DR 120 Spec

The document describes a 120W single output industrial DIN rail power supply series. It provides 120W of power with outputs of 12V/10A, 24V/5A or 48V/2.5A. It has protections for overloads, over voltages and over temperatures. It is approved for industrial use and has a 3 year warranty. Key specifications include AC input ranges, adjustable DC output voltages, efficiencies up to 85%, hold up times over 30ms, and operating temperatures from -10°C to 60°C.

Uploaded by

Antonio Serrano
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
263 views2 pages

DR 120 Spec

The document describes a 120W single output industrial DIN rail power supply series. It provides 120W of power with outputs of 12V/10A, 24V/5A or 48V/2.5A. It has protections for overloads, over voltages and over temperatures. It is approved for industrial use and has a 3 year warranty. Key specifications include AC input ranges, adjustable DC output voltages, efficiencies up to 85%, hold up times over 30ms, and operating temperatures from -10°C to 60°C.

Uploaded by

Antonio Serrano
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

120W Single Output Industrial DIN RAIL Power Supply DR-120 series

■ Features :
AC input range selectable by switch
Protections: Short circuit / Overload / Over voltage / Over temperature
Cooling by free air convection
Can be installed on DIN rail TS-35/7.5 or 15
UL 508(industrial control equipment)approved
LED indicator for power on
100% full load burn-in test
Fixed switching frequency at 55KHz
3 years warranty
Bauar t gepruft
Sicherheit
egel ma ge
od o s
be wac g

SPECIFICATION
www. tuv.com
ID 2000000000

MODEL DR-120-12 DR-120-24 DR-120-48


DC VOLTAGE 12V 24V 48V
RATED CURRENT 10A 5A 2.5A
CURRENT RANGE 0 ~ 10A 0 ~ 5A 0 ~ 2.5A
RATED POWER 120W 120W 120W
RIPPLE & NOISE (max.) Note.2 80mVp-p 80mVp-p 100mVp-p
OUTPUT VOLTAGE ADJ. RANGE 12 ~ 14V 24 ~ 28V 48 ~ 53V
VOLTAGE TOLERANCE Note.3 ±2.0% ±1.0% ±1.0%
LINE REGULATION ±0.5% ±0.5% ±0.5%
NR

LOAD REGULATION ±1.0% ±1.0% ±1.0%


SETUP, RISE TIME 500ms, 70ms/230VAC 500ms, 70ms/115VAC at full load
HOLD UP TIME (Typ.) 36ms/230VAC 32ms/115VAC at full load
VOLTAGE RANGE 88 ~ 132VAC/176 ~ 264VAC by switch 248 ~ 370VDC
FREQUENCY RANGE 47 ~ 63Hz
EFFICIENCY (Typ.) 80% 84% 85%
ND

INPUT
AC CURRENT (Typ.) 2.6A/115VAC 1.6A/230VAC
INRUSH CURRENT (Typ.) COLD START 20A/115VAC 40A/230VAC
LEAKAGE CURRENT <3.5mA / 240VAC
105 ~ 150% rated output power
OVERLOAD
Protection type : Constant current limiting, recovers automatically after fault condition is removed
15 ~ 16.5V 29 ~ 33V 58 ~ 65V
PROTECTION OVER VOLTAGE
Protection type : Shut down o/p voltage, re-power on to recover
85℃±5℃ (TSW1) 90℃±5℃(TSW1) 90℃±5℃(TSW1)
OVER TEMPERATURE
Protection type : Shut down o/p voltage, recovers automatically after temperature goes down
WORKING TEMP. -10 ~ +60℃ (Refer to "Derating Curve")
WORKING HUMIDITY 20 ~ 90% RH non-condensing
ENVIRONMENT STORAGE TEMP., HUMIDITY -20 ~ +85℃, 10 ~ 95% RH
TEMP. COEFFICIENT ±0.03%/℃ (0 ~ 50℃)
VIBRATION 10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes; Mounting: Compliance to IEC60068-2-6
SAFETY STANDARDS UL508, UL60950-1, TUV EN60950-1, EAC TP TC 004 approved
SAFETY & WITHSTAND VOLTAGE I/P-O/P:3KVAC I/P-FG:2.0KVAC O/P-FG:0.5KVAC
EMC ISOLATION RESISTANCE I/P-O/P, I/P-FG, O/P-FG:100M Ohms / 500VDC / 25℃/ 70% RH
(Note 4) EMC EMISSION Compliance to EN55011,EN55032 (CISPR32) Class B, EN61000-3-2,-3, EAC TP TC 020
EMC IMMUNITY Compliance to EN61000-4-2,3,4,5,6,8,11, EN55024, EN61000-6-2 (EN50082-2), heavy industry level, criteria A, EAC TP TC 020
MTBF 432.1Khrs min. MIL-HDBK-217F (25℃)
OTHERS DIMENSION 65.5*125.2*100mm (W*H*D)
PACKING 0.79Kg; 20pcs/16.5Kg/1.29CUFT
1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25℃ of ambient temperature.
NOTE
2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor.
3. Tolerance : includes set up tolerance, line regulation and load regulation.
4. The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets
EMC directives.
5. The ambient temperature derating of 3.5℃/1000m with fanless models and of 5℃/1000m with fan models for operating altitude higher than 2000m(6500ft).

File Name:DR-120-SPEC 2018-01-12


120W Single Output Industrial DIN RAIL Power Supply DR-120 series

Mechanical Specification Case No. 921A Unit:mm

100
125.2
+V ADJ.

115VAC

230VAC
TB1 TB2
1 1
2
65.5

2
3 3
4
LED

Terminal Pin No. Assignment (TB1)


Pin No. Assignment
1 FG
35

2 AC/N
3 AC/L
NR

ADMISSIBLE DIN-RAIL: TS35/7.5 OR TS35/15


Terminal Pin No. Assignment (TB2)
Pin No. Assignment
1,2 DC OUTPUT +V
3,4 DC OUTPUT -V
ND

Block Diagram 230 fosc : 55KHz


115

EMI RECTIFIERS POWER RECTIFIERS +V


I/P FILTER & &
SWITCHING -V
FILTER FILTER

DETECTION
FG CIRCUIT
O.L.P. PWM
CONTROL
O.T.P. O.V.P.

Derating Curve Static Characteristics (24V)

48V 32 350
100
OUTPUT RIPPLE (mVp-p)

28 300
OUTPUT VOLTAGE (V)

80
24 250

60 12V,24V 20 200
LOAD (%)

16 150
40
12 100
20
8 80

-10 0 10 20 30 45 50 60 (VERTICAL) 80 85 90 95 100 105 110 115 120 125 132


160 170 180 190 200 210 220 230 240 250 264

AMBIENT TEMPERATURE (℃) INPUT VOLTAGE (V) 60Hz

File Name:DR-120-SPEC 2018-01-12