0% found this document useful (0 votes)
349 views9 pages

Panasonic FP

This document provides connection guidelines for connecting Panasonic FP series PLCs to HMI devices including: - Supported FP PLC models - Recommended HMI settings for communicating with FP PLCs via RS232 or RS485 - Device address formats for accessing FP PLC registers - Wiring diagrams for connecting various HMI port types to FP PLC ports - Information is concisely organized to assist users in properly setting up communication between Panasonic FP PLCs and HMI/SCADA devices.

Uploaded by

jamaza
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
349 views9 pages

Panasonic FP

This document provides connection guidelines for connecting Panasonic FP series PLCs to HMI devices including: - Supported FP PLC models - Recommended HMI settings for communicating with FP PLCs via RS232 or RS485 - Device address formats for accessing FP PLC registers - Wiring diagrams for connecting various HMI port types to FP PLC ports - Information is concisely organized to assist users in properly setting up communication between Panasonic FP PLCs and HMI/SCADA devices.

Uploaded by

jamaza
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 9

PLC Connection Guide

Panasonic FP
Supported Series: NAIS (Matsushita) FP series include FP-X, FP-Σ, FP0, FP1, FP2,
FP2SH, FP10SH and FP3 Ethernet support FP-X with AFPX-COM5.
Website:http://pewa.panasonic.com/

HMI Setting:
Parameters Recommended Options Notes
PLC type Panasonic FP
PLC I/F RS232 RS232/RS485
Baud rate 9600 9600, 19200, 38400,
Data bits 8 7 or 8
Parity Odd Even, Odd, None
Stop bits 1 1 or 2
Must match the PLC port setting.
PLC sta. no. 1 0-255
FP3 must set to 0.
*Support communications between HMI and PLC in pass-through mode
*Set LW-9903 to 2 to enhance the speed of download/upload PLC program in
pass-through mode

Device Address:
Bit/Word Device type Format Range Memo
B X DDDDh 0 ~ 9999f Input (X)
B Y DDDDh 0 ~ 9999f Output (Y)
B R DDDDh 0 ~ 9999f Internal Relay (R)
B L DDDD 0 ~ 9999 Link Relay (L)
B L_Bit DDDDh 0 ~ 9999f
B T DDDD 0 ~ 9999 Timer (T)
B C DDDD 0 ~ 9999 Counter (C)
W SV DDDD 0 ~ 9999 Timer/Counter Set Value (SV)
W EV DDDDD 0 ~ 65535 Timer/Counter Elapse Value (EV)
W DT DDDDD 0 ~ 99999 Data Register (DT)
W LD DDDD 0 ~ 8447 Link Register (LD)
W WX DDDD 0 ~ 9999 Input (WX) (read only)
W WY DDDD 0 ~ 9999 Output (WY)
W WR DDDD 0 ~ 9999 Internal Relay (WR)
PLC Connection Guide
Bit/Word Device type Format Range Memo
W WL DDDD 0 ~ 9999 Link Relay (WL)
W FL DDDDD 0 ~ 99999 File Register (FL)

Wiring Diagram:
The following is the view from the soldering point of a cable.
FP0, FP2, FP2SH, FPM CPU : 9P D-Sub to 5P Mini-DIN
eMT3000 series
COM1 RS232 9P COM3 RS232 9P RS232 5P Mini-DIN
D-Sub Female D-Sub Female Female socket
2 RX 8 RX 2 TXD
3 TX 7 TX 3 RXD
5 GND 5 GND 1 GND
cMT/mTV series
COM1 RS232 9P RS232 5P Mini-DIN
D-Sub Female Female socket
2 RX 2 TXD
3 TX 3 RXD
5 GND 1 GND
MT8000iE/MT8000XE series except MT8050iE
COM1 RS232 9P RS232 5P Mini-DIN
D-Sub Female Female socket
2 RX 2 TXD
3 TX 3 RXD
5 GND 1 GND
MT6000/8000 series except MT6050i/MT8050i
COM1 RS232 9P COM2 RS232 9P COM3 RS232 9P RS232 5P Mini-DIN
D-Sub Female D-Sub Female D-Sub Male Female socket
2 RX 6 RX 8 RX 2 TXD
3 TX 4 TX 7 TX 3 RXD
5 GND 5 GND 5 GND 1 GND
PLC Connection Guide
MT6050i/MT8050i/MT8050iE
COM1 RS232 9P RS232 5P Mini-DIN
D-Sub Female Female socket
9 RX 2 TXD
6 TX 3 RXD
5 GND 1 GND

The following is the view from the soldering point of a cable.


FP0 CPU : 9P D-Sub to 3P Terminal:
eMT3000 series
COM1 RS232 9P COM3 RS232 9P RS232 3P Terminal
D-Sub Female D-Sub Female
2 RX 8 RX S
3 TX 7 TX R
5 GND 5 GND G
cMT/mTV series
COM1 RS232 9P RS232 3P Terminal
D-Sub Female
2 RX S
3 TX R
5 GND G
MT8000iE/MT8000XE series except MT8050iE
COM1 RS232 9P RS232 3P Terminal
D-Sub Female
2 RX S
3 TX R
5 GND G
MT6000/8000 series except MT6050i/MT8050i
COM1 RS232 9P COM2 RS232 9P COM3 RS232 9P RS232 3P Terminal
D-Sub Female D-Sub Female D-Sub Male
2 RX 6 RX 8 RX S
3 TX 4 TX 7 TX R
5 GND 5 GND 5 GND G
PLC Connection Guide
MT6050i/MT8050i/MT8050iE
COM1 RS232 9P RS232 3P Terminal
D-Sub Female
9 RX S
6 TX R
5 GND G

