Transfloor Catalog
Transfloor Catalog
0   Introduction
                     The Transfloor™ System (also known by the name of the original
                     licensors - ABE, Filigran, Kaiser-Omnia floor) has been widely used in
                     Europe and elsewhere for over 40 years. Overseas trends indicate that
                     this precast flooring system is a favoured method of construction for sus-
                     pended concrete slabs and in some parts of Europe it accounts for 60%
                     of all suspended work reaching production rates of 80 million square
                     metres per year. As a precast flooring system it offers many advantages
                     over cast in-situ floors while maintaining the full structural integrity and
                     monolithic requirements of the slab.
                     In Australia this type of flooring has been in use since 1982 and in
                     February 1988 Transfloor™ Pty Ltd was purchased by Smorgon ARC and
                     traded as Transfloor™ Australia Pty Ltd until 1991. Since 1992 the
                     manufacture of Transfloor™ has been licensed to a number of independent
                     precast companies. Each agreement allows the manufacturer to market
                     Transfloor™, in the specified territory, using the same expertise and
                     technical know how that was developed by Transfloor™.
Introduction                                                                                 Page 1
                                                 2.0           The Transfloor™ System
                                                               The Transfloor™ system uses a combination of precast steel reinforced
                                                               concrete panels and a poured in-situ topping as a means of constructing a
                                                               suspended concrete slab. The use of site placed steel reinforced concrete
                                                               effectively ties all the precast elements together providing safety, rigidity
                                                               and structural redundancy.
                                                               Transfloor™ Features
                                                               Size - A Transfloor™ panel is a factory made precast concrete slab of
                                                               variable width up to a maximum of 2.5 metres and variable length, usually
                                                               limited to about 12 metres for transport and handling purposes.
                         PANEL FABRIC RF62 MINIMUM.                      POLYSTYRENE VOID FORMERS (OF ANY CROSS-SECTION)
                         HEAVIER IF REQUIRED BY DESIGN.                  BONDED TO PANEL AT FACTORY (VOID PERCENTAGE IS
                                                                         VARIABLE FROM ZERO TO ABOUT 35%)
                            NOTE
                            TRANSFLOOR UNITS CAN BE MADE TO ANY SIZE AND ANY SHAPE WITHIN THE LIMITS SHOWN ABOVE. SEMICIRCULAR OR RECTANGULAR CUT
                            OUTS, SKEWED ENDS AND IRREGULAR SHAPES CAN BE USED TO SUIT PARTICULAR JOB REQUIREMENTS.
                                    Lighter structure - Use of polystyrene void formers reduces the self weight
                                    of the slab and provides cost savings in foundations, columns and beams.
                                    The void formers also reduce the volume of in-situ concrete.
                                    Soffit finish - A class 2 off-form grey finish is easily achieved, suitable for
                                    painting with minimum preparation (refer Figure 3).
Total Cycle (approximate hours) 464 Total Cycle (approximate hours) 216
Table 1: Comparison of cycle times and labour requirements for slab over precast walls-Brookland Apartments.
                                                         Flexibility in design - Transfloor™ is an engineered product made to suit
                                                         individual project requirements. Penetrations, cantilevers and unusual
                                                         panel shapes can be easily accommodated (refer Figure 4).
                                                         Eliminates bar chairs - If concrete cover and overall slab thickness are
                                                         suited to the truss type, top reinforcement can be supported directly on the
                                                         Transfloor™ trusses.
                                                         2. Supplier personnel will then assess and arrange for a preliminary design
                                                            and prepare concept layout plans and a quotation.
                                                         4. After approval has been obtained for dimensional accuracy and engi-
                                                            neering integrity, the panels are produced and delivered to site at a time
Figure 5: Transfloor™ on load bearing block walls           specified by the builder.
                                     4.1   Reinforcement
                                           Transfloor™ trusses are fabricated from plain round hard drawn 500L
                                           grade bar conforming to AS4671. The diagonal bars of the truss are
                                           electronically welded to both the top and bottom chords. Weld tests are
                                           carried out at regular intervals as part of the Smorgon ARC Quality
                                           Assurance programme.
