This document discusses the selection of a surge arrester for a 2.5MVA 34.5kV/400V indoor substation for SM San Jose. It specifies the equipment including a 2500kVA power transformer. The objective is to select a surge arrester that protects the transformer without compromising its 170kV BIL rating. It determines that an INAEL INZSP 30/10/2 arrester with a 73.2kV residual voltage meets this need with over 67% protective margin above the minimum requirement.

Uploaded by

CH Asia
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOC, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
228 views5 pages

Insulation Coordination 11.02.15

This document discusses the selection of a surge arrester for a 2.5MVA 34.5kV/400V indoor substation for SM San Jose. It specifies the equipment including a 2500kVA power transformer. The objective is to select a surge arrester that protects the transformer without compromising its 170kV BIL rating. It determines that an INAEL INZSP 30/10/2 arrester with a 73.2kV residual voltage meets this need with over 67% protective margin above the minimum requirement.

Uploaded by

CH Asia
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOC, PDF, TXT or read online on Scribd
You are on page 1/ 5

SURGE ARRESTER SELECTION ..

Project : 2.5MVA 34.5kV/400V Indoor Substation


Location : SM San Jose
Client : SM Prime Holdings Inc.
Date : Nov 2, 2015

I. PROJECT SCOPE OF WORKS

Supply and installation of 2.5MVA 34.5kV/400V Indoor Substation for SM San


Jose Del Monte.

II. OBJECTIVE

The objective of this study is to properly select the surge arrester at the HV
side of the power transformer without compromising the transformer’s HV BIL rating.

III. EQUIPMENT SPECIFICATIONS

Power Transformer

Brand : SHILIN
Country of Origin : Taiwan
Type : Oil-immersed Conservator Type
kVA Rating : 2500/3125kVA
Vector Group : Dyn11
Primary Voltage : 34.5kV
Secondary Voltage : 400/231V
Tap : 5 taps +/- 2.5%
BIL (HV) : 170kV
Ref. Standard : IEC-60076

*Please see technical specifications for reference

Surge Arrester

Brand : INAEL
Country of Origin : Spain
Type : Station Class, Gapless
Model : INZSP 30/10/2
Rated Voltage : 30kV
MCOV : 24.4kV
Residual Voltage under 8/20µS – 10kA (kV) : 73.2kV
Residual voltage under switching impulse – kV : 59.7kV
Location : 34.5kV MVSG

*Please see attached brochures for reference

#366 2nd ST.Bet. 9th & 10th Avenue brgy. 107, Caloocan City
TEL. No. 365-6793 & 365-3430
Website: www.chasia.com.ph
Email Add: info@chasia.com.ph
IV. SINGLE LINE DIAGRAM

Note: Surge arresters at First Private Pole are also to be installed.

#366 2nd ST.Bet. 9th & 10th Avenue brgy. 107, Caloocan City
TEL. No. 365-6793 & 365-3430
Website: www.chasia.com.ph
Email Add: info@chasia.com.ph
V. SELECTION OF SURGE ARRESTER MCOV IS BASED ON THE FOLLOWING
TABLE CONSIDERING MERALCO LINE IS GROUNDED NEUTRAL CIRCUIT

INAEL Surge Arrester’s available MCOV rating higher than 21.6MCOV is 24.4MCOV.
Thus selecting INZSP 30/10/2.

#366 2nd ST.Bet. 9th & 10th Avenue brgy. 107, Caloocan City
TEL. No. 365-6793 & 365-3430
Website: www.chasia.com.ph
Email Add: info@chasia.com.ph
VI. INSULATION COORDINATION

The generally recommended minimum protective margin, defined in IEEE Std. 141-
1993, 6.7.2 (Insulation Coordination), is 20% for impulse coordination (front-of-wave, full
wave) and 15% for switching coordination. The Shilin power transformer to be installed at
SM San Jose has a HV BIL rating of 170kV. The Inael surge arrester (INZSP 30/10/2) has a
residual voltage under 8/20µS – 10kA (kV) at 73.2kV and a residual voltage under switching
impulse at 59.7kV.

PRL2 = Basic Lightning Impulse Level / Lightning Protective Level = BIL / LPL
= 170kV / 73.2kV
= 2.3224

PML2 = Protective Margin


= (PR-1)100%
= (2.3224-1)100%
= 167.76%

PML2 has a margin of 67.76% which is greater than the recommended 20% margin. Thus,
the Inael Surge Arrester (INZP 30/10/2) will be sufficient to protect the Shilin Power
Transformer.

#366 2nd ST.Bet. 9th & 10th Avenue brgy. 107, Caloocan City
TEL. No. 365-6793 & 365-3430
Website: www.chasia.com.ph
Email Add: info@chasia.com.ph
VII. CONCLUSION:

VIII. REFERENCES:

a. OHIO Brass Arrester Application Table 4, 204-6 May 2012


b. Insulation Coordination, IEEE Std – 1993, 6.7.2 and 6.7.3.1

Prepared by: Noted by:

LEE RANDALL TIONGSON DANILO P. VILLADOS


Engineering Manager Operations Manager

Conforme by:

____________________________
Client Authorized Representative

#366 2nd ST.Bet. 9th & 10th Avenue brgy. 107, Caloocan City
TEL. No. 365-6793 & 365-3430
Website: www.chasia.com.ph
Email Add: info@chasia.com.ph