ETI - PSI - 124 (07-95) - Scott
ETI - PSI - 124 (07-95) - Scott
FOR
    54 MVA, 220/2x27 kV SCOTT CONNECTED
       TRACTION POWER TRANSFORMER
                       FOR
         2 x 25 kV AT FEEDING SYSTEM
                       FOR
     RAILWAY ac TRACTION SUBSTATIONS
No. ETI/PSI/124(07/95)
ISSUED BY:
                         -1-
         GOVERNMENT OF INDIA : MINISTRY OF RAILWAYS
         RESEARCH DESIGNS & STANDARDS ORGANISATION
1.0 SCOPE
1.1            This specification applies to 54 MVA, ONAN, 220kV/2x27kV
      Scott-connected traction power transformer for autotransformer (AT)
      feeding system for installation in Indian Railway's unattended traction
      substation in any part of India.
1.2            The transformer shall be complete with all parts, fittings and
      accessories necessary for its efficient operation in the unattended traction
      substation. All such parts, fittings and accessories shall be deemed to be
      within the scope of this specification, whether specifically mentioned
      herein or not.
1.3            This      specification       supersedes      the     specification
      No.ETI/PSI/124(8/89)
2.0            GOVERNING SPECIFICATION
2.1            In the preparation of this specification assistance has been
      derived from the following Standards and Codes of Practices (latest
      version), and Indian Electricity Rules wherever applicable.
1. IS:5                 Colours for ready mixed paints and enamels.
2. IS:335               New insulating oils.
3. IS:1554              PVC insulated (Heavy duty) electric cables for working
     (Part-I)           voltages up to and including 1100 volts.
4. IS:1570              Stainless and heat resisting steels.
     (Part-V)
5. IS:1576              Solid pressboard for electrical purposes.
6. IS:1866              Code of practice for maintenance and supervision of
                        mineral insulating oil in equipment.
7. IS:2026              Power Transformers.
8. IS:2099              Bushing for alternating voltages above 1000 volts.
9. IS:2705              Current transformers.
10. IS:2927             Brazing alloys
11. IS:3024             Electrical steel sheets (oriented)
12. IS:3637             Gas operated relays.
13. IS:3639             Fittings and accessories for power transformers.
14. IS:4253             Cork and rubber.
     (Part-II)
15. IS:5561             Electrical power connectors.
                                           -2-
16.   IS:5621          Hollow insulators for use in electrical equipment.
17.   IS:5728          Guide for short-circuit calculations.
18.   IS:6209          Methods for partial discharge measurements.
19.   IS:6600          Guide for loading of oil-immersed transformers.
20.   IS:8468          On-load tap-changers.
21.   IS:10028         Code of practice for selection, installation and
                       maintenance of transformers.
22. IS:10593           Method of evaluating the analysis of gases in oil-filled
                       electrical equipment in service
23. IS:12676           Oil impregnated paper insulated condenser bushings-
                       dimensions and requirements.
24.   IEC:76           Power transformers.
25.   IEC:137          Bushings for alternating voltages above 1000 volts.
26.   IEC:185          Current transformers.
27.   DIN:7733         Laminated products, pressboard for electrical
                       engineering, types.
3.1   The transformer shall be suitable for outdoor use in moist tropical
      climate and in areas subject to heavy rainfall, pollution due to industry
      and marine atmosphere and severe lightning. The limiting weather
      conditions which the equipment has to withstand in service are indicated
      below:
1. Maximum ambient air temperature                   500C
2. Average ambient air temperature over a 400C
    period of 24 hours
3. Maximum relative humidity                         100%
4. Annual rainfall                                   Ranging from
                                                     1750 to 6250 mm
5. Maximum number of thunder storm days per 85
    annum
6. Maximum number of dust storm days per 35
    annum
7. Number of rainy days per annum                    120
8. Basic wind pressure                               200 kgf/m2
9. Altitude                                          Not exceeding 1000 m
10. Minimum ambient air temperature                  00 C
                                           -3-
3.2        The transformer would also be subjected to vibrations on account of
           trains running on nearby railway tracks. The amplitude of those
           vibrations which occur with rapidly varying time periods in the range of
           15 to 70 ms lies in the range of 30 to 150 microns at present, with the
           instantaneous peaks going up to 350 microns. These vibrations may
           become more severe as the speeds and loads of trains increase in future.
                                                -4-
4.1.4             One outer terminal of the secondary windings of the traction
        transformer is connected to the catenary, and the other outer terminal is
        connected to the feeder. The two inner terminals are connected to each
        other, either directly or through series capacitors, and then solidly
        earthed and connected to the traction rails.
4.2.1 The protection system of the traction transformer comprises the following:
        1.     Differential protection.
        2.     Instantaneous and IDMT over current, and earth fault protection
               on the primary side.
        3.     Protection against phase-failure on the secondary side (i.e. to
               detect malfunction of feeder/transformer circuit breaker).
4.2.2 The protection system for the OHE comprises the following:
        1.     Distance protection.
        2.     Delta-I type fault selective protection.
        3.     Instantaneous over current protection.
        4.     Under voltage protection to avoid wrong phase coupling.
                                           -5-
4.3      OHE- general data
4.3.1               The OHE consists of (i) a grooved copper contact wire of 107
         mm2 section suspended directly from a stranded cadmium copper
         catenary of 65 mm2 section by a number of vertical dropper wires,
         usually at regular intervals (the contact wire and catenary together
         generally being referred as 'catenary' or 'catenary wire'), and (ii) a feeder
         wire of stranded all aluminium conductor (size 19/3.99 mm) of 240 mm2
         section.
4.5.1    The traction load is a frequently and rapidly varying one between no-
         load and over load. The TSS equipment is subject to frequent earth
         faults/ short circuits caused by failure of insulation, snapping of OHE
         touching the earth, wire dropped by bird connecting the OHE to earth/
         over line structure, and miscreant activity. On an average the number of
         faults/ short circuits per month is about 40 but in exceptional cases the
         number could be as high as 120. The magnitude of the fault current may
         vary between 40% and 100% of the dead short-circuit value. These
         faults are cleared by the feeder circuit breaker on operation of the
         distance, delta-I and instantaneous over current relays associated with
         the concerned feeder circuit breaker.
4.5.2    The ac electric locomotives are fitted, for conversion of ac to dc, with
         single-phase bridge-connected silicon rectifiers with smoothing reactor
         for feeding the dc traction motors. The rectifiers introduce harmonic
         currents in the 25 kV power supply system. On few of the electrified
         sections, locomotives fitted with phase controlled asymmetrical thyristor
         bridge, in place of silicon rectifiers are also in use; these introduce
         further harmonics in the system. The typical percentages of harmonics
         present in the traction current with electric locomotives are as follows:
                                              -6-
4.5.3 The average power-factor of electric locomotives and electric multiple
      units generally varies between 0.7 and 0.8 lagging, without reactive
      power compensation.
4.6.1 The Short-circuit apparent power at the transformer location for various
      system voltages is as under:
       Highest system voltage                   Short-circuit apparent
                 kV                                 power, MVA
                72.5                                    3,500
                123                                     6,000
                145                                    10,000
                245                                    20,000
4.7.2 Alarm/trip devices, relays and motor for the off-circuit tap-changer on
      the traction power transformer shall operate off 110 V dc.
                                          -7-
                                  The primary and secondary windings shall be
                                  uniformly insulated.
                                          -8-
11.   Polarity                 :   Subtractive
12.   Tappings (off-circuit)   :   Separate tapped winding on each
                                   secondary winding to give rated
                                   secondary voltage for variation in
                                   primary voltage of +10% to -15 %, in
                                   steps of 5% each.
13.   Temperature rise         :   The temperature rise over an ambient
                                   temperature of 500C both at rated and
                                   overload conditions shall not exceed the
                                   value indicated below:
                                   1. Winding: 50 K at rated load, and 60
                                       K for overloads as specified in Clause
                                       5.1(10) (temperature measured by
                                       resistance method).
                                   2. Top oil: 40 K (temperature rise
                                       measured by thermometer).
                                   3. Current carrying parts in air: 40 K
                                       (temperature rise measured by
                                       thermometer).
14.   Maximum permissible          40.0
      losses at the principal
      tapping:
      1. No-load loss, kW
      2. Load loss, kW             200.0
15.   Ability to withstand :
      short circuit:
      1. Thermal ability           5 s
      2. Dynamic ability       :   0.5 s
16.   Flux density at rated :      Shall not exceed 1.55 tesla.
      voltage and frequency
      at principal tapping
17.   Current density in the       Shall preferable not exceed 2.5 A/mm2
      windings       at  rated
      current.
18.   Acoustic sound level         Not more than 75 dB at a distance of one
      when energised at rated      meter.
      voltage and at no-load.
                                       -9-
19. Bushings:
                                             - 10 -
6.2   Tank
6.2.1 The tank for the transformer shall be of bell type construction with
      flanges on the outside, and shall have a flat top. The flanges of the upper
      and lower tanks shall be jointed by bolts, nuts and washers. The winding
      and core shall be fully exposed when the bell tank cover is lifted.
6.2.2 The tank shall be constructed from mild steel of a quality that allows
      welding without any defect/flaw, with a single tier construction so
      shaped as to reduce welding to the minimum. The welded joints shall be
      made using the latest welding rigidity to permit hoisting of the
      transformer filled with oil by crane. The tank body shall be designed to
      withstand a vacuum of 760 mm of Hg.