                                           All fabric used in the panels is welded wire fabric, grade 500L
                                           conforming to AS4671 and all bar reinforcement is grade 500N
                                           conforming to AS4671.
     Typical Sections:
                                                                                    200 STANDARD PITCH
                                    DIAGONALS 6.0 mm HD WIRE                                                          TOP CHORD SIZES
                                                                                                                      AS SHOWN ABOVE
                                        HEIGHT (H)
                       W=105
                                                                                    BOTTOM CHORDS 6.0 mm HD WIRE
SECTION ELEVATION
                                                               The system is best suited to one way action, however, two way action can
                                                               be achieved by eliminating void formers to allow placement of transverse
Figure 9: Biaxial trusses - panels engineered to suit          bars. The transverse bars should be placed near the upper surface of the
project requirements                                           panel ensuring that in-situ concrete flows under the bars and anchorage is
                                                               achieved. Note that a reduced effective depth for the transverse reinforce-
                                                               ment will have to be used.
                                                               In a uniaxial design the precast panel will normally contain all of the bottom
                                                               reinforcement required in the final design which can consist of a light fab-
                                                               ric, truss bottom chords and additional bar reinforcement. It should be
                                                               noted that the presence of voids will not usually result in design of the sec-
                                                               tion as a tee beam since large amounts of steel are required to shift the
                                                               neutral axis below the top of the void. Refer to Figure 10 for a general
                                                               cross section of a finished slab.
                                             360 MIN RIB OVER PANEL JOINT               440 MAX POLYSTYRENE VOIDS                   120 INTERNAL RIB
            NEUTRAL AXIS AT ULTIMATE                                                                                                    MINIMUM
            LOAD IS USUALLY ABOVE
                                                             LAPPED FABRIC
            TOP OF VOID
                                                             (MIN RF62)                                  TRANSFLOOR TRUSSES
                                                                                                                                                           500N EXTRA BARS
                                                                                                         SEE FIGURE 8 FOR DETAILS
                                                                                                                                                           AS REQUIRED
                                                                                                                                                                       65 (MIN)
                     EFFECTIVE DEPTH
20
                                                        When the precast element is used to form a wide shallow beam (band
                                                        beam/slab system on columns) and shear reinforcement is required, the
                                                        ligatures should extend over the entire section depth and tie into the pre-
                                                        cast element. However, if the actual shear is less than the shear capacity
                                                        and the beam depth is less than half the beam width, nominal shear
                                                        ligatures can be incorporated as shown in Figure A8 in Appendix A.
                                                50mm                                               2500mm
                                                55mm                                               2502mm
                                                60mm                                               2504mm
                                                65mm                                               2506mm
                                                70mm                                               2508mm
Table 3: Standard truss thickness and typical fire rating for voided slabs
Note:
                          2. The overall slab thickness is the minimum that can be used with the
                             nominated truss type.
                          3. The actual panel width will depend on the panel thickness used due to
                             the tapered edge forms.
                           a
                                                                                               a     Lsy.t         TOP BARS TO ACHIEVE
                                                                                                                   NEGATIVE MOMENT
                                                                                                                   CAPACITY
(1) PANEL EXTENDS INTO SUPPORT (3) END SUPPORT WITH END RESTRAINT
a Lsy.t
                                                                                                                Lsy.t
                                                                                TOP REINFORCEMENT
(2) SPLICE BARS EXTEND INTO SUPPORT (4) INTERMEDIATE SUPPORT WITH SLAB CONTINUITY
                REFER TO AS3600 CLAUSE 9.1.3.1                                  Ast = TOTAL POSITIVE REINFORCEMENT AT MID SPAN
                Ast = TOTAL POSITIVE REINFORCEMENT AT MID SPAN                  As=0.5Ast BUT CAN BE REDUCED TO 0.25Ast WHEN
                a=100 FOR As=0.5Ast, A=50 FOR As=Ast                            THE BENDING MOMENT ENVELOPE HAS BEEN CALCULATED.
