50% found this document useful (2 votes)
575 views2 pages

Carina FP GB

The CARINA fire detection unit is a conventional panel with 8 zones and a capacity of 256 detectors. It is DNV and WheelMark certified for marine applications. The panel monitors for fire and faults, automatically switches the backup power supply if main power is lost, and stores the last 500 events with timestamps. It has 3 access levels and supports configuration through the front panel or a connected PC. The panel includes monitored fire and fault outputs as well as programmable outputs for additional control.

Uploaded by

Ahmed Mostafa
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
50% found this document useful (2 votes)
575 views2 pages

Carina FP GB

The CARINA fire detection unit is a conventional panel with 8 zones and a capacity of 256 detectors. It is DNV and WheelMark certified for marine applications. The panel monitors for fire and faults, automatically switches the backup power supply if main power is lost, and stores the last 500 events with timestamps. It has 3 access levels and supports configuration through the front panel or a connected PC. The panel includes monitored fire and fault outputs as well as programmable outputs for additional control.

Uploaded by

Ahmed Mostafa
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

CARINA CONVENTIONAL FIRE DETECTION

The CARINA fire detection unit is a conventional type panel including 8 zones. Its
total capacity is 256 detectors.
It is DNV and WheelMark certified. It is suitable for any application.

PG01 PRODUCT DATA SHEET

Functions

• Fire and fault monitoring (insulation defect, open or short-


circuited in an area)
• Main supply automatically switched over to the backup supply
if lost
Automatic return to the main supply when it is available again
• History of the last 500 events with timestamping
• Day/night lighting
• 3 access levels:
- Level 1 = all users have read-only access to information, to
the audio alarm acknowledgement, to the test function and
to the Day/Night lighting function
- Level 2 = keypad code access for anyone having a safety
responsibility for fire or fault resetting. Unit intentional
prolonged stoppage
- Level 3 = keypad code access for anyone having a safety
responsibility for configuration creation or modification
DESCRIPTION

Application
Configuration
The CARINA fire detection unit is a conventional type panel • Through a flat keyboard on the front panel through a PC
including 8 zones. connected to the serial port (RS232):
Its total capacity is 256 manual call points or detectors, with a - Identification of zones
standard or waterproof base. - Adjustment of time delays
For each zone, you can connect 32 detectors and/or manual initiators - Password creation or modification
(optical smoke detectors, rate of temperature rise detectors, flame
detectors, in standard or intrinsically safe mode), remote alarm Outputs
indicators, etc.
• Monitored 24 VDC fire output, with a 2 minute factory set time
Functional characteristics delay (*) in accordance with the Bureau Veritas requirement.
(*) If no one has acknowledged the audio signal after 2 minutes,
Display the output is enabled
• Immediate, monitored fault output
• Functional conditions: Wide viewing angle leds • Immediate, monitored fire output fire.
+ LCD (8x40 characters) • 1 24 VDC programmable output (fire, fire in two specific zones
7 or 8, fault, fire and fault, acknowledged or otherwise, time
• Multilingual text: Language definable by the display: delay), monitored and protected by a resettable fuse.
French, English, Spanish • 1 programmable, dry contact type output (fire, fire in two
• Front panel: Texts in 3 languages (French/English specific zones 7 or 8, fault, fire and fault, acknowledged or
and Spanish) otherwise, time delay, NO or NC), not monitored, and protected
by a resettable fuse.

Written by MOB, 08/03/11 Approved by JMA, 15/04/2011 FP CARINA REV A.doc Page 1/2
Document not contractual

MARINELEC TECHNOLOGIES Tel :33 (0) 2 98 52 16 44 Fax : 33(0) 2 98 64 74 05 marinelec@marinelec.com www.marinelec.com


• RS485 port for transfer to an external box or supervision Loops:
equipment and V.D.R., NMEA protocol
• RS232 for connection to a PC (configuration, history) • 2-conductor shielded cable, recommended cross-section
0.75mm²
Mechanical features • Maximum length for each loop = 300 m
• Consumption = 0.03 A nominal, 0.15 A max
Dimensions (LxWxH): (With 32 alarm detectors and 32 Leds for alarm transfer)
• Protection by 0.2 A resettable fuse
• Box: 231 x 194 x 95 mm
• Front panel: 270 x 204 mm Breaking capacity on outputs:
• Flush mounting: 233x 196 mm
• 1 A for a 24 VDC supply
270.00

231.00

Standards and Approvals

14 X PG9
• Wheelmark, DNV, GL.
204.00

Connection

MAXI 1A / 24VCC
MAXI 1A / 24VCC

MAXI 1A / 24VCC
CARINA BC FR

MAXI 1A / 24VCC *
MAXI 1A / 24VCC *

ligne de détection

ligne de détection 24

ligne de détection 26

ligne de détection 28

ligne de détection

ligne de détection 32

ligne de détection 34

ligne de détection 36
INDICE C

8
270.00

"A" = de 0 à 30mm

10

11

12

13

14

15

16

17

18

19
2

20

21

22

23

25

27

29

30

31

33

35
"A"

+24VDC alimentation principale

sortie DERANGEMENT
immédiate
RS485 A+
0VDC alimentation principale

+24VDC alimentation secours

sortie FEU

immédiate
0VDC OUT
0VDC alimentation secours

RS 485 B-

sortie prog. B
+24VDC OUT
VDR A+ *
- -

+
VDR B- *
Découpe d'encastrement :

cablage identique

cablage identique

cablage identique

cablage identique

cablage identique

cablage identique

cablage identique
97.00

+ sortie prog. A (24VDC)


+ SIRENE (24VDC)
Longueur = 243+2=245mm

- SIRENE (0VDC) sortie FEU


si non acquittée sur la centrale

- sortie prog. A (0VDC)


123.00

Largeur = 194+2= 196mm

temporisée à deux minutes

ligne 1

ligne 1

ligne 1

ligne 1

ligne 1

ligne 1

ligne 1
indicateur d'action indicateur d'action

Weight 3 kg
detecteur 1 bris de glace detecteur .... bris de glace detecteur 10 2,2 Kohm/1W
étanche

Ingress Protection: IP44 -R


L1in L1out

L2
nc nc no no c c
-R
L1in L1out

L2 +
- -R
L1in L1out

L2
1 Kohm/1W E E

Materials: Protected steel box


earth earth earth earth earth earth earth earth earth
earth earth earth

Aluminium front panel, covered with a silk-screen printed lexan


Associated products
Electrical characteristics
Detectors: Call points: Horns: Test equipment:
Main power supply:

• 24 VDC (- 25% + 30%)

Backup power supply:

• 24 VDC (-25% +30%)

3rd power source :

• two 3V batteries (CR2032) to supply the alarm in the event of


loss of the main and backup power sources

Power supply switching:

• Automatic

Supply protection:

• By a 3.15 A 5x20 mm fuse


Details in the "conventional accessories" product data sheet

REPORT10S: Carte with relay possessing 10 dry


Consumption: contact output NO/NC driven by the CARINA fire
detection
• 0.5 A max

Written by MOB, 08/03/11 Approved by JMA, 15/04/2011 FP CARINA FR REV A.doc Page 2/2
Document not contractual

MARINELEC TECHNOLOGIES Tel :33 (0) 2 98 52 16 44 Fax : 33(0) 2 98 64 74 05 marinelec@marinelec.com www.marinelec.com