6.2.3 The tank shall be fitted with four lifting pads at the lower end to enable
      lifting of the transformer filled with oil by means of lifting jacks.
6.2.4 The tank shall be fitted with an under carriage and mounted on eight bi-
      directional swivelling type flanged rollers for being rolled on 1676mm
      (5' 6") gauge track on which it shall also rest in the final position-
      reference the sketch at Annexure-2. The rollers shall be provided with
      detachable type locking arrangement to enable their locking after
      installing the transformer in the final position, to prevent any accidental
      movement of the transformer.
6.2.5 There shall be at least five inspection covers of suitable size on the tank
      to enable inspection of the lower portions of bushings. and the leads as
      well as various connections of the motorised off- circuit tap-changer.
6.2.6 The rubberised cork gaskets used in the transformer shall conform to
      IS:4253 (Part-II).
6.2.7 All valves used in the transformer shall conform to IS:3639 and shall be
      of good quality and leak proof. The manufacturer shall ensure that
      suitable anti-theft measures are provided on these valves so as to prevent
      theft of oil during transit/service.
6.3.1 A vermin proof, weatherproof and well ventilated marshalling box made
      of sheet steel of thickness not less than 2mm, strengthened with adequate
      stiffeners, shall be provided on the left hand side of the transformer
      thank as viewed from, the secondary terminals side. It shall have a
      hinged door with provision for padlocking- the door opening outward
      horizontally.
6.3.2 The marshalling box shall have a sloping roof. The top of the
      marshalling box shall be at a height of about 2 m from the rail level.
6.3.3 The marshalling box shall house the winding and oil temperature
      indicators and terminal board. To prevent condensation of moisture in
                                          - 11 -
      the marshalling box metal clad space heater, controlled by an associated
      thermostat and switch, shall also be provided, Cable glands shall be
      provided for the incoming and outgoing cables.
6.3.4 The temperature indicators shall be so mounted that their dials are at a
      height of not more than 1.6 m from the rail level. Transparent windows
      of tough acrylic plastic or similar non-fragile transparent material shall
      be provided on the marshalling box so as to enable reading of the
      temperature indicators without opening the door of the marshalling box.
6.3.5 All cables from the bushing current transformers. Buchhlz relay,
      magnetic oil level gauge, pressure relief device and temperature
      indicators shall be run through suitable conduits/perforated covered
      cable trays up to the marshalling box. The cables shall be of 1100 V
      grade, PVC insulated, PVC sheathed, steel wire armoured, stranded
      copper conductor conforming to IS:1554 (Part-I). The cable shall be
      adequately insulated for heat from the tank surface and the sun.
6.4 Core
6.4.1 The core shall be built-up of high permeability cod rolled grain oriented
      silicon steel laminations conforming to IS: 3024. The flux density in any
      part of the core and yokes at the principal tapping with primary winding
      excited at the rated primary voltages and frequency shall not exceed 1.55
      T. The successful tenderer/ manufacturer shall furnish calculations to
      prove that this value shall not be exceeded.
6.4.2 The lamination for the core shall be free from waves, deformations and
      signs of rust. Both sides of the laminations shall be coated with suitable
      insulation capable of withstanding stress relief annealing. In assembling
      the core, air gaps shall be avoided. Necessary cooling ducts shall be
      provided in the core and yoke for heat dissipation. The core-clamping
      frame shall be provided with lifting eyes for the purpose of tanking and
      untanking the core and winding of the transformer.
6.4.4 Yoke/core clamping bolts shall have adequate threaded length beyond
      the face of the nuts for tightening at a later stage, if need arises. Each of
      the core clamping bots and the core clamping frame work shall be
      insulated from the core laminations and tested after completion of the
                                           - 12 -
       core assembly to ensure that they withstand a voltage of 2 kV r.m.s. with
       respect to core for duration of 60 s.
6.5 Windings
6.5.1 The winding shall be of concentric disc or interleaved for the primary,
      and disc or helical/cylindrical for the secondary windings. The primary
      and secondary windings shall be uniformly insulated. All the four
      terminals of the two secondary windings of each of 'M' and 'T' phases
      shall be brought out separately through 52 kV OIP condenser bushings,
      for cascade connection externally.
6.5.4 The ratio of width to thickness of copper conductor used for winding
      shall be as small as possible but shall not exceed 5:1 so as to avoid
      tilting of conductors when the windings are subjected to axial and radial
      forces during short circuits.
6.5.5 Separate tapped winding shall be provided for each secondary winding
      for connection of the motorised off-circuit tap-changer. The tapped
      windings shall be distributed in multi sections in order to reduce the
      imbalance in apmere turns to the minimum at any tap position.
6.5.6 The transformer windings shall be designed for the following rated
      withstand voltages:
                                          - 13 -
6.5.7 The windings shall be so designed that the transfer of lightning and
      switching surges from primary to secondary windings and vice=versa is
      kept to the minimum level.
                                          - 14 -
6.5.20 The vertical locking strips and radial spacers shall be made of pre-
       compressed pressboard conforming to grade PSP:3052 of DIN 7733.
6.5.21 To prevent end blocks from shifting, pre-compressed pressboard ring
       shall be provided in between the two adjacent blocks. Coil clamping
       rings made of densified wood or mild steel shall be located in position
       with pressure screws.
6.5.22 Leads from the windings to the terminals, from the tap switch to the
       tappings of the secondary windings and other interconnections shall be
       properly supported and secured.
6.5.23 The following particulars/ documents in respect of the radial spacer
       blocks (winding blocks), vertical locking strips (axial ribs), end blocks,
       insulating cylinder, angle rings, paper insulation of the conductor and
       coil clamping plates used in the manufacture of the conductor and coil
       clamping plates used in the manufacture of the windings shall be
       furnished.
      1. Reference to specification and grade of material.
      2. Source(s) of supply.
      3. Test certificates.
7.1      The transformer shall be supplied with new insulating oil conforming to
         IS:335 In addition, 10 % extra oil, by volume, shall be supplied in non-
         returnable steel drums. The characteristics of the insulating oil before
         energisation of the new transformer and during its maintenance and
         supervision in service shall conform to IS: 1866.
8.1      Both the primary and secondary side bushings shall conform to IS:2099.
         On the primary side, sealed draw lead type oil impregnated paper (OIP)
         condenser bushings shall be used. On the secondary side, sealed solid
         stem type OIP condenser bushings shall be used. The dimensions of the
         bushings shall conform to IS:12676.
8.2      The bushings on the primary side shall be designed for a rated current of
         800 A, whereas the bushings on te secondary side for a rated current of
         1250 A. The temperature rise of any part of the bushing shall not exceed
         40 K over an ambient temperature of 500C while carrying the rated
         current continuously.
8.3      The procelain housing of bushing shall be of a single piece construction
         i.e. there shall be no joint in the porcelain. The shed profile shall have a
         lip at the extremities but free from ribs on the underside so as to avoid
         accumulation of dust and pollutants and to permit easy cleaning.
8.4      The bushings shall have a non-breathing oil expansion chamber. The
         expansion chamber shall be provided with an oil Level indicator, which
         shall be so designed and dimensioned that oil level is clearly visible
         from ground level.
                                             - 15 -
8.5     A test tap shall be provided for dielectric or power factor measurement.
8.6     The bushings shall be designed for the following insulation Level:
1. Highest voltage for equipment 52                            245
   Um, kV
2. Rated short duration wet power 95                           460
   frequency withstand voltage, kV
3. Rated      Lightning      impulse 250                       1050
   withstand voltage, kV peak
8.7 Adjustable arcing horns shall be provided on both the primary and
    secondary bushings. The horn gap setting shall be variable as indicated
    below:
8.8 The design and construction of the bushing shall be such that stresses due
    to expansion and contraction in any part of the bushings shall not lead to its
    deterioration/breakage.
8.9    The bushings shall be free from corona and shall not cause radio
    interference.
8.10 The bushing terminals shall be provided with terminal connectors of
    bimetallic type and conform to the following:
8.10.1 The terminal connectors shall conform to IS:5561. The design shall be
     such as to be connected to the equipment terminal stud with a minimum of
     four 12 mm diameter bolts, nuts, spring and flat washers. The fasteners
     shall conform to Clause 14.0 of this specification.
                                           - 16 -
9.2       The BCTs shall be so designed as to withstand thermal and mechanical
       stresses resulting from frequent short circuits experienced by the
       transformer on which these are fitted.
9.3      Apart from the BCTs required for the biased differential protection, BCT
       of accuracy class 5 and conforming to IS:2705, with suitable tappings,
       shall be mounted inside one bushing of the left-hand side (as viewed from
       the secondary terminals side) secondary winding (which feeds the catenary
       and would carry a higher current in service as compared to the other
       secondary winding which feeds the feeder) of each of 'M' and 'T' phases for
       use with the winding temperature indicators.
9.4      The BCTs and the bushings shall be so mounted that removal of a
       bushing without disturbing the current transformers, terminals and
       connections or pipe work is easy and convenient.
9.5      The leads from the BCTs shall be terminated in terminal boxes provided
       on the bushing turrets. Suitable links shall be provided in the terminal
       boxes for shorting the secondary terminals of the BCTs, when not
       connected to the external measuring circuits.
9.6       The leads from the secondary winding of the BCTs terminated in the
       terminal box on the bushing turret upto the marshalling box shall be of
       1100 V grade, PVC insulated, PVC sheathed, steel wire armoured, stranded
       copper cable of cross-section not less than 4 mm2 to IS:1554 (Part-I).