SPAN
                                                          Since this is a serviceability limit state design, unfactored loads have been
                                                          used. The tensile stress in the panel concrete is limited to (AS3600,
                                                            .6 f'c Clause. 6.1.1.2) and the compressive force in the truss wires is
                                                          limited to AS4100 Clause. 6.1
SPAN SPAN
1200 PS
                                                                                                                         BEAM
                                                                                                                  BAND
                                PS
                                                                                                                  SLAB
                                PS
                                PS
                                                                                                                         BEAM
                                                                                                                  BAND
PART PLAN A
                                      EXAMPLE: 200 O/ALL VOIDED SLAB WITH TRUSSES AT 500 CRS, MAX PS = 2800 MM.
                                               400 O/ALL BEAM WITH TRUSSES AT 400 CRS, MAXIMUM PS = 2300 MM.
                                               PS = MAXIMUM PROP SPACING (REFER TABLES 4 AND 5).
SLAB PANEL
                                                      360 mm RIB OVER PANEL JOINT                         440 mm POLYSTYRENE VOIDS                120 mm INTERNAL RIB
          NEUTRAL AXIS AT ULTIMATE
          LOAD IS USUALLY ABOVE
                                                                     LAPPED FABRIC
          TOP OF VOID
                                                                     (MIN RF62)                                        TRANSFLOOR TRUSSES
                                                                                                                                                                                     500N EXTRA BARS
                                                                                                                       SEE FIGURE 8 FOR DETAILS
                                                                                                                                                                                     AS REQUIRED
                    EFFECTIVE DEPTH
190 55 3.6 3.1 5.4 0.090 2.0 3.5 5.2 7.3 10.5
230 55 3.9 3.1 6.5 0.104 2.5 3.7 5.0 6.7 9.1 12.3
270 55 4.3 3.1 7.5 0.120 2.5 3.7 4.8 6.2 8.1 10.5 13.8
300 55 4.6 3.1 7.9 0.130 2.0 2.8 3.7 4.7 6.1 7.8 10.0 12.8
190 55 3.6 4.9 5.0 0.090 1.5 2.5 4.1 5.5 7.5
230 55 3.9 5.6 6.1 0.104 2.0 3.4 4.5 5.8 7.5 9.7
270 55 4.3 6.1 6.8 0.120 2.5 3.3 4.3 5.4 6.8 8.6 10.9
300 55 4.6 6.7 7.6 0.130 2.5 3.2 4.0 5.0 6.2 7.6 9.4 11.7
                                                    Seismic considerations for Transfloor™ will follow the same design rules as
                                                    for in-situ floors but will require adequate detailing to achieve
                                                    seismic integrity at the connections. The main criteria to consider are:
                                                           • Flexibility of thin cast in-situ topping slab that forms the horizontal
                                                             diaphragm causing overstressing and cracking resulting in
                                                             separation from the precast elements.
                         CONTINUOUS REINFORCEMENT TO BE AT
                         LEAST 33% OF TOP REINFORCEMENT.          MIN 50% ALL BOTTOM REINFORCEMENT TO BE
                         BARS TO DEVELOP FULL STRENGTH AT         CONTINUOUS THROUGH THE SUPPORT TO DEVELOP
                         FACE OF SUPPORT.                         FULL STRENGTH AT FACE OF SUPPORT
TYPICAL SLAB REINFORCEMENT DETAILS FOR EARTHQUAKE LOADING (REFER AS3600, APPENDIX A)
                                                                                                                         NOTCH PANEL
                                                                TRANSFLOOR PANEL
                                                                                                                         AROUND COLUMN
                                                                TRUSSES NOT SHOWN
            CONTINUITY STEEL REINFORCEMENT MIN 33% OF                                      CONTINUITY STEEL REINFORCEMENT
            NEGATIVE MOVEMENT STEEL REINFORCEMENT                                          MIN 33% OF NEGATIVE MOMENT
                                                                                           REINFORCEMENT SPLICE TO DEVELOP
            PROVIDE COGS TO DEVELOP FULL STRENGTH AT                                       STRENGTH OF BAR
            FACE OF SUPPORT
                                              8.1      Manufacture
                                                       The manufacture of Transfloor™ panels takes place in a factory
                                                       environment where a system of controls and checks ensures optimum
                                                       product quality.
                                                       Panels are cast on steel forms using high strength concrete, externally
                                                       vibrated, to ensure thorough compaction and uniform density.