The following is the view from the soldering point of a cable.


eMT3000 series
COM1 RS232 9P COM3 RS232 9P RS232 9P D-Sub Male
D-Sub Female D-Sub Female
2 RX 8 RX 2 TXD
3 TX 7 TX 3 RXD
5 GND 5 GND 7 GND
4 RTS
short
5 CTS
8 CD
short
9 ER
cMT/mTV series
COM1 RS232 9P RS232 9P D-Sub Male
D-Sub Female
2 RX 2 TXD
3 TX 3 RXD
5 GND 7 GND
4 RTS
short
5 CTS
8 CD
short
9 ER
PLC Connection Guide
MT8000iE/MT8000XE series except MT8050iE
COM1 RS232 9P RS232 9P D-Sub Male
D-Sub Female
2 RX 2 TXD
3 TX 3 RXD
5 GND 7 GND
4 RTS
short
5 CTS
8 CD
short
9 ER
MT6000/8000 series except MT6050i/MT8050i
COM1 RS232 9P COM2 RS232 9P COM3 RS232 9P RS232 9P D-Sub Male
D-Sub Female D-Sub Female D-Sub Male
2 RX 6 RX 8 RX 2 TXD
3 TX 4 TX 7 TX 3 RXD
5 GND 5 GND 5 GND 7 GND
4 RTS
short
5 CTS
8 CD
short
9 ER
MT6050i/MT8050i/MT8050iE
COM1 RS232 9P RS232 9P D-Sub Male
D-Sub Female
9 RX 2 TXD
6 TX 3 RXD
5 GND 7 GND
4 RTS
short
5 CTS
8 CD
short
9 ER
PLC Connection Guide
The following is the view from the soldering point of a cable.
FP1 CPU : 9P D-Sub to 8P MiniDIN
eMT3000 series
COM1 RS485 4W RS485 4W 8P Hirose
9P D-Sub Male Female socket
1 RX- 2 TXDA
2 RX+ 5 TXDB
3 TX- 3 RXDA
4 TX+ 6 RXDB
5 GND 1 GND
cMT/mTV series
COM2 RS485 4W RS485 4W 8P Hirose
9P D-Sub Female Female socket
7 RX- 2 TXDA
6 RX+ 5 TXDB
9 TX- 3 RXDA
8 TX+ 6 RXDB
5 GND 1 GND
MT8000iE/MT8000XE series except MT8050iE
COM1 RS485 4W COM2 RS485 4W RS485 4W 8P Hirose
9P D-Sub Male 9P D-Sub Male Female socket
1 RX- 1 RX- 2 TXDA
2 RX+ 2 RX+ 5 TXDB
3 TX- 3 TX- 3 RXDA
4 TX+ 4 TX+ 6 RXDB
5 GND 5 GND 1 GND
MT6000/8000 series except MT6050i/MT8050i
COM1 RS485 4W RS485 4W 8P Hirose
9P D-Sub Male Male
1 RX- 2 TXDA
2 RX+ 5 TXDB
3 TX- 3 RXDA
4 TX+ 6 RXDB
5 GND 1 GND
PLC Connection Guide
MT6050i/MT8050i/MT8050iE
COM1 RS485 4W RS485 4W 8P Hirose
9P D-Sub Female Male
1 RX- 2 TXDA
2 RX+ 5 TXDB
3 TX- 3 RXDA
4 TX+ 6 RXDB
5 GND 1 GND

The following is the view from the soldering point of a cable.


FP3 CPU : 9P D-Sub to 15P D-Sub
eMT3000 series
COM1 RS485 4W RS485 4W 15P D-Sub
9P D-Sub Male Male
1 RX- 9 TXDA
2 RX+ 2 TXDB
3 TX- 10 RXDA
4 TX+ 3 RXDB
5 GND 7 GND
4 RTS+
short
5 CTS+
11 RTS-
short
12 CTS-
cMT/mTV series
COM2 RS485 4W RS485 4W 15P D-Sub
9P D-Sub Female Male
7 RX- 9 TXDA
6 RX+ 2 TXDB
9 TX- 10 RXDA
8 TX+ 3 RXDB
5 GND 7 GND
4 RTS+
short
5 CTS+
11 RTS-
short
12 CTS-
PLC Connection Guide
MT8000iE/MT8000XE series except MT8050iE
COM1 RS485 4W COM2 RS485 4W RS485 4W 15P D-Sub
9P D-Sub Male 9P D-Sub Male Male
1 RX- 1 RX- 9 TXDA
2 RX+ 2 RX+ 2 TXDB
3 TX- 3 TX- 10 RXDA
4 TX+ 4 TX+ 3 RXDB
5 GND 5 GND 7 GND
4 RTS+
short
5 CTS+
11 RTS-
short
12 CTS-
MT6000/8000 series except MT6050i/MT8050i
COM1 RS485 4W RS485 4W 15P D-Sub
9P D-Sub Male Male
1 RX- 9 TXDA
2 RX+ 2 TXDB
3 TX- 10 RXDA
4 TX+ 3 RXDB
5 GND 7 GND
4 RTS+
short
5 CTS+
11 RTS-
short
12 CTS-
PLC Connection Guide
MT6050i/MT8050i/MT8050iE
COM1 RS485 4W RS485 4W 15P D-Sub
9P D-Sub Female Male
1 RX- 9 TXDA
2 RX+ 2 TXDB
3 TX- 10 RXDA
4 TX+ 3 RXDB
5 GND 7 GND
4 RTS+
short
5 CTS+
11 RTS-
short
12 CTS-

Driver Version:
Version Date Description
V1.80 Apr/09/2010 Added registers: FL

You might also like