Manual ABB
Manual ABB
Document Status: 4
1 Work may proceed 4 Review not required. Work may
proceed
Hardware Manual
Equipment No:
NA
Submittal Number: 001
delivery)
3AFE64382101 (English)
3AFE64567373 (English)
3AFE68367883 (English)
3AFE68599954 (English)
3AFE68372984 (English)
3AFE64702165 (English)
3AFE64731165 (English)
3AFE64681338 (English)
3AFE68557925 (English)
Safety instructions
Maintenance
Technical data
Dimensional drawings
Resistor braking
3AFE64527592 (English)
3AFE63700177 (English)
3AFE64616340 (English)
3AFE68478952 (English)
3AFE64527274 (English)
5.5 to 110 kW
ACS800-U31 Drives
7.5 to 125 HP
Hardware Manual
3AFE68599954 Rev A EN
EFFECTIVE: 14.10.2005
Update Notice
Hardware Manuals:
the manual
3AFE68599954 A English EN
The headings in this update notice refer to the modified
3AFE68626552 A German DE
subsections in the original English manual. Each heading also
3AFE68626561 A French FR DELETED. The page number refers to the page number in the
the modification.
inside the module, retest the functioning of the safety circuit according to the
start-up instructions.
• Do not change the electrical installations of the drive except for the essential
control and power connections. Changes may affect the safety performance or
customer's responsibility.
[...]
Note:
• The Safe torque off function (option +Q967) does not remove the voltage from the
• The Safe torque off function (option +Q967) can be used for stopping the drive in
emergency stop situations. In the normal operating mode, use the Stop command
instead.
• Installation of ASTO board (Safe torque off, +Q967) describes the electrical
See Electrical installation, Motor control and I/O board (RMIO), Installation of AGPS
torque off, +Q967) and the optional module manual delivered with the module.
Update Notice
The table below contains the new option code definition for the Safe torque off
function.
Code Description
Note: If you add or modify the wiring in the drive safety circuits, ensure that the
appropriate standards (e.g. IEC 61800-5-1, EN 62061, EN/ISO 13849-1 and -2) and
the ABB guidelines are met. After making the changes, verify the operation of the
The drive supports the Safe torque off (STO) function according to standards
The STO may be used where power removal is required to prevent an unexpected
start. The function disables the control voltage of the power semiconductors of the
drive output stage, thus preventing the inverter from generating the voltage required
to rotate the motor (see the diagram below). By using this function, short-time
machinery can be performed without switching off the power supply to the drive.
Update Notice
Update Notice
WARNING! The Safe torque off function does not disconnect the voltage of the main
and auxiliary circuits from the drive. Therefore maintenance work on electrical parts
of the drive or the motor can only be carried out after isolating the drive system from
Note: The Safe torque off function can be used for stopping the drive in emergency
stop situations. In the normal operating mode, use the Stop command instead. If a
running drive is stopped by using the function, the drive will trip and stop by coasting.
If this is not acceptable, e.g. causes danger, the drive and machinery must be
stopped using the appropriate stopping mode before using this function.
power semiconductor failure: In spite of the activation of the Safe torque off
function, the drive system can produce an alignment torque which maximally rotates
the motor shaft by 180/p degrees. p denotes the pole pair number.
Note: If you add or modify the wiring in the drive safety circuits, ensure that the
appropriate standards (e.g. IEC 61800-5-1, EN 62061, EN/ISO 13849-1 and -2) and
the ABB guidelines are met. After making the changes, verify the operation of the
NEW (page 75): Installation of ASTO board (Safe torque off, +Q967)
• electrical installation of the optional Safe torque off function (+Q967) of the drive.
The optional Safe torque off function includes an ASTO board, which is connected to
the drive and an external power supply. See also chapter Planning the electrical
WARNING! Dangerous voltages can be present at the ASTO board even when the
24 V supply is switched off. Follow the Safety instructions on the first pages of this
manual and the instruction in this chapter when working on the ASTO board.
Make sure that the drive is disconnected from the mains (input power) and the
24 V source for the ASTO board is switched off during installation and
maintenance. If the drive is already connected to the mains, wait for 5 min after
Update Notice
See
• page 6 (in this Update Notice) for the dimensions of the ASTO-11C board
• section ASTO-11C in chapter Technical data for the technical data of the ASTO-
11C board.
Note: Maximum cable length between ASTO terminal block X2 and the drive
• Remove the cover of the enclosed ASTO unit by undoing the fixing screws (1).
• Ground the ASTO unit via the bottom plate of the enclosure or via terminal X1:2
• Connect the cable delivered with the kit between terminal block X2 of the ASTO
• Connect a cable between connector X1 of the ASTO board (3) and the 24 V
source.
X2
X1
24 V
3
Update Notice
Circuit diagram
The diagram below shows the connection between the ASTO board and the drive
when it is ready. For an example diagram of a complete Safe torque off circuit, see
3AUA0000069101
Dimensions
The dimensions of the ASTO board are the same as the dimensions of the AGPS
Dimensions (with
167 x 128 x 52 mm (Height x Weight x Depth)
enclosure)
Update Notice
Modules with option +Q967: the installation site altitude in operation is 0 to 2000 m.