                                              8.3      Installation
                                                       Where the Transfloor™ panels are not designed to sustain construction
                                                       loads over the clear span without intermediate supports, a simple
                                                       system of frames and props with timber headers is normally erected prior
                                                       to arrival of panels on site (see Figure 16).
                                                       Prop spacing should be specified by the design engineer and will vary
                                                       according to the type and number of trusses in the Transfloor™ panels and
                                                       the construction loads to be supported. Tables 4 and 5 can be used to
                                                       determine the required prop spacing or alternatively contact an approved
                                                       Transfloor™ supplier for more information.
Figure 24: Panels in storage ready for delivery to
site
                                                              Panels up to 8.5 metres in length can be lifted by crane using four chains.
                                                              The chain hooks must be attached to the top chord of the trusses as
                                                              shown in Figure 26. The lifting capacity has been verified by testing for this
                                                              method. Panels between 8.5 and 10 m long may require a lifting frame.
                                                              Lifting point locations should be marked on shop drawings.
                                                                  90
                                                                 MAX
1/4 L 1/4 L
                                                  Fixing of edge forms can usually proceed while services are being
                                                  installed. A turnbuckle engaging truss wires can be used as a
                                                  connection device for edge forms. Appendix A, Figure A6, includes edge
                                                  form details.
Figure 27: Temporary props are positioned prior
to placing panels
TRANSFLOOR PANEL
                                                                                                25
                                                                                                                           PANEL SOFFIT
Figure 29: Unpainted soffit finish showing shadow                                         (A) SHADOW JOINT
point
TRANSFLOOR PANEL
25 PANEL SOFFIT
                                                         The Transfloor™ panel can cover the entire width of a bridge, including the
                                                         cantilever beyond the external beams, thus eliminating the need for form-
                                                         work and additional scaffolding. This application for Transfloor™ has been
                                                         widely accepted and shown to be very cost effective in terms of speed of
                                                         erection, safety in construction (instant safe working platform), efficient use
                                                         of materials (no lost formwork) and significantly reduced traffic interference.
Figure 31: Ready made bridges - Transfloor™ bridge deck panel being lifted into position
                                                                Continuity at the joint is provided by the in-situ portion of the deck and
                                                                research results indicate that the presence of the joint is not detrimental to
                                                                the load distribution performance of the bridge deck system (Reference
                                                                6,9 and 10).
                                             CONTINUITY REINF
                O/ALL TRUSS HEIGHT           (IF REQUIRED)           TRANSVERSE REINF        TOP REINFORCEMENT                 TRUSSES
                (SEE FIGURE 8)                                                               (MAIN BARS)                                     TOP COVER
                                                                                                                                                                  SLAB DEPTH
                                                                                                                                                      PANEL THK
                                                                                                                             CLEAR COVER TO
                                                                                                   RF72 FABRIC
                                         0.5 (TS)                                                                            TRANSVERSE WIRES
                         N50 PANEL
                                                       0.5 (TS)       * TRUSS SPACING (TS)         MIN PANEL REINF
                         CONCRETE
                                                                  PANEL WIDTH (2436 MAX)
                                                                                                                * TRUSS SPACING AS REQUIRED SEE
                                                                                                                  "Design For Construction Loads" (SECTION 5.7)
                                                                   TYPICAL SECTION AA
                                                    70                         40
                                                   TYP                         MIN
STEEL BEAM
DETAIL 'A'
                                                        5. The top concrete should first be placed in continuous strips over gird-
                                                           ers and allowed to flow under panels before being placed on the
                                                           remaining deck. This procedure improves the flow of concrete under
                                                           panel ends, helps eliminate air pockets and places concrete under
                                                           panel ends before the temporary bearing strips are compressed due to
                                                           the weight of wet concrete.
              10. Jones H.L. and Furr H.L., “Study of In Service Bridges Constructed
                  with Prestressed Panel Sub-decks”, Research Report 145-1, Texas
                  Transportation Institute.