9.7       Cable glands of proper size shall be provided in the terminal boxes to
       lead in/lead out the cables.
10.0 CLEARANCES
10.1 The relative orientation in space of the bushings fitted with terminal
     connectors, the main tank, radiators, conservator, pressure relief device, oil
     piping and other parts when mounted on the transformer shall be such that
     the various clearances in air from bushing live parts shall not be less than
     the appropriate values given hereunder:
1.     Highest voltage for equipment 52                        245
       Um, kV
2.     Minimum clearance, mm               500                 1900
       The same distance shall apply for clearances phase-to-earth (including oil
       piping work, conservator, pressure relief device and such other parts),
       phase-to-phase, and towards terminals of a lower voltage winding.
                                           - 17 -
       less than 2 mm thick with adequate stiffeners to prevent deformation
       during transit and handling. The cubicle shall have a sloping roof. The top
       of the cubicle shall be at a height of about 1.5 m from the rail level. The
       cubicle shall be so positioned that the hinge of the operating handle- for
       manual operation - is at a height of about 1.1 m from the rail level.
11.2     To prevent condensation of moisture in the cubicle, metal clad space
       heater, controlled by an associated thermostat and switch, shall be
       provided.
11.3      All wiring in the cubicle shall be clearly identified by lettered/figured
       ferrules of the interlock type, preferable of yellow colour with black
       letters/figures. The ac and dc circuits shall be clearly distinguished and
       well separated from each other.
11.4      Suitable legend and schematic diagram plates made of anodised
       aluminium with black lettering and lines shall be fixed on the inside
       surface of the cubicle door.
11.5     A tap position indicator shall be provided to indicate the tap position
       which shall be clearly visible to an operator standing on the ground.
11.6      The tap-changer shall be of 52 kV voltage class with a continuous
       current rating of 1250 A and a short-circuit current withstand capability of
       12.5 kA r.m.s. for 5 s. The tap-changer motor shall be suitable for
       operation off 110 V from a battery. The voltage at the battery terminals
       may vary between 110% and 85% of the normal value. The voltage at the
       tap-changer motor terminals is likely to be less than 85% of the normal
       value of 110 V due to voltage drop in control cable.
11.7      Once the tap changing operation has been initiated, it must be completed
       automatically (snap action) even if there is a failure of 110 V dc supply. In
       case off-circuit tap-changer with snap action is not readily available, on-
       load tap-changer (without the diverter and other such parts necessary for
       the on-load tap changing), shall be provided so as to have the snap action.
11.8      The tap-changer shall be provided with suitable interlocking
       arrangement to prevent its operation (including manual tap changing) when
       either one or both circuit breakers on the primary as well as on the
       secondary sides of the transformer is/are in closed condition.
11.9      The tap-changer and its control circuit shall be designed for operation
       from the Remote Control Centre (RCC) by the Traction Power Controller
       (TPC) as well as from the tap-changer cubicle. A local/remote switch as
       well as necessary terminations for telesignals and telecommands from and
       to the tap-changer-for-operation from the RCC-shall therefore be provided
       in the tap-changer cubicle.
                                            - 18 -
12.0     COLLING EQUIPMENT
12.1     The transformer shall be designed for ONAN type of cooling.
12.2      The radiators shall consist of a pressed steel plate assembly formed into
       elleptical oil channels as per IEEMA (Indian Electrical & Electronic
       Manufacturers Association)'s standard) or a series of separate elliptical
       tubes. The radiators shall be designed in such a manner that the
       temperature-rise limits specified under Clause 5.1 (13) of this specification
       are not exceeded.
12.3      The radiators shall be removable (after isolating the same from the main
       tank) to facilitate transportation of the transformer. A drain plug of size 19
       mm and an air-release plug of size 19 mm shall be provided at the bottom
       and at the top of each radiator bank for draining and filling of oil
       respectively. Each radiator bank shall also be provided with shut-off valves
       of size 80 mm.
12.4      The radiators shall preferable be supported directly on the transformer
       tank. Each radiator bank shall be fitted with lifting lugs.
13.0     PARTS, FITTINGS AND ACCESSORIES
13.1     Apart from the parts, fittings and accessories specifically detailed in the
       foregoing Clauses, the parts, fittings and accessories detailed hereunder
       shall be supplied with each transformer.
13.1.1 Conservator tank: It shall be of adequate capacity and complete with
     supporting bracket or structure, oil filling cap and drain valve of size 25
     mm. The cylindrical portion of the conservator tank shall be of single piece
     construction without any gasketed joint.
13.1.2 Oil level gauge: It shall be of magnetic type having a dial diameter of
     250 mm. The gauge shall have markings corresponding to minimum oil
     level, maximum oil level and oil level corresponding to oil temperature of
     300C, 450C and 850C. The oil level indicator shall be so designed and
     mounted that the oil level is clearly visible to an operator standing on the
     ground.
13.1.3 Silicagel breather: It shall be complete with oil seal and connecting
     pipes. The connecting pipes shall be secured properly. The container of the
     silicagel breather shall be of transparent flexiglass or similar material
     suitable for outdoor application.
13.1.4 Pressure relief device: It shall operate to release internal pressure at
     preset value without endangering the equipment or operator and shall be of
     instantaneous reset type.
                                             - 19 -
13.1.5 Filter Valves: The bottom and upper filter valves shall be of 50 mm size
     and suitably baffled to reduce aeration of oil. The valves shall be flanged to
     seat 40 mm adopter threaded to thread size P 1-1/2 for connection for
     conection to oil filtration plant.
13.1.6 Drain valve: It shall be of size 80 mm fitted with an oil sampling
     device of size 15 mm.
13.1.7 Earthing terminals: Two earthing terminals shall be provided on the
     tank for its earthing with the help of 3 mild steel flats, each of size 75 mm
     x 8 mm. The terminals shall be clearly marked for earthing.
13.1.8 Buchholz relay: It shall be of double float type, with two shut-off valves
     of 80 mm size, one between the conservator tank and the Buchholz relay
     and the other between the transformer tank and the Buchholz relay. The
     relay shall have one alarm contact and one trip contact, none of the
     contacts being earthed. The contacts shall be of mercury-switch type,
     electrically independent and wired up to the marshalling box. A testing
     petcock shall be brought down through a pipe for the purpose of sampling
     the gas, if any, collected in the Buchholz relay.
13.1.9 Oil temperature indicator (OTI): It shall have one alarm contact, one
     trip contact and two normally open spare contacts none of the contacts
     being earthed. The contacts shall be electrically independent.
13.1.10 Winding temperature indicator (WTI): Two WTIs shall be
     provided, one for the M-phase and the other for the T-phase. Each WTI
     shall have one alarm contact, one trip contact and two normally open spare
     contacts, none of the contacts being earthed. The contacts shall be
     electrically independent.
13.1.11 Thermometer pockets: A separate thermometer pocket with cap shall
     be provided on the bell tank for measuring the top oil temperature in the
     tank.
13.1.12 Rating plate: The rating plate shall indicate the ratings of the
     transformer, the connection diagram of the windings, the particulars of the
     bushing current transformers and other details as per IS:2026. The rating
     plate shall be both in English and Hindi version.
13.2     All valves shall be of the double flange type and fitted with suitable
       blanking plates on the outer face of the exposed flange.
13.3     The capillary tubes for temperature indicators shall be able to withstand
       normal bending. They shall be supported properly without sharp or
       repeated bends or twists.
13.4      The parts, fittings and accessories for the transformer shall be only of
       those manufacturers approved by RDSO. If any item from fresh
       manufacturers/sources are proposed to be used, it shall have to be type
       tested in the presence of RDSO's representative and approval obtained
       before obtaining the item for use.
                                           - 20 -
14.0   FASTENERS
14.1 All fasteners of 12 mm diameter and less exposed to atmosphere shall be of
     stainless steel and those above 12 mm diameter shall preferable be of
     stainless steel or of mild steel hot dip galvanised to 610 g/m2 of zinc. The
     material of the stainless steel fasteners shall conform to IS: 1570 (Part-V),
     Grade 04Cr17Ni 12Mo2.
15.0   PAINTING
15.1 Shot blasting/sand blasting shall be done on the transformer tank to remove
     all scales, rust and other residue before applying the paint inside the tank.
     All steel surfaces which are in contact with insulating oil shall be painted
     with heat resistant oil-insoluble insulating varnish. All steel surface
     exposed to weather shall be given, one primer coat of zinc chromate and
     two coats of grey paint to shad No. 631 of IS:5 An additional coat of paint
     shall be applied at site by the manufacturer.
16.0   TESTING OF TRANSFORMER
16.1   General
16.1.1 Once a purchase order is placed for supply of a transformer the designs
     and drawings together with the Quality Assurance Plan (QAP) shall be
     furnished to the purchaser/Director General (Traction Installation),
     Research Designs and Standards Organisation (DG(TI), RDSO), Lucknow,
     as the case may be, within the period stipulated in the order. Only after all
     the designs and drawings as well as the QAP have been approved for
     prototype tests and a written advice given to that effect, shall the successful
     tenderer/manufacturer take up manufacture of the prototype of the
     transformer. It is to be clearly understood that any change or modification
     required by the above authorities to be done in the prototype shall be done
     expeditiously, not withstanding approval having already been given for the
     designs and drawings. Such change or modification shall be incorporated
     in the drawings. Such change or modification shall be incorporated in the
     drawings as indicated in Clause 17.4 of this specification.