Operation
: 0 to 2000 m
Update Notice
Update Notice
Safety instructions
This chapter contains the safety instructions which you must follow when installing,
operating and servicing the drive. If ignored, physical injury or death may follow, or
damage may occur to the drive, motor or driven equipment. Read the safety
There are two types of safety instructions throughout this manual: warnings and
notes. Warnings caution you about conditions which can result in serious injury or
death and/or damage to the equipment. They also tell you how to avoid the danger.
equipment.
Safety instructions
These warnings are intended for all who work on the drive, motor cable or motor.
WARNING! Ignoring the following instructions can cause physical injury or death, or
Only qualified electricians are allowed to install and maintain the drive.
Never work on the drive, motor cable or motor when main power is applied.
After disconnecting the input power, always wait for 5 min to let the intermediate
circuit capacitors discharge before you start working on the drive, motor or
motor cable.
that:
1. voltage between drive input phases U1, V1 and W1 and the frame is close to
0 V.
2. voltage between terminals UDC+ and UDC- and the frame is close to 0 V.
Do not work on the control cables when power is applied to the drive or to the
dangerous voltages inside the drive even when the main power on the drive is
switched off.
Do not make any insulation or voltage withstand tests on the drive or drive
modules.
When reconnecting the motor cable, always check that the phase order is
correct.
Note:
The motor cable terminals on the drive are at a dangerously high voltage when
the input power is on, regardless of whether the motor is running or not.
The brake control terminals (UDC+, UDC-, R+ and R- terminals) carry a
Depending on the external wiring, dangerous voltages (115 V, 220 V or 230 V)
ACS800-02 with enclosure extension: The main switch on the cabinet door
does not remove the voltage from the input busbars of the drive. Before working
ACS800-04M, ACS800-07: The Prevention of Unexpected Start function does
not remove the voltage from the main and auxiliary circuits.
At installation sites above 2000 m (6562 ft), the terminals of the RMIO board
and optional modules attached to the board do not fulfil the Protective Extra
Safety instructions
Grounding
These instructions are intended for all who are responsible for the grounding of the
drive.
WARNING! Ignoring the following instructions can cause physical injury, death,
Ground the drive, motor and adjoining equipment to ensure personnel safety in
Make sure that grounding conductors are adequately sized as required by
safety regulations.
In a multiple-drive installation, connect each drive separately to protective
earth (PE).
ACS800-01, ACS800-11, ACS800-31: In European CE compliant installations
ACS800-04 (45 to 560 kW) and ACS800-02 in first environment: make a 360°
Do not install a drive with EMC filter option +E202 or +E200 (available for
Note:
Power cable shields are suitable for equipment grounding conductors only
As the normal leakage current of the drive is higher than 3.5 mA AC or 10 mA
required.
Safety instructions
These instructions are intended for all who install and service the drive.
WARNING! Ignoring the following instructions can cause physical injury or death,
Handle the unit carefully.
ACS800-01, ACS800-11, ACS800-31: The drive is heavy. Do not lift it alone.
Do not lift the unit by the front cover. Place the unit only on its back.
ACS800-02, ACS800-04: The drive is heavy. Lift the drive by the lifting lugs
only. Do not tilt the unit. The unit will overturn from a tilt of about 6 degrees.
Do not tilt!
Beware of hot surfaces. Some parts, such as heatsinks of power
supply.
Make sure that dust from drilling does not enter the drive when installing.
malfunctioning.
Ensure sufficient cooling.
Do not fasten the drive by riveting or welding.
Safety instructions
WARNING! Ignoring the following instructions can cause damage to the printed
circuit boards:
The printed circuit boards contain components sensitive to electrostatic
discharge. Wear a grounding wrist band when handling the boards. Do not
Handle the fibre optic cables with care. When unplugging optic cables, always
grab the connector, not the cable itself. Do not touch the ends of the fibres with
bare hands as the fibre is extremely sensitive to dirt. The minimum allowed
Safety instructions
10
Operation
These warnings are intended for all who plan the operation of the drive or operate
the drive.
WARNING! Ignoring the following instructions can cause physical injury or death,
Before adjusting the drive and putting it into service, make sure that the motor
and all driven equipment are suitable for operation throughout the speed range
provided by the drive. The drive can be adjusted to operate the motor at
speeds above and below the speed provided by connecting the motor directly
Do not activate automatic fault reset functions of the Standard Application
Do not control the motor with the disconnecting device (disconnecting means);
instead, use the control panel keys and , or commands via the I/O
board of the drive. The maximum allowed number of charging cycles of the DC
ACS800-04M, ACS800-07: Do not use the optional Prevention of Unexpected
Start function for stopping the drive when the drive is running. Give a Stop
command instead.
Note:
If an external source for start command is selected and it is ON, the drive (with
Standard Application Program) will start immediately after fault reset unless the
When the control location is not set to Local (L not shown in the status row of
the display), the stop key on the control panel will not stop the drive. To stop
the drive using the control panel, press the LOC/REM key and then the stop
key .
Safety instructions
11
These are additional warnings concerning permanent magnet motor drives. Ignoring
the instructions can cause physical injury or death, or damage to the equipment.
WARNING! Do not work on the drive when the permanent magnet motor is rotating.
Also, when the supply power is switched off and the inverter is stopped, a rotating
permanent magnet motor feeds power to the intermediate circuit of the drive and the
Alternative 1) Disconnect the motor from the drive with a safety switch or by other
means. Measure that there is no voltage present on the drive input or output
Alternative 2) Measure that there is no voltage present on the drive input or output
terminals (U1, V1, W1, U2, V2, W2, UDC+, UDC-). Ground the drive output
WARNING! Do not run the motor over the rated speed. Motor overspeed leads to
overvoltage which may damage or explode the capacitors in the intermediate circuit
of the drive.