Appendix A                                                                      Page 27
                                                         11.0 Appendix A
                                                                           40 mmTHICK POLYSTYRENE
                                                                           VOID FORMER (OPTIONAL)
                                                                           70 mmTHICK POLYSTYRENE
                                                                           VOID FORMER (OPTIONAL)
Appendix A                                                                                               Page 29
                                                            Appendix A
Appendix A                                                                                     Page 31
                                            Appendix A
Appendix A                                                                              Page 33
                                               Appendix A
65 mm (TYP)
Appendix A                                                                                 Page 35
                                                          Appendix A
IN-SITU STEP
Appendix A                                                Page 37
                                                    Appendix A
   *16mm clear provides tolerance for location of the wall. An alternative detail is to place the panel on the wall with
    40mm bearing as shown for “PRECAST INTERNAL WALL”.
Appendix A                                                                                         Page 39
                                                          Appendix B
B1 - EXAMPLE CALCULATION - ESTIMATE DESIGN
                                                Estimate Design & Detailed Design
From Table 7:
Overall slab thickness                 190      mm
Panel thickness                        55       mm
Polystyrene void former thickness      65       mm         (from Appendix A)
Slab self weight                       3.6      kPa
Average bottom reinforcement           5.0      kg/m2
Average top reinforcement              4.9      kg/m2
Average in-situ concrete               0.090    m3/m2
SLAB DESIGN
MINIMUM THICKNESS
Ln/Ds                            31.58
70(1/wK)1/3                      32.06             Ln/Ds < 70(1/wK)1/3
BOTTOM REINFORCEMENT
BENDING
Ultimate design bending moment   26.68     kNm     wl2/11
Effective depth d                158       mm
Fsy                              500       MPa
fc'                              32        MPa                                     AS3600-2001 Cl 8.1.2.2 (b)
gamma                            0.822
Ast                              449       mm2/m
b                                1000      mm
Mu                               33.37     kNm
phi Mu                           26.96     kNm     phi Mu ≥ M*
Ast/bd                           0.00284
0.22(D/d)2 f'cf /fsy             0.00216           Ast/db > 0.22(D/d)2 f'cf /fsy   AS3600-2001 CI 8.1.4.1
ku                               0.0636            <0.4                            AS3600-2001 CI 8.1.3
dn                               8.25 mm           gamma ku d                      AS3600-2001 CI 8.1.2.2 (b)
TOP REINFORCEMENT
BENDING
Ultimate design bending moment   29.35     kNm     wl2/10
Effective depth d                159       mm
Fsy                              500       MPa
fc'                              50        MPa     Transfloor panel strength
gamma                            0.696                                             AS3600-2001 CI 8.1.2.2 (b)
Ast                              480       mm2/m
b                                1000      mm
Mu                               36.72     kNm
Page 41                                                                                                         Appendix B
                                                                        Appendix B
phi Mu                                29.38             kNm               phi Mu ≥ M*
Ast/bd                                0.00302
0.22 (D/d)2 f'cf/fsy                  0.00267                             Ast/db> 0.22(D/d)2 f'cf/fsy               AS3600-2001 CI 8.1.4.1
ku                                    0.051                               <0.4                                      AS3600-2001 CI 8.1.3
dn                                    5.65              mm                gamma ku d                                AS3600-2001 CI 8.1.2.2 (b)
SHEAR
Ultimate Shear Force at support Vs*   28.13             kN                1.15 wl/2
Vuc                                   127.53            kN                B1B2B3bvdo(Ast f’c/bv do).333             AS3600-2001 CI 8.2.7.1
phi Vuc                               89.27             kN                phi Vuc ≥ Vs*
Ultimate Shear Force of void Vv*      26.19             kN                1.15 wI/2
bv                                    296               mm
Vuc                                   56.62             kN                B1B2B3bvdo(Ast f’c/bv do).333             AS3600-2001 CI 8.2.7.1
phi Vuc                               39.63             kN                phi Vuc ≥ Vv*
DEFLECTION
Lef/d                                 37.74
k3 k4 ((delta/lef) Ec/Fd.ef)0.333     39.05                               Lef/d<k3 k4 ((delta/lef) Ec/Fd.ef)0.333   AS3600-2001 CI 9.3.4.1
CRACK CONTROL
Fd.ef1                                6.12              kPa               G + 1xQ                                   AS3600-2001 CI 9.4.1(a)
Fd.ser                                5.52              kPa               G + Xs x Q
320 mm truss spacings selected to reduce propping of 6 m span to a single prop mid-span of the panel
reduce void width by 40 mm to 400 mm to accommodate the 8 trusses required for the 2500 wide panel
REINFORCEMENT
Page 43                                                                                                                                                Appendix B
                                                 Appendix C
                         TranspanTM TransfloorTM Design Software Output
Introduction           The purpose of the following calculations is to determine the maximum simply supported
                       double span for a Transfloor panel given structural properties and construction loads.