16.1.2 Prior to giving a call to the Purchaser/ DG(TI), RDSO Lucknow, for
     inspection and testing of the prototype, the successful tenderer/
     manufacturer shall submit a detailed test schedule consisting of schematic
     circuit diagrams for each of the tests and the number of days required to
     complete all the tests at one stretch. Once the schedule is approved, the
     tests shall invariably be done accordingly. However, during the process of
     type testing or even later, the purchaser reserves the right to conduct any
     additional test(s), besides those specified here in on any equipment/items
     as to test the equipment/item to his satisfaction or for gaining additional
     information and knowledge, In case any dispute or disagreement arises
     between the successful tenderer/ manufacturer and representative of the
     Purchaser/DG(TI), RDSO, Lucknow, during the process of testing as
     regards the procedure for type tests and/or the interpretation and
     acceptability of the results of type tests, it shall be brought to the notice of
     the Purchaser/DG(TI), RDSO, Lucknow, as the case may be, whose
     decision shall be final and binding. Only after the prototype transformer is
                                            - 21 -
    completed and ready in each and every respect, shall the successful
    tenderer/manufacturer give the actual call for the inspection and testing
    with at least 15 days notice for the purpose.
16.1.3 The type tests shall be carried out on the prototype transformer at the
     works of the successful tenderer/manufacturer or at a reputed testing
     laboratory in the presence of the representative of the purchaser/DG(TI),
     RDSO, Lucknow, in accordance with the relevant specifications and as
     modified or amplified by this specification.
16.2 Tests during manufacture
16.2.1 Though the tests described below shall form part of the type tests, the
     manufacturer shall carry out these tests on each and every unit during the
     process of manufacture and submit the test reports to the Purchaser's
     Inspector deputed for witnessing the routine tests:
   1.   Oil leakage test.
   2.   Vacuum test.
   3.   Pressure test.
   4.   Insulation test for core bolts.
   5.   Test for pressure relief device.
   6.   Measurement of capacitance and tan-delta values.
16.2.1.1 Oil leakage test: The transformer with its radiators, conservator tank
     and other parts, fittings and accessories completely assembled shall be
     tested for oil leakage by being filled with oil conforming to IS:335 at the
     ambient temperature and subjected to a pressure corresponding to twice the
     normal static oil head or to the normal static oil head plus 35 kN/m2 (0.35
     kgf/cm2) whichever is lower, the static oil head being measured at the base
     of the tank. This pressure shall be maintained for a period of not less than
     12 h, during which time no leakage shall occur.
16.2.1.2 Vacuum test: The transformer tank only shall be tested at a vacuum
     of 3.33 kN/m2(0.0333 kgf/cm2) for 60 min. The permanent deflection of
     flat plates after release of vacuum shall not exceed the values specified
     below:-
                                          - 22 -
          Horizontal length of flat plate      Permanent deflection, mm
       upto and including 750 mm                          5.0
                 751 mm to 1250 mm                        6.5
                 1251 mm to 1750 mm                       8.0
                 1751 mm to 2000 mm                       9.5
                 2001 mm to 2250 mm                      11.0
                 2251 mm to 2500 mm                      12.5
                 2501 mm to 3000 mm                      16.0
                       above 3000 mm                     19.0
16.2.1.3 Pressure test: Every transformer tank, radiator and conservator tank
     shall be subjected to an air pressure corresponding to twice the normal
     static head of oil or to the normal static oil head pressure plus 35 kN/m2
     (0.35 kgf/cm2) whichever is lower, as measured at the base of the tank.
     The pressure shall remain constant for 1 h to indicate that there is no
     leakage.
16.2.1.4 Insulation test for core bolts: This test shall be done as described in
     Clause 6.4.4 of this specification.
16.2.1.5 Test for pressure relief device: Every pressure relief device shall be
     subjected to gradually increasing oil pressure. It shall operate before the
     pressure reaches the test pressure specified in Clause 16.2.1.3 hereof and
     the value at which it has operated shall be recorded.
16.2.1.6 Measurement of capacitance and tan-delta values: The
     measurement of capacitance and tan-delta (dielectric loss factor ) of the
     transformer windings shall be made by Schering bridge.
16.2.2 The Purchaser may, if he so desires, carry out any checks or tests on the
     quality of manufacture at any stage during coil winding, drying of coils,
     assembly of coils on core and method of drying, vacuum impregnation,
     tightness of core clamping bolts, adequacy of pressure on coils or any other
     aspects as deemed necessary so as to ensure that proper quality is
     maintained.
16.3   Type Tests
16.3.1 The type tests shall be carried out on the prototype transformer at the
     works of the successful tenderer/manufacturer or at any reputed laboratory
     in the presence of the representative of the Purchaser/DG(TI), RDSO,
     Lucknow, and in accordance with the relevant specifications and as altered,
     amended or supplemented by this specification. The following shall
     constitute the type tests:
1. Temperature-rise test.
                                            - 23 -
   2. Lightning impulse test.
   3. Test with lightning impulse, chopped on the tail.
   4. Short-circuit test.
   5. Measurement of acoustic sound level.
   6. Measurement of partial discharge quantity.
   7. Measurement of harmonics of no-load current.
16.3.2 Temperature-rise test
16.3.2.1 The temperature-rise test shall be done with the tap-changer on the
     lowest tap position (-15%) in accordance with IS:2026(Part II) except as
     modified hereunder.
   1. At rated load.
   2. At 150% rated load for 15 min after continuous operation at rated load
      for 1 h.
   3. At 200% rated load for 5 min after continuous operation at rated load for
      1 h.
     The tests shall be done continuously without any power supply
     interruption. In case interruptions of power supply do take place for some
     reason, then the entire test shall be repeated after steady state conditions
     are attained.
16.3.2.2 The points to be ensured during the temperature-rise test shall be:
   1. The ambient temperature shall be measured using alcohol in glass
      thermometers only.
   2. The winding temperature shall be determined by the resistance method
      only.
   3. The temperature of the top oil shall be measured by an alcohol in glass
      thermometer placed in an oil-filled thermometer pocket.
   4. The average oil temperature shall be calculated as the difference
      between the top oil temperature and half the temperature drop in the
      cooling equipment (radiators).
   5. The temperature of the hot-spot in the winding shall be the sum of the
      temperature rise of the winding above the average oil temperature.
                                           - 24 -
       temperature rise does not vary by more than 10C during four consecutive
       hourly readings.
   3. On attaining the steady state temperature, the current in the primary
      winding of the transformer shall be brought to the rated current which
      shall be maintained for 1 h. At the end of the period the power supply to
      the transformer shall be switched off and the time of switching off
      recorded.
   4. The measurement of hot resistance shall commence as soon as is
      possible after switching off. The first reading of the resistance shall be
      taken before the expiry of 90 s from the instant of switching off and the
      first ten readings shall be taken at intervals of 15 s apart. Thereafter,
      another ten readings shall be taken at intervals of 30 s apart.
   5. The time at which each of the resistance values is read shall also be
      recorded.
   6. The temperatures of the ambient, top oil, the top and bottom radiator
      header oils shall also be recorded at half-hourly intervals throughout the
      test starting from the instant power supply is switched on to commence
      the test till it is switched off.
   7. The WTI and OTI readings shall also be recorded at half-hourly
      intervals right from the instant the power supply is switched on to
      commence the test till it is switched off.
   8. After power supply is switched off, the readings of OTI and WTI shall
      be recorded at intervals of 1 min apart for 30 min.
                                         - 25 -
   2. The current shall thereafter be increased to 200% of the rated current and
      maintained for a period of 5 min. At the end of the 5 min period the
      power supply shall be switched off and the time of switching off
      recorded.
   3. Thereafter the readings as indicated in Clauses 16.3.2.3.1(4) to (8) shall
      be recorded.
   4. The temperatures of ambient, top oil, top and bottom radiator header oils
      and the temperatures indicated by OTI and WTI shall also be recorded at
      the time of switching on 200% load as well as at the time of switching
      off the power supply.
16.3.2.4 Determination of thermal time constant of the windings: The thermal
       time constant of the primary and secondary windings. under both rated
       load and over loads shall be verified during the temperature-rise tests.
16.3.2.5 The temperature rise of the oil, windings and current carrying parts
       in air under both the overload conditions stipulated in Clauses 16.3.2.3.2
       and 16.3.2.3.3 above shall not exceed the values stipulated in Clause
       5.1(13) of this specification. The winding hot-spot temperature under the
       overload conditions shall not exceed 1150C.
16.3.2.6 Testing and calibration of the temperature indicators: The
       functioning of the OTI and WTI shall be verified during the tests
       described above. Both the OTI and WTI shall be recalibrated, if
       necessary, to reflect the respective temperatures correctly. In particular,
       the reading of the WTI shall be the same as the calculated value of the
       hot-spot temperature of the winding.
16.3.2.7 Determination of the thermal time constant of the WTI: the thermal
       time constant of the WTI shall be determined for comparison with the
       thermal time constant of the winding of the transformer with respect to
       the transformer oil. For this purpose, the indications of the WTI and the
       OTI shall be recorded every 1 or 2 min during the first 1 h from the
       instant the transformer is loaded. From the slope of the curve plotted
       with the time on the X-axis and the difference between the readings of
       the WTI and OTI at the particular time on the Y-axis, the thermal time
       constant of the WTI shall be determined. This value shall not vary
       appreciably from the thermal time constant of the winding as calculated
       theoretically and as ascertained from the slope of the cooling curves.