Controlling a permanent magnet motor is only allowed using the ACS800 Permanent
Safety instructions
12
Safety instructions
13
Table of contents
Safety instructions
Grounding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Table of contents
Intended audience . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Contents . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Inquiries . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
The ACS800-31/U31
The ACS800-31/U31 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Terms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Operation principle . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Line-side converter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Motor-side converter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Table of contents
14
Type code . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Mechanical installation
Delivery check . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Before installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Wall . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Floor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Cabinet installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Requirements table . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
Supply connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
EU . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
US . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
Fuses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
Short-circuit protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
General rules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
Additional US requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
Conduit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
Table of contents
15
Bypass connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
Protecting the relay output contacts and attenuating disturbances in case of inductive loads . . . . 55
Relay cable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
Electrical installation
Drive . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
Input cable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
IT (ungrounded) systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
Warning sticker . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
Terminals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
When the outer surface of the shield is covered with non-conductive material . . . . . . . . . . . 68
Circuit diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73
Dimensional drawing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74
Table of contents
16
Note for the ACS800-02 with enclosure extension and the ACS800-07 . . . . . . . . . . . . . . . . . . . . 75
Parameter settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76
Analogue inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79
Analogue outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79
Digital inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79
Relay outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80
Installation checklist
Installation checklist . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83
Control panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 86
Line-side converter actual signals and parameters in the motor-side converter application
program . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89
Actual signals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89
09 ACTUAL SIGNALS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89
Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90
95 HARDWARE SPECIF . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90
Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91
31 AUTOMATIC RESET . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 92
Table of contents
17
Maintenance
Safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 95
Maintenance intervals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 95
Heatsink . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 96
Additional fan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 97
Replacement (R5) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 97
Replacement (R6) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 98
Capacitors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 98
Reforming . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 98
LEDs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 98
Fault tracing
Conflicting ID numbers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 99
Technical data
Ratings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 102
Symbols . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 103
Sizing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 103
Derating . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 103
Ratings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 106
Symbols . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 106
Efficiency . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 110
Cooling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 110
AGPS-11C . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 110
Table of contents
18
Materials . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 112
CE marking . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 113
Definitions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 113
Definitions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 115
UL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 117
Dimensional drawings
Resistor braking
Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 125
External +24 V power supply for the RMIO boards via terminal X34
Table of contents
19
This chapter describes the intended audience and contents of this manual. It
the drive. The flowchart refers to chapters/sections in this manual and other
manuals.
Intended audience
This manual is intended for people who plan the installation, install, commission, use
and service the drive. Read the manual before working on the drive. The reader is
This manual is written for readers worldwide. Both SI and imperial units are shown.
Special US instructions for installations within the United States that must be
installed per the National Electrical Code and local codes are marked with (US).
Chapters Safety instructions, Planning the electrical installation and Motor control
and I/O board (RMIO) apply to several ACS800 products which are listed at the
Some instructions, technical data and dimensional drawings which concern only
certain frame sizes are marked with the symbol of the frame size R2, R3, ... or R8.
The frame size is not marked on the drive designation label. To identify the frame
size of your drive, see the rating tables in chapter Technical data.
The instructions, technical data and dimensional drawings which concern only
certain optional selections are marked with plus codes, e.g. +E202. The options
included in the drive can be identified from the plus codes visible on the type
designation label of the drive. The plus code selections are listed in chapter The
20
Contents
About this manual lists the steps in checking the delivery and installing and
commissioning the drive and refers to chapters/sections in this manual and other
Planning the electrical installation instructs in the motor and cable selection,
(+Q950).
Motor control and I/O board (RMIO) shows the external control connections to the
I/O board.
Installation checklist contains a list for checking the mechanical and electrical
Start-up and use describes the start-up procedure and use of the drive.
Technical data contains the technical specifications of the drive, e.g. the ratings,
sizes and technical requirements, provisions for fulfilling the requirements for CE
Resistor braking describes how to select, protect and wire external brake choppers
and resistors for the drive. The chapter also contains installation instructions and the
technical data.
External +24 V power supply for the RMIO boards via terminal X34 describes how to
connect an external +24 V power supply for the RMIO board using terminal X34.
21
Task See
Identify the frame size of your drive: R5 or R6. Technical data /IEC data or NEMA data
data.
included)
instructions.
systems.
Technical data
cables
22
Task See
cable.
the installation
Connect the control and auxiliary control cables. Electrical installation, Motor control and I/O
module.
Inquiries
Address any inquiries about the product to the local ABB representative, quoting the
type code and serial number of the unit. If the local ABB representative cannot be
23
The ACS800-31/U31
This chapter describes the operating principle and construction of the drive in short.
motors.
Cooling fan
Top cover
Control panel
CDP312R
Heat sink
Front cover
Clear plastic
shroud
Frame size R6
The ACS800-31/U31
24
UDC+
UDC-
I/O
X41
terminals
U1
V1
W1
U2
V2
W2
UDC+
UDC-
U1 V1
W1 X41 U2 V2 W2
Power
cable
PE
terminals
PE
covers
RMIO board
RMIO board
The ACS800-31/U31
25
Terms
Motor-side converter: A converter that is connected to the motor and controls the
motor operation.
