ _ • •
1"
ANSI 300 22 _ _ _ BCC _ _ _ _ _ _ • •
ANSI 150 22 _ _ _ BGA _ _ _ _ _ _ • •
1-1/2"
ANSI 300 22 _ _ _ BGC _ _ _ _ _ _ • •
2.4"
ANSI 150 22 _ _ _ BDA _ _ _ _ _ _ • •
2"
ANSI 300 22 _ _ _ BDC _ _ _ _ _ _ • •
ANSI 150 22 _ _ _ BFA _ _ _ _ _ _ • •
3"
ANSI 300 22 _ _ _ BFC _ _ _ _ _ _ • •
1/2" ANSI 150 23 _ _ _ CAA _ _ _ _ _ _ • •
ANSI 150 23 _ _ _ CCA _ _ _ _ _ _ • •
1"
ANSI 300 23 _ _ _ CCC _ _ _ _ _ _ • •
2.9" ANSI 150 22 _ _ _ CGA _ _ _ _ _ _ • •
1-1/2"
ANSI 300 22 _ _ _ CGC _ _ _ _ _ _ • •
Flush Flanged ANSI 150 22 _ _ _ CDA _ _ _ _ _ _ • •
Seal with Lower 2"
ANSI 300 22 _ _ _ CDC _ _ _ _ _ _ • •
1/2" ANSI 150 23 _ _ _ DAA _ _ _ _ _ _ • •
ANSI 150 23 _ _ _ DCA _ _ _ _ _ _ • •
1"
ANSI 300 23 _ _ _ DCC _ _ _ _ _ _ • •
ANSI 150 23 _ _ _ DGA _ _ _ _ _ _ • •
1-1/2"
4.1" ANSI 300 23 _ _ _ DGC _ _ _ _ _ _ • •
ANSI 150 23 _ _ _ DDA _ _ _ _ _ _ • •
2"
ANSI 300 22 _ _ _ DDC _ _ _ _ _ _ • •
ANSI 150 22 _ _ _ DFA _ _ _ _ _ _ • •
3"
ANSI 300 22 _ _ _ DFC _ _ _ _ _ _ • •
Table II continued next page
1
Standard facing 125-250 AARH RF (raised face) serrated surface finish.
4
Plastic Plugs are TEMPORARY ONLY to protect threads and MUST be REMOVED before installation
Note: Remote seal system pressure rating is body rating or seal rating, whichever is less.
32 ST 3000 Smart Pressure Transmitter
34-ST-16U-34
Issue 47
Page 4 of 11
Availability
STR9xx
TABLE II - SEALS (continued)
Diaphragm Lower Selection 3D 4G
316L SS 316L SS _ _ _ _ _ _ BA _ _ _ _ • •
®
Hastelloy C-276 316L SS _ _ _ _ _ _ BB _ _ _ _ • •
®
Hastelloy C-276
®
Hastelloy C-276 _ _ _ _ _ _ BC _ _ _ _ • •
Wetted Material ®
Monel 400 Monel 400® _ _ _ _ _ _ BE _ _ _ _ • •
Tantalum 316L SS _ _ _ _ _ _ BF _ _ _ _ 1 1
®
Tantalum Hastelloy C-276 _ _ _ _ _ _ BG _ _ _ _ 1 1
Tantalum Tantalum Clad _ _ _ _ _ _ BH _ _ _ _ 10 10
Upper Upper Insert Selection
Non-Wetted Material
316L SS 316L SS ________4___ • •
(upper, upper insert)
Carbon Steel 316L SS ________5___ • •
Flush Flanged Bolts 6 No Selection _________0__ • •
Seal with Flushing None __________0 _ • •
Lower Connections One 1/4" with plastic plug __________H_ • •
(continued)
and Plugs4 One 1/4" with metal plug __________J _ • •
Metal plug material Two 1/4" with plastic plugs __________M_ • •
will be the same as Two 1/4" with metal plugs __________N_ • •
Lower material, if One 1/2" with plastic plug __________P_ • •
metal plug is chosen - One 1/2" with metal plug __________Q_ • •
(SS Plug for CS Lower Two 1/2" with plastic plugs __________R_ • •
and Tantalum Clad) Two 1/2" with metal plugs __________S_ • •
Klinger® C-4401
___________K c c
(non-asbestos)
Gasket Grafoil® ___________G • •
Teflon® ___________T c c
Gylon® 3510 ___________L d d
Diaphragm 1
Flange Size Flange Pressure Rating Selection
Diameter
3" ANSI Class 150 _ _ _ EFA _ _ _ _ _ _ • •
2.8" (2.8" OD ANSI Class 300 _ _ _ EFC _ _ _ _ _ _ • •
