Halogen-Free Fire-Resistant Security Cable

This document provides information on an N2XH-FE 180/E 30 security cable that is halogen-free and has improved fire characteristics. Some key points: - It has a temperature range of -30°C to +70°C and can operate at 90°C. It has a voltage rating of 0.6/1 kV and passed a 4000V test. - The cable structure includes bare copper conductors, cross-linked polyethylene insulation, cores stranded in layers, and a thermoplastic halogen-free polyolefin outer sheath. - It passes various fire tests including flame tests and tests for corrosiveness of combustion gases and smoke density. It is self

Uploaded by

Delwin
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
147 views17 pages

Halogen-Free Fire-Resistant Security Cable

This document provides information on an N2XH-FE 180/E 30 security cable that is halogen-free and has improved fire characteristics. Some key points: - It has a temperature range of -30°C to +70°C and can operate at 90°C. It has a voltage rating of 0.6/1 kV and passed a 4000V test. - The cable structure includes bare copper conductors, cross-linked polyethylene insulation, cores stranded in layers, and a thermoplastic halogen-free polyolefin outer sheath. - It passes various fire tests including flame tests and tests for corrosiveness of combustion gases and smoke density. It is self

Uploaded by

Delwin
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 17

Energy- and Power Cable / Low Voltage and Security Cables

N2XH-FE 180/E 30 security cable, halogen-free, 0,6/1 kV, with improved fire
characteristics

Technical data Cable structure Properties


Ⴠ Halogen-free security cable with improved Ⴠ Bare copper-conductor, to Ⴠ Halogen free, no separation of corrosive
characteristics in the case of fire to DIN VDE 0295 cl.1 or cl.2, single-wire and toxic gases
DIN VDE 0266 or multi-wire, BS 6360 cl.1 or cl.2, Ⴠ Flame retardant and hardly flammable
Ⴠ Temperature range IEC 60228 cl.1 or cl.2 Ⴠ Self-extinguished and fire resistant
-30°C to +70°C Ⴠ Core insulation of cross-linked Ⴠ No flame propagation, therefore security
Ⴠ Permissible operating temperature polyethylene, compound type 2XI1 to from fire
at conductor +90°C DIN VDE 0276 part 604 Ⴠ low smoke density, low impairment of
Ⴠ Nominal voltage U0/U 0,6/1 kV Ⴠ Core identification to DIN VDE 0293-308 escape routes and fire extinguishing
Ⴠ Test voltage 4000 V and 0276 part 604 activities
Ⴠ Minimum bending radius Ⴠ GN-YE conductor, 3 cores and above Ⴠ Toxicological harmless
15x cable Ø Ⴠ Cores stranded in layers Ⴠ No self-ignition
Ⴠ Radiation resistance Ⴠ Overall core covering, halogen-free filling Ⴠ Maintenance of functionality during the
up to 200x106 cJ/kg (up to 200 Mrad) compound, pressed increased current load
Ⴠ Caloric load values Ⴠ Outer sheath of thermoplastic halogen-free Ⴠ FE 180: Insulation integrity for 180
see Technical Informations polyolefine, flame retardant minutes. Tests acc.to DIN VDE 0472
Ⴠ Sheath colour orange part 814 ฬ IEC 60331.
Tests Insulation integrity under direct
Ⴠ Flame test acc. to flame propagation for the test period
DIN VDE 0482-332-3, BS 4066 part 3, of 180 minutes.
DIN EN 60332-3, IEC 60332-3 (previously Ⴠ E 30: Functionality of electrical cable
DIN VDE 0472 part 804 test method C) systems for minimum 30 minutes. Test to
Ⴠ Corrosiveness of combustion gases DIN 4102 part 12. This fulfils the demands
acc. to DIN VDE 0482 part 267, of technical guide lines for fire protection
DIN EN 50267-2-2, IEC 60754-2 (supplement 1 to DIN VDE 0108 part 1).
(equivalent DIN VDE 0472 part 813) The functionality for 30 minutes assures
Ⴠ Halogen-free acc. to DIN VDE 0482 when persons and animals are to be saved
part 267, DIN EN 50267-2-1, IEC 60754-1 from a burning building. 30 minutes
(equivalent DIN VDE 0472 part 815) secures the functional performance of the
Ⴠ Smoke density acc. to DIN VDE 0482 fire warning and alarm systems, safety and
part 1034-1+2, DIN EN 61034-1+2, spare lighting, passenger lifts with
IEC 61034-1+2, BS 7622 part 1+2 evacuation circuits, except the cables which
(previously DIN VDE 0472 part 816) are installed within the ladder shafts and
engine rooms.

Note
Ⴠ re = round conductor, single-wire
rm = round conductor, multi-wire
Ⴠ AWG sizes are approximate equivalent
values. The actual cross-section is in mm².
Ⴠ LS0H = Low Smoke Zero Halogen
Q
Application
Security cables are ideal for use everywhere, where in case of fire human life and material assets are to be protected and safety conciousness take a
special significance, e. g. in industrial complexes, power stations, communal establishment, hotels, airports, underground railway networks, hospitals
and outpatients clinic (DIN VDE 0107), department stores, data processing centres, theaters, cinemas, in multi-storey buildings, public gatherings,
schools etc. (DIN VDE 0108), mining works, offshore plants, leading centres, traffic communication, emergency power supply and alarm systems.
The cables are suitable for fixed installation in dry and moist rooms, in, above, on and beneath plaster as well as in masonary walls and in concrete.
For the installation in conduit all precautions must be taken that no accumulation of water can occur in the pipes.
= The product is conformed with the EC Low-Voltage Directive 2006/95/EC.

Part no. No.cores x Outer Ø Cop. Weight AWG-No. Part no. No.cores x Outer Ø Cop. Weight AWG-No.
cross-sec. app. mm weight app. kg / km cross-sec. app. mm weight app. kg / km
mm² kg / km mm² kg / km
52058 1 x 4 re 8,0 38,0 155,0 12 52063 1 x 35 rm 14,0 336,0 460,0 2
52059 1 x 6 re 9,0 58,0 190,0 10 52064 1 x 50 rm 15,5 480,0 590,0 1
52060 1 x 10 re 10,0 96,0 215,0 8 52065 1 x 70 rm 17,5 672,0 820,0 2/0
52061 1 x 16 re 10,5 154,0 240,0 6 52066 1 x 95 rm 19,5 912,0 1090,0 3/0
52062 1 x 25 rm 13,0 240,0 380,0 4 52067 1 x 120 rm 21,0 1152,0 1350,0 4/0

Continuation Ⴇ

563
CW&A Edition 27 (published 01.04.2015)
Energy- and Power Cable / Low Voltage and Security Cables

N2XH-FE 180/E 30 security cable, halogen-free, 0,6/1 kV, with improved fire
characteristics
Part no. No.cores x Outer Ø Cop. Weight AWG-No. Part no. No.cores x Outer Ø Cop. Weight AWG-No.
cross-sec. app. mm weight app. kg / km cross-sec. app. mm weight app. kg / km
mm² kg / km mm² kg / km
52068 1 x 150 rm 23,0 1440,0 1650,0 300 kcmil 52093 3 x 120 / 70 rm 45,0 4128,0 5550,0 4/0
52069 1 x 185 rm 25,0 1776,0 2030,0 350 kcmil 52094 3 x 150 / 70 rm 48,5 4992,0 6560,0 300 kcmil
52070 1 x 240 rm 29,0 2304,0 2590,0 500 kcmil 52095 3 x 185 / 95 rm 54,0 6240,0 8240,0 350 kcmil
52071 2 x 1,5 re 11,5 29,0 170,0 16 52096 4 x 1,5 re 12,5 58,0 210,0 16
52072 2 x 2,5 re 12,0 48,0 190,0 14 52097 4 x 2,5 re 13,0 96,0 260,0 14
52073 2 x 4 re 13,0 77,0 260,0 12 52614 4 x 4 re 13,0 154,0 310,0 12
52074 2 x 6 re 14,0 115,0 310,0 10 52615 4 x 6 re 14,5 230,0 410,0 10
52075 2 x 10 re 15,5 192,0 430,0 8 52616 4 x 10 re 16,0 384,0 620,0 8
52076 2 x 16 re 17,5 307,0 600,0 6 52617 4 x 16 re 18,0 614,0 900,0 6
52077 2 x 25 rm 22,0 480,0 930,0 4 52628 4 x 25 rm 23,6 960,0 1600,0 4
52078 3 x 1,5 re 12,0 43,0 170,0 16 52629 4 x 35 rm 26,4 1344,0 2050,0 2
52079 3 x 2,5 re 12,5 72,0 220,0 14 52383 4 x 50 rm 29,5 1920,0 2761,0 1
52080 3 x 4 re 13,5 115,0 290,0 12 52432 4 x 70 rm 34,6 2688,0 3785,0 2/0
52081 3 x 6 re 14,5 173,0 370,0 10 52433 4 x 95 rm 39,0 3648,0 5010,0 3/0
52082 3 x 10 re 16,5 288,0 530,0 8 52434 4 x 120 rm 43,5 4608,0 6135,0 4/0
52083 3 x 16 re 18,5 461,0 760,0 6 52618 5 x 1,5 re 12,0 72,0 210,0 16
52084 3 x 25 rm 23,5 720,0 1160,0 4 52619 5 x 2,5 re 13,0 120,0 280,0 14
52088 3 x 25 / 16 rm 22,5 874,0 1430,0 4 52620 5 x 4 re 14,5 192,0 380,0 12
52085 3 x 35 rm 26,0 1080,0 1560,0 2 52621 5 x 6 re 15,5 288,0 510,0 10
52089 3 x 35 / 16 rm 28,0 1162,0 1810,0 2 52622 5 x 10 re 18,0 480,0 760,0 8
52086 3 x 50 rm 29,0 1440,0 2030,0 1 52623 5 x 16 re 20,0 768,0 1120,0 6
52090 3 x 50 / 25 rm 32,0 1680,0 2340,0 1 52626 5 x 25 rm 24,5 1200,0 1840,0 4
52087 3 x 70 rm 34,0 2016,0 2890,0 2/0 52627 5 x 35 rm 33,5 1680,0 2510,0 2
52091 3 x 70 / 35 rm 35,0 2352,0 3190,0 2/0 52624 7 x 1,5 re 13,0 101,0 250,0 16
52092 3 x 95 / 50 rm 40,0 3216,0 4350,0 3/0 52625 12 x 1,5 re 16,5 173,0 390,0 16