Operation principle
The line-side and motor-side converters consist of six insulated gate bipolar
The converters have their own control programs. The parameters of both programs
can be viewed and changed using one control panel. The control panel can be
Line-side converter
The IGBT supply module rectifies three phase AC current to direct current for the
intermediate DC link of the drive. The intermediate DC link is further supplying the
motor-side converter that runs the motor. The line filter suppresses the AC voltage
By default, the converter controls the DC link voltage to the peak value of the line-to-
line voltage. The DC voltage reference can be set also higher by a parameter. The
control of the IGBT power semiconductors is based on the Direct Torque Control
(DTC) method also used in the motor control of the drive. Two line currents and the
Motor-side converter
The motor control is based on the Direct Torque Control (DTC) method. Two phase
currents and DC link voltage are measured and used for the control. The third phase
The ACS800-31/U31
26
The AC line current of the drive is sinusoidal with power factor equal to 1. The IGBT
supply unit does not generate characteristic current or voltage overtones like a
The Total Harmonic Distortion (THD) in current is given in chapter Technical data /
Input power connection. The THD in voltage depends slightly on the Short Circuit
Ratio in the Point of Common Coupling (PCC). The high frequency switching and
high du/dt slightly distort the voltage waveform at the input of the converter.
Typical line current (i) and voltage (u) waveforms are shown below.
u (V)
t (ms)
i (A)
t (ms)
Example spectra of the current and voltage distortion at the output of the transformer
Test 13
Test 13
1.4
1.4
1.2
1.2
1.0
1.0
0.8
IL1 [A]
0.8
UL12 [%]
0.6
0.6
0.4
0.4
0.2
0.2
0.0
0.0
n
n
17
47
20
23
35
50
29
38
32
26
44
14
11
41
17
29
38
47
20
23
35
50
26
32
14
44
11
41
The ACS800-31/U31
27
The drive includes an RDCO-03 module in the line-side converter and another
The ACS800-31/U31
28
External
control via
analogue/
digital
inputs and
outputs
The ACS800-31/U31
X39
X39
Optional module 1:
RMIO board of
RMIO board of
the line-side
the motor-side
converter
converter
ID number 1
RMBP, RETA, RRIA
ID number 2
Input
=
~
Output
power
power
Application
or RTAC
=
Line-side
~
specific program
Optional module 2: RTAC,
converter
and motor
RAIO, RRIA or RDIO
control program
UDC+ UDC-
control program
DDCS communication
DDCS
module: RDCO-03 (default),
CH0
Optional
EMC
filter
LCL filter
U1
U2
K1
V2
V1
M
W2
3~
W1
Line-side converter
Motor-side converter
Varistor
connection
UDC+
UDC-
29
Fieldbus control of the line-side converter can only be performed via the motor-side
converter RMIO board. The control signal dataset receive and actual signal dataset
The figure below shows the parameters for DC and reactive power reference
selection of the line-side converter control program. The AMC table contains actual
values and parameters of the line-side converter. The control and actual signal
Motor-side
Line-side converter
PARAM 24.01
converter RMIO
RMIO board
MCW
MCW (fixed)
PERCENT
kVAr
+
PARAM 24.02
PHI
MSW
MSW (fixed)
24.04
110
AMC
AI1
table AI2
23.01
AI3
FIELD BUS
The ACS800-31/U31
30
Internal connections to the RMIO board for the ACS800 IGBT Supply Control
X20
Tightening torque:
X21
2 GND
1 kohm < RL < 10 kohm
4 AI1-
Rin
6 AI2-
R
= 100 ohm
in
8 AI3-
Rin
= 100 ohm
10 AO1-
R
12 AO2-
RL < 700 ohm
1)
non-programmable I/O
X22
1 1)
2)
5 3)
3)
8 +24V
11 DI7(DIIL) Stop/Start
X23
2 GND
isolated, 24 VDC 250 mA
X25
2 RO12
use.
3 RO13
X26
2 RO22
use.
3 RO23
X27
1)
control
2 RO32
3 RO33
+ 24 VDC
The ACS800-31/U31
31
Type code
The type code contains information on the specifications and configuration of the
drive. The first digits from left express the basic configuration (e.g. ACS800-31-
0030-5). The optional selections are given thereafter, separated by plus signs (e.g.
+E202). The main selections are described below. Not all selections are available for
all types. For more information, refer to ACS800 Ordering Information (EN code:
Selection Alternatives
Type 31 wall mounted. When no options are selected: IP21, Control Panel
U31 wall mounted (USA). When no options are selected: UL type 1, Control
Voltage range
2 208/220/230/240 VAC
5 380/400/415/440/460/480/500 VAC
7 525/575/600/690 VAC
+ options
I/O L...
The ACS800-31/U31
32
The ACS800-31/U31
33
Mechanical installation
hardware manual
delivery documents.
Delivery check
Check that there are no signs of damage. Before attempting installation and
operation, check the information on the type designation label of the drive to verify
that the unit is of the correct type. The label includes an IEC and NEMA rating, C-UL,
CSA and CE markings, a type code and a serial number, which allow individual
recognition of each unit. The first digit of the serial number refers to the
manufacturing plant. The next four digits refer to the units manufacturing year and
week, respectively. The remaining digits complete the serial number so that there
Mechanical installation
34
The type designation label is attached to the heat sink and the serial number label to
the lower part of the back plate of the unit. Example labels are shown below.