extension) DIN DN80-PN40 _ _ _ EFM _ _ _ _ _ _ • •
4" ANSI Class 150 _ _ _ FGA _ _ _ _ _ _ • •
3.5" (3.70" OD ANSI Class 300 _ _ _ FGC _ _ _ _ _ _ • •
extension) DIN DN100-PN40 _ _ _ FGP _ _ _ _ _ _ • •
Flange Seal Diaphragm Ext. Tube Selection
with Extended 316L SS 316L SS _ _ _ _ _ _ EA _ _ _ _ • •
Wetted Material
Diaphragm
®
Hastelloy C-276 316L SS _ _ _ _ _ _ EB _ _ _ _ • •
® ®
Hastelloy C-276 Hastelloy C-276 _ _ _ _ _ _ EC _ _ _ _ • •
CS (Nickel Plated) ________7___ • •
Flange Material
316L SS ________8___ • •
Bolts No Selection _________0__ • •
2" __________2 _ • •
Extension Length 4" __________4_ • •
6" __________6_ • •
No Selection No Selection ___________0 • •
Table II continued next page
1
Standard facing 125-250 AARH RF (raised face) serrated surface finish.
4
Plastic Plugs are TEMPORARY ONLY to protect threads and MUST be REMOVED before installation
6
Bolt material will be same as Upper Material. However, if Table III bolt/nut option is chosen, seal bolt material will be the same.
Note: Remote seal system pressure rating is body rating or seal rating, whichever is less.
ST 3000 Smart Pressure Transmitter 33
34-ST-16U-34
Issue 47
Page 5 of 11
Availability
STR9xx
TABLE II - SEALS (continued)
Availability
STR9xx
TABLE II - SEALS (continued)
Diaphragm 1
Flange Size Flange Pressure Rating Selection 3D 4G
Diameter
Taylor
3.5" Wedge 5" 750 psi _ _ _ HM0 _ _ _ _ _ _ v
O.D.
Diaphragm Body Selection
316L SS 316L SS _ _ _ _ _ _ HA _ _ _ _ •
Wetted Material ®
Hastelloy C-276 316L SS _ _ _ _ _ _ HB _ _ _ _ •
® ®
Hastelloy C-276 Hastelloy C-276 _ _ _ _ _ _ HC _ _ _ _ •
Chemical Tee
"Taylor" Wedge
Non-Wetted Material No Selection ________0___ •
Bolts No Selection _________0__ •
Styles No Selection __________0 _ •
No Selection No Selection ___________0 •
Table II continued next page
1
Standard facing 125-250 AARH RF (raised face) serrated surface finish.
4
Plastic Plugs are TEMPORARY ONLY to protect threads and MUST be REMOVED before installation
7
Tantalum Body has Tantalum wetted parts and 316 SS non-wetted parts
Note: Remote seal system pressure rating is body rating or seal rating, whichever is less.
34 ST 3000 Smart Pressure Transmitter
34-ST-16U-34
Issue 47
Page 6 of 11
Availability
STR9xx
TABLE II - SEALS (continued)
Seal Pressure Rating
Diaphragm Threaded Process Connection *
304 SS
Selection 3D 4G
Diameter Size (NPT Female)
C.S. Bolts
Bolts
1/2 NPT _ _ _ JJG _ _ _ _ _ _ • •
2.4" 3/4 NPT 2,500 psi 1,250 psi _ _ _ JKG _ _ _ _ _ _ • •
1 NPT _ _ _ JLG _ _ _ _ _ _ • •
1/2 NPT _ _ _ KJG _ _ _ _ _ _ • •
2.9" 3/4 NPT 2,500 psi 1,250 psi _ _ _ KKG _ _ _ _ _ _ • •
1 NPT _ _ _ KLG _ _ _ _ _ _ • •
1/2 NPT _ _ _ LJG _ _ _ _ _ _ • •
4.1" 3/4 NPT 1,500 psi 750 psi _ _ _ LKG _ _ _ _ _ _ • •
1 NPT _ _ _ LLG _ _ _ _ _ _ • •
Diaphragm Lower Selection
316L SS Carbon Steel _ _ _ _ _ _ JA _ _ _ _ • •
316L SS 316L SS _ _ _ _ _ _ JB _ _ _ _ • •