Dimensions and specifications may be changed without prior notice. (RQ02)

564
CW&A Edition 27 (published 01.04.2015)
Energy- and Power Cable / Low Voltage and Security Cables

N2XCH-FE 180/E 30 security cable, halogen-free, 0,6/1 kV, with improved


fire characteristics

Technical data Cable structure Properties


Ⴠ Halogen-free security cable with improved Ⴠ Bare copper-conductor, to Ⴠ Halogen-free; no evolution of corrosive
characteristics in the case of fire to DIN VDE 0295 cl.1 or cl.2, single-wire and toxic gases
DIN VDE 0266 or multi-wire, BS 6360 cl.1 or cl.2, Ⴠ Flame retardant and hardly flammable
Ⴠ Temperature range IEC 60228 cl.1 or cl.2 Ⴠ Self-extinguished and fire resistant
-30°C to +70°C Ⴠ Core insulation of cross-linked Ⴠ No flame propagation, therefore security
Ⴠ Permissible operating temperature polyethylene, compound type 2XI1 to from fire
at conductor +90°C DIN VDE 0276 part 604 Ⴠ Low smoke density, no darkening of
Ⴠ Nominal voltage U0/U 0,6/1 kV Ⴠ Core identification to DIN VDE 0293-308 emergency exits without hindering the fire
Ⴠ Test voltage 4000 V and 0276 part 604 extinguishing works
Ⴠ Minimum bending radius Ⴠ Cores stranded in layers Ⴠ Toxicological harmless
15x cable Ø Ⴠ Overall core covering, halogen-free filling Ⴠ No self-ignition
Ⴠ Radiation resistance compound, pressed Ⴠ Maintenance of functionality during the
up to 200x106 cJ/kg (up to 200 Mrad) Ⴠ Concentric conductor of Cu-bare wires with increased current load
Ⴠ Caloric load values helix of copper tape Ⴠ FE 180: Insulation integrity for 180
see Technical Informations Ⴠ Outer sheath of thermoplastic halogen-free minutes. Tests acc.to DIN VDE 0472
polyolefine, flame retardant part 814 ฬ IEC 60331.
Ⴠ Sheath colour orange Insulation integrity under direct
Tests flame propagation for the test period
Ⴠ Flame test acc. to of 180 minutes.
DIN VDE 0482-332-3, BS 4066 part 3, Ⴠ E 30: Functionality of electrical cable
DIN EN 60332-3, IEC 60332-3 (previously systems for minimum 30 minutes. Test
DIN VDE 0472 part 804 test method C) method to DIN 4102 part 12. This fulfils the
Ⴠ Corrosiveness of combustion gases demands of technical guide lines for fire
acc. to DIN VDE 0482 part 267, protection (supplement 1 to DIN VDE 0108
DIN EN 50267-2-2, IEC 60754-2 part 1).
(equivalent DIN VDE 0472 part 813) The functionality for 30 minutes assures
Ⴠ Halogen-free acc. to DIN VDE 0482 when persons and animals are to be saved
part 267, DIN EN 50267-2-1, IEC 60754-1 from a burning building. 30 minutes
(equivalent DIN VDE 0472 part 815) secures the functional performance of the
Ⴠ Smoke density acc. to DIN VDE 0482 fire warning and alarm systems, safety and
part 1034-1+2, DIN EN 61034-1+2, spare lighting, passenger lifts with
IEC 61034-1+2, BS 7622 part 1+2 evacuation circuits, except the cables which
(previously DIN VDE 0472 part 816) are installed within the ladder shafts and
engine rooms.

Note
Ⴠ re = round conductor, single-wire
rm = round conductor, multi-wire
Ⴠ AWG sizes are approximate equivalent
values. The actual cross-section is in mm².
Q
Ⴠ LS0H = Low Smoke Zero Halogen

Application
Everywhere, where in case of fire human life and material assets are to be protected and safety conciousness take a special significance, e. g. in
industrial complexes, power stations, communal establishment, hotels, airports, underground railway networks, hospitals and outpatients clinic (DIN
VDE 0107), department stores, data processing centres, theaters, cinemas, in multi-storey buildings, public gatherings, schools etc. (DIN VDE 0108),
mining works, offshore plants, leading centres, traffic communication, emergency power supply and alarm systems. Suitable for fixed installation in
dry and moist rooms, in, above, on and beneath plaster as well as in masonary walls and in concrete. These cables are suitable for outdoor applications
and in underground by using in conduits or tubes. For the installation in conduit all precautions must be taken that no accumulation of water can occur
in the pipes.
= The product is conformed with the EC Low-Voltage Directive 2006/95/EC.

Part no. No.cores x Outer Ø Cop. Weight AWG-No. Part no. No.cores x Outer Ø Cop. Weight AWG-No.
cross-sec. app. mm weight app. kg / km cross-sec. app. mm weight app. kg / km
mm² kg / km mm² kg / km
52098 2 x 1,5 / 1,5 re 13,0 52,0 200,0 16 52101 2 x 6 / 6 re 16,0 182,0 400,0 10
52099 2 x 2,5 / 2,5 re 14,0 80,0 250,0 14 52102 2 x 10 / 10 re 17,5 312,0 570,0 8
52100 2 x 4 / 4 re 15,0 123,0 310,0 12 52103 3 x 1,5 / 1,5 re 13,0 66,0 220,0 16

Continuation Ⴇ

565
CW&A Edition 27 (published 01.04.2015)
Energy- and Power Cable / Low Voltage and Security Cables

(N)HXH-FE 180/E 30 security cable, halogen-free, 0,6/1 kV, with improved


fire characteristics
Part no. No.cores x Outer Ø Cop. Weight AWG-No. Part no. No.cores x Outer Ø Cop. Weight AWG-No.
cross-sec. app. mm weight app. kg / km cross-sec. app. mm weight app. kg / km
mm² kg / km mm² kg / km
52714 2 x 2,5 re 12,5 48,0 290,0 14 52748 4 x 150 rm 49,0 5760,0 7650,0 300 kcmil
52715 2 x 4 re 13,5 77,0 345,0 12 52749 5 x 1,5 re 14,0 72,0 375,0 16
52716 2 x 6 re 14,5 115,0 410,0 10 52750 5 x 2,5 re 15,0 120,0 445,0 14
52717 2 x 10 re 16,0 192,0 540,0 8 52751 5 x 4 re 16,5 192,0 560,0 12
52718 2 x 16 rm 18,0 307,0 720,0 6 52752 5 x 6 re 18,0 288,0 690,0 10
52719 2 x 25 rm 21,0 480,0 1100,0 4 52753 5 x 10 re 20,0 480,0 950,0 8
52720 2 x 35 rm 24,0 672,0 1120,0 2 52754 5 x 16 rm 22,5 768,0 1300,0 6
52721 3 x 1,5 re 12,5 43,0 280,0 16 52755 5 x 25 rm 26,5 1200,0 1980,0 4
52722 3 x 2,5 re 13,5 72,0 330,0 14 52756 5 x 35 rm 36,0 1680,0 2600,0 2
52723 3 x 4 re 14,5 115,0 400,0 12 52757 7 x 1,5 re 15,0 101,0 365,0 16
52724 3 x 6 re 15,5 173,0 480,0 10 52758 7 x 2,5 re 16,5 168,0 540,0 14
52725 3 x 10 re 17,0 288,0 650,0 8 52759 10 x 1,5 re 18,0 144,0 580,0 16
52726 3 x 16 rm 19,0 461,0 850,0 6 52760 10 x 2,5 re 20,0 240,0 710,0 14
52727 3 x 25 rm 22,5 720,0 1300,0 4 52761 12 x 1,5 re 19,0 173,0 640,0 16
52728 3 x 35 rm 24,5 1080,0 1700,0 2 52762 12 x 2,5 re 20,5 288,0 790,0 14
52729 3 x 50 rm 27,5 1440,0 2200,0 1 52763 14 x 1,5 re 20,0 202,0 740,0 16
52730 3 x 70 rm 32,0 2016,0 3000,0 2/0 52764 14 x 2,5 re 21,5 336,0 880,0 14
52731 3 x 95 rm 35,5 2736,0 4000,0 3/0 52765 19 x 1,5 re 21,5 274,0 880,0 16
52732 3 x 120 rm 39,5 3456,0 4850,0 4/0 52766 19 x 2,5 re 23,5 456,0 1150,0 14
52733 3 x 150 rm 44,0 4320,0 5950,0 300 kcmil 52767 24 x 1,5 re 25,0 346,0 1100,0 16
52734 3 x 185 rm 49,5 5328,0 7450,0 350 kcmil 52768 24 x 2,5 re 27,0 576,0 1400,0 14
52735 3 x 240 rm 60,0 6910,0 8600,0 500 kcmil 52769 30 x 1,5 re 26,0 432,0 1300,0 16
52736 4 x 1,5 re 13,5 58,0 325,0 16 52770 30 x 2,5 re 28,5 720,0 1650,0 14
52737 4 x 2,5 re 14,0 96,0 385,0 14
52738 4 x 4 re 15,5 154,0 470,0 12
52739 4 x 6 re 16,5 230,0 580,0 10
52740 4 x 10 re 18,5 384,0 790,0 8
52741 4 x 16 rm 20,5 614,0 1100,0 6
52742 4 x 25 rm 24,5 960,0 1650,0 4
52743 4 x 35 rm 27,0 1344,0 2150,0 2
52744 4 x 50 rm 30,0 1920,0 2800,0 1
52745 4 x 70 rm 35,0 2688,0 3800,0 2/0
52746 4 x 95 rm 39,5 3648,0 5050,0 3/0
52747 4 x 120 rm 43,5 4608,0 6150,0 4/0

Dimensions and specifications may be changed without prior notice. (RQ02)

568
CW&A Edition 27 (published 01.04.2015)
Energy- and Power Cable / Low Voltage and Security Cables

(N)HXCH-FE 180/E 30 security cable, halogen-free, 0,6/1 kV, with improved fire
characteristics