Lift the unit using the lifting holes at the top and bottom.
Mechanical installation
35
Before installation
The drive must be installed in an upright position with the cooling section facing a
wall. Check the installation site according to the requirements below. Refer to
See chapter Technical data for the allowed operation conditions of the drive.
Wall
strong enough to carry the weight of the unit. Check that there is nothing on the wall
Floor
Required free space around the drive to enable cooling air flow, service and
200 [7.9]
50 [2.0]
50 [2.0]
200 [7.9]
IP21 (UL 1)
Cooling air flow
Mechanical installation
36
1. Mark the locations for the four holes. The mounting points are shown in chapter
Dimensional drawings.
3. Position the drive onto the screws on the wall. Note: Lift the drive by its lifting
100 Hz, vibration dampers can be used. For units of frame size R5, see ACS800-01/
Cabinet installation
The drive can be installed in a cabinet without the plastic front, top and connection
box covers and without the lead-through plate. Vibration dampers are not needed.
installations without the front cover. The cooling air entering the unit must not exceed
+40°C (+104°F). Contact ABB, if two units are to be installed side by side at a
distance smaller than 50 millimetres (1.97 in.), i.e. the side air holes will be covered
at one side.
Mechanical installation
37
Example
HOT
AREA
COOL
AREA
Mechanical installation
38
Lead the out-coming hot cooling air away from the air input of the drive above.
Example
max.+40°C (+104°F)
Mechanical installation
39
This chapter contains the instructions that you must follow when selecting the motor,
cables, protections, cable routing and way of operation for the drive system.
Note: The installation must always be designed and made according to applicable
local laws and regulations. ABB does not assume any liability whatsoever for any
installation which breaches the local laws and/or other regulations. Furthermore, if
the recommendations given by ABB are not followed, the drive may experience
Note: All options described in this chapter are not available for all products. Check
1. Select the motor according to the rating tables in chapter Technical Data. Use the
2. Check that the motor ratings lie within the allowed ranges of the drive control
program:
N of the drive
0 ... 2 · I
40
3. Check that the motor voltage rating meets the application requirements:
with
rating should be
diode supply
no resistor braking is in use U
ACeq1
IGBT supply
DC link voltage will not be increased
U
ACeq2
N
= Rated input voltage of the drive
ACeq1
= U
DC/1.35
ACeq2
= U
DC/1.41
ACeq
is the equivalent AC power source voltage of the drive in VAC.
DC
is the maximum DC link voltage of the drive in VDC.
N × 1.35 or U
N × 1.41 in VDC.)
See notes 6 and 7 below the Requirements table, pages 43 and 44.
4. Consult the motor manufacturer before using a motor in a drive system where the
5. Ensure that the motor insulation system withstands the maximum peak voltage in
the motor terminals. See the Requirements table below for the required motor
Example 1: When the supply voltage is 440 V and a drive with a diode supply is
operating in motor mode only, the maximum peak voltage in the motor terminals
can be approximated as follows: 440 V · 1.35 · 2 = 1190 V. Check that the motor
Example 2: When the supply voltage is 440 V and the drive is equipped with an
IGBT supply, the maximum peak voltage in the motor terminals can be
41
approximately 1.35 times the equivalent mains network voltage with a very short rise
time. This is the case with all drives employing modern IGBT inverter technology.
The voltage of the pulses can be almost double at the motor terminals, depending on
the attenuation and reflection properties of the motor cable and the terminals. This in
turn can cause additional stress on the motor and motor cable insulation.
Modern variable speed drives with their fast rising voltage pulses and high switching
frequencies can generate current pulses that flow through the motor bearings, which
The stress on motor insulation can be avoided by using optional ABB du/dt filters.
To avoid damage to motor bearings, the cables must be selected and installed
end (non-driven end) bearings and output filters from ABB must be used according
to the following table. Two types of filters are used individually or in combinations:
optional du/dt filter (protects motor insulation system and reduces bearing
currents).
42
Requirements table
The following table shows how to select the motor insulation system and when an optional ABB du/dt
filter, insulated N-end (non-driven end) motor bearings and ABB common mode filters are required. The
motor manufacturer should be consulted regarding the construction of the motor insulation and
additional requirements for explosion-safe (EX) motors. Failure of the motor to fulfil the following
requirements or improper installation may shorten motor life or damage the motor bearings.
Manufacturer
ABB du/dt filter, insulated N-end bearing and ABB common mode
voltage)
system
filter
N < 100 kW
P
100 kW < P
N < 350 kW
N > 350 kW
and
or
or
PN < 134 HP
134 HP < P
N < 469 HP
PN > 469 HP
NEMA500
NEMA500
NEMA580
A
Random-
U
B
wound M2_
500 V < U
B
and M3_
or
Reinforced - +N + N + CMF
600 V < U
Form-wound
380 V < U
CMF + du/dt
Old* form-
380 V < U
wound HX_
motor
and modular
manufacturer.