16.3.3 Lightning impulse test
16.3.3.1 This test shall be done in accordance with IS:2026 (Part III). Each of
       the terminals of the primary and secondary windings shall be tested with
       the following voltages:
1. Highest voltage for equipment Um, kV                          52           245
2. Lightning impulse withstand voltage, kV                      250           950
   peak
                                          - 26 -
16.3.4 Test with lightning impulse, chopped on the tail
16.3.5.1 This test shall be done in accordance with IS:2026 (Part III) with the
       appropriate test voltage as stipulated in clause 16.3.3.1 above.
16.3.5 Short-circuit test
16.3.5.1 The short-circuit test shall be conducted in accordance with IS:2026
       (Part-I) with the following schedule:
16.3.5.2 Prior to commencement of the test, the following measurements/tests
       shall be made:
   1. Insulation resistance of the windings with respect to the earth and
      between the windings.
   2. No-load current.
   3. No-load loss.
   4. Resistance of windings.
   5. Percentage impedance voltages.
   6. Load loss.
   7. Voltage ratio.
   8. Di-electric tests comprising:
           1) Separate-source voltage withstand test, and
           2) Induced over voltage withstand test.
   9. Recording if recurrent surge oscillogram (RSO) at the breakers on the
      secondary side of the transformer after energizing the primary windings
      at its rated voltage.
16.3.5.3 The test shall preferable be done by closing the breakers on the
       secondary side of the transformer after energisig the primary windings at
       its rated voltage.
16.3.5.4 The transformer shall be subjected to a total of seven shots in the
       following sequence:
1st Shot      - Asymmetrical and symmetrical currents in M-phase and T-
                phase respectively at the highest tap (+10%)
2nd Shot      - Symmetrical and asymmetrical currents in M-phase and T-
                phase respectively at the highest tap (+10%)
3rd Shot      - Asymmetrical and symmetrical currents in M-phase and T-
                phase respectively at the principal tap.
4th Shot      - Symmetrical and asymmetrical currents in M-phase and T-
                phase respectively at the principal tap.
5th Shot      - Asymmetrical and symmetrical currents in M-phase and T-
                phase respectively at the lowest tap (-15%).
6th Shot      - Symmetrical and asymmetrical currents in M-phase and T-
                phase respectively at the lowest tap (-15%).
                                         - 27 -
7th Shot       - Symmetrical currents in M-phase and T-phase at the lowest
                 tap (-15%).
                                            - 28 -
16.4 Type tests on parts, fittings and accessories
16.4.1 Motorised off-circuit tap-changer
16.4.1.1 Though there is no Indian Standard Specification at present for
      motorised off-circuit tap-changer, the following tests shall be carried out
      thereon in accordance with IS:8468.
16.4.1.2 Test for temperature rise of contacts: The test shall be carried out at
       rated current of 1250 A. The temperature rise shall not exceed the limit
       specified in IS:8468.
16.4.1.3 Mechanical endurance test: With the tap-changer in oil, 100
      operations shall be done manually and 10,000 operations shall be done
      with the motor drive unit. An operation shall comprise moving the tap-
      changer from one tap position to the next higher or lower tap position. All
      the taps of the tap-changer i.e. +10% position tap to the -15% position tap
      shall be covered during the test. While testing with the motor drive unit
      the d.c. voltage for the motor drive unit shall be adjusted to the value
      indicated below, and the number of operations at each value of voltage
      shall be as indicated against each.
1. At the minimum voltage of 93.5 V dc       2,500 operations
2. At the maximum voltage of 121 V dc        2,500 operations
3. At the rated voltage of 110 V dc          5,000 operations
16.4.1.4 Milli-volt drop test: The test shall be done both before and after the
     mechanical endurance test to assess the condition of the contacts. The
     variation in the milli-volt drop values shall be not more than 20%.
16.4.1.5 Short-circuit current test: The test shall be done in accordance with
      IS:8468 with short-circuit currents of 12.5 kA r.m.s., each of 5 s duration.
16.4.1.6 Dielectric tests: The tests shall be done in accordance with IS:8468.
16.4.1.7 Auxiliary circuits insulation tests: Auxiliary circuits including the
      motor and other auxiliary equipment shall be tested in accordance with
      IS:8468.
16.4.2 Condenser bushings
16.4.2.1 The type tests shall be carried out in accordance with IS:5621 on
       porcelain housing of the condenser bushings. The following shall
       constitute the type tests:
   1. Visual inspection.
   2. Verification of dimensions.
   3. Electrical routine test.
   4. Porosity test.
   5. Temperature cycle test.
   6. Bending test.
                                          - 29 -
16.4.2.2 The type tests shall be carried out in accordance with IS:2099 on the
       prototype of the condenser bushings. The following shall constitute the
       type tests:
   1. Wet power frequency withstand voltage test.
   2. Dry lightning impulse voltage withstand test.
   3. Thermal stability test.
   4. Temperature-rise test.
   5. Thermal short time current withstand test.
   6. Dynamic current withstand test.
   7. Cantilever load withstand test.
   8. Tightness test.
   9. Test of tap insulation.
   10. Tightness test at flange or other fixing device.
   11. Measurement of partial discharge quantity.
16.4.3 Bushing type current transformers
16.4.3.1 The bushing type current transformers shall be tested in accordance
       with IS:2705(Part-I & IV).
16.4.4 Buchholz relay
16.4.4.1 The Buchholz relay shall be tested in accordance with IS:3637.
16.4.5 Terminal connectors
16.4.5.1 The terminal connectors shall be tested in accordance with IS:5561.
16.4.6 Temperature indicators
16.4.6.1 The following tests shall be conducted on prototypes of OTI and WTI:
   1. Accuracy with reference to a standard instrument.
   2. Calibration of the indictors to reflect the actual temperature of the
      oil/winding.
   3. Dielectric test at 2.5 kV for 60 s.
   4. Vibration test.
   5. Dust and water splash test to IP 55 degree of protection.
16.4.7 Pressure relief device
16.4.7.1 The following tests shall be conducted on the prototype of pressure
       relief device:
   1. Air pressure test.
   2. Leakage test.
   3. Contact rating and operation test.
   4. Dielectric test on contacts at 2.5 kV for 60 s.
                                            - 30 -
16.4.8 Radiators
16.4.8.1 The radiators shall be tested for air leakage at a pressure of 2.5 kg/cm2.
       The pressure shall remain constant for 1 h to indicate that there is no
       leakage.
16.5 Insulating oil
16.5.1 The following tests shall be carried out in accordance with IS:335 on the
       sample of new insulating oil for use in the prototype transformer:
   1. Density at 270C.
   2. Kinetic viscosity at 270C.
   3. Interfacial tension at 270C.
   4. Flash point.
   5. Neutralisation value (acidity).
   6. Electric strength (with 2.5 mm gap).
   7. Dielectric dissipation factor (tan-delta).
   8. Specific resistance at 270C and at 900C.
   9. Oxidation stability.
   10. Water content.
16.6 Routine tests
16.6.1 The following routine tests shall be performed on each transformer
       including the prototype unit in accordance with IS:2026:
   1. Visual examination.
   2. Insulation resistance test.
   3. Measurement of no-load current.
   4. Measurement of no-load loss.
   5. Measurement of resistance of the windings.
   6. Measurement of percentage impedance voltages.
   7. Measurement of load loss.
   8. Polarity test.
   9. Voltage ratio test.
   10. Dielectric test comprising:
          1) Separate-source voltage withstand test, and
          2) Induced over voltage withstand test.
                                           - 31 -
16.6.4 Measurement of no-load current: Measurement of no-load current
       referred to the primary side shall be done at:
   1. 90%, 100% and 110% of the rated voltage at the principal tapping, and
   2. the appropriate tap voltage at the +10% and -15% tap positions.
16.6.5 Measurement of no-load loss: Measurement of no-load loss referred to
the primary side shall be done at:
   1. 90%, 100% and 110% of the rated voltage at the principal tapping, and
   2. the appropriate tap voltage at the +10% and -15% tap positions.
                                           - 32 -
16.6.12 Recording of recurrent surge oscillogram (RSO): The oscillorgams
       shall be taken at the +10%, -15% and principal tappings.
16.6.13 Tests on motorised off-circuit tap-changer: The tests shall be conducted
       in accordance with IS:8468.
16.6.14 During the routine tests on any unit if it is found that the sum of the
       measured losses (i.e. no-load and load losses) measured at -15% tap
       position (corrected to 750C) exceeds the value defined in Clause
       16.3.2.3.1(1), or if the no-load loss/ load loss at the principal tapping
       exceeds the maximum guaranteed figures, then the transformer shall be
       rejected.
16.7   IF the prototype of a transformer conforming to this specification has
       already been approved in connection with previous supplies to Indian
       Railways, fresh type testing may be waived at the discreation of the
       Purchaser, provided that no changes whatsoever in the design or material
       (s) used or the process of manufacture have been made. However, the
       Purchaser reserves the right to conduct type tests if he gained from
       previous supplies.
