Singly Reinforced Beam Analysis

This document provides information for analyzing and designing a composite beam-slab section, including: 1) Load and geometry data for the secondary beam and slab section. 2) Calculations to check the moment capacity, shear capacity, and design of shear connectors between the beam and slab. 3) A proposed I-section is selected that satisfies the moment and shear requirements. 4) Deflection is also checked and found to satisfy code requirements.

Uploaded by

Mahinda
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
324 views11 pages

Singly Reinforced Beam Analysis

This document provides information for analyzing and designing a composite beam-slab section, including: 1) Load and geometry data for the secondary beam and slab section. 2) Calculations to check the moment capacity, shear capacity, and design of shear connectors between the beam and slab. 3) A proposed I-section is selected that satisfies the moment and shear requirements. 4) Deflection is also checked and found to satisfy code requirements.

Uploaded by

Mahinda
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
You are on page 1/ 11

As Calculater / Rectangle Beam Section Analyser (Singly)

BS8110:1985
Advantages of Singly R/f sections fy 460 N/mm2
* Low As required fcu 20 N/mm2
* High shear area Mu 20 kNm
* High Span/d b 1000 mm
d 125 mm
216.0493827161 h 150 mm
-27006.1728395062 k1 8.15047
393.3217857302 Singly Rf design k2 0.459788
-108.024691358 M/bd2 1.28
196.6608928651 As/bd 0.003472
88.6362015071 Asr 434.0 mm2 79.9 kg/m3
Asp 2500 mm2
x 88.6 mm x/d 0.71 Over RF
T32 T25 T20 T16 T12 T10
Options 1 1 2 3 4 6

SETTLEMENT
�=6𝐸�∆/𝐿^2
24 kNm V
Beam Data b (m) 0.225 H(m) 0.4 0.0012
Settlement Allowed 0.005 m
Span
𝐸=24 𝑥 〖 10 〗 ^9 6m
for concrete

Min 100As/Ac for This Tie beam ( 0.45%) 405 mm2

TORSION
Torsional Moment about center of beams for 1m strip
Rate Rs 23000 210
Concrete/m Steel/m TotalCost
0.15 19.79592 7607.1429

on Analyser (Singly)
SHEAR CHECK
BS8110:1985
Asp 224 mm2
bv 225 mm
d 350 mm
d min 79.82949 mm if singly fcu 20 N/mm2 <40 N/mm2
d' = 50 mm d' = h-d Link Dia. 6 mm ;Asv 28.3 mm2
h normally =150mm for singly R/f design fyv 250 N/mm2
Vd 90 KN
Doubly Rf design vd 1.1428571 N/mm2 <3.57770876399966N/mm2 - Ok
vc 0.385845 Shear FAIL withoutlinks
Shear Limit for nominal links 105kN vc+0.4 0.785845 0.8√𝑓𝑐�
100(Asr x 0.5)/bvd 0.173601 3.5777088 N/mm2
Vc + 0.4 0.837746 Design links at 72.3 mm
0.557850216 1.337481 0.928325
Nominal Links R6 - 30 T10 - 93.75

DEFLECTION CHECK
Span = 5300 mm
All (S/d) = 20 cant simply conti.
Act (S/d) = 42.4 7 20 26
M/bd2 = 1.28
As r = 434.0023 mm2 For starcase increse All(s/d) by 15% if steps comprise more than 60%
As p = 1120 mm2
fs = 111.4068
F1 = 1.947527 82.575159 261.6 365.5931508 1.947527
Mod. All(S/d) = 38.95055 < Act (S/d)=42.4
Deflection Fail
for stair 15% = 1.15 if steps comprise more than 60% of span then cell L31= 1.15 or else 1
For Stair Deflection OK
(100As/bd)^0.33 = 0.657657
(400/d)^0.25= 0.927719
b 1
a 0.657657
c 0.928318
Revised a 1.947952
Asp to pass sheer 5820.832
76399966N/mm2 - Ok

se more than 60%


DESIGN OF COMPOSITE SLABS ( WITH DECKING DECKING SHEET)

Load Data (kN/m2)

a Live(qk) 7.5 kN/m2


b Finishes 1.2 kN/m2
c Parttions 1 kN/m2
d Ceiling+ Services 1 kN/m2
Total Live(a+c) 8.5 kN/m2

Dead (gk)( b+d) 5.88 kN/m2 (Beam SW+ Slab SW)

Total Ser 14.38 kN/m2


Total Ult 21.83 kN/m2

Profile Data
Ds 175 mm
Dp 51 mm
Ds1 26 mm
Ds2 137 mm
S 300 mm
Dsr 163 mm
Def (Ds-Ds1) 149 mm

Geomatry Data (GA)