Technical data Cable structure Properties


Ⴠ Halogen-free security cable with improved Ⴠ Bare copper-conductor, to Ⴠ Halogen-free; no evolution of corrosive
characteristics in the case of fire adapted to DIN VDE 0295 cl.1 or cl.2, single-wire and toxic gases
DIN VDE 0266 or multi-wire, BS 6360 cl.1 or cl.2, Ⴠ Flame retardant and hardly flammable
Ⴠ Temperature range IEC 60228 cl.1 or cl.2 Ⴠ Self-extinguished and fire resistant
-30°C to +70°C Ⴠ Core insulation of polymer Ⴠ No flame propagation, therefore security
Ⴠ Permissible operating temperature Ⴠ Core identification to DIN VDE 0293-308 from fire
at conductor +90°C Ⴠ Core stranded in layer Ⴠ Low smoke density, no darkening
Ⴠ Nominal voltage U0/U 0,6/1 kV Ⴠ Overall core covering Ⴠ Toxicological harmless
Ⴠ Test voltage 4000 V Ⴠ Copper wire screening with helix of copper Ⴠ No self-ignition
Ⴠ Minimum bending radius tape Ⴠ Maintenance of functionality during the
15xcable Ø Ⴠ Separator of special tape increased current load
Ⴠ Radiation resistance Ⴠ Outer sheath of polyolefin-compound, Ⴠ FE 180: Insulation integrity for 180
up to 200x106 cJ/kg (up to 200 Mrad) flame retardant minutes. Tests acc.to DIN VDE 0472
Ⴠ Caloric load values Ⴠ Sheath colour orange part 814 ฬ IEC 60331.
see Technical Informations Tests Insulation integrity under direct
Ⴠ Flame test acc. to flame propagation for the test period
DIN VDE 0482-332-3, BS 4066 part 3, of 180 minutes.
DIN EN 60332-3, IEC 60332-3 (previously Ⴠ E 30: Functionality of electrical cable
DIN VDE 0472 part 804 test method C) systems for minimum 30 minutes. Test
Ⴠ Corrosiveness of combustion gases method to DIN 4102 part 12. This fulfils
acc. to DIN VDE 0482 part 267, the demands of technical guide lines for
DIN EN 50267-2-2, IEC 60754-2 fire protection (supplement 1 to
(equivalent DIN VDE 0472 part 813) DIN VDE 0108 part 1).
Ⴠ Halogen-free acc. to DIN VDE 0482 The functionality for 30 minutes assures
part 267, DIN EN 50267-2-1, IEC 60754-1 when persons and animals are to be saved
(equivalent DIN VDE 0472 part 815) from a burning building. 30 minutes
Ⴠ Smoke density acc. to DIN VDE 0482 secures the functional performance of the
part 1034-1+2, DIN EN 61034-1+2, fire warning and alarm systems, safety and
IEC 61034-1+2, BS 7622 part 1+2 spare lighting, passenger lifts with
(previously DIN VDE 0472 part 816) evacuation circuits, except the cables which
are installed within the ladder shafts and
engine rooms.

Note
Ⴠ re = round conductor, single-wire
Ⴠ rm = round conductor, multi-wire
Ⴠ AWG sizes are approximate equivalent
values. The actual cross-section is in mm².
Ⴠ LS0H = Low Smoke Zero Halogen Q
Application
Everywhere, where in case of fire human life and material assets are to be protected and safety conciousness take a special significance, e. g. in
industrial complexes, power stations, communal establishment, hotels, airports, underground railway networks, hospitals and outpatients clinic (DIN
VDE 0107), department stores, data processing centres, theaters, cinemas, in multi-storey buildings, public gatherings, schools etc. (DIN VDE 0108),
mining works, offshore plants, leading centres, traffic communication, emergency power supply and alarm systems. Suitable for fixed installation in
dry and moist rooms, in, above, on and beneath plaster as well as in masonary walls and in concrete. These cables are suitable for outdoor applications
and in underground by using in conduits or tubes. For the installation in conduit all precautions must be taken that no accumulation of water can occur
in the pipes.
= The product is conformed with the EC Low-Voltage Directive 2006/95/EC.

Part no. No.cores x Outer Ø Cop. Weight AWG-No. Part no. No.cores x Outer Ø Cop. Weight AWG-No.
cross-sec. app. mm weight app. kg / km cross-sec. app. mm weight app. kg / km
mm² kg / km mm² kg / km
52900 2 x 1,5 / 1,5 re 13,0 52,0 220,0 16 52907 3 x 4 / 4 re 15,5 161,0 530,0 12
52901 2 x 2,5 / 2,5 re 13,5 80,0 385,0 14 52908 3 x 6 / 6 re 16,5 240,0 630,0 10
52902 2 x 4 / 4 re 14,5 123,0 470,0 10 52909 3 x 10 / 10 re 18,5 408,0 850,0 8
52903 2 x 6 / 6 re 16,0 182,0 550,0 10 52910 3 x 16 / 16 rm 20,5 643,0 1150,0 6
52904 2 x 10 / 10 re 18,0 312,0 730,0 8 52911 3 x 25 / 16 rm 24,0 902,0 1700,0 4
52905 3 x 1,5 / 1,5 re 13,5 66,0 380,0 16 52912 3 x 35 / 16 rm 26,5 1190,0 2150,0 2
52906 3 x 2,5 / 2,5 re 14,5 104,0 430,0 14 52913 3 x 50 / 25 rm 29,5 1723,0 2800,0 1

Continuation Ⴇ

569
CW&A Edition 27 (published 01.04.2015)
Energy- and Power Cable / Low Voltage and Security Cables

(N)HXCH-FE 180/E 30 security cable, halogen-free, 0,6/1 kV, with improved fire
characteristics
Part no. No.cores x Outer Ø Cop. Weight AWG-No. Part no. No.cores x Outer Ø Cop. Weight AWG-No.
cross-sec. app. mm weight app. kg / km cross-sec. app. mm weight app. kg / km
mm² kg / km mm² kg / km
52914 3 x 70 / 35 rm 33,0 2410,0 3800,0 2/0 52930 4 x 95 / 50 rm 41,5 4208,0 5750,0 3/0
52915 3 x 95 / 50 rm 37,5 3296,0 5100,0 3/0 52931 4 x 120 / 70 rm 47,0 5388,0 7100,0 4/0
52916 3 x 120 / 70 rm 42,5 4236,0 6250,0 4/0 52932 4 x 150 / 70 rm 52,0 6558,0 8550,0 300 kcmil
52917 3 x 150 / 70 rm 47,0 5100,0 6900,0 300 kcmil 52933 4 x 185 / 95 rm 58,0 8159,0 10700,0 350 kcmil
52918 3 x 185 / 95 rm 52,5 6383,0 8550,0 350 kcmil 52934 4 x 240 / 120 rm 64,0 10546,0 13930,0 500 kcmil
52919 3 x 240 / 120 rm 58,5 8242,0 11150,0 500 kcmil 52935 7 x 1,5 / 2,5 re 16,5 133,0 635,0 16
52920 4 x 1,5 / 1,5 re 14,5 81,0 435,0 16 52936 7 x 2,5 / 2,5 re 17,5 200,0 680,0 14
52921 4 x 2,5 / 2,5 re 15,5 128,0 500,0 14 52937 10 x 1,5 / 2,5 re 19,5 176,0 870,0 16
52922 4 x 4 / 4 re 16,5 200,0 610,0 12 52938 10 x 2,5 / 4 re 21,0 286,0 980,0 14
52923 4 x 6 / 6 re 17,5 297,0 740,0 10 52939 12 x 1,5 / 2,5 re 20,0 205,0 1050,0 16
52924 4 x 10 / 10 re 20,0 504,0 1050,0 8 52940 12 x 2,5 / 4 re 21,5 334,0 1050,0 14
52925 4 x 16 / 16 re 22,0 796,0 1350,0 6 52941 24 x 1,5 / 6 re 26,0 413,0 1900,0 16
52926 4 x 25 / 16 rm 26,0 1142,0 1950,0 4 52942 24 x 2,5 / 10 re 28,5 696,0 1900,0 14
52927 4 x 35 / 16 rm 28,5 1526,0 2400,0 2 52943 30 x 1,5 / 6 re 27,0 499,0 2200,0 16
52928 4 x 50 / 25 rm 32,0 2203,0 3200,0 1 52944 30 x 2,5 / 10 re 30,0 840,0 2200,0 14
52929 4 x 70 / 35 rm 37,0 3082,0 4300,0 2/0

Dimensions and specifications may be changed without prior notice. (RQ02)

570
CW&A Edition 27 (published 01.04.2015)
Energy- and Power Cable / Low Voltage and Security Cables

N2XH-FE 180/E 90 security cable, halogen-free, 0,6/1 kV, with improved fire
characteristics

Technical data Cable structure Properties


Ⴠ Halogen-free security cable with improved Ⴠ Bare copper-conductor, to Ⴠ Halogen-free; no evolution of corrosive
characteristics in the case of fire to DIN VDE 0295 cl.1 or cl.2, single-wire and toxic gases
DIN VDE 0266 or multi-wire, BS 6360 cl.1 or cl.2, Ⴠ Flame retardant and hardly flammable
Ⴠ Temperature range IEC 60228 cl.1 or cl.2 Ⴠ Self-extinguished and fire resistant
-30°C to +70°C Ⴠ Core insulation with cross-linked Ⴠ No flame propagation, therefore security
Ⴠ Permissible operating temperature polyethylene, compound type 2XI1 to from fire
at conductor +90°C DIN VDE 0276 part 604 Ⴠ Low smoke density, no darkening of
Ⴠ Nominal voltage U0/U 0,6/1 kV Ⴠ Core identification to DIN VDE 0293-308 emergency exits without hindering the fire
Ⴠ Test voltage 4000 V and 0276 part 604 extinguishing works
Ⴠ Minimum bending radius Ⴠ GN-YE conductor, 3 cores and above Ⴠ Toxicological harmless
12x cable Ø Ⴠ Cores stranded in layers Ⴠ No self-ignition
Ⴠ Radiation resistance Ⴠ Overall core covering, halogen-free filling Ⴠ Maintenance of functionality during the
up to 200x106 cJ/kg (up to 200 Mrad) compound, pressed increased current load
Ⴠ Caloric load values Ⴠ Outer sheath of thermoplastic halogen-free Ⴠ FE 180: Insulation integrity for 180
see Technical Informations polyolefine, flame retardant minutes. Tests acc.to DIN VDE 0472
Ⴠ Sheath colour orange part 814 ฬ IEC 60331.
Tests Insulation integrity under direct
Ⴠ Flame test acc. to flame propagation for the test period
DIN VDE 0482-332-3, BS 4066 part 3, of 180 minutes.
DIN EN 60332-3, IEC 60332-3 (previously Ⴠ E 90: Functionality of electrical cable
DIN VDE 0472 part 804 test method C) systems for minimum 90 minutes. Test
Ⴠ Corrosiveness of combustion gases method to DIN 4102 part 12. This fulfils the
acc. to DIN VDE 0482 part 267, demands of technical guide lines for fire
DIN EN 50267-2-2, IEC 60754-2 protection (supplement 1 to DIN VDE 0108
(equivalent DIN VDE 0472 part 813) part 1).
Ⴠ Halogen-free acc. to DIN VDE 0482 The functionality for 90 minutes assures
part 267, DIN EN 50267-2-1, IEC 60754-1 the functional performance of
(equivalent DIN VDE 0472 part 815) water-pressure-rising stations for the
Ⴠ Smoke density acc. to DIN VDE 0482 supply to avoid smoke and heat in
part 1034-1+2, DIN EN 61034-1+2, safety-stairs and inner rooms, ladder shafts
IEC 61034-1+2, BS 7622 part 1+2 and engine rooms for fire brigade lifts,
(previously DIN VDE 0472 part 816) emergency lifts for sickbeds in hospitals
and the fire brigade lifts.