16.8   Only after approval of the original tracings of drawings incorporating
       changes, if any, as a result of the prototype tests and clear written
       approval of the results of the tests on the prototype is communicated by
       the Purchaser/DG(TI), RDSO, Lucknow, to the successful tenderer/
       manufacturer, shall he taken up bulk manufacture of the transformer-
       which shall be strictly with the same materials and process of
       manufacture as adopted for the prototype. In no circumstances shall
       materials other than those approved in the design/drawings and/or during
       the prototype testing be used for bulk manufacture on the plea that they
       had been obtained prior to the approval of the prototype.
16.9   The tenderer may quote separately his charges for short-circuit and
       temperature-rise tests. No charges shall be payable for any other type
       and routine tests.
17.0 TECHNICAL DATA AND DRAWINGS
17.1 The tenderer shall furnish along with his offer, in the proforma at
      Annexure-3, the Schedule of Guaranteed Performance, Technical and
      Other Particulars (SOGP) for the transformer. The particulars shall be
      complete in all respects. If there is any entry like "shall be furnished
      later" or a blank is left against any item, the offer is not likely to be
      considered as the evaluation of the offer is rendered difficult and cannot
      be compared with other offers, if any.
17.2 The tenderer shall specifically indicate in a "Statement of Compliance"
      attached with the offer his compliance with each and every Clause of
      this specification. In case to tenderer wishes to deviate from any Clause
      of this specification, he may do so giving reference to the Clause(s) with
      the reasons/justification for the deviation. This shall be in the form of a
      separate statement called the "Statement of Deviations". If there is no
      deviation at all, specific "NIL" "Statement of Deviations" shall be
      attached with the offer. If the "Statement of Compliance" and Statement
      of Deviations" are not attached with the offer, it is not likely to be
                                          - 33 -
       considered for the reason that it is an incomplete offer which cannot be
       properly evaluated and compared with other offers, if any.
17.3 The tenderer shall furnish the following information along with his offer:-
17.3.1 Calculations for:
   1. Temperature rise of winding at rated current.
   2. Hot-spot temperature of the winding at 150% and 200% rated loads for
      15 min and 5 min respectively.
   3. Thermal withstand capacity of the windings for a short circuit of 5 s
      duration.
   4. Mechanical forces in respect of the following as per IEEMA (Indian
      Electrical & Electronic Manufacturer's Association) formulae given in
      Annexure-4:
           1) Asymmetrical short-circuit current
           2) Hoop stress in primary and secondary windings.
           3) Compressive pressure in the radial spacers.
           4) Internal axial compressive force.
           5) Axial imbalance force.
           6) Radial bursting force.
           7) Resistance to collapse.
           8) Bending stress on clamping ring and densified wood.
           9) Maximum allowable torque on pressure screws for coil clamping
              bolts at the time of tightening, if any.
   5. Flux density with the characteristic curve.
   6. Maximum value of inrush current.
17.3.2 Drawings for:
   1. Outline general arrangement drawing giving complete details of the
      transformer.
   2. Arrangement of the core, windings and magnetic path.
   3. Magnetizing characteristic of CRGO sheet steel.
   4. Drawing showing elevation of the core and winding and other insulation
      materials.
   5. A sectional view showing the position of core, cylinders, winding
      blocks, vertical ribs and other insulating materials.
   6. Details of coil claming arrangement.
   7. General arrangement of the off-circuit tap-changer.
                                          - 34 -
      per Indian Railways standard in sizes of 210 mm x 297 mm or any
      integral multiples thereof:-
   1. Outline general arrangement of the transformer indicating plan, front
       elevation, side elevation with all parts, fittings and accessories, electrical
       clearances as well as salient guaranteed particulars.
   2. Internal arrangement of the transformer indicating primary and
       secondary bushing lead connections, core to core-clamp earthing, core-
       clamp to tank earthing, core-clamp to core-base bolting, and the locking
       arrangement of the core & coil assembly with the tank.
   3. Cross sectional view of the core and windings with material
       specifications and makes.
   4. Details of the pressure screws/ oil dash-pot/ coil clamping bolts or other
       devices and their location with materials specifications and makes.
   5. Schematic view of the valves used on the transformer and the antitheft
       device so as to prevent theft of oil.
   6. Transport outline dimensional diagram.
   7. General arrangement of the off-circuit tap-changer assembly with salient
       technical parameters.
   8. Tap-changer cubicle layout.
   9. Schematic diagram for driving of motorised off-circuit tap-changer from
       remote control centre by telecommand and corresponding telesignalling.
   10. Name and rating plate of motorised off-circuit tap-changer.
   11. General arrangement of marshalling box indicating protection and
       control equipment.
   12. Wiring diagram of marshalling box.
   13. Schematic diagram of protection and control circuits in marshalling box
       with cable schedule.
   14. Legend plate showing protection and control circuits for fitment in the
       marshalling box.
   15. OIP condenser bushing for primary side including cross sectional view,
       shed profile and salient electrical and mechanical characteristics.
   16. OIP condenser bushing for secondary side including cross sectional
       view, shed proview and salient electrical and mechanical characteristics.
   17. Dimensional drawing, V-I characteristic and rating plate for bushing
       type current transformers.
   18. Rigid type terminal connector for primary side bushing terminal.
   19. Rigid type terminal connector for secondary side bushing terminal.
   20. Rating plate with diagram of connections, both in English and Hindi
       versions.
   21. Details of radiators.
   22. Details of breather.
   23. External cable run with cable schedule.
   24. Any other drawings considered necessary by the successful tenderer/
       manufacturer and/ or Purchaser.
17.4.1 The format of the title sheet to be adopted for preparation of the
       drawings is attached at Appendix-2
                                            - 35 -
17.4.2 After approval, six copies of each of the approved drawings along with
       two sets of reproducible prints for each drawing shall be supplied to each
       consignee (s). Besides, two copies of drawings along with one set of
       reproducible prints shall be supplied to DG(TI), RDSO, Lucknow.
17.4.3 Two copies of the "Operation/ Maintenance Manual" for each
      transformer shall be supplied to the consignee(s). Two copies of the
      manual shall be supplied to the DG(TI), RDSO, Lucknow.
                                          - 36 -
     the successful tenderer/ manufacturer. No charges shall be payable by the
     purchaser to the successful tenderer/manufacturer for the services of his
     engineer in this regard.
20.2 If any transformer has been received at site in a damaged condition and in
     the opinion of the Railway's engineer at site it is required to be repaired at
     the successful tenderer/ manufacturer's works, the transformer shall be
     taken back to the works promptly and after repairs, all necessary tests
     including the routine tests shall be done on the complete transformer in the
     presence of and to the satisfaction of the Railway's Engineer prior to
     returning the transformer to site. Such tests are necessary to ensure that the
     quality of the workmanship during repairs is satisfactory and shall be done
     free of cost. Any tests, as decided by the Railway's engineer at site shall
     also be conducted on the transformer at site free of cost.
21.0 TRAINING OF INDIAN RAILWAY'S ENGINEERS
21.1 The offer shall include the training of two Engineers of the Indian
    Railways free of cost at the manufacturer's works and at the maintenance
    depots/workshops on a railway system or other public utility where
    transformers of similar design are in operation. The total duration of
    training for each Engineer shall be 12 weeks of which approximately 6
    weeks shall be at the manufacturer's works and 6 weeks on a railway
    system or other public utility. The cost of travel to the place of manufacture
    and back shall be borne by the Indian Railways. Other details shall be
    settled at the time of finalizing the contract or Purchaser order.
22.0 AFTER SALES SERVICE
22.1 The successful tenderer/ manufacturer shall make necessary arrangements
     for closely monitoring the performance of the transformer(s) through
     periodical (preferable once in two months during the warranty period)
     visits to the locations where they have been erected for observations and
     interaction with the operating and maintenance personnel of the Indian
     Railways. Arrangements shall also be made by the successful tenderer/
     manufacturer for emergency/standby spare parts being kept readily
     available to meet exigencies warranting replacement so as to keep the
     transformers in service with least down time.
22.2 The successful tenderer/ manufacturer shall respond promptly and in a
     workman-like manner to any call given by Indian Railways for any
     assistance by way of attending to failures, investigation into the causes of
     failures including tests, if any, to be done and such other items with a view
     to seeing that the transformer serves the purpose for which it is intended.
     Besides technical guidance to ensure proper operation and maintenance of
     the traction transformer shall be constantly rendered.
                                           - 37 -
23.0   WARRANTY
23.1 The successful tenderer/ manufacturer shall warrant that all equipment
    shall be free from defects and faults in design, material, workmanship and
    manufacture and of the highest grade consistent with the established and
    generally accepted standards for the equipment of the type ordered and in
    full conformity with the specifications and shall operate properly.
23.2 This warranty shall survive inspection of, payment for and acceptance of
     the equipment, but shall expire 24 (Twenty Four) months after the delivery
     at ultimate destination in India, or 18(Eighteen) months from the date of
     commissioning and proving test of the equipment at ultimate destination in
     India, whichever period expires earlier, except in respect of complaints,
     defects and/or claims notified to the successful tenderer/ manufacturer
     within 3 (Three) months of the expiry of such date. Any approval or
     acceptance by the Purchaser of the equipment shall not in any way limit the
     successful tenderer/ manufacturer's liability.
23.3 The successful tender/ manufacturer's liability in respect of any complaint,
     defects and/or claims shall be limited to the furnishing and installation of
     replacement parts free of any charge or the repair of defective parts only to
     the extent that such replacement or repairs are attributable to or arise from
     faulty workmanship or material or design in the manufacture of the goods,
     provided that the defects are brought to the notice of the successful
     tenderer/ manufacturer within 3(Three) months of their being first
     discovered during the warranty period or 3 (Three) months from the date of
     expiry of warranty period, or at the option of the Purchaser, to the payment
     of the value, expenditure and damage as hereafter mentioned.