SPAN SPAN
                       The panel must comply with the stability, strength and service limit state criteria specified
                       in AS3610-1995 Formwork for Concrete (Ref. [2]).
           Stability   The panel must resist overturning, uplift and sliding under the action of all the appropriate
                       load combinations:
                       a) Overturning: In the case of a simply supported span overturning is not applicable
                       b) Uplift: The panel must resist forces from the appropriate load combination causing uplift.
                       Uplift is commonly caused by wind loads that are beyond the scope of this analysis and there
                       fore uplift is not considered.
                       c) Sliding: The panel and its supports must resist forces from the appropriate load
                       combination causing sliding.
                       AS3610 requires that formwork resist an applied horizontal live load of 1 kN/m plus the lateral
                       pressure of concrete.
          Strength     The Panel must resist the bending and shear action effects from all the appropriate load
                       combinations. In the case of a simply supported panel the following load combinations are
                       appropriate:
                               Stage I – prior to placement of concrete.
                                        1.25G + 1.5Quv + 1.5M1                                             (2)
                               Stage II – during placement of concrete.
                                        1.25G + 1.25Gc + 1.5Quv + 1.5M2                                    (3)
                                        1.25G + 1.25Gc + Qc                                                (4)
                               Stage III – after placement of concrete.
                                        1.25G + 1.5Gc + 1.5Quv + 1.5M3                       (5)
          Stiffness    The panel stiffness must be such that the deformation under the appropriate load
                       combination does not exceed the limits specified in Ref. [2]. In the case of a simply
                       supported panel the following load combinations are appropriate:
     Surface Finish    The surface finish of the panel soffit conforms with the physical quality of a “Class 2”
                       surface finish as specified in Ref. [2].
                        Stability          a) Sliding
                                           b) Overturning
                        Service            a) Deflection
                                           b) Cracking
   Maximum Span       The maximum span is selected on the basis that the design action, calculated from the
                      factored load combinations, does not exceed the capacity of the panel.
                      A summary of the calculations showing the maximum span for each action is given in the table
                      below:
          Stability   The formwork assembly including the Transfloor panel, falsework and connections are required
                      to be designed to transfer the following limit state design load to anchorage or reaction points:
                                           Limit State Sliding Load, H*         1.5         kN/m
Stacked Materials
                      The maximum span is based on the live load for stacked materials, before and after
                      placement of concrete, being limited to a maximum of 2.0 kPa.
                      This load must be clearly indicated in the formwork documentation and construction
                      control put in place to ensure it is not exceeded.
    Appendix C                                                                                                   Page 45
                                        Appendix C
Assumptions 1 Vertical and horizontal action effects from environmental loads have been ignored.
               2   The value for stacked materials during Stage I (M 1) applies also to Stage III (M3) and
                   during Stage II the value for stacked materials (M2) is 0 kPa.
3 The effects of form face deflection and construction tolerances can be ignored.
               4   The deviations specified for surface undulation, in Ref[2], will be interpreted as the
                   deflection criteria for the panel as per the following table:
                          2                        3                         500
                          3                        5                         300
                          4                        8                         188
               5   The welds connecting the diagonal wires to the top and bottom chord of the truss are
                   capable of transmitting the full design action effects.
II Stiffness
                             (7) * Although AS3610 specifies that Qc will apply over an area of 1.6 m x 1.6 m, it has
                             been applied over the full area of the panel.