Hastelloy® C-276 316L SS _ _ _ _ _ _ JC _ _ _ _ • •
Wetted Material
Hastelloy® C-276 Hastelloy® C-276 _ _ _ _ _ _ JD _ _ _ _ • •
®
Monel 400 Monel 400® _ _ _ _ _ _ JE _ _ _ _ • •
Tantalum 316L SS _ _ _ _ _ _ JF _ _ _ _ 1 1
Seal with Tantalum Hastelloy® C-276 _ _ _ _ _ _ JG _ _ _ _ 1 1
Threaded Non-Wetted Material CS (Nickel Plated) ________A___ • •
Process (upper) Stainless Steel ________C___ w w
Connection Carbon Steel _________C__ 1 1
Bolts 8
304 SS _________D__ • •
Flushing None __________0 _ • •
Connections One 1/4" with plastic plug __________H_ • •
and Plugs4 One 1/4" with metal plug __________J _ • •
Metal plug material Two 1/4" with plastic plugs __________M_ • •
will be the same as Two 1/4" with metal plugs __________N_ • •
Lower material, if One 1/2" with plastic plug __________P_ 11 11
metal plug is chosen - One 1/2" with metal plug __________Q_ 11 11
(SS Plug for CS Lower Two 1/2" with plastic plugs __________R_ 11 11
and Tantalum Clad) Two 1/2" with metal plugs __________S_ 11 11
Klinger® C-4401
___________K c c
(non-asbestos)
Gasket Grafoil® ___________G • •
Teflon® ___________T c c
Gylon® 3510 ___________L d d
4
Plastic Plugs are TEMPORARY ONLY to protect threads and MUST be REMOVED before installation
8
If Table III Bolt/Nut option is chosen, Seal bolts will ship as same material, and MAWP may change.
Note: Remote seal system pressure rating is body rating or seal rating, whichever is less.
ST 3000 Smart Pressure Transmitter 35
34-ST-16U-34
Issue 47
Page 7 of 11
Availability
STR9xx
TABLE II - SEALS (continued)
Diaphragm
Flange Size Pressure Rating Selection 3D 4G
Diameter
2.4" _ _ _ RFK _ _ _ _ _ _ • •
for 3" Pipe ≥
8-Bolt 1,500 psi 1,500 psi
4" pipe
Design _ _ _ RGK _ _ _ _ _ _ • •
2.4" _ _ _ RPK _ _ _ _ _ _ • •
for 3" Pipe ≥
6-Bolt 1,250 psi 1,250 psi
4" pipe
Design _ _ _ RQK _ _ _ _ _ _ • •
Diaphragm Lower Housing Selection
316L SS Carbon Steel _ _ _ _ _ _ RA _ _ _ _ • •
316L SS 316L SS _ _ _ _ _ _ RB _ _ _ _ • •
®
Wetted Material Hastelloy C-276 316L SS _ _ _ _ _ _ RC _ _ _ _ • •
Saddle Seal ®
Hastelloy C-276
®
Hastelloy C-276 _ _ _ _ _ _ RD _ _ _ _ • •
10
316L SS N/A-Body Only _ _ _ _ _ _ SB _ _ _ _ • •
® 10
Hastelloy C-276 N/A-Body Only _ _ _ _ _ _ SC _ _ _ _ • •
Body Bolts 8, 10 Selection
Non-Wetted Material Carbon Steel Carbon Steel ________B___ 1 1
316L SS 304 SS ________C___ • •
No Selection No Selection _________0__ • •
Styles No Selection __________0 _ • •
Klinger® C-4401
___________K • •
(non-asbestos)
Gasket Grafoil® ___________G • •
Teflon® ___________T • •
Gylon® 3510 ___________L • •
8
If Table III Bolt/Nut option is chosen, Seal bolts will ship as same material, and MAWP may change.
9
All sanitary seals have dairy grade 3A approval.
10
Bolts are not included with "body only" selection.
Note: Remote seal system pressure rating is body rating or seal rating, whichever is less.