Random-
0 V < U
wound HX_
with fibre glass
500 V < U
and AM_ **
N
Random-
U
O
wound and
1300 V
N
form-wound
420 V < U
-
1300 V
or
+ du/dt + CMF
or
Reinforced: Û
=
-
LL
+ N or CMF + N + CMF
1600 V, 0.2
microsecond rise
time
500 V < U
LL =
+ du/dt + du/dt + N + du/dt + N + CMF
1600 V
or
+ du/dt + CMF
or
Reinforced: Û
=
-
LL
+ N or CMF + N + CMF
1800 V
600 V < U
1800 V
Reinforced: Û
=
-
LL
N + CMF N + CMF
2000 V, 0.3
microsecond rise
time ***
43
** For motors manufactured before 1.1.1998, check for additional instructions with the motor manufacturer.
*** If the intermediate DC circuit voltage of the drive is increased from the nominal level by resistor braking or by the
IGBT supply unit control program (parameter selectable function), check with the motor manufacturer if
additional output filters are needed in the applied drive operation range.
Abbreviation Definition
N
nominal voltage of the supply network
LL
peak line-to-line voltage at motor terminals which the motor insulation must withstand
N
motor nominal power
n.a. Motors of this power range are not available as standard units. Consult the motor manufacturer.
The motor manufacturer should be consulted regarding the construction of the motor insulation and
For motors with higher rated output than what is stated for the particular frame size in EN 50347 (2001)
and for IP 23 motors, the requirements of ABB random-wound motor series M3AA, M3AP, M3BP are
given below. For other motor types, see the Requirements table above. Apply the requirements of
manufacturer.
Manufacturer
Motor insulation
ABB du/dt filter, insulated N-end bearing and ABB common mode
voltage)
system
filter
PN < 55 kW 55 kW < P
N < 74 HP
P
N < 268 HP
74 HP < P
N > 268 HP
A
Random-
U
B
wound M3AA,
500 V < U
< 600 V Standard + du/dt + du/dt + N + du/dt + N + CMF
N
B
M3AP, M3BP
or
Reinforced - +N + N + CMF
600 V < U
All AMA machines (manufactured in Helsinki) for drive systems have form-wound windings. All HXR
Note 5: ABB motors of types other than M2_, M3_, HX_ and AM_
When the drive is in braking mode for a large part of its operation time, the intermediate circuit DC
voltage of the drive increases, the effect being similar to increasing the supply voltage by up to
20 percent. The voltage increase should be taken into consideration when determining the motor
insulation requirement.
Example: Motor insulation requirement for a 400 V application must be selected as if the drive were
44
If voltage is raised by the drive (this is a parameter selectable function), select the motor insulation
system according to the increased intermediate circuit DC voltage level, especially in the 500 V supply
voltage range.
Note 8: Calculating the rise time and the peak line-to-line voltage
The peak line-to-line voltage at the motor terminals generated by the drive as well as the voltage rise
time depend on the cable length. The requirements for the motor insulation system given in the table
are worst case requirements covering installations with 30 metre and longer cables. The rise time can
braking, the Û
LL and du/dt values are approximately 20 % higher.
3.0
5.5
Û
LL/U
N
5.0
2.5
du/dt
------------- (1/µs)
4.5
U
N
2.0
4.0
3.5
1.5
3.0
LL/U
1.0
2.5
du/dt
------------- (1/µs)
U
N
2.0
0.5
1.5
0.0
1.0
Note 9: Sine filters protect the motor insulation system. Therefore, du/dt filter can be replaced with a
sine filter. The peak phase-to-phase voltage with the sine filter is approximately 1.5 × U
N.
Only one permanent magnet motor can be connected to the inverter output.
synchronous motor and the drive output. The switch is needed to isolate the motor
45
Supply connection
the AC power source and the drive. The disconnecting device must be of a type that
can be locked to the open position for installation and maintenance work.
(disconnecting means) which isolates the drive and the motor from the AC power as
standard. The disconnecting device does not, however, isolate the input busbars
from the AC power. Therefore, during installation and maintenance work on the
drive, the input cables and busbars must be isolated from the input power with a
EU
disconnector that has an auxiliary contact that in all cases causes switching
devices to break the load circuit before the opening of the main contacts of the
US
Fuses
46
The drive protects itself and the input and motor cables against thermal overload
when the cables are dimensioned according to the nominal current of the drive. No
switch or a circuit breaker must be used for protecting each cable and motor. These
devices may require a separate fuse to cut off the short-circuit current.
The drive protects the motor cable and motor in a short-circuit situation when the
47
Short-circuit protection
Protect the input cable and drive against short-circuit according to the following
guide lines.
protection
ACS800-01
Protect the drive and
Distribution
Drive or drive
ACS800-U1
input cable with fuses
board
Input cable
module
or a circuit breaker.
ACS800-02
1)
ACS800-U2+0C111
2).
~
M
~
3~
ACS800-11
ACS800-U11
ACS800-31
ACS800-U31
I >
2)
ACS800-04
~
M
~
3~
ACS800-U4
ACS800-02+C111
Protect the input cable
Distribution
ACS800-U2
with fuses or a circuit
board
Input cable
Drive
breaker according to
ACS800-07
3)
4)
~
M
ACS800-U7
footnotes 3) and 4).
~
3~
Drive
4)
~
M
I>
~
3~
1) Size the fuses according to local safety regulations, appropriate input voltage and the rated current of
Standard gG fuses (US: CC or T for the ACS800-U1, ACS800-U11 and ACS800-U31; T or L for the
ACS800-U2 and ACS800-U4) will protect the input cable in short-circuit situations, restrict drive
damage and prevent damage to adjoining equipment in case of a short-circuit inside the drive.