                             ** - The loads from stacked materials (M) may apply to one span only.
        Design Load
                                          Therefore the design loads are as follows:
Appendix C                                                                                                   Page 47
                                                   Appendix C
   Truss Properties
                                                   Transfloor Truss Type, T     T110/10
                                                Average Truss Spacing, Ts         312               mm            Ref.[1]
                                                          Truss Height, Th        111               mm
                                              Truss Bar Yield Strength, fsyt      450               mPa
Ν∗ ≤ φ Α g f y
                                  where                        φ       0.9
                                     Limit State Capacity, φAg fy    254.5             kN
                                                 Truss Height, Th     111             mm
                              Limit State Moment Capacity, M*tt       28.2            kNm
       Bottom Chord
        Compression      In accordance with AS4100 – 1998 Steel Structures (Ref.[3]), Clause 6.1
                                                              Ν∗ ≤ φ α c Ν s
                                  where                        φ       0.9
                                   Section Capacity, N s= Abfsyt     224.4             kN
                                                             λn      153.3
                                                              αa      12.6
                                                              αb      -1.0
                                                               λ     140.7
                                                               η       0.4
                                                                ε      0.8
                                                              αc       0.3
                                     Limit State Capacity, φαcNs      66.0             kN
                                              Truss Height, Th        111             mm
                             Limit State Moment Capacity, M*bc         7.3            kNm
Appendix C                                                                                         Page 49
                                          Appendix C
           Bottom Chord
                Tension    In accordance with AS4100 – 1998 Steel Structures (Ref.[3]), Clause 7.1
Ν∗ ≤ φ Α g f y
                                    where                         φ      0.9
                                       Limit State Capacity, φAg fy     202.0                kN
                                                   Truss Height, Th      111                mm
                                Limit State Moment Capacity, M*b        22.4                kNm
          Panel Concrete
            Compression    The maximum concrete compressive force is given by:
                                                             Ν ∗ ≤ 0.68 f cm t p b
                                    therefore
                                         Limit State Capacity, N*c     4675.0                kN
                                                  Truss Height, Th       111                mm
                               Limit State Moment Capacity, M*pc        518.9               kNm
               Diagonal
            Compression    In accordance with AS4100 – 1998 Steel Structures (Ref.[3]), Clause 6.1
                                                                  Ν∗ ≤ φ α c Ν s
                                    where                         φ      0.9
                                     Section Capacity, N s= Abfsyt      224.4                kN
                                                               λn       101.8
                                                                 αa     17.1
                                                                 αb     -1.0
                                                                  λ     84.7
                                                                  η      0.2
                                                                   ε     1.2
                                                                  αc     0.6
                                            Limit State Capacity, N*    130.8               kNm
             Tensile Cracking   AS3600, Ref[4] requires the maximum flexural stress in the concrete under short
                                 term service loads to be limited to
0.5 f ’c
                                                       0.5        f cm I g
                                                M*=
                                                              y   g
                                therefore
                                Limit State Service Moment Capacity, M*c          8.9             kNm
or
AS3600 also provides an alternative of limiting the increment in steel stress to 150 mPa.
                      Sliding   The force causing sliding must be transferred to an anchorage or reaction point
                                on the permanent structure or foundation.
                                    Limit state horizontal live load, Quh         1.0             kN/m
                                 Limit state lateral concrete pressure, P         0.1             kN/m
                                   Limit State horizontal design load, H*         1.5             kN/m
Appendix C                                                                                                       Page 51
                                                Appendix C
Span
Calculations
 Positive Bending      The positive moment capacity of the panel is given by the following:
                                                     1 2M *
                                                       wb
                       therefore
                         Positive Bending Maximum Span, S b         3.25              m
Negative Bending       The negative moment capacity of the panel is given by the following:
                                    Top Chord Tension, M*tt         28.2            kNm
                        Compression of Concrete Panel, M*pc         518.9           kNm
                          Bottom Chord Compression, M*bc             7.3            kNm          Ignored in this
                                                                                                 calculation
                        Negative Bending Design Moment, M*          28.2            kNm
                                                      8M *
                                                       wb
                       therefore
                        Negative Bending Maximum Span, S b          3.20              m
               Shear   The shear capacity of the panel is governed by the compression of the truss diagonal.
                       The maximum span can be derived from the following equation:
                                                    ( 2N *sinθ
                                                              (
                                                        w sb
                       therefore
                                      Shear Maximum Span, S v       14.18             m
                                                                 1 2M *
                                                                      c
                              therefore
                                             Cracking Maximum Span, Sc            3.60           m
Deflection The maximum deflection of the panel can be calculated from the following equation:
Δ= 0.0074w s
bS4
To maintain the specified class the following Span/Deflection ratio must be achieved:
                                                              ( 135Ecj Ig
                                                                          (
                                                                  βw s b
                              therefore
                                             Deflection Maximum Span, S d         3.54           m
Appendix C                                                                                                   Page 53
                                                 Appendix D
                                        Construction Practice
Delivery
Panels are delivered in stacks on semi-trailers, approximately 150m2 per load. Stacks are normally loaded onto
the truck in reverse order of placement so that the top panel on the stack is the first to be placed on site. The
only exception being in the case of a load of mixed panel sizes when small panels are loaded on the top of the
stack irrespective of placing sequence. This should be the only circumstance which requires a panel to be
grounded on site before placing. However, such panels may be placed directly in position if their location can be
accurately fixed prior to commencement of panel placement.
Installation
Except in cases where the TransfloorTM panels are designed to sustain construction load over the clear span
without propping, a simple system of frames and props with 150 x 100 timber headers is normally erected prior
to arrival of panels on site. Prop spacing should be specified or shown on the engineer’s drawing and will vary
according to the type and number of trusses in the TransfloorTM panels and the construction loads to be
supported. Prop spacing generally varying from 1.8 to 2.4 metres is typical for slabs.
Crane Capacity
TransfloorTM 55mm thick has an average weight of 145kg/m2. In cases where the spreader is used for lifting, the
weight of the spreader (500kg) must be added to the panel weight to determine the maximum load for lifting. It
is important to ensure that the crane selected has adequate capacity at the reach required to place all panels.
Alternatively, where crane capacity is limited it may be necessary to limit the size and weight of panels to ensure
that the load/reach capacity of the crane is not exceeded.
During production, each panel is marked with an Identification number corresponding to the panel layout
drawing so that the placement of each panel in it’s correct position in the structure is simplified.
Most panels up to about 8 metres in length containing truss types T110 or T150 can be lifted by crane using four
chains, the hooks being attached to the top bars of the TransfloorTM trusses.
In windy conditions it may be preferable to lift long panels using a 16 hook spreader.
For lifting and placing panels a crew of two men on the deck should achieve a placing rate of approximately 10
panels per hour.
Services
After a reasonable area of floor has been covered with panels a stable deck is available for following trades to
commence work. Conduits for electrical and communications services and water reticulation pipes are installed
as for in-situ concrete slabs. A hot wire cutter is used to quickly chase into polystyrene void formers to
accommodate conduits.
Generally penetrations smaller than 200mm diameter shall not be included in the panel. Small penetrations such
as those required for waste pipes and electrical outlets are make by core drilling through the 55mm TransfloorTM.
Cracking of Panel
The TransfloorTM panel may exhibit cracking for a number of reasons, eg.
       • Incorrect loading of stacking on site.
       • Poor handling techniques.
       • Inadequate propping.
Minor cracking will not affect the structural integrity of the final slab, however, if more severe cracking (i.e. crack
widths greater than 0.2mm) has occurred it should be inspected by a suitably qualified engineer.
Immediately following Installation of services, fixing of top steel is carried out and the slab is then ready for
pouring of site placed concrete.
The thickness of topping concrete above polystyrene will be shown on drawings, but generally should not be
less than 70mm, additional top reinforcement fabric wire diameter and other factors may require this topping
thickness to be increased in some cases, to ensure that reinforcement is fully embedded and adequate cover
provided.
Edge Forms
Fixing of edge forms can usually proceed while services are being installed. A turn buckle engaging truss wires
may be used as a connection device for edge forms.
Appendix D                                                                                                          Page 55
                                                    Appendix E
                Typically 10 panels can be placed per hour after the crane is conveniently
                located
          3.    Propping.......................................................................= $_____________per m2
                See quotation for propping centres.
          4.    Labour...........................................................................= $_____________per m2
                Typically 2 men are required to place the above 10 panels/hr.
End of Report