23.4 The successful tenderer/ manufacturer shall, if required, replace or repair
     the equipment or such portion thereof as is rejected by the Purchaser free
     of cost at the ultimate destination or at the option of the Purchaser, the
     successful tenderer/ manufacturer shall pay to the Purchaser value thereof
     at the contract price or in the absence of such price at a price decided by
     the Purchaser and such other expenditure and damages as may arise by
     reason of the breach of the conditions herein specified.
23.5 All replacements and repairs that the Purchaser shall call upon the
    successful tenderer/ manufacturer to deliver or perform under this
    Warranty shall be delivered and performed by the successful tenderer/
    manufacturer promptly and satisfactorily and in any case within 2 (Two)
    months of the date of advice to this effect.
23.6 If the successful tenderer/ manufacturer so desires, the parts that are
    removed may be taken over by him or his representative for disposal as he
    deems fit at the time of replacement with good parts. No claim whatsoever
    shall lie on the Purchaser thereafter for the parts so removed.
                                          - 38 -
23.7 The Warranty herein contained shall not apply to any material which shall
     have been repaired or altered by the Purchaser or on his behalf in any way
     without the consent of the successful tenderer/ manufacturer, so as to affect
     the strength, performance or reliability or to any defects to any part due to
     misuse, negligence or accident.
23.8 the decision of the Purchaser in regard to successful tenderer/
    manufacturer's liability and the amount, if any, payable under this warranty
    shall be final and conclusive.
24.0 SHIPMENT OF THE TRANSFORMER
24.1 The transformer shall be transported depending upon the transport
    facilities available for the route i.e. by rail or truck or ship.
24.2 The transformer shall be dispatched with its core and windings along with
    the tap-changer assembly in the transformer tank filled with oil and the
    space above the oil filled with pure dry air or inert gas like nitrogen at a
    pressure slightly above atmospheric pressure. However, if there are
    limitations on account of weight, the tank shall be filled with nitrogen
    under pressure and the oil for the first filling shall be supplied separately in
    steel drums. In case the tank is filled with inert gas the temperature and
    pressure at the time of filling shall be marked conspicuously on the
    transformer.
24.3 All openings created on the tank by removal of any items shall be closed
    with suitable blanking plates. All the parts, fitting and accessories such as
    conservator tank, bushings, silicagel breather, radiator, Buchholz relay,
    temperature indicators and other items shall be packed/crated separately
    along with a packing list in each crate containing the following particulars:
24.4 The packing shall be done properly so that no damage occurs during
    transit.
24.5 All the parts, fittings and accessories for each transformer shall be so
    dispatched that they arrive at site together to enable erection of the
    complete transformer without delay.
24.6 Necessary instructions for handling and storage of all items shall be
    included along with the packing lists.
24.7 In case of overseas supply, packing shall be sea worthy.
*******************
                                            - 39 -
                                                                  ANNEXURE-'3'
                                         (For Specification No. ETI/PSI/124(07/95)
SCHEDULE OF GUARANTEED PERFORMANCE, TECHNICAL AND
OTHER PARTICULARS (GUARANTEED PARTICULARS ARE TO BE
ESTABLISHED BY ACTUAL TESTS/ TEST REPORTS)
Sl.                DESCRIPTION                    UNIT OF            VALUE/
No.                                             MEASUREMENT       INFORMATION
 1                       2                              3                4
A     RATINGS/PARTICULARS
1.    Name of the Manufacturer
2.    Country of manufacture
3.    Reference to specification based on
      which performance data is prescribed
4.    Rated power                               MVA
5.    Primary current at:
      a) Rated load                             A
      b) 150% rated load for 15 min             A
      c) 200% rated load for 5 min              A
6.    Secondary current at:
      a) Rated load                             A
      b) 150% rated load for 15 min             A
      c) 200% rated load for 5 min              A
7.    Rated voltage :
      a) Primary                                kV
      b) Secondary (at no-load)                 kV
8.    Rated frequency                           Hz
9.    Temperature rise above         ambient
      temperature of 500C :
      (i). Oil :
                                                0
      a) At rated load                              C
                                                0
      b) At 150% rated load for 15 min              C
                                                0
      c) At 200% rated load for 5 min               C
                                               - 40 -
      (ii) Winding :
                                            0
      a) At rated load                          C
                                            0
      b) At 150% rated load for 15 min.         C
                                            0
      c) At 200% rated load for 5 min           C
10.   Hot-spot temperature of winding
      over ambient temperature of 500C
                                            0
      a) At rated load                          C
                                            0
      b) At 150% rated load for 15 min.         C
                                            0
      c) At 200% rated load for 5 min           C
11.   Interval of time between two
      successive    overloads    after
      continuous working at full load,
      at maximum ambient temperature
      of 500C:
      a) Between two consecutive over min
      loads of 50% for 15 min.
      b) Between two consecutive min
      overloads of which one is of 50%
      for 15 min and the other of 100%
      for 5 min.
12.   No-load current referred to
      primary side at rated frequency
      and at:
      a) 90% rated voltage                  A
      b) Rated voltage                      A
      c) 110% rated voltage                 A
13.   Power factor of no-load current at
      rated voltage and rated frequency
14.   Value of the inrush current at A
      rated voltage on primary side, the
      secondary side being open
      circuited
15.   Losses:
      (i). No-load loss       at    rated
      frequency and at:
      a) 90% rated voltage at the kW
      principal tapping.
      b) rated voltage         at    the kW
      principal tapping.
      c) 110% rated voltage at the kW
      primary tapping.
                                                    - 41 -
      d) Appropriate voltage at the - kW
      15% tapping.
      e) Appropriate voltage at the kW
      +10% tapping/
      (ii) Load loss (at 750C) at rated kW
      current and frequency
      a) Principal tapping             kW
      b) -15% tapping                  kW
      c) +10% tapping                  kW
      (iii) Total losses at rated
      current and frequency
      a) Principal tapping             kW
      b) -15% tapping                  kW
      c) +10% tapping                  kW
16.   Resistance voltage (at 750C) at %
      rated current
17.   Reactance voltage (at 750C) at %
      rated current and frequency
18.   Impedance voltage (at 750C) at %
      rated current and frequency
19.   Resistance (at         750C)   of ohm
      primary winding
20.   Resistance (at 750C)           of ohm
      secondary winding
21.   Reactance of winding :           H
      i) Primary                       H
      II) Secondary at
      a). Principal tapping            H
      b). +10% tapping                 H
      c). -15% tapping                 H
                              0
22.   Regulation (at 75 C) with
      rated current and at power
      factor of:
      a) Unity                         %
      b) 0.8 lagging                   %
                                           - 42 -
23.   Efficiencies:
      (i). Efficiency (at 750C) at unity
      power factor at:
      a). 100% load                               %
      b). 75% load                                %
      c). 50% load                                %
      d). 25% load                                %
                             0
      (ii). Efficiency (at 75 C) at 0.8 power
      factor lagging at:
      a). 100% load                               %
      b). 75% load                                %
      c). 50% load                                %
      d). 25% load                                %
      (iii). Percentage of rated load at which %
      maximum efficiency occurs.
24.   Ability to withstand short-circuit:
      a). Thermal                                 s
      b). Dynamic                                 s
25.   Thermal time constant (calculated):
      (i). for winding with respect to oil at:
      a). rated current                           min
      b). 150% rated current                      min
      c). 200% rated current                      min
      (ii). Complete transformer at rated min
      current
26.   Temperature gradient between oil and
      winding at:
                                                  0
      a). Rated current                               C
                                                  0
      b). 150% rated current for 15 min               C
      c). 200% rated current for 5 min.
                                                  0
                                                      C
27.   Temperature rise of oil:
      (i). Calculated average temperature
      rise of oil at:
                                                  0
      a). Rated current                               C
                                                  0
      b). 150% rated current for 15 min               C
                                             - 43 -
                                                   0
      c). 200% rated current for 5 min                 C
      (ii) Estimated temperature rise of top
      oil at:
                                                   0
      a). Rated current                                C
                                                   0
      b). 150% rated current for 15 min                C
                                                   0
      c). 200% rated current for 5 min                 C
28.   Details of core:
      (i)     Type of core
      (ii)    Flux density at rated voltage tesla
              and frequency
      (iii)   Flux density at 110% rated tesla
              voltage and frequency
                                           mm
      (iv)    Thickness of steel stampings
      (v)     Grade of core material and
              conforming specification
      (vi)    Exciting VA/kg       for    core
              stampings at:
              a) Flux density of 1.55 tesla        VA/kg
              b) Flux density at rated voltage VA/kg
              c) Flux density at 110% rated VA/kg
                 voltage
      (vii) Exciting VA/kg for assembled
            core at:
              a) Flux density of 1.55 tesla        VA/kg
              b) Flux density at rated voltage VA/kg
              c) Flux density at 110% rated Va/kg
                 voltage
      (viii) Type of insulation between core
             laminations.
      (ix)    Type of joint between the core
              limbs and yoke.