Note
Ⴠ re = round conductor, single-wire
rm = round conductor, multi-wire
Ⴠ AWG sizes are approximate equivalent
values. The actual cross-section is in mm².
Ⴠ LSOH = Low Smoke Zero Halogen
Q
Application
Everywhere, where in case of fire human life and material assets are to be protected and safety conciousness take a special significance, e. g. in
industrial complexes, power stations, communal establishment, hotels, airports, underground railway networks, hospitals and outpatients clinic (DIN
VDE 0107), department stores, data processing centres, theaters, cinemas, in multi-storey buildings, public gatherings, schools etc. (DIN VDE 0108),
mining works, offshore plants, leading centres, traffic communication, emergency power supply and alarm systems. Suitable for fixed installation in
dry and moist rooms, in, above, on and beneath plaster as well as in masonary walls and in concrete. These cables are suitable for outdoor applications
and in underground by using in conduits or tubes. For the installation in conduit all precautions must be taken that no accumulation of water can occur
in the pipes.
= The product is conformed with the EC Low-Voltage Directive 2006/95/EC.

Part no. No.cores x Outer Ø Cop. Weight AWG-No. Part no. No.cores x Outer Ø Cop. Weight AWG-No.
cross-sec. app. mm weight app. kg / km cross-sec. app. mm weight app. kg / km
mm² kg / km mm² kg / km
52534 1 x 16 rm 11,5 154,0 250,0 6 52538 1 x 70 rm 17,5 672,0 840,0 2/0
52535 1 x 25 rm 13,0 240,0 360,0 4 52539 1 x 95 rm 19,5 912,0 1120,0 3/0
52536 1 x 35 rm 14,0 336,0 460,0 2 52540 1 x 120 rm 21,5 1152,0 1390,0 4/0
52537 1 x 50 rm 15,5 480,0 610,0 1 52541 1 x 150 rm 23,5 1440,0 1690,0 300 kcmil

Continuation Ⴇ

571
CW&A Edition 27 (published 01.04.2015)
Energy- and Power Cable / Low Voltage and Security Cables

N2XH-FE 180/E 90 security cable, halogen-free, 0,6/1 kV, with improved fire
characteristics
Part no. No.cores x Outer Ø Cop. Weight AWG-No. Part no. No.cores x Outer Ø Cop. Weight AWG-No.
cross-sec. app. mm weight app. kg / km cross-sec. app. mm weight app. kg / km
mm² kg / km mm² kg / km
52542 1 x 185 rm 25,5 1776,0 2090,0 350 kcmil 52583 4 x 6 re 19,5 230,0 630,0 10
52899 1 x 240 rm 28,5 2304,0 2660,0 500 kcmil 52584 4 x 10 rm 22,5 384,0 880,0 8
52543 1 x 300 rm 31,0 2880,0 3350,0 600 kcmil 52585 4 x 16 rm 24,5 614,0 1180,0 6
52544 1 x 400 rm 34,5 3840,0 4230,0 750 kcmil 52586 4 x 25 rm 28,5 960,0 1730,0 4
52545 2 x 1,5 re 14,5 29,0 270,0 16 52587 4 x 35 rm 31,0 1344,0 2220,0 2
52546 2 x 2,5 re 15,5 48,0 310,0 14 52588 4 x 50 rm 35,0 1920,0 2940,0 1
52547 2 x 4 re 16,5 77,0 370,0 12 52589 4 x 70 rm 39,0 2688,0 3960,0 2/0
52548 2 x 6 re 17,5 115,0 440,0 10 52590 4 x 95 rm 45,0 3648,0 5360,0 3/0
52549 2 x 10 rm 19,5 192,0 600,0 8 52591 4 x 120 rm 48,5 4608,0 6550,0 4/0
52550 2 x 16 rm 21,0 307,0 780,0 6 52592 4 x 150 rm 54,0 5760,0 8070,0 300 kcmil
52551 2 x 25 rm 23,5 480,0 1100,0 4 52593 4 x 185 rm 59,0 7104,0 9970,0 350 kcmil
52552 2 x 35 rm 26,5 672,0 1400,0 2 52594 4 x 240 rm 66,0 9216,0 12830,0 500 kcmil
52553 2 x 50 rm 30,0 960,0 1830,0 1 52595 5 x 1,5 re 18,0 72,0 420,0 16
52554 2 x 70 rm 33,0 1344,0 2420,0 2/0 52596 5 x 2,5 re 19,0 120,0 500,0 14
52555 2 x 95 rm 37,5 1824,0 3240,0 3/0 52597 5 x 4 re 20,0 192,0 610,0 12
52556 2 x 120 rm 41,0 2304,0 3940,0 4/0 52598 5 x 6 re 21,5 288,0 760,0 10
52557 3 x 1,5 re 15,0 43,0 260,0 16 52599 5 x 10 rm 24,5 480,0 1070,0 8
52558 3 x 2,5 re 16,0 72,0 350,0 14 52600 5 x 16 rm 27,0 768,0 1450,0 6
52559 3 x 4 re 17,0 115,0 420,0 12 52601 5 x 25 rm 31,0 1200,0 2120,0 4
52560 3 x 6 re 18,0 173,0 520,0 10 52602 5 x 35 rm 34,0 1680,0 2730,0 2
52561 3 x 10 rm 20,5 288,0 710,0 8 52603 5 x 50 rm 38,5 2400,0 3620,0 1
52562 3 x 16 rm 22,5 461,0 950,0 6 52604 5 x 70 rm 43,5 3360,0 4940,0 2/0
52563 3 x 25 rm 26,0 720,0 1370,0 4 52605 7 x 1,5 re 19,5 101,0 480,0 16
52564 3 x 35 rm 28,0 1008,0 1750,0 2 52606 7 x 2,5 re 20,5 168,0 580,0 14
52572 3 x 35 / 16 rm 29,5 1162,0 1950,0 2 52607 7 x 4 re 22,0 269,0 730,0 12
52565 3 x 50 rm 32,0 1440,0 2310,0 1 52608 10 x 1,5 re 24,0 144,0 650,0 16
52573 3 x 50 / 25 rm 33,5 1680,0 2640,0 1 52609 10 x 2,5 re 25,5 240,0 790,0 14
52566 3 x 70 rm 35,5 2016,0 3100,0 2/0 52610 12 x 1,5 re 24,5 173,0 720,0 16
52574 3 x 70 / 35 rm 37,0 2352,0 3520,0 2/0 52611 12 x 2,5 re 26,0 288,0 890,0 14
52567 3 x 95 rm 40,5 2736,0 4180,0 3/0 52612 24 x 1,5 re 33,0 346,0 1270,0 16
52575 3 x 95 / 50 rm 42,0 3216,0 4710,0 3/0
52568 3 x 120 rm 44,0 3456,0 5130,0 4/0
52576 3 x 120 / 70 rm 46,5 4128,0 5910,0 4/0
52569 3 x 150 rm 48,5 4320,0 6260,0 300 kcmil
52577 3 x 150 / 70 rm 50,0 4992,0 6970,0 300 kcmil
52570 3 x 185 rm 53,0 5328,0 7720,0 350 kcmil
52578 3 x 185 / 95 rm 55,5 6240,0 8750,0 350 kcmil
52571 3 x 240 rm 59,5 6912,0 9990,0 500 kcmil
52579 3 x 240 / 120 rm 61,5 8064,0 11180,0 500 kcmil
52580 4 x 1,5 re 16,5 58,0 350,0 16
52581 4 x 2,5 re 17,5 96,0 420,0 14
52582 4 x 4 re 18,5 154,0 510,0 12

Dimensions and specifications may be changed without prior notice. (RQ02)

572
CW&A Edition 27 (published 01.04.2015)
Energy- and Power Cable / Low Voltage and Security Cables

N2XCH-FE 180/E 90 security cable, halogen-free, 0,6/1 kV, with improved fire
characteristics