36 ST 3000 Smart Pressure Transmitter
34-ST-16U-34
Issue 47
Page 8 of 11 Availability
STR9xx
34-ST-16U-34
Issue 47
Page 9 of 11
STR9xx
TABLE III - OPTIONS (continued) Selection
Warranty Options 3D 4G
Additional W arranty - 1 year W1 • •
Additional W arranty - 2 years W2 • • b
Additional W arranty - 3 years W3 • •
Additional W arranty - 4 years W4 • •
Approval
Approval Type Location or Classification Selection 3D 4G
Body
No hazardous location approvals 9X • •
Explosion Proof Class I, Div. 1, Groups A,B,C,D
FM Dust-Ignitionproof Class II, III Div. 1, Groups E,F,G
SM 1C • •
Approvals Non-Incendive Class I, Div. 2, Groups A,B,C,D
Intrinsically Safe Class I, II, III, Div. 1, Groups A,B,C,D,E,F,G
Ex ia IIC
T4 (Ta = –50°C to +93°C);
Intrinsically Safe,
T5 (Ta = –50°C to +85°C);
Zone 0 T6 (Ta = –50°C to +70°C)
Enclosure IP 66/67
3S • •
Ex ia IIC
T4 (Ta = –50°C to +93°C);
Intrinsically Safe,
T5 (Ta = –50°C to +85°C);
Zone 1 T6 (Ta = –50°C to +70°C)
Enclosure IP 66/67
Ex tD A20 IP6X
Dust-tight Enclosure, T95°C (at Ta = 93°C) or
Zone 0 T80°C (at Ta = 78°C))
Enclosure IP 66/67
Ex d IIC
T5 (Ta = –40°C to +93°C), 33 26 26
T6 (Ta = –40°C to +78°C)
Flameproof and
Supply 11- 42Vdc
Dust-tight Enclosure,
Ex tD A21 IP6X
Zone 1 T95°C (at Ta = 93°C) or
T80°C (at Ta = 78°C)
Enclosure IP 66/67
Ex nA, IIC
T5 (Ta = –40°C to +93°C),
T6 (Ta = –40°C to +78°C);
Non-Sparking, Zone 2 Supply < 42Vdc, 23mA
ATEX 10 3N • •
Zone 2 Ex tD A22 IP6X
(LCIE) T95°C (at Ta = 93°C) or
T80°C (at Ta = 78°C) (Honeywell).
Enclosure IP 66/67
Ex ia IIC
T4 (Ta = –50°C to +93°C);
T5 (Ta = –50°C to +85°C);
T6 (Ta = –50°C to +70°C);
Ui = 30V; Ii = 100mA
Ex tD A20 IP6X
Multiple Marking 11 T95°C (at Ta = 93°C) or
T80°C (at Ta = 78°C)
Int. Safe, Zone 0/1 and
Dust-tight Enclosure, Ex d IIC
T5 (Ta = –40°C to +93°C),
or T6 (Ta = –40°C to +78°C)
Supply 11- 42Vdc 3C 26 26
Flameproof, Zone 1 and Ex tD A21 IP6X
and Dust-tight Enclosure, T95°C (at Ta = 93°C) or
T80°C (at Ta = 78°C)
or
Ex nA, IIC
T5 (Ta = –40°C to +93°C),
Non-Sparking, Zone 2
T6 (Ta = –40°C to +78°C);
Zone 2 Supply < 42Vdc, 23mA
Ex tD A22 IP6X
T95°C (at Ta = 93°C) or
T80°C (at Ta = 78°C) (Honeywell)
Enclosure IP 66/67
34-ST-16U-34
Issue 47
Page 10 of 11
STR9xx
TABLE III - Approvals Options (continued)
3D 4G
Approval Body Approval Type Location or Classification Selection
Ex d IIC;
Flameproof,
T5 (Ta = -40 to +93ºC),
Zone 1
T6 (Ta = -40 to +78ºC)
IECEx CA 26 26
Ex ia IIC; T3, T4, T5 , T6
Intrinsically Safe,
See Spec for detailed temperature codes by b
Zone 0/1
Communications option
Intrinsically Safe,
Ex ia IIC T4, T5, T6 Z2 ● ●
Zone 0/1
SAEx
Flameproof, Zone 1 Ex d IIC T5, T6 Enclosure IP 66/67 ZD ● ●
(South
Africa) Multiple Marking 11
Int. Safe, Zone 0/1, or Ex ia IIC T4, T5, T6 ZA ● ●
Flameproof, Zone 1 Ex d IIC T5, T6 Enclosure IP 66/67
CERTUSP Flameproof, Zone 1 BR- Ex d IIC T5, T6 6D ● ●
INMETRO Intrinsically Safe, BR- Ex ia IIC; T4, T5, T6
(See CERTUSP certificate for detailed temperature codes by 6S ● ●
(Brazil) Zone 0/1 Communications option)
10
See ATEX installation requirements in the ST 3000 User's Manual
11
The user must determine the type of protection required for installation of the equipment. The user shall then check
the box [√] adjacent to the type of protection used on the equipment certification nameplate. Once a type of protection
has been checked on the nameplate, subsequently the equipment shall not be reinstalled using any of the other
certification types.