      (x)     core bolt Insulation withstand kV
              voltage
      (xi)    Core bolt insulation flashover kV
              voltage
                                              - 44 -
29.   Details of windings:
      (i) Type of winding
        (a)    Primary
        (b)    Secondary
        (c)    Number of turns of primary
               winding
        (d)    Number     of    turns     of
               secondary winding
        (e)    Number of parallel paths in
               primary winding
        (f)    Number of parallel paths in
               secondary winding.
        (g)    Is interleaving/inter shielding Yes/No
               of the winding adopted to
               ensure better impulse voltage
               distribution?
        (i) Primary
        (ii) Secondary
                                          - 45 -
             a) Primary                      A/mm2
             b) Secondary                    A/mm2
(v)    Insulation used over the
       conductor (details of material
       and specification there for)
(vi)   Type of joints, if any, in the
       windings
(vii) Dielectric        strength        of
      windings:
       a)     Full    wave      lightning
              impulse           withstand
              voltage:
             a) Primary winding              kV peak
             b) Secondary winding.           kV peak
       (b)       Lightning      Impulse
              chopped on the tail
              withstand voltage:
       (i) Primary winding
                                             kV peak
       (ii) Secondary winding
                                   kV peak
       (c) Separate source power
           frequency     withstand
           voltage                 kV
       (i) Primary
       (ii) Secondary
       (d)    Induced over         voltage
              withstand value
                                             kV
(viii) Minimum flashover distance
       to earth in oil of :
             a) Secondary winding to
                core
             b) Primary      winding    to
                yoke
             c) Primary      winding    to
                tank
(ix) Material     used     for coil
     clamping         rings    and
     specification there for
(x) Magnitude of axial pre-
     compressive force on the
     winding
    (a) Primary
    (b) Secondary
                                       - 46 -
       (xi)    Calculated maximum axial
               thrust in the winding due to
               dead short circuit at the
               terminals                    t
              (a) Primary
              (b) Secondary
       (xii) Calculated short circuit forces:
              a) Hoop stress     in   primary
                 winding                        kgf/cm2
              b) Hoop stress in secondary
                 winding
                                                kgf/cm2
              c) Compressive pressure in the
                 radial spacers
                                                   2
              d) Internal axial compressive kgf/cm
                 force                      kgf
              e) Axial imbalance force
              f) Resistance to college          kgf
              g) Bending stress on clamping kgf
                 ring
                                            kgf/cm2
              h) Radial bursting force
       (xiii) Arrangement to          maintain
              constant pressure       on the kgf
              windings
       (xiv) Maximum permissible torque
             on pressure screws for coil
                                         N.m
             clamping at the time of
             tightening, if any.
       (xv) Can either end of each
            secondary winding (25 kV) be Yes/No.
            connected directly to earth?
30.   Motorised off-circuit tap changer:
       a) Name of the manufacturer
       b) Country of origin.
       c) Type designation
       d) Governing specification.
       e) Is a separate taped winding
           provided n each secondary.
       f) Number of tappings:
                i)      Plus tappings
                ii)     Minus tappings
       g) Percentage variation of voltage
           on different tapping.
       h) Minimum contact pressure kgf
           between moving and stationery
                                          - 47 -
              contacts                          A
         i) Maximum rated through current       kV
         j) Voltage class                       V(dc)
         k) Rated voltage of control circuit
         l) Tap changer motor particulars:
                   i)     Make and type         V(dc)
                   ii)    Rated voltage         A
                   iii)   Rated current         kW
                   iv)    Rated power           rpm.
                   v)     Speed
                   vi)    Class of insulation
31.   Bushings:
      (i). Primary side:
         a) Name of the manufacturer
         b) Country of origin
         c) Governing specification
         d) Type designation (specify as
               to whether it is OIP condenser
               bushing)
         e) Voltage class                       kV
         f) Rated current                       A
         g) Visible       power     frequency
               discharge voltage                kV
         h) Wet one minute power                kV peak
               frequency withstand voltage
         i) Lightning impulse withstand         mm
               voltage
         j) Creepage distance
         k) Weight of assembled bushing         kV
                                          - 48 -
        f)     Rated current                    A
        g)     Visible     power    frequency   kV
               discharge voltage
         h) Wet one minute power                kV
               frequency withstand voltage
         i) Lightning impulse withstand         kV peak
               voltage
         j) Creepage distance                   mm
         k) Weight of assembled bushing         kgf
32.      Bushing type current transformers:
      (i). Primary side:
         a) Name of the manufacturer
         b) Governing specification
         c) Transformation ratio
         d) Accuracy class and rated
              accuracy limit factor
         e) Rated current                       A
         f) Rated output                        VA
         g) Exciting current at the rated       mA
              knee point emf
         h) Rated knee point emf                V
         i) Secondary winding resistance        ohm
              corrected to 750C
         j) Short time thermal current and      kA,s
              duration.
      (ii). Secondary side:
         a) Name of the manufacturer
         b) Governing specification
         c) Transformation ration
         d) Accuracy class
         e) Rated current                       A
         f) Rated output                        VA
         g) Exciting current at the rated
              knee point emf                    VA
         h) Rated knee point emf                V
         i) Secondary winding resistance        Ohm.
              corrected to 750C.
         j) Short time thermal current and      kA,s.
              duration
                                          - 49 -
40.       Details of pressure relief device:
          a) Make and type
          b) Governing specification
          c) Does it reset itself               Yes/No
41.       Bimetallic terminal connectors:
          (i). Primary side:
          a) Source of supply
          b) Governing specification
          c) Type
          d) Rated current                      A
                                                0
          e) Temperature rise over an             C
               ambient temperature of 450C
               while carrying rated current.
          f) Short time current and duration    kA,s
          (ii). Secondary side:
          a) Source of supply
          b) Governing specification
          c) Type
          d) Rated current                      A
                                                0
          e) Temperature rise over an             C
               ambient temperature of 450C
               while current rated current
          f) Short time current and duration    kA,s
42.       Acoustic sound level at a distance    dB
          of 1 m, when energised at rated
          voltage and rated frequency
          without load.
43.       Partial discharge value at 1.5Um/ 3   pC
          kV r.m.s.
44.       Weights and dimensions:
          (i) Net weight of core
          (ii) Net weight of cooper:
          a) Primary winding                    kg
          b) Secondary winding                  kg
      (iii) Net untanking weight of core        kg
      frame and coils
      (iv) Net weight of insulating oil         kg
                                          - 50 -
      e) Dielectric, dissipation factor (tan-
      delta) at 90 C
      f) Dielectric strength                     kV
      g) Water content                           ppm
      h) Interfacial tension                     N/m
      i) Neutralisation value                    mg KOH/gm
                                                 0
      j) Flash point                               C
                                            - 51 -
(v) Volume of insulating oil           l
(vi) Total weight of cooling equipment t
    a) Overall length                   mm
    b) Overall breadth                  mm
    c) From rail level to the topmost   mm
        point
(xiii) Minimum thickness of steel
    plate/ sheet used:
    a) Bell tank                        mm
    b) Tank bottom                      mm
    c) Conservator                      mm
    d) Radiator                         mm
    e) Marshalling box.                 mm
                                  - 52 -
      Other particulars
                                         - 53 -
58.   What are the designed values of
      short-circuit current for:
      a) Symmetrical :
i) Primary winding A
b) Asymmetrical:
i) Primary winding A
                                        - 54 -
70.   Is the Buchholz relay provided with      Yes/ No
      two shut-off valves, one on either
      side?
71.   Is separate conservator tank &           Yes/ No
      Buchholz ralay provided for tap
      chaning equipment?
72.   Are fasteners of 12 mm diameter and      Yes/ No
      less exposed to atmosphere of
      stainless steel to Grade 04Cr17
      Ni12Mo to IS 1570 Part-V?
73.   Are the fasteners of more than 12        Yes/ No
      mm diameter exposed to atmosphere
      of stainless steel or MS hot dip
      galvanised?
74.   Are test certificates for tests as per   Yes/ No
      Clause 15.0 attached?
75.   Are all the calculations required as Yes/ No
      per clause 16.3.1 attached?
76.   Are all the drawings required as per Yes/ No
      clause 16.3.2 attached ?
77.     (a) Are all the parts, fittings and Yes/ No
            accessories from RDSO's
            approved manufacturers ?
        (b) If not, list the items which are Yes/No
            to be type tested in the
            presence         of     RDSO's
            representative
**********************
                                          - 55 -
                                                                           ANNEXURE-5
              CAPITALISATION OF TRANSFORMER LOSSES
        Following formula shall be used for the purpose of calculating the
present worth of the transformer after taking in account capitalization of its
losses.
               K           =                                D{(1+i)n-1
                                                              i(1+i)n
Where,         K           =          Present worth of transformer in Rupee.
               D           =          Annual cost of combined no-load and load
                                      losses in Rupee.
                                      Rate of compound interest on unit price of
               i           =
                                      transformer @ 12% per annum.
               n           =
                                      Life of transformer.
Substituting value of D, which is :
               D           =                        ( I + F2 C) 365 x 24 x T
                                                               1000
where,
               I           =          Maximum No- load loss in watt.
               C           =          Maximum Load-loss in watt.
               F           =          Load factor.
               T           =          Tariff.
Assuming values of n as 25 year, F as 50% and T as Rupee 2 per kwh, the value
of K is,
K              =                                         (1+0.12)25-1
                            17.52 (I + 0.25 C)
                                                         0.12 (1+0.12)25
K              =            137.41 (I +0.25 C)
                                                - 56 -
- 57 -
- 58 -
- 59 -
- 60 -