Technical data Cable structure Properties


Ⴠ Halogen-free security cable with improved Ⴠ Bare copper-conductor, to Ⴠ Halogen-free; no evolution of corrosive
characteristics in the case of fire to DIN VDE 0295 cl.1 or cl.2, single-wire and toxic gases
DIN VDE 0266 or multi-wire, BS 6360 cl.1 or cl.2, Ⴠ Flame retardant and hardly flammable
Ⴠ Temperature range IEC 60228 cl.1 or cl.2 Ⴠ Self-extinguished and fire resistant
-30°C to +70°C Ⴠ Core insulation with cross-linked Ⴠ No flame propagation, therefore security
Ⴠ Permissible operating temperature polyethylene, compound type 2XI1 to from fire
at conductor +90°C DIN VDE 0276 part 604 Ⴠ Low smoke density, no darkening of
Ⴠ Nominal voltage U0/U 0,6/1 kV Ⴠ Core identification to DIN VDE 0293-308 emergency exits without hindering the
Ⴠ Test voltage 4000 V and 0276 part 604 fire extinguishing works
Ⴠ Minimum bending radius Ⴠ Cores stranded in layers Ⴠ Toxicological harmless
12x cable Ø Ⴠ Overall core covering, halogen-free filling Ⴠ No self-ignition
Ⴠ Radiation resistance compound, pressed Ⴠ Maintenance of functionallity during the
up to 200x106 cJ/kg (up to 200 Mrad) Ⴠ Concentric conductor of Cu-bare wires with increased current load
Ⴠ Caloric load values helix of copper tape Ⴠ FE 180: Insulation integrity for 180
see Technical Informations Ⴠ Outer sheath of thermoplastic halogen-free minutes. Tests acc.to DIN VDE 0472
polyolefine, flame retardant part 814 ฬ IEC 60331.
Ⴠ Sheath colour orange Insulation integrity under direct
Tests flame propagation for the test period
Ⴠ Flame test acc. to of 180 minutes.
DIN VDE 0482-332-3, BS 4066 part 3, Ⴠ E 90: Functionality of electrical cable
DIN EN 60332-3, IEC 60332-3 (previously systems for minimum 90 minutes. Test
DIN VDE 0472 part 804 test method C) method to DIN 4102 part 12. This fulfils the
Ⴠ Corrosiveness of combustion gases demands of technical guide lines for fire
acc. to DIN VDE 0482 part 267, protection (supplement 1 to DIN VDE 0108
DIN EN 50267-2-2, IEC 60754-2 part 1).
(equivalent DIN VDE 0472 part 813) The functionality for 90 minutes assures
Ⴠ Halogen-free acc. to DIN VDE 0482 the functional performance of
part 267, DIN EN 50267-2-1, IEC 60754-1 water-pressure-rising stations for the
(equivalent DIN VDE 0472 part 815) supply to avoid smoke and heat in
Ⴠ Smoke density acc. to DIN VDE 0482 safety-stairs and inner rooms, ladder shafts
part 1034-1+2, DIN EN 61034-1+2, and engine rooms for fire brigade lifts,
IEC 61034-1+2, BS 7622 part 1+2 emergency lifts for sickbeds in hospitals and
(previously DIN VDE 0472 part 816) the fire brigade lifts.

Note
Ⴠ re = round conductor, single-wire
rm = round conductor, multi-wire
Ⴠ AWG sizes are approximate equivalent
values. The actual cross-section is in mm².
Ⴠ LSOH = Low Smoke Zero Halogen
Q
Application
Everywhere, where in case of fire human life and material assets are to be protected and safety conciousness take a special significance, e. g. in
industrial complexes, power stations, communal establishment, hotels, airports, underground railway networks, hospitals and outpatients clinic (DIN
VDE 0107), department stores, data processing centres, theaters, cinemas, in multi-storey buildings, public gatherings, schools etc. (DIN VDE 0108),
mining works, offshore plants, leading centres, traffic communication, emergency power supply and alarm systems. Suitable for fixed installation in
dry and moist rooms, in, above, on and beneath plaster as well as in masonary walls and in concrete. These cables are suitable for outdoor applications
and in underground by using in conduits or tubes. For the installation in conduit all precautions must be taken that no accumulation of water can occur
in the pipes.
= The product is conformed with the EC Low-Voltage Directive 2006/95/EC.

Part no. No.cores x Outer Ø Cop. Weight AWG-No. Part no. No.cores x Outer Ø Cop. Weight AWG-No.
cross-sec. app. mm weight app. kg / km cross-sec. app. mm weight app. kg / km
mm² kg / km mm² kg / km
52771 3 x 1,5 / 1,5 re 16,5 66,0 330,0 16 52776 3 x 16 / 16 rm 24,5 643,0 1130,0 6
52772 3 x 2,5 / 2,5 re 17,5 104,0 400,0 14 52777 3 x 25 / 16 rm 28,0 902,0 1560,0 4
52773 3 x 4 / 4 re 18,5 161,0 480,0 12 52778 3 x 35 / 16 rm 30,5 1190,0 1960,0 2
52774 3 x 6 / 6 re 20,0 240,0 600,0 10 52779 3 x 50 / 25 rm 34,0 1723,0 2610,0 1
52775 3 x 10 / 10 rm 22,0 408,0 840,0 8 52780 3 x 70 / 35 rm 37,5 2410,0 3500,0 2/0

Continuation Ⴇ

573
CW&A Edition 27 (published 01.04.2015)
Energy- and Power Cable / Low Voltage and Security Cables

N2XCH-FE 180/E 90 security cable, halogen-free, 0,6/1 kV, with improved fire
characteristics
Part no. No.cores x Outer Ø Cop. Weight AWG-No. Part no. No.cores x Outer Ø Cop. Weight AWG-No.
cross-sec. app. mm weight app. kg / km cross-sec. app. mm weight app. kg / km
mm² kg / km mm² kg / km
52781 3 x 95 / 50 rm 43,0 3296,0 4700,0 3/0 52795 4 x 70 / 35 rm 41,5 3082,0 4360,0 2/0
52782 3 x 120 / 70 rm 48,0 4236,0 5880,0 4/0 52796 4 x 95 / 50 rm 47,5 4208,0 5900,0 3/0
52783 3 x 150 / 70 rm 52,0 4992,0 7300,0 300 kcmil 52797 4 x 120 / 70 rm 52,5 5388,0 7340,0 4/0
52784 3 x 185 / 95 rm 57,5 6383,0 8760,0 350 kcmil 52798 4 x 150 / 70 rm 57,5 6540,0 8840,0 300 kcmil
52785 3 x 240 / 120 rm 63,5 8242,0 11280,0 500 kcmil 52799 4 x 185 / 95 rm 63,5 8159,0 11020,0 350 kcmil
52786 4 x 1,5 / 1,5 re 17,5 81,0 390,0 16 52800 4 x 240 / 120 rm 70,0 10546,0 14140,0 500 kcmil
52787 4 x 2,5 / 2,5 re 19,0 128,0 470,0 14 52801 7 x 1,5 / 2,5 re 20,5 133,0 520,0 16
52788 4 x 4 / 4 re 20,0 200,0 570,0 12 52805 7 x 2,5 / 2,5 re 22,0 200,0 630,0 14
52789 4 x 6 / 6 re 21,5 297,0 720,0 10 52802 12 x 1,5 / 2,5 re 26,0 205,0 770,0 16
52790 4 x 10 / 10 rm 24,0 504,0 1010,0 8 52806 12 x 2,5 / 4 re 28,0 334,0 950,0 14
52791 4 x 16 / 16 rm 26,5 796,0 1370,0 6 52803 24 x 1,5 / 6 re 35,0 413,0 1380,0 16
52792 4 x 25 / 16 rm 30,5 1142,0 1940,0 4 52807 24 x 2,5 / 10 re 37,5 696,0 1750,0 14
52793 4 x 35 / 16 rm 33,0 1526,0 2420,0 2 52804 30 x 1,5 / 6 re 37,0 499,0 1630,0 16
52794 4 x 50 / 25 rm 37,5 2203,0 3240,0 1 52808 30 x 2,5 / 10 re 39,5 840,0 2080,0 14

Dimensions and specifications may be changed without prior notice. (RQ02)

574
CW&A Edition 27 (published 01.04.2015)
Energy- and Power Cable / Low Voltage and Security Cables

(N)HXH-FE 180/E 90 security cable, halogen-free, 0,6/1 kV, with improved


fire characteristics

Technical data Cable structure Properties


Ⴠ Halogen-free security cable with improved Ⴠ Bare copper-conductor, to Ⴠ Halogen-free; no evolution of corrosive
characteristics in the case of fire adapted to DIN VDE 0295 cl.1 or cl.2, single-wire and toxic gases
DIN VDE 0266 or multi-wire, BS 6360 cl.1 or cl.2, Ⴠ Flame retardant and hardly flammable
Ⴠ Temperature range IEC 60228 cl.1 or cl.2 Ⴠ Self-extinguished and fire resistant
-30°C to +70°C Ⴠ Core insulation of polymer Ⴠ No flame propagation, therefore security
Ⴠ Permissible operating temperature Ⴠ Core identification to DIN VDE 0293-308 from fire
at conductor +90°C Ⴠ GN-YE conductor, 3 cores and above Ⴠ Low smoke density, no darkening of
Ⴠ Nominal voltage U0/U 0,6/1 kV Ⴠ Cores stranded in layer emergency exits without hindering the fire
Ⴠ Test voltage 4000 V Ⴠ Core wrapping with glass-fibre tape as extinguishing works
Ⴠ Minimum bending radius flame-protection Ⴠ Toxicological harmless
12x cable Ø Ⴠ Outer sheath of polyolefin-compound, Ⴠ No self-ignition
Ⴠ Radiation resistance flame retardant Ⴠ Maintenance of functionallity during the
up to 200x106 cJ/kg (up to 200 Mrad) Ⴠ Sheath colour orange increased current load
Ⴠ Caloric load values Tests Ⴠ FE 180: Insulation integrity for 180
see Technical Informations Ⴠ Flame test acc. to minutes. Tests acc.to DIN VDE 0472
DIN VDE 0482-332-3, BS 4066 part 3, part 814 ฬ IEC 60331.
DIN EN 60332-3, IEC 60332-3 (previously Insulation integrity under direct
DIN VDE 0472 part 804 test method C) flame propagation for the test period
Ⴠ Corrosiveness of combustion gases of 180 minutes.
acc. to DIN VDE 0482 part 267, Ⴠ E 90: Functionality of electrical cable
DIN EN 50267-2-2, IEC 60754-2 systems for minimum 90 minutes. Test
(equivalent DIN VDE 0472 part 813) method to DIN 4102 part 12. This fulfils the
Ⴠ Halogen-free acc. to DIN VDE 0482 demands of technical guide lines for fire
part 267, DIN EN 50267-2-1, IEC 60754-1 protection (supplement 1 to DIN VDE 0108
(equivalent DIN VDE 0472 part 815) part 1).
Ⴠ Smoke density acc. to DIN VDE 0482 The functionality for 90 minutes assures
part 1034-1+2, DIN EN 61034-1+2, the functional performance of
IEC 61034-1+2, BS 7622 part 1+2 water-pressure-rising stations for the
(previously DIN VDE 0472 part 816) supply to avoid smoke and heat in
safety-stairs and inner rooms, ladder shafts
and engine rooms for fire brigade lifts,
emergency lifts for sickbeds in hospitals
and the fire brigade lifts.