TABLE IV Selection
Factory Identification XXXX • •
RESTRICTIONS
Restriction Available Only With Not Available With
Letter Table Selection Table Selection
b Select only one option from this group
_ _ _ _ _ _ BF _ _ _ _,
_ _ _ _ _ _ BG _ _ _ _,
c II _ _ _ _ _ _ BH _ _ _ _,
_ _ _ _ _ _ JF _ _ _ _,
_ _ _ _ _ _ JG _ _ _ _,
_ _ _ _ _ _ BF _ _ _ _,
_ _ _ _ _ _ BG _ _ _ _,
d II
_ _ _ _ _ _ JF _ _ _ _,
_ _ _ _ _ _ JG _ _ _ _,
h I, II _2_-2___________
i III 1C or 2J
_ _ _ _ _ _ AF _ _ _ _
_ _ _ _ _ _ BF _ _ _ _
_ _ _ _ _ _ BG _ _ _ _
j II _ _ _ _ _ _ BH _ _ _ _
_ _ _ _ _ _ GG _ _ _ _
_ _ _ _ _ _ JF _ _ _ _
_ _ _ _ _ _ JG _ _ _ _
m III SM
n III 1C, 2J
o III CR
0 _ _ _ _ _ _ _ _ _ _ _ _,
q II 2 _ _ _ _ _ _ _ _ _ _ _ _,
4____________
s III FF, ME
v I 2__
w II _ _ _ _ _ _ JA _ _ _ _
x III FF, SM
Restrictions continued next page
ST 3000 Smart Pressure Transmitter 39
34-ST-16U-34
Issue 47
Page 11 of 11
RESTRICTIONS - (continued)
Restriction Available Only With Not Available With
Letter Table Selection Table Selection
I 2__
y III MB, SB, FB
II _2__________
z I __D
1 III F7
2 III MX, SX III FB, MB, SB
3 I 5__
5 II ___________0
6 II __________A_
I 1 _ _, 3 _ _
7
III CR
CC, G1, G2, N1, N2, 0X, TP, MT, F1,
8 III
TC, FC
_ _ _ _ _ _ AA2_ _ _
9 II
_ _ _ _ _ _ AB2_ _ _
II ___________T
10 II __________0_
III F7
_ _ _ _ _ _JJG_ _ _
_ _ _ _ _ _JKG_ _ _
_ _ _ _ _ _JLG_ _ _
11 II
_ _ _ _ _ _CAA_ _ _
_ _ _ _ _ _CCA_ _ _
_ _ _ _ _ _CCC_ _ _
14 III HC or H6 and WP III FF
15 III FF
16 I __C
21 III FF
22 III SL
24 III I & II 2__-_2__________
_A__________,
25 II _G _ _ _ _ _ _ _ _ _ _ ,
_2 _ _ _ _ _ _ _ _ _ _
This approval code requires the selection of
26 III a certified conduit plug:
A5, A6 or A7
SM
FM Approvals is a service mark of FM Global
®
Hastelloy is a registered trademark of Haynes International
®
Monel 400 is a registered trademark of Special Metals Corporation.
®
HART is a registered trademark of HART Communication Foundation.
TM
FOUNDATION Fieldbus is a registered trademark of Fieldbus Foundation.
®
Teflon is a registered trademark of DuPont.
®
Neobee is a registered trademark of Stepan Company.
®
Syltherm 800 is a Trademark of Dow Corning Corporation
®
Klingersil C-4401 is a registered trademark of THERMOSEAL, INC
®
GRAFOIL is a registered trademarks of GrafTech International Holdings Inc
®
Gylon 3510 is registered trademark of Garlock Sealing Technologies
®
Tri-Clover Tri-Clamp is a registered trademark of Alfa-Laval
® ®
DC 200 and DC 704 are registered trademarks of Dow Corning
40 ST 3000 Smart Pressure Transmitter
Singapore
Honeywell Pte Ltd.
Phone: +(65) 6580 3278
Fax: +(65) 6445-3033
South Korea
Honeywell Korea Co Ltd
Phone: +(822) 799 6114
Fax: +(822) 792 9015