Instruction Manual: Blast and Fluid Bed Freezer
Instruction Manual: Blast and Fluid Bed Freezer
FT36
            FT36
           AL8721
ISSU E 1
                           OCTOBER 1996
                         ARMFIELD LIMITED
PAGE NO.
SAFETY 1
RECEIPT OF EQUIPMENT 5
FLOW DIAGRAM 6
WIRING DIAGRAM 8
WIRING DIAGRAM 9
FUSES 10
CONNECTION TO SERVICES 11
OPERATING INSTRUCTIONS 12
ROUTINE MAINTENANCE 17
GENERAL SAFETY                                         a
SAFETY IN THE USE OF EQUIPMENT SUPPLIED BY ARMFIELD
Although designed for safe operation, any laboratory equipment may involve
processes or procedures which are potentially hazardous. The major potential
hazards associated with this particular equipment are listed below.
. DAMGE TO CLOTHING
Accidents can be avoided provided that equipment is regularly maintained and staf
and students are made aware of potential hazards. A list of general safety rules is
included in this manual, to assist staff and students in this regard. The list is not
intended to be fully comprehensive but for guidance only.
Please refer to the notes overleaf regarding the Control of Substances Hazardous to
Health Regulations.
                                       - i -
The COSHH Regulations
Since the equipment supplied by Armfield Limited may involve the use of
substances which can be hazardous (for example, cleaning fluids used for
maintenance or chemicals used for particular demonstrations) it is essential that
the laboratory supervisor or some other person in authority is responsible for
implementing the COSHH regulations.
Part of the above regulations are to ensure that the relevant Health and Safety Data
Sheets are available for all hazardous substances used in the laboratory. Any person
using a hazardous substance must be informed of the following:
Physical data about the substance
Any hazard from fire or explosion
Any hazard to health
Appropriate First Aid treatment
Any hazard from reaction with other substances
How to clean/dispose of spilage
Appropriate protective measures
Appropriate storage and handling
Although these regulations may not be applicable in your country, it is strongly
recommended that a similar approach is adopted for the protection of the students
operating the equipment. Local regulations must also be considered.
                                       -2-
USE OF EARTH LEAKAGE CIRCUIT BREAKER AS AN ELECTRICAL
SAFETY DEVICE
The equipment described in this Instruction Manual operates from a mains voltage
electrical supply. The equipment is designed and manufactured in accordance with
appropriate regulations relating to the use of electricity. Similarly, it is assumed that
regulations applying to the operation of electrical equipment are observed by the end
user.
Note: If any doubt exists whether the electrical supply incorporates a device then the
      ELCB supplied should be fitted.
At least once each month, check that the ELCB is operating correctly by pressing the
TEST button. The circuit breaker MUST trip when the button is pressed. Failure to
trip means that the operator is not protected and the equipment must be checked and
repaired by a competent electrician before it is used.
                                         -3-
~ a
             0:
             Li
             N
            W
            UJ
            0:
            lL
            o
            UJ
            ai
            o
            =:
            ..
            lL
            c:
            z
            ~
            t-
            V'
            ~
            -i
            CD
            1O
            (Y
            l-
            lL
.-
      -4-
RECEIPT OF EQUIPMENT
The apparatus should be carefully unpacked and the components checked against the
Advice Note. A copy of the Advice Note is supplied with this instruction manual
for reference.
2. SALES OVERSEAS
The apparatus should be carefully unpacked and the components checked against the
Advice Note. A copy of the Advice Note is supplied with this instruction manual
for reference.