Note
Ⴠ re = round conductor, single-wire
rm = round conductor, multi-wire
Ⴠ AWG sizes are approximate equivalent
values. The actual cross-section is in mm².
Ⴠ LSOH = Low Smoke Zero Halogen
Q
Application
Everywhere, where in case of fire human life and material assets are to be protected and safety conciousness take a special significance, e. g. in
industrial complexes, power stations, communal establishment, hotels, airports, underground railway networks, hospitals and outpatients clinic (DIN
VDE 0107), department stores, data processing centres, theaters, cinemas, in multi-storey buildings, public gatherings, schools etc. (DIN VDE 0108),
mining works, offshore plants, leading centres, traffic communication, emergency power supply and alarm systems. Suitable for fixed installation in
dry and moist rooms, in, above, on and beneath plaster as well as in masonary walls and in concrete. These cables are suitable for outdoor applications
and in underground by using in conduits or tubes. For the installation in conduit all precautions must be taken that no accumulation of water can occur
in the pipes.
= The product is conformed with the EC Low-Voltage Directive 2006/95/EC.

Part no. No.cores x Outer Ø Cop. Weight AWG-No. Part no. No.cores x Outer Ø Cop. Weight AWG-No.
cross-sec. app. mm weight app. kg / km cross-sec. app. mm weight app. kg / km
mm² kg / km mm² kg / km
53180 1 x 16 rm 11,0 154,0 255,0 6 53188 1 x 185 rm 24,5 1776,0 2140,0 350 kcmil
53181 1 x 25 rm 12,5 240,0 375,0 4 53189 1 x 240 rm 27,0 2304,0 2700,0 500 kcmil
53182 1 x 35 rm 13,5 336,0 475,0 2 53190 1 x 300 rm 30,0 2880,0 3420,0 600 kcmil
53183 1 x 50 rm 15,0 480,0 625,0 1 53191 1 x 400 rm 33,5 3840,0 4310,0 750 kcmil
53184 1 x 70 rm 16,5 672,0 855,0 2/0 53000 3 x 1,5 re 14,0 43,0 280,0 16
53185 1 x 95 rm 18,0 912,0 1140,0 3/0 53001 3 x 2,5 re 15,0 72,0 330,0 14
53186 1 x 120 rm 20,5 1152,0 1410,0 4/0 53002 3 x 4 re 16,0 115,0 400,0 12
53187 1 x 150 rm 22,5 1440,0 1730,0 300 kcmil 53003 3 x 6 re 17,0 173,0 480,0 10

Continuation Ⴇ

575
CW&A Edition 27 (published 01.04.2015)
Energy- and Power Cable / Low Voltage and Security Cables

(N)HXH-FE 180/E 90 security cable, halogen-free, 0,6/1 kV, with improved


fire characteristics
Part no. No.cores x Outer Ø Cop. Weight AWG-No. Part no. No.cores x Outer Ø Cop. Weight AWG-No.
cross-sec. app. mm weight app. kg / km cross-sec. app. mm weight app. kg / km
mm² kg / km mm² kg / km
53004 3 x 10 re 19,0 288,0 650,0 8 53070 4 x 120 rm 47,0 4608,0 6150,0 4/0
53005 3 x 16 re 21,0 461,0 850,0 6 53390 4 x 150 rm 51,2 5760,0 7662,0 4/0
52990 3 x 25 rm 25,0 720,0 1300,0 4 53015 5 x 1,5 re 16,0 72,0 375,0 16
52991 3 x 35 rm 28,0 1008,0 1700,0 2 53016 5 x 2,5 re 17,0 120,0 445,0 14
52992 3 x 35 / 16 rm 28,0 1162,0 1850,0 2 53017 5 x 4 re 18,0 192,0 560,0 12
52993 3 x 50 / 25 rm 32,0 1680,0 2500,0 1 53018 5 x 6 re 20,0 288,0 690,0 10
52994 3 x 70 / 35 rm 36,0 2352,0 3350,0 2/0 53019 5 x 10 re 22,0 480,0 950,0 8
52995 3 x 95 / 50 rm 42,0 3216,0 4500,0 3/0 53020 5 x 16 rm 24,0 768,0 1300,0 6
52996 3 x 120 / 70 rm 45,0 4128,0 5600,0 4/0 53021 5 x 25 rm 29,0 1200,0 1980,0 4
52997 3 x 150 / 70 rm 49,0 4992,0 6700,0 300 kcmil 53028 5 x 35 rm 33,0 1680,0 2350,0 2
52998 3 x 185 / 95 rm 55,0 6240,0 8350,0 350 kcmil 53029 5 x 50 rm 38,0 2500,0 3100,0 1
52999 3 x 240 / 120 rm 63,0 8064,0 10000,0 500 kcmil 53022 7 x 1,5 re 19,0 101,0 560,0 16
53006 4 x 1,5 re 15,0 58,0 325,0 16 53027 7 x 2,5 re 21,0 168,0 650,0 14
53007 4 x 2,5 re 16,0 96,0 385,0 14 53025 10 x 1,5 re 23,0 144,0 750,0 16
53008 4 x 4 re 17,0 154,0 470,0 12 53026 10 x 2,5 re 25,0 240,0 910,0 14
53009 4 x 6 re 18,0 230,0 580,0 10 53023 12 x 1,5 re 25,0 173,0 850,0 16
53010 4 x 10 re 20,0 384,0 790,0 8 53024 12 x 2,5 re 26,0 288,0 1000,0 14
53011 4 x 16 re 22,0 614,0 1100,0 6
53012 4 x 25 rm 27,0 960,0 1650,0 4
53013 4 x 35 rm 30,0 1344,0 2150,0 2
53014 4 x 50 rm 34,0 1920,0 2800,0 1
53030 4 x 70 rm 39,0 2688,0 3800,0 2/0
53031 4 x 95 rm 44,0 3648,0 5050,0 3/0

Dimensions and specifications may be changed without prior notice. (RQ02)

576
CW&A Edition 27 (published 01.04.2015)
Energy- and Power Cable / Low Voltage and Security Cables

(N)HXCH-FE 180/E 90 security cable, halogen-free, 0,6/1 kV, with improved


fire characteristics

Technical data Cable structure Properties


Ⴠ Halogen-free security cable with Ⴠ Bare copper-conductor, to Ⴠ Halogen-free; no evolution of corrosive
improved characteristics in the DIN VDE 0295 cl.1 or cl.2, single-wire and toxic gases
case of fire adapted to DIN VDE 0266 or multi-wire, BS 6360 cl.1 or cl.2, Ⴠ Flame retardant and hardly flammable
Ⴠ Temperature range IEC 60228 cl.1 or cl.2 Ⴠ Self-extinguished and fire resistant
-30°C to +70°C Ⴠ Core insulation of polymer Ⴠ No flame propagation, therefore security
Ⴠ Permissible operating temperature Ⴠ Each single core covering with flame from fire
at conductor +90°C resistant glass-fibre tape Ⴠ Low smoke density, no darkening of
Ⴠ Nominal voltage U0/U 0,6/1 kV Ⴠ Core identification to DIN VDE 0293-308 emergency exits without hindering the fire
Ⴠ Test voltage 4000 V Ⴠ Cores stranded in layer extinguishing works
Ⴠ Minimum bending radius Ⴠ Core wire screening with helix of copper Ⴠ Toxicological harmless
12x cable Ø tape Ⴠ No self-ignition
Ⴠ Radiation resistance Ⴠ Bare copper wire screening with helix of Ⴠ Maintenance of functionallity during the
up to 200x106 cJ/kg (up to 200 Mrad) copper tape increased current load
Ⴠ Caloric load values Ⴠ Outer sheath of polyolefin-compound, Ⴠ FE 180: Insulation integrity for 180
see Technical Informations flame ratardant minutes. Tests acc.to DIN VDE 0472
Ⴠ Sheath colour orange part 814 ฬ IEC 60331.
Tests Insulation integrity under direct
Ⴠ Flame test acc. to flame propagation for the test period
DIN VDE 0482-332-3, BS 4066 part 3, of 180 minutes.
DIN EN 60332-3, IEC 60332-3 (previously Ⴠ E 90: Functionality of electrical cable
DIN VDE 0472 part 804 test method C) systems for minimum 90 minutes. Test
Ⴠ Corrosiveness of combustion gases method to DIN 4102 part 12. This fulfils
acc. to DIN VDE 0482 part 267, the demands of technical guide lines for
DIN EN 50267-2-2, IEC 60754-2 fire protection (supplement 1 to
(equivalent DIN VDE 0472 part 813) DIN VDE 0108 part 1).
Ⴠ Halogen-free acc. to DIN VDE 0482 The functionality for 90 minutes assures
part 267, DIN EN 50267-2-1, IEC 60754-1 the functional performance of
(equivalent DIN VDE 0472 part 815) water-pressure-rising stations for the
Ⴠ Smoke density acc. to DIN VDE 0482 supply to avoid smoke and heat in
part 1034-1+2, DIN EN 61034-1+2, safety-stairs and inner rooms, ladder shafts
IEC 61034-1+2, BS 7622 part 1+2 and engine rooms for fire brigade lifts,
(previously DIN VDE 0472 part 816) emergency lifts for sickbeds in hospitals
and the fire brigade lifts.

Note
Ⴠ re = round conductor, single-wire
rm = round conductor, multi-wire
Ⴠ AWG sizes are approximate equivalent
values. The actual cross-section is in mm².
Ⴠ LSOH = Low Smoke Zero Halogen
Q
Application
Everywhere, where in case of fire human life and material assets are to be protected and safety conciousness take a special significance, e. g. in
industrial complexes, power stations, communal establishment, hotels, airports, underground railway networks, hospitals and outpatients clinic (DIN
VDE 0107), department stores, data processing centres, theaters, cinemas, in multi-storey buildings, public gatherings, schools etc. (DIN VDE 0108),
mining works, offshore plants, leading centres, traffic communication, emergency power supply and alarm systems. Suitable for fixed installation in
dry and moist rooms, in, above, on and beneath plaster as well as in masonary walls and in concrete. For the installation in conduit all precautions
must be taken that no accumulation of water can occur in the pipes.
= The product is conformed with the EC Low-Voltage Directive 2006/95/EC.

Part no. No.cores x Outer Ø Cop. Weight AWG-No. Part no. No.cores x Outer Ø Cop. Weight AWG-No.
cross-sec. app. mm weight app. kg / km cross-sec. app. mm weight app. kg / km
mm² kg / km mm² kg / km
59028 2 x 2,5 / 2,5 re 16,0 80,0 390,0 14 53041 3 x 70 / 35 rm 38,0 2410,0 3800,0 2/0
53032 3 x 1,5 / 1,5 re 16,9 66,0 380,0 16 53042 3 x 95 / 50 rm 44,0 3296,0 5100,0 3/0
53033 3 x 2,5 / 2,5 re 18,0 104,0 430,0 14 53043 3 x 120 / 70 rm 47,0 4236,0 6250,0 4/0
53034 3 x 4 / 4 re 19,0 161,0 530,0 12 53044 3 x 150 / 70 rm 51,0 4992,0 6900,0 300 kcmil
53035 3 x 6 / 6 re 20,1 240,0 640,0 10 53045 3 x 185 / 95 rm 56,0 6383,0 8550,0 350 kcmil
53036 3 x 10 / 10 re 22,0 408,0 850,0 8 53046 3 x 240 / 120 rm 65,0 8242,0 11150,0 500 kcmil
53037 3 x 16 / 16 rm 24,0 643,0 1150,0 6
53038 3 x 25 / 16 rm 28,0 902,0 1700,0 4
53039 3 x 35 / 16 rm 30,0 1190,0 2150,0 2
53040 3 x 50 / 25 rm 34,0 1723,0 2800,0 1

Continuation Ⴇ

577
CW&A Edition 27 (published 01.04.2015)
Energy- and Power Cable / Low Voltage and Security Cables

(N)HXCH-FE 180/E 90 security cable, halogen-free, 0,6/1 kV, with improved


fire characteristics
Part no. No.cores x Outer Ø Cop. Weight AWG-No. Part no. No.cores x Outer Ø Cop. Weight AWG-No.
cross-sec. app. mm weight app. kg / km cross-sec. app. mm weight app. kg / km
mm² kg / km mm² kg / km
53047 4 x 1,5 / 1,5 re 18,0 81,0 435,0 16 53066 7 x 2,5 / 2,5 re 21,0 200,0 680,0 14
53048 4 x 2,5 / 2,5 re 18,9 128,0 500,0 14 53063 12 x 1,5 / 2,5 re 27,0 205,0 1050,0 16
53049 4 x 4 / 4 re 20,0 200,0 610,0 12 53067 12 x 2,5 / 4 re 28,0 334,0 1050,0 14
53050 4 x 6 / 6 re 21,0 297,0 740,0 10 53064 24 x 1,5 / 6 re 37,0 413,0 1900,0 16
53051 4 x 10 / 10 re 23,0 504,0 1050,0 8 53068 24 x 2,5 / 10 re 37,5 696,0 1900,0 14
53052 4 x 16 / 16 rm 25,0 796,0 1350,0 6 53065 30 x 1,5 / 6 re 39,0 499,0 2200,0 16
53053 4 x 25 / 16 rm 30,0 1142,0 1950,0 4 53069 30 x 2,5 / 10 re 39,5 840,0 2200,0 14
53054 4 x 35 / 16 rm 33,0 1526,0 2400,0 2
53055 4 x 50 / 25 rm 37,0 2203,0 3200,0 1
53056 4 x 70 / 35 rm 42,0 3082,0 4300,0 2/0
53057 4 x 95 / 50 rm 47,0 4208,0 5750,0 3/0
53058 4 x 120 / 70 rm 51,0 5388,0 7100,0 4/0
53059 4 x 150 / 70 rm 56,0 6540,0 8550,0 300 kcmil
53060 4 x 185 / 95 rm 68,0 8159,0 10700,0 350 kcmil
53061 4 x 240 / 120 rm 70,0 10546,0 13930,0 500 kcmil
53062 7 x 1,5 / 2,5 re 21,0 133,0 680,0 16

Dimensions and specifications may be changed without prior notice. (RQ02)

578
CW&A Edition 27 (published 01.04.2015)
Energy- and Power Cable / Low Voltage and Security Cables

JE-H(St)H Bd FE 180/E 30 up to E 90 (orange), halogen-free

Technical data Cable structure Properties


Ⴠ Flame retardant, halogen-free Ⴠ Bare copper-conductor, single-wire Ⴠ No fire propagation
installation cable adapted to Ⴠ Core insulation halogen-free, cross-linked Ⴠ Low smoke density
DIN VDE 0815 polymer, compound type HI1 flame retardant Ⴠ Not for purposes of high current
Ⴠ Loop resistance (E90 with special foil wrapping over and power installation as well as
max. 73,2 Ohm/km conductor) underground laying.
Ⴠ Temperature range Ⴠ Core identification with colour rings and Ⴠ FE 180: Insulation integrity for 180
flexing -5°C to +50°C ring-groups to DIN VDE 0815 minutes. Tests acc.to DIN VDE 0472
fixed installation -30°C to +70°C Ⴠ Cores twisted to pairs, 4 pairs consist to part 814 ฬ IEC 60331.
Ⴠ Operating peak voltage unit, several units stranded to layers Insulation integrity under direct
225 V (not for purposes of Ⴠ Units identified by numbered tape flame propagation for the test period
high current and power installation) Ⴠ Core wrapping with special polyester and of 180 minutes.
Ⴠ Test voltage glass-fibre tape Ⴠ E 30: Functionality of electrical cable
core/core 500 V Ⴠ Screening with alu-laminated polyester tape systems for minimum 30 minutes. Test to
core/screen 2000 V and solid tinned copper drain wire DIN 4102 part 12.
Ⴠ Insulation resistance 0,8 mm Ø The functionality for 30 minutes assures
min. 100 MOhm x km Ⴠ Outer sheath halogen-free, flame retardant when persons and animals are to be saved
Ⴠ Mutual capacitance to DIN VDE 0207 part 24 HM2 from a burning building. 30 minutes secures
max. 120 nF/km at 800 Hz Ⴠ Sheath colour orange the functional performance of the fire
(this values may be extended at Tests warning and alarm systems, safety and
20% with a make-up up to 4 pairs) Ⴠ Flame test acc. to DIN VDE 0482-332-3, spare lighting, passenger lifts with
Ⴠ Capacitance unbalance BS 4066 part 3, DIN EN 60332-3, evacuation circuits, except the cables which
max. 200 pF/100 m IEC 60332-3 (previously DIN VDE 0472 are installed within the ladder shafts and
(20% of the values, but one part 804 test method C) engine rooms.
value up to 400 pF is allowed) Ⴠ Corrosiveness of combustion gases Ⴠ E 90: Functionality of electrical cable
Ⴠ Minimum bending radius acc. to DIN VDE 0482 part 267, systems for minimum 90 minutes. Test
6x cable Ø DIN EN 50267-2-2, IEC 60754-2 method to DIN 4102 part 12.
Ⴠ Radiation resistance (equivalent DIN VDE 0472 part 813) The functionality for 90 minutes assures
up to 100x106 cJ/kg (up to 100 Mrad) Ⴠ Smoke density acc. to DIN VDE 0482 the functional performance of
Ⴠ Caloric load values part 1034-1+2, DIN EN 61034-1+2, water-pressure-rising stations for the
see Technical Informations IEC 61034-1+2, BS 7622 part 1+2 supply to avoid smoke and heat in
(previously DIN VDE 0472 part 816) safety-stairs and inner rooms, ladder shafts
and engine rooms for fire brigade lifts,
Note emergency lifts for sickbeds in hospitals
Ⴠ E 30 to E 90 and the fire brigade lifts.
Functionality (burning behaviour) is
dependant on corresponding installation
technique.
Ⴠ LS0H = Low Smoke Zero Halogen

Application
Flame resistant, halogen-free, static screened installation cables for telecommunication purpose. The static screen prevents strong interference impulse.
Q
Suitable for fixed installation everywhere, where in case of fire human life and material assets are to be protected and a safety conciousness take a
special significance, e. g. in industrial complexes, public buildings, hotels, airports, under ground railway networks, hospitals.
= The product is conformed with the EC Low-Voltage Directive 2006/95/EC.
Functionality E 30 to E 90 Functionality E 30
Part no. No.pairs x Outer Ø Cop. Weight Part no. No.pairs x Outer Ø Cop. Weight
cross-sec. app. mm weight app. kg / km cross-sec. app. mm weight app. kg / km
mm kg / km mm kg / km
34081 2 x 2 x 0,8 7,4 25,0 74,0 - 34148 2 x 2 x 0,8 7,5 25,0 74,0 -
34082 4 x 2 x 0,8 10,8 45,0 127,0 - 34149 4 x 2 x 0,8 9,3 45,0 127,0 -
34083 8 x 2 x 0,8 16,9 85,0 300,0 - 34150 8 x 2 x 0,8 11,4 85,0 300,0 -
34084 12 x 2 x 0,8 18,5 126,0 336,0 - 34151 12 x 2 x 0,8 13,0 126,0 336,0 -
34085 16 x 2 x 0,8 20,1 166,0 426,0 - 34152 16 x 2 x 0,8 15,7 166,0 426,0 -
34086 20 x 2 x 0,8 22,2 206,0 529,0 - 34153 20 x 2 x 0,8 16,5 206,0 529,0 -
34087 32 x 2 x 0,8 29,1 326,0 859,0 - 34154 32 x 2 x 0,8 20,3 326,0 859,0 -
34088 40 x 2 x 0,8 34,2 407,0 1094,0 - 34155 40 x 2 x 0,8 23,4 407,0 1094,0 -
34089 52 x 2 x 0,8 37,3 529,0 1280,0 - 34156 52 x 2 x 0,8 25,2 529,0 1280,0 -

Dimensions and specifications may be changed without prior notice. (RQ02)

579
CW&A Edition 27 (published 01.04.2015)
Energy- and Power Cable / Low Voltage and Security Cables

JE-H(St)H Bd fire warning cable, FE 180/E 30 to E 90 (red), halogen-free

Technical data Cable structure Properties


Ⴠ Flame retardant, halogen-free Ⴠ Bare copper-conductor, single-wire Ⴠ No fire propagation
installation cable, adapted to Ⴠ Core insulation halogen-free, cross-linked Ⴠ Low smoke density
DIN VDE 0815 polymer HI1, flame retardant (E90 with Ⴠ Not for purposes of high current
Ⴠ Loop resistance special foil wrapping over and power installation as well as
max. 73,2 Ohm/km conductor) underground laying
Ⴠ Temperature range Ⴠ Core identification with colour rings and Ⴠ FE 180: Insulation integrity for 180
flexing -5°C to +50°C ring-groups to DIN VDE 0815 minutes. Tests acc.to DIN VDE 0472
fixed installation -30°C to +70°C Ⴠ Cores twisted to pairs, each 4 pairs consist part 814 ฬ IEC 60331.
Ⴠ Operating peak voltage to unit, several units stranded to layers Insulation integrity under direct
225 V (not for purposes of Ⴠ Units identified with numbered tape flame propagation for the test period
high current and power installation) Ⴠ Core wrapping with special polyester and of 180 minutes.
Ⴠ Test voltage glass-fibre tape Ⴠ E 30: Functionality of electrical cable
core/core 500 V Ⴠ Screening with alu-laminated polyester tape systems for minimum 30 minutes. Test to
core/screen 2000 V and solid copper drain wire 0,8 mm Ø DIN 4102 part 12.
Ⴠ Insulation resistance Ⴠ Outer sheath halogen-free, flame retardant The functionality for 30 minutes assures
min. 100 MOhm x km to DIN VDE 0207 part 24, HM2 when persons and animals are to be saved
Ⴠ Mutual capacitance Ⴠ Sheath colour red, RAL 3000 with imprint from a burning building. 30 minutes
max. 120 nF/km at 800 Hz "BRANDMELDEKABEL" secures the functional performance of the
(this values may be extended at Tests fire warning and alarm systems, safety and
20% with a make-up up to 4 pairs) Ⴠ Flame test acc. to spare lighting, passenger lifts with
Ⴠ Capacitance unbalance DIN VDE 0482-332-3, BS 4066 part 3, evacuation circuits, except the cables which
max. 200 pF/100 m (20% of the values, but DIN EN 60332-3, IEC 60332-3 (previously are installed within the ladder shafts and
one value up to 400 pF is allowed) DIN VDE 0472 part 804 test method C) engine rooms.
Ⴠ Minimum bending radius Ⴠ Corrosiveness of combustion gases Ⴠ E 90: Functionality of electrical cable
6x cable Ø acc. to DIN VDE 0482 part 267, systems for minimum 90 minutes. Test
Ⴠ Radiation resistance DIN EN 50267-2-2, IEC 60754-2 method to DIN 4102 part 12.
up to 100x106 cJ/kg (up to 100 Mrad) (equivalent DIN VDE 0472 part 813) The functionality for 90 minutes assures
Ⴠ Caloric load values Ⴠ Smoke density acc. to DIN VDE 0482 the functional performance of
see Technical Informations part 1034-1+2, DIN EN 61034-1+2, water-pressure-rising stations for the
IEC 61034-1+2, BS 7622 part 1+2 supply to avoid smoke and heat in
(previously DIN VDE 0472 part 816) safety-stairs and inner rooms, ladder shafts
and engine rooms for fire brigade lifts,
Note emergency lifts for sickbeds in hospitals
Ⴠ E 30 to E 90 and the fire brigade lifts.
Functionality (burning behaviour) is
dependant on corresponding installation
technique.
Ⴠ LS0H = Low Smoke Zero Halogen

Application
Static screened installation cables for telecommunication purposes. The static screen prevents strong interference impulse. Suitable for fixed installation
everywhere, where in case of fire human life and material assets are to be protected and a safety conciousness take a special significance, e. g. in
industrial complexes, public buildings, hotels, airports, under ground railway networks, hospitals.
= The product is conformed with the EC Low-Voltage Directive 2006/95/EC.
Functionality E 30 to E 90 Functionality E 30
Part no. No.pairs x Outer Ø Cop. Weight Part no. No.pairs x Outer Ø Cop. Weight
cross-sec. app. mm weight app. kg / km cross-sec. app. mm weight app. kg / km
mm kg / km mm kg / km
34091 2 x 2 x 0,8 7,4 25,0 74,0 - 34157 2 x 2 x 0,8 7,5 25,0 67,0 -
34092 4 x 2 x 0,8 10,8 45,0 127,0 - 34158 4 x 2 x 0,8 9,3 45,0 103,0 -
34093 8 x 2 x 0,8 16,9 85,0 300,0 - 34159 8 x 2 x 0,8 11,4 85,0 168,0 -
34094 12 x 2 x 0,8 18,5 126,0 336,0 - 34160 12 x 2 x 0,8 13,0 126,0 237,0 -
34095 16 x 2 x 0,8 20,1 166,0 426,0 - 34161 16 x 2 x 0,8 15,7 166,0 303,0 -
34096 20 x 2 x 0,8 22,2 206,0 529,0 - 34162 20 x 2 x 0,8 16,5 206,0 361,0 -
34097 32 x 2 x 0,8 29,1 326,0 859,0 - 34163 32 x 2 x 0,8 20,3 326,0 553,0 -
34098 40 x 2 x 0,8 34,2 407,0 1094,0 - 34164 40 x 2 x 0,8 23,4 407,0 699,0 -
34099 52 x 2 x 0,8 37,3 529,0 1280,0 - 34165 52 x 2 x 0,8 25,2 529,0 865,0 -

Dimensions and specifications may be changed without prior notice. (RQ02)

580
CW&A Edition 27 (published 01.04.2015)
Energy- and Power Cable / Low Voltage and Security Cables

JE-H(St)HRH Bd fire warning cable, FE 180/E 30 to E 90, halogen-free

Technical data Cable structure Properties


Ⴠ Special insulation for cores and outer Ⴠ Bare copper-conductor, single-wire Ⴠ No fire propagation
sheath adapted to DIN VDE 0815. Ⴠ Core insulation of cross-linked Ⴠ Low smoke density
Ⴠ Loop resistance polymer, compound type HI1 with Ⴠ Not for purposes of high current
max. 73,2 Ohm/km mica tape, flame retardant and power installation as well as
Ⴠ Temperature range Ⴠ Core identification with colour rings and underground laying
flexing -5°C to +50°C ring-groups to DIN VDE 0815 Ⴠ FE 180: Insulation integrity for 180
fixed installation -30°C to +70°C Ⴠ Cores twisted to pairs, each 4 pairs consist minutes. Tests acc.to DIN VDE 0472
Ⴠ Operating peakvoltage to unit, several units stranded to layers part 814 ฬ IEC 60331.
max. 225 V (not for purposes of high Ⴠ Units identified with numbered tape Insulation integrity under direct
current and power installation) Ⴠ Glass-fibre taped flame propagation for the test period
Ⴠ Test voltage Ⴠ Screening with alu-laminated polyester tape of 180 minutes.
core/core 500 V Ⴠ solid copper drain wire 0,8 mm Ø Ⴠ E 30: Functionality of electrical cable
core/screen 2000 V Ⴠ Inner sheath, flame retardant polyolefin systems for minimum 30 minutes. Test to
Ⴠ Insulation resistance compound to DIN VDE 0207 part 24 HM3 DIN 4102 part 12.
min. 100 MOhm x km Ⴠ Galvanized steel wire braided screen The functionality for 30 minutes assures
Ⴠ Mutual capacitance Ⴠ Outer sheath of polyolefin when persons and animals are to be saved
max. 120 nF/km at 800 Hz compound type HM2 from a burning building. 30 minutes
Ⴠ Minimum bending radius to DIN VDE 0207 part 24 secures the functional performance of the
6x cable Ø Ⴠ Outer sheath red (RAL 3000) with imprint fire warning and alarm systems, safety and
Ⴠ Caloric load values "BRANDMELDEKABEL" spare lighting, passenger lifts with
see Technical Informations Tests evacuation circuits, except the cables which
Ⴠ Flame test acc. to are installed within the ladder shafts and
DIN VDE 0482-332-3, BS 4066 part 3, engine rooms.
DIN EN 60332-3, IEC 60332-3 (previously Ⴠ E 90: Functionality of electrical cable
DIN VDE 0472 part 804 test method C) systems for minimum 90 minutes. Test
Ⴠ Corrosiveness of combustion gases method to DIN 4102 part 12.
acc. to DIN VDE 0482 part 267, The functionality for 90 minutes assures
DIN EN 50267-2-2, IEC 60754-2 the functional performance of
(equivalent DIN VDE 0472 part 813) water-pressure-rising stations for the
Ⴠ Smoke density acc. to DIN VDE 0482 supply to avoid smoke and heat in
part 1034-1+2, DIN EN 61034-1+2, safety-stairs and inner rooms, ladder shafts
IEC 61034-1+2, BS 7622 part 1+2 and engine rooms for fire brigade lifts,
(previously DIN VDE 0472 part 816) emergency lifts for sickbeds in hospitals
and the fire brigade lifts.
Note
Ⴠ E 30 to E 90
Functionality is dependant on installation
technique.
Ⴠ LS0H = Low Smoke Zero Halogen

Application Q
Wherever necessary to prevent high property value in case of fire damage to human and material. The static screen prevents strong interference
impulse. Suitable for fixed installation everywhere, where in case of fire human life and material assets are to be protected and a safety conciousness
take a special significance, e. g. in industrial complexes, public buildings, hotels, airports, under ground railway networks, hospitals.
= The product is conformed with the EC Low-Voltage Directive 2006/95/EC.

Part no. No.pairs x Outer Ø Cop. Weight Part no. No.pairs x Outer Ø Cop. Weight
cross-sec. app. mm weight app. kg / km cross-sec. app. mm weight app. kg / km
mm kg / km mm kg / km
34075 2 x 2 x 0,8 11,7 25,0 150,0 - 34080 20 x 2 x 0,8 28,9 206,0 870,0 -
34076 4 x 2 x 0,8 15,7 45,0 275,0 - 34072 32 x 2 x 0,8 41,1 326,0 1360,0 -
34077 8 x 2 x 0,8 21,6 85,0 545,0 - 34073 40 x 2 x 0,8 42,3 407,0 1800,0 -
34078 12 x 2 x 0,8 23,8 126,0 602,0 - 34074 52 x 2 x 0,8 45,2 529,0 2038,0 -
34079 16 x 2 x 0,8 27,7 166,0 734,0 -