Check that the operating time of the fuse is below 0.5 seconds (0.1 seconds with ACS800-11/
U11, ACS800-31/U31). The operating time depends on the fuse type (gG or aR), supply network
impedance and the cross-sectional area, material and length of the supply cable. In case the 0.5
seconds (0.1 seconds with ACS800-11/U11 and ACS800-31/U31) operating time is exceeded with gG
fuses (US: CC/T/L), ultrarapid (aR) fuses will in most cases reduce the operating time to an acceptable
48
2) Circuit breakers which have been tested by ABB with the ACS800 can be used. Fuses must be used
with other circuit breakers. Contact your local ABB representative for approved breaker types and
The protective characteristics of circuit breakers depend on the type, construction and settings of the
breakers. There are also limitations pertaining to the short-circuit capacity of the supply network.
WARNING! Due to the inherent operating principle and construction of circuit breakers,
independent of the manufacturer, hot ionized gases may escape from the breaker
enclosure in case of a short-circuit. To ensure safe use, special attention must be paid to
the installation and placement of the breakers. Follow the manufacturers instructions.
Note: Circuit breakers without fuses are not recommended in the USA.
3) Size the fuses according to local safety regulations, appropriate input voltage and the rated current of
4) ACS800-07/U7 units and ACS800-02/U2 units with enclosure extension are equipped with standard gG
(US: T/L) or optional aR fuses listed in Technical data. The fuses restrict drive damage and prevent
Check that the operating time of the fuse is below 0.5 seconds. The operating time depends on the
fuse type (gG or aR), supply network impedance and the cross-sectional area, material and length of
the supply cable. In case the 0.5 seconds operating time is exceeded with gG fuses (US: CC/T/L),
ultrarapid (aR) fuses will in most cases reduce the operating time to an acceptable level. The US fuses
49
The drive is equipped with an internal ground fault protective function to protect the
unit against ground faults in the motor and motor cable. This is not a personal safety
or a fire protection feature. The ground fault protective function can be disabled with
The EMC filter of the drive includes capacitors connected between the main circuit
and the frame. These capacitors and long motor cables increase the ground leakage
For safety reasons, install the emergency stop devices at each operator control
station and at other operating stations where emergency stop may be needed.
Note: Pressing the stop key ( ) on the control panel of the drive does not generate
an emergency stop of the motor or separate the drive from dangerous potential.
An emergency stop function is optionally available for stopping and switching off the
whole drive. Two stop categories according to IEC/EN 60204-1 (1997) are available:
After an emergency stop, the emergency stop button must be released and the drive
started by turning the operating switch of the drive from position ON to START.
50
The Prevention of Unexpected Start function disables the control voltage of the
power semiconductors, thus preventing the inverter from generating the AC voltage
required to rotate the motor. By using this function, short-time operations (like
switch on a control desk. An indicating lamp on the control desk will light, signalling
EN 60204-1: 1997.
For connections to the drive, see the circuit diagram delivered with the drive.
WARNING! The Prevention of Unexpected Start function does not disconnect the
voltage of the main and auxiliary circuits from the drive. Therefore maintenance work
on electrical parts of the drive or the motor can only be carried out after isolating the
Note: The Prevention of Unexpected Start function is not intended for stopping the
function, the drive will cut off the motor supply voltage and the motor will coast to
stop.
51
General rules
Dimension the mains (input power) and motor cables according to local
regulations:
The cable must be able to carry the drive load current. See chapter Technical
(so that the fault point voltage will not rise excessively when a ground fault
occurs).
600 VAC cable is accepted for up to 500 VAC. 750 VAC cable is accepted for up
to 600 VAC. For 690 VAC rated equipment, the rated voltage between the
For drive frame size R5 and larger, or motors larger than 30 kW (40 HP),
system can be used up to frame size R4 with up to 30 kW (40 HP) motors, but
A four-conductor system is allowed for input cabling, but shielded symmetrical cable
be as follows when the protective conductor is made of the same metal as the phase
conductors:
conductors
corresponding protective conductor
2
2
S (mm
)
Sp (mm
)
S < 16 S
16 < S < 35 16
35 < S S/2
The motor cable and its PE pigtail (twisted shield) should be kept as short as
52
Power cable types that can be used with the drive are represented below.
Recommended
PE conductor
Shield
and shield
Shield
PE
PE
PE
Shield
A four-conductor system:
and a protective
conductor
shield conductivity must be at least 1/10 of the phase conductor conductivity. The
requirements are easily met with a copper or aluminium shield. The minimum
requirement of the motor cable shield of the drive is shown below. It consists of a
concentric layer of copper wires with an open helix of copper tape. The better and
tighter the shield, the lower the emission level and bearing currents.
Cable core
53
Additional US requirements
shielded power cable must be used for the motor cables if metallic conduit is not
used. For the North American market, 600 VAC cable is accepted for up to 500 VAC.
1000 VAC cable is required above 500 VAC (below 600 VAC). For drives rated over
100 amperes, the power cables must be rated for 75 °C (167 °F).
Conduit
Where conduits must be coupled together, bridge the joint with a ground conductor
bonded to the conduit on each side of the joint. Bond the conduits also to the drive
enclosure. Use separate conduits for input power, motor, brake resistor, and control
cable or shielded cable is not required. A dedicated ground cable is always required.
