To produce ultra filtration water we need 3000m3 River water /day
Quantity
Component Description unit of measure
Caustic Soda NaOH (48%)
30
kg/day
Sodium Hypochlorite (NaOCl)
1
Kg/day
Hydrochloric acid (HCl) 60 Kg/day
To produce service water from UF water we need below chemicals required
Quantity
Component Description unit of measure
Sodium Hypochlorite (NaOCl)
4.23
Kg/day
To produce Ro water from service water we required below chemicals
Component Description Quantity unit of measure
1.Hypesperse MDC714/ Genesys LF Membrane
1
antiscalant Kg/day
2.Hydrochloric acid (HCl) 32-33% 22 Kg/day
3. Caustic Soda NaOH (48%) 28 Kg/day
4. Sudscav S Bisulphite 3 Kg/day
To produce electricity from Ro we required below chemicals and demin water
Component Description Quantity unit of measure
Oxygen scavenger (Carbohydrazide) CORTROL
0.04
OS5601 Kg/day
Demin water from RO 200 M3 /day
Ammonia STEAMATE NA 1320 / SUDAMINE N1000 0.138 Kg/day
PHOSPHATE OPTISPERSE; HP 3100 & HP 5493 0.00014 Kg/day
Cooling tower we need blow chemicals
Component Description Quantity unit of measure
Sodium Hypochlorite Solution 83 Kg/day
Sulphuric Acid (H2SO4) 98% 108 Kg/day
Non oxidant Biocide;SPECTRUS NX100; 210L 120 Kg/day
Antiscalant (*) DEPOSITROL BL 6510 5.83 Kg/day
Corrosion Inhibitor Corrshield MD 4103 5.5l Kg/day
Sludge treatment area/recovery system from backwash basin. Recovered water is sent back to raw
water tank and used in the Ultrafiltration. Roughly 500M3
Component Description Quantity unit of measure
ZE TAG 7557 FLOCCULENT 1 Kg/day
Coagulant Ferric Chloride 40% (SUDFLOC 300) 75 Kg/day
Potable water from service water tank. It is used for safety showers, sanitation.
Component Description Quantity unit of measure
Sodium Hypochlorite (NaOCl) 12-16% 4.05 Kg/day