                                      -5-
                                                            Expansion Valve                                   31
       3     34       35
                                                                                                                                   liquid line
0\
                                                                               Pressure
                                                   low                         Cut Out
                                                 Pressure                            24         Discharge
                                                  Cut Out
                                                                                 -                line
                                                 37
                      36                                                                                                             28
                                                                                          : i I                                                  SIght   130
                                                                                                                                 Filer I
             Suction accumulator                                                                                                 drier     I     glass
                                                                                          1
                                                                                          1
                                                                                                             t               t
                                                                                          126
                                                                                                                    27
                                                                                          LJ             I                       L             liquid
                                                                         Oil          all                    liquid receiver I             Solenoid
                                                                      Return       Separator                 Water cooled Condenser
211=
       D          GJ                Q
       04    05 06      07     08   09
020
CONTROL PANEL
                  -7-
                                         21.0 VOLT 50HZ CONTROL
                                                       CIRCUIT             -
                                                                           r-   n
                                                                                ."
 SUPPLY ON
 THERMOSTAT
                   ~e
 SAFETY RELAY
                                I?  ? w~O~ ~n.. ~m
                                ~--
                                  IIQ
                                    I\!ZI!!
                                          \:0r-~
                           c.
                           Q
                                 ~T--~---o--~--
                                             g~n~
CABINET OVERHEAT
                   :: ø
                                           m
                                           X
                                        I -c
                                       --'::
                                      ,. m
                                               ~
                                              "l
                                              Ul~
                                                0
                                                                      ~
                                                                      -4
SAFETY CIRCUIT
TRIPPED                    c.
                        ~-
COMPRESSOR         n
                   -      c.
                          c.     or-
                                            ~-o-o-o~~~
                                                   Ul ..
                                          ~fir-0~yI :cnq
                                                     ~ I ~~~8
COMPRESSOR RELAY   ::
                   ..
                                  ..
                                             II~-
                                               o~"lI Ix I ~
                                              I ~~ I: i ~ II
                                                  I:: I ~
                                                       "l Cl
                                                           ¡
                                                            ~
HOURS RUN          X
                   :: e                   IIr-Ul
                                             ~~ II ~~ II m~ n¡
                                           I
                                           I   ::~I zI I:i
                                              C:~         I ;0
COMP RUN
                                           1m.,   I ~ i c: r-
iow OIL PRESSURE        o                __.J if::~ l:u
                                           I ~ - I c: i ~
                   :: ê           lo                 I m
                                            00 I~c: I(§~
HIGH PRESSURE                            ________J ~ i ~          I
                   :u C9          ô                               I
PUMP DOWN
                   ~G             --
COMP TRlP
TRIP RELAY
                                  -or-
OIL SWITCH
HEATER
                   -~mn--l~
OIL RETURN
SOLENOID           1Ƨ----- :
                                            -8-
                                 CONTINUED FROM PREVIOUS PAGE
LIGUID SOLENOID
                                   -,.                                              w
                                                                                    fa
THERMOSTAT
                                                       ,.-
                                                                               e     C§
                                                                                                 :z
                                                                                                 m
                                                                                                 "T
                                                                                                 :z
SATISFIED
                      ~e                                                                         ~
                                                                                                 m
                                                                                                 :z
                                                                                                 ~
EVAPORATOR FAN        ("                                                                         -4
                      N    ,.N           0r-                                                     Õ%
                                         N                                                       0"T
EVA"ORA TOR FAN RUN
                                                                                                 "T
                                                                                                 i
                                                                                                 0%
EVAPORATOR FAN TRIP
                      :z                 0r-
TAl.. RELAY                ê
DEFROST TIMER
  0-60 MINS                ,.~
                                                                          -
                                                                          -4
                                                                                    -.
                                                                                   ~C:i
                                                                                     m.
                                                                                                         ,.
                                                                                                         IØ
                                                                                                                ::
                                                                                         ~ r-
DEFROST                                                      i~
                      11 G                            ~ g~
                                                    ___~ Zu
DEFROST TERMINATION
                                               ;; 'v ~ v- u;                             ::
                                                                                         on
RELAY
DEFROST HEATER
                      ur -
                                   ,.
                                   IØ
DOOR HEATERS
                      i. -
                      J6---------o                                                                     ~ ci"T        r-
                       :i -- oN_~_Il,.