Note: Do not run motor wiring from more than one drive in the same conduit.
armor cable with symmetrical grounds is available from the following suppliers (trade
names in parentheses):
Oaknite (CLX).
Shielded power cables are available from Belden, LAPPKABEL (ÖLFLEX) and
Pirelli.
restrictions.
cables (between the drive and the motor). They are not meant to be used with AC
54
If there are power factor compensation capacitors in parallel with the three phase
1. Do not connect a high-power capacitor to the power line while the drive is
connected. The connection will cause voltage transients that may trip or even
connected to the power line: Ensure that the connection steps are low enough not
3. Check that the power factor compensation unit is suitable for use in systems with
AC drives i.e. harmonic generating loads. In such systems, the compensation unit
To minimize the emission level when safety switches, contactors, connection boxes
or similar equipment are installed in the motor cable between the drive and the
motor:
EU: Install the equipment in a metal enclosure with 360 degrees grounding for the
shields of both the incoming and outgoing cable, or connect the shields of the
US: Install the equipment in a metal enclosure in a way that the conduit or motor
cable shielding runs consistently without breaks from the drive to the motor.
Bypass connection
WARNING! Never connect the supply power to the drive output terminals U2, V2
or contactors. Mains (line) voltage applied to the output can result in permanent
Stop the drive and wait for the motor to stop before opening a contactor between the
output of the drive and the motor when the DTC control mode is selected. See the
parameter settings. Otherwise, the contactor will be damaged. In scalar control, the
55
of inductive loads
Inductive loads (relays, contactors, motors) cause voltage transients when switched
off.
The relay contacts on the RMIO board are protected with varistors (250 V) against
with noise attenuating circuits [varistors, RC filters (AC) or diodes (DC)] in order to
minimize the EMC emission at switch-off. If not suppressed, the disturbances may
connect capacitively or inductively to other conductors in the control cable and form
Install the protective component as close to the inductive load as possible. Do not
RMIO
Relay outputs
Varistor
X25
1 RO1
2 RO1
230 VAC
3 RO1
RC filter X26
1 RO2
2 RO2
230 VAC
3 RO2
Diode
X27
1 RO3
2 RO3
24 VDC
3 RO3
56
Finland) for analogue signals. This type of cable is recommended for the pulse
encoder signals also. Employ one individually shielded pair for each signal. Do not
A double-shielded cable is the best alternative for low-voltage digital signals but
a
b
Adouble-shielded twisted
A single-shielded twisted
pair cable
pair cable
Relay-controlled signals, providing their voltage does not exceed 48 V, can be run in
the same cables as digital input signals. It is recommended that the relay-controlled
Never mix 24 VDC and 115/230 VAC signals in the same cable.
Relay cable
The cable type with braided metallic screen (e.g. ÖLFLEX by LAPPKABEL,
In remote use, the cable connecting the control panel to the drive must not exceed 3
metres (10 ft). The cable type tested and approved by ABB is used in control panel
option kits.
57
WARNING! IEC 60664 requires double or reinforced insulation between live parts
and the surface of accessible parts of electrical equipment which are either non-
components) to the digital inputs of the drive can be implemented in three alternate
ways:
1. There is double or reinforced insulation between the thermistor and live parts of
the motor.
2. Circuits connected to all digital and analogue inputs of the drive are protected
against contact and insulated with basic insulation (the same voltage level as the
3. An external thermistor relay is used. The insulation of the relay must be rated for
the same voltage level as the main circuit of the drive. For connection, see
WARNING! Protect against direct contact when installing, operating and servicing
the RMIO board wiring and optional modules attached to the board. The Protective
Extra Low Voltage (PELV) requirements stated in EN 50178 are not fulfilled at
Route the motor cable away from other cable routes. Motor cables of several drives
can be run in parallel installed next to each other. It is recommended that the motor
cable, input power cable and control cables be installed on separate trays. Avoid
long parallel runs of motor cables with other cables in order to decrease
voltage.
Where control cables must cross power cables make sure they are arranged at an
angle as near to 90 degrees as possible. Do not run extra cables through the drive.
The cable trays must have good electrical bonding to each other and to the
equalizing of potential.
58
Motor cable
Drive
Power cable
Control cables
230 V
230 V
24 V
(120 V)
24 V
(120 V)
(120 V).
59
Electrical installation
WARNING! The work described in this chapter may only be carried out by a qualified
electrician. Follow the Safety instructions on the first pages of this manual. Ignoring
Make sure that the drive is disconnected from the mains (input power) during
the installation. If the drive is already connected to the mains, wait for 5 min
Drive
Every drive has been tested for insulation between the main circuit and the chassis
(2500 V rms 50 Hz for 1 second) at the factory. Therefore, do not make any voltage
tolerance or insulation resistance tests (e.g. hi-pot or megger) on any part of the
drive.
Input cable
Check the insulation of the input cable according to local regulations before
1. Check that the motor cable is disconnected from the drive output terminals U2,
V2 and W2.
M 2. Measure the insulation resistances of the motor cable and motor between each
ohm
phase and the Protective Earth by using a measuring voltage of 1 kV DC. The
PE
Electrical installation
60
IT (ungrounded) systems
In units with EMC filter options (+E202 and +E200 in the type code), disconnect the
power system], the system will be connