Rockwell 1606-XL60D Power Supply Guide

1) This document provides information on a power supply unit with worldwide approvals that has high overload current capability without switching off. 2) It has an input voltage range of AC 100-120V/200-240V (switchable) and output of 24V/2.5A. It features wide-range input, robust mechanics, and EMC compliance. 3) The unit has no disconnection or hiccup mode even when overloaded, providing high overload current up to 1.5 times the nominal level while gradually reducing output voltage. This allows for reliable starting of loads.

Uploaded by

Nixius
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
129 views2 pages

Rockwell 1606-XL60D Power Supply Guide

1) This document provides information on a power supply unit with worldwide approvals that has high overload current capability without switching off. 2) It has an input voltage range of AC 100-120V/200-240V (switchable) and output of 24V/2.5A. It features wide-range input, robust mechanics, and EMC compliance. 3) The unit has no disconnection or hiccup mode even when overloaded, providing high overload current up to 1.5 times the nominal level while gradually reducing output voltage. This allows for reliable starting of loads.

Uploaded by

Nixius
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

Application Note

1606-XL60D
• World-wide approvals ( ) • High overload current, no switch-off
for industry • Wide-Range Input
• Input: AC 230V / 115V • Robust mechanics and EMC
• Output: 24V / 2.5A
Input Rise time ca. 5...20 ms, depending on load

Input voltage AC100...120/200...240V (switchable), 47...63 Hz Overload Behavior


(85...132 V AC / 176...264 V AC, 160...375 V DC, see • Special Overload Design – no disconnection, no hiccup if overloaded
also Output: Continuous Loading) (see diagram) – high overload current (up to 1.5 INom), Vout is
gradually reduced with increasing current.
Wide-Range Input: With the switch in the 230V position the power-supply unit op-
erates at low and moderate loads at any input voltage between 95 and 264 V AC (see Advantages:
Output at the right side). • High short-circuit current, giving large ‘start-up window’: unit starts reliably
Note: With DC input, always leave the switch in the 230V position even with awkward loads (DC-DC converters, motors).
• No sticking as can occur with fold-back characteristics
Input current < 1.3 A (switch in 115V position) • Secondary fuses operate reliably
< 0.7 A (switch in 230V position)
DC input current typ. 5.3 mA at 110 V DC, 3.9 mA at 300 V DC (pre-
Output
at open output serves battery sources)
Output voltage 24V DC +5% –1% (12V on request)
Inrush current typ. 25 A at 264 V AC and cold start
Output noise Radiated EMI values below EN50081-1, even when
If you intend to protect the primary side of the power supply with a fuse or a circuit suppression using long, unscreened output cables.
breaker, a 10 A slow acting fuse (HBC) or a supplementary protector 1492- Ambient temperature range Operation: -10°C...+70°C (>60°C: Derating)
SPU1C100 is recommended. In order to meet local requirements, please consult lo-
Tamb Storage: -25°C...+85°C
cal codes and regulations for proper installation.
Continuous loading Switch AC/DCin Iout
EN 61000-3-2 (harmonic current emissions) is fulfilled (at Tamb = -10°C...+60°C, 230V 176...264V ACin 2.5 A
convection cooling), 95...176V ACin 1.5 A
Transient Transient resistance acc. to VDE 0160 / W2 (750 V / see also diagram. For start at
handling 1.3 ms), for all load conditions. Tamb<0°C and low input volt- 160...375V DCin 2.5 A
age, please contact Rockwell 120...160V DCin 2.0 A
Hold up time > 20 ms at 196 VAC, 24V/ 2.5 A Automation. 80*...120V DCin 1.5 A
(see diagram) * For start with DC input > 95V 115V 85...132V ACin 2.5 A
DC needed
Efficiency, Reliability etc. Output protected against short circuit, open circuit and overload
Derating typ. 1.5 W/K (at Tamb=+60°C...+70°C)
Efficiency typ. 87.5 % (230 V AC, 24V/ 2.5 A)
Voltage regulation better than 2% Vout overall
Losses typ. 8.6 W (230 V AC, 24V / 2.5 A)
Ripple / Noise < 25 mVPP, (20 MHz bandwidth, 50 Ω measurement)
MTBF 740,000 h acc. to Siemensnorm SN 29500
Overvolt. protection typ. 32V
(24V/2.5 A, 230 V AC, Tamb = +40 °C)
Parallel operation yes; current sharing available on request
Life cycle (electrolytics) The unit exclusively uses longlife electrolytics, speci-
fied for +105°C. Power back immunity 26V
Front panel indicator Green LED, goes out at Vout < 18V
Start / Overload Behavior
Startup delay typ. 0.1 s

1 Publication 1606-AP011A-EN-E March 2003


2 Application Note

Construction / Mechanics Design advantages:


• All connection blocks are easy to reach as mounted at the front panel.
Housing dimensions and Weight • Input and output are strictly apart from each other and so cannot be mixed up (In-
• WxHxD 49 mm x 124 mm x 102 mm (+ DIN rail) put below, output above).
• Free space for ventilation above/below 25 mm recommended; right 10 mm rec- Wire Size Input/Output:
ommended (front view) • Stranded 20...10 AWG (0.5...4 mm²), Solid 20...10 AWG (0.5...6 mm²)
• Weight 460 g Tightening Torque: 7 lbs in (0.8 Nm) recommended

Output Current over Input Voltage (min.) Output characteristic (min.)

3 28
DCin

Tamb = 60°C / 45°C / 25°C / 0°C


2
24

1
20
Output current Iout [A]

Output voltage Vout [V]


>95 VDC for start

80 160 375 16
100 200 300 400
Input voltage V DCin [V]
12
3
switch at 115V ACin
8
2 switch at
230V
4
1

95 0
85 132 176 264 0 1 2 3 4 5 6
100 200 300 400
Input voltage V ACin [V] Output current Iout [A]

Hold-up time (min.)

100 100
Iout=1,0 A
90 DCin 90 ACin
Iout=1,0 Switch pos.
80 80 115V
Iout=1,5 A Iout=1,5 A
70 70
Hold-up time [ms]
Hold-up time [ms]

60 60
Iout=1,5 Iout=2,5 A Iout=2,5 A
50 50 Switch pos
40 40 230V

30 30
Iout=2,5
20 20
10 10
0 0
80 120 160 200 240 280 320 90 120 150 180 210 240
Input voltage VDCin [V] Input voltage VACin [V]

Specifications valid for 230V AC input voltage, +25°C ambient temperature, and 5 min
run-in time, unless otherwise stated. They are subject to change without prior notice

www.rockwellautomation.com

Corporate Headquarters
Rockwell Automation, 777 East Wisconsin Avenue, Suite 1400, Milwaukee, WI, 53202-5302 USA, Tel: (1) 414.212.5200, Fax: (1) 414.212.5201

Headquarters for Allen-Bradley Products, Rockwell Software Products and Global Manufacturing Solutions
Americas: Rockwell Automation, 1201 South Second Street, Milwaukee, WI 53204-2496 USA, Tel: (1) 414.382.2000, Fax: (1) 414.382.4444
Europe: Rockwell Automation SA/NV, Vorstlaan/Boulevard du Souverain 36-BP 3A/B, 1170 Brussels, Belgium, Tel: (32) 2 663 0600, Fax: (32) 2 663 0640
Asia Pacific: Rockwell Automation, 27/F Citicorp Centre, 18 Whitfield Road, Causeway Bay, Hong Kong, Tel: (852) 2887 4788, Fax: (852) 2508 1846

Headquarters for Dodge and Reliance Electric Products


Americas: Rockwell Automation, 6040 Ponders Court, Greenville, SC 29615-4617 USA, Tel: (1) 864.297.4800, Fax: (1) 864.281.2433
Europe: Rockwell Automation, Brühlstraße 22, D-74834 Elztal-Dallau, Germany, Tel: (49) 6261 9410, Fax: (49) 6261 1774
Asia Pacific: Rockwell Automation, 55 Newton Road, #11-01/02 Revenue House, Singapore 307987, Tel: (65) 351 6723, Fax: (65) 355 1733

Publication 1606-AP011A-EN-E March 2003  2003 Rockwell International. All Rights Reserved. Printed in US