                                     ~~IØ
                                    "T.. ~r--
                                               fa                                                                    N
                      l~.     -----~
CABINET LIGHTS
                        ~________________~                        -~
                                                                  -4 :i
                                                                  n -4
                                                                  :i
                                         -9-
  FUSE            ITEM             KW   FLC FUSE
NUMBER                                        SIZE
CF1        CONTROL                              6
F1 F2 F3   COMPRESSOR MOTOR        f.   8-4   20M 25
F4 F5 F6   EVAPORATOR    FAN       0.75 27      6
F7 Fa F9   DEFR OST   HEATERS      4.5 6.25    10
F10        CRANKCASE HEATER        0.2 -       4
F 11       DOOR  HEATERS           0.2 -       6
F12        CABINET LI GHTS         0-2 -       6
                          - 10 -
CONNECTION TO SERVICES
Cooling Water
It is EXTREMELY IMPORTANT that the compressor must NEVER be run without a
continuous supply of cooling water. The cooling water inlet and outlet connections
are located at the extreme left-hand side of the unit at the rear.
The water supply must have a line pressure of not less than 3.0 bar and a flow
capacity of more than 25litres/min at 20°C.
Electricity
Ensure that the live wires are correctly wired by briefly switching on the compressor.
The compressor motor can run in either direction but the fan inside the cabinet must
run in the direction indicated on the fan blades (embossed arrow). If the fan rotates
in the opposite direction, turn off the unit and swap over any two live connections.
                                         - 11 -
 ACCESSORIES
 TEMPERA TURE SENSORS
 The sensors are located into the blast freezer compartment by inserting them
 through the plastic conduit via the gland outside the freezer cabinet, to the right of
 the front door.
 The Data Logger is supplied with a comprehensive instruction leaflet which should
 be used for set up of the temperature sensors to the logger hardware and to a suitable
 computer.
 The thermocouple sensors are then positioned within the freezer compartment at
 the desired locations. These locations wil depend on the experiment being
performed but can be, for example:
             *           Air temperature (sensor tip in airstream)
             *
                         Tray temperature (sensor tip in contact with one or more of the
                         stainless steel trays using adhesive tape)
             *
                         Food package temperature (sensor tip taped to outside/inside of food
                         package)
             *
                         inside food sample being frozen (sensor tip positioned inside sample
                         after making an access passage - centre of good sample wil be last to
                         freeze)
ANEMOMETER
The telescopic anemometer is installed by insertion into the air stream in the blast
freezer duct through the plastic conduit located outside the freezer to the right of the
front door. It is used for measuring the air speed in the freezer duct.
The anemometer has an analogue readout display and can also be connected to the
data logger so that the output can be stored and recorded continuously. The air speed
is adjusted using the manual baffle adjusting handwheel on the freezer cabinet.
Before using the freezer it is advisable to take readings of the air speed relating to
various settings of the baffles using either the meter readout or data logger. This
calibration wil be useful for later reference.
                                                     - 12-
 OPERATING INSTRUCTIONS
It is assumed that the Blast and Fluid Bed Freezer has been installed and connected to
the appropriate services as detailed in previous sections.
QUICK DEFROST
              Push the defrost button (19). Defrost light wil come on, evaporator
              fan switches off and the compressor wil pump down, defrost heaters
              wil come on. After pre-set, time heaters and the defrost light wil go
              off automatically and refrigeration wil start automatically.
              If refrigeration switch turned off and push button is pressed, the
              cabinet wil defrost and then stop until the switch is put into position
              again.
                                         - 13 -
7.   The fluid bed freezer section is accessed by the smaller door on the
     right-hand end of the cabinet. Items such as peas or diced vegetables
     can be fluidised here to differing degrees depending on the cold air
     flow velocity.
8.   The air flow rate from the fan can be adjusted using the external
     adjust handwheel which moves a 'damper' plate inside the duct. The
     maximum air velocity obtainable is 10 m.s.-I. When fluidising
     material it is better to start with the minimum velocity and slowly
     open the 'damper' until a satisfactory fluidised bed is achieved.
                             - 14 -
 DESCRIPTION OF INSTRUMENTS ON CONTROL CONSOLE
1. Compressor Ammeter
9.            Defrost Indicates once the Push Button (19) is depressed and also
              means the defrost heaters in the cabinet are on. This indicator can
              also be on with the Low Pressure /Pump Down Indicator. The defrost
              wil terminate either by time or temperature in the cabinet.
10.           Compressor Trip Indicates if an electrical fault has developed on the
              compressor drive motor or supply to the control panel is defective.
11.           Evaporator Fan Trip Indicates the evaporator fan has cut out on the
              thermal   overload. Possible cause would be running for too long with
              the air flow damper closed.
12.           Low Oil Pressure Indicates if the differential oil pressure in the
              compressor drops below a pre-determined setting. Possible cause,
              compressor control switch switched off or main supply to control
              panel off for long periods, not allowing the oil to be kept warm. This
              is reset on the oil control switch on the compressor.
13.           High Pressure Indicates when the discharge pressure is too high.
              Possible cause water not switched on to the condenser. To reset,
              depress the red button on the control marked 'High Pressure', below
              the compressor.
                                       - 15 -
 14.   Cabinet Overheat Indicates if the cabinet temperature rises above a
       pre-set leveL. The cabinet must be allowed to cool down naturally and
       can be reset by depressing the button (18). Possible caused, defrosting
       cabinet more than required.
 15.   Safety Cut Out Indicates if the emergency stop push button (21) has
       been activated, also the light wil indicate if the cabinet has been out
       on cabinet overheat. These faults can only be reset by reset button
       (18).
 16.   Compressor Control This switch should only be used to turn off the
       compressor for servicing and should always be left in the ON
       position.
17.    Refrigeration Off/On This switch activates the liquid solenoid valve
       and the evaporator fan. Starting the refrigeration cycle.
       After finishing with the freezer, turn this switch to OFF.
       This is the only switch required to operate the freezer.
18.    Control Reset Push Button Each time the mains switch (20) is
       switched off this button must be pressed to reset the control paneL.
22.    Compressor
23.    High Pressure Gauge
24.    High Pressure cut-out
25.    Oil Return Solenoid
26.    Oil Separator
                                 - 16 -
33.   Evaporator
                               - 17 -
ROUTINE MAINTENANCE
To preserve the life and efficient operation of the equipment it is important that the
equipment is properly maintained. Regular servicing/maintenance of the
equipment is the responsibilty of the end user and must be performed by qualified
personnel who understand the operation of the equipment.
                                       - 18 -
GENERAL SAFETY RULES
1 Follow Relevant Instructions
2 Installation
a Use lifting tackle where possible to install heavy equipment. Where manual
      lifting is necessary beware of strained backs and crushed toes. Get help from an
      assistant if necessary. Wear safety shoes where appropriate.
b Extreme care should be exercised to avoid damage to the equipment during
      handling and unpacking. When using slings to lift equipment, ensure that the
      slings are attached to structural framework and do not foul adjacent pipework,
      glassware etc. When using fork lift trucks, position the forks beneath
     structural framework ensuring that the forks do not foul adjacent pipework,
     glassware etc. Damage may go unseen during commissioning creating a
     potential hazard to subsequent operators.
c Where special foundations are required follow the instructions provided and
      do not improvise. Locate heavy equipment at low leveL.
d Equipment involving inflammable or corrosive liquids should be sited in a
     containment area or bund with a capacity 50% greater than the maximum
     equipment contents.
e Ensure that all services are compatible with the equipment and that
      independent isolators are always provided and labelled. Use reliable
      connections in all instances, do not improvise.
f Ensure that all equipment is reliably earthed and connected to an electrical
      supply at the correct voltage. The electrical supply must incorporate a Residual
      Current Device (RCD) (alternatively called an Earth Leakage Circuit Breaker -
      ELCB) to protect the operator from severe electric shock in the event of misuse
      or accident.
g Potential hazards should always be the first consideration when deciding on a
      suitable location for equipment. Leave sufficient space between equipment
      and between walls and equipment.
                                          a
3 Commissioning
4 Operation
a Ensure that students are fully aware of the potential hazards when operating
      equipment.
b Students should be supervised by a competent member of staff at all times
      when in the laboratory. No one should operate equipment alone. Do not leave
      equipment running unattended.
c Do not allow students to derive their own experimental procedures unless
      they are competent to do so.
d Serious injury can result from touching apparently stationary equipment
      when using a stroboscope to 'freeze/ rotary motion.
5 Maintenance
a Badly maintained equipment is a potential hazard. Ensure that a competent
      member of staff is responsible for organising maintenance and repairs on a
      planned basis.
b Do not permit faulty equipment to be operated. Ensure that repairs are carried
      out competently and checked before students are permitted to operate the
      equipment.
6 Using Electricity
a At least once each month, check that ELCB's (RCCB's) are operating correctly
      by pressing the TEST button. The circuit breaker must trip when the button is
      pressed (failure to trip means that the operator is not protected and a repair
      must be effected by a competent electrician before the equipment or electrical
      supply is used).
b Electricity is the commonest cause of accidents in the laboratory. Ensure that
      all members of staff and students respect it.
c Ensure that the electrical supply has been disconnected from the equipment
      before attempting repairs or adjustments.
d Water and electricity are not compatible and can cause serious injury if they
      come into contact. Never operate portable electric appliances adjacent to
      equipment involving water unless some form of constraint or barrier is
     incorporated to prevent accidental contact.
e Always disconnect equipment from the electrical supply when not in use.
                                           b
 7 A voiding fires or explosion
a Take care when handling sharp edged components. Do not exert undue force
            on glass or fragile items.
b Hot surfaces camiot in most cases be totally shielded and can pl'duce severe
           burns even when not 'visibly hot~. Use common sense and think which parts
           of the equipment are likely to be hot.
                                                            c
 10 Eye protection
a Goggles must be worn whenever there is a risk to the eyes. Risk may arise
                                       pours or splinters. Beware of debris from fast
       from powders, liquid splashes, va
     moving air streams. Alkaline solutions are particularly dangerous to the eyes.
b Never look directly at a strong source of light such as a laser or Xenon arc
     lamp. Ensure that equipment using such a source is positioned so that passers-
     by cannot accidentally view the source or reflected ray.
c Facilities for eye irrigation should always be available.
11 Ear protection
a Ear protectors must be worn when operating noisy equipment.
12 Clothing
a Suitable clothing should be worn in the laboratory. Loose garments can cause
       serious injury if caught in rotating machinery. Ties, rings on fingers etc.
      should be removed in these situations.
b Additional protective clothing should be available for all members of staff and
      students as appropriate.
a Guards and safety devices are installed on equipment to protect the operator.
     The equipment must not be operated with such devices removed.
b Safety valves, cut-outs or other safety devices wil have been set to protect the
      equipment. Interference with these devices may create a potential hazard.
c It is not possible to guard the operator against all contingencies. Use common
      sense at all times when in the laboratory.
d Before starting a rotating machine, make sure staff are aware how to stop it in
      an emergency.
e Ensure that speed control devices are always set at zero before starting
     equipment.
14 First aid
a If an accident does occur in the laboratory it is essential that first aid
      equipment is available and that the supervisor knows how to use it.
b A notice giving details of a proficient first-aider should be prominently
      displayed.
c A 'short list/ of the antidotes for the chemicals used in a particular
      laboratory should be prominently displayed.