Main Beam Span 10 m
Secondory beam Span (L) 6m
Secondory beam Spacing 2.5 m

Design of Secondary beam

Design load 54.57 kN/m


B Design Moment (M) 245.55 kNm
Eff. Width of slab L/4 1.5 m Or Beam space 2.5
Select the lesser Value 1.5 m
Grade of steel (py) 275 N/mm2 ( S275 or S355)
Grade of Concrete 35 N/mm2 ( 30 or 35)

Moment capacity
Resistance of Concrete, Rc
Rc=(0.45fcu)Be(Ds-Dp) 2929.5 kN
A Cross section Area of Beam ,A < 10652.7 mm2

Select a suitable section satisfying both A & B Condions T= 14.5


450x200x76 t= 9
BM Capacity 455 kNm Py = 275
Shear Capacity 693 kN B= 200
H= 450
A1= 9850
Ixx = 3.31E+08
Resistance of steel beam, Rs
Rs( =A1py) 2708.75 kN < 2929.5 kN
yp = A1Py/(0.45fcuBe) 114.7 mm
Ds-Dp 124 mm Ds-Dp > Yp,Nutral axislies within the slab,Hence O

Moment Capacity of Composite section, Mc


928.2 kNm Mc > M , OK
Mc=𝑅𝑠[𝐻/2+𝐷𝑠 − (𝑅𝑠 (𝐷𝑠−𝐷𝑝))/2𝑅𝑐]

Shear capacity

Shear Force Fv=1/2 𝑛𝐿 163.7 kN

Shear Resistance, Pv=0.6𝑃𝑦𝑡𝐷 668.3 kN Pv>Fv, Hence OK

Shear Connectors

Height assumed 100 mm


Dia. Assumed 25 mm
Characteristic strength Qk 161 N/mm2
Design strength Q𝑝=0.8 𝑄� 128.8 N/mm2
Shear strength reduction factor,k
�=0.6(𝐷𝑠𝑟/𝐷𝑝){(𝐷𝑒𝑓/𝐷𝑝) 0.8
−1}≤0.8
Q'p 103.0 kN
Maximum longitudinal force in
Concrete, Fc 2708.75 kN
Total number of studs required 26
Studs per trough 3 Studs per trough =3

Deflection 3.31E+08 23832800


Ig 1090604864 mm4
�=5𝑤𝐿^4/384EI 1.6 mm
L/360 16.66666667 mm Deflection OK
Ds

Dp

Ds2 Ds1

mm if grater than 16mm refer Table: of BS5950 for Py


mm
N/mm2
mm
mm
mm2
mm4 55963845.75
275108983.3

xislies within the slab,Hence Ok


Finding Reinforcements for shell stresses

Geomatry data Modal data

Slab/Wall thickness = 300 mm (+) ve values


Top clear cover = 25 mm f11 = 600 kN
R/f T1 bar = 16 mm f22 = 350 kN
R/f T2 bar = 10 mm f12 = 125 kN
Bottom clear cover = 25 mm m11 = 2 kN/m
R/f B1 bar = 16 mm m22 = 1.5 kN/m
R/f B2 Bar = 10 mm m12 = 0.5 kN/m
Fy 460 N/mm2

Membrane Parameters Equivalent membrane forces


Ct1 = 33 mm N11(top) = 291.5 kN>0
Ct2 = 38 mm N22(top) = 168.3 kN>0
Cb1 = 33 mm N12(top) = 60.3 kN
Cb2 = 38 mm N11(bot) = 308.5 kN
dt1 = 117 mm N22(bot) = 181.7 kN
dt2 = 112 mm N12(bot) = 64.7 kN
db1 = 117 mm
db2 = 112 mm
d1 = 234 mm
d2 = 224 mm
dmin = 224 mm
dbmin = 112 mm
dtmin = 112 mm

Top Rf layer Bottom R/f Layer


F11 = 168.3036 kN F11 = 181.6964
F22 = 291.453 kN F22 = 308.547
F12 = 60.26786 kN F12 = 64.73214
Ndes1 = 228.5714 kN Ndes1 = 246.4286
Ndes2 = 351.7208 kN Ndes2 = 373.2792
Fc(top) = -120.536 kN Fc(top) = -204.758

Ndes1(top) = 351.7208 kN Ndes1(bot) = 373.2792 kN


Ndes2(top) = 228.5714 kN Ndes2(bot) = 246.4286 kN
Ast1(top) = 849.5673 mm2/m Ast1(bot) = 901.6405 mm2/m
Ast2(top) = 849.5673 mm2/m Ast2(bot) = 595.2381 mm2/m
0.033
0.038
0.033
0.038
0.117
0.112
0.117
0.112
0.234
0.224
0.224
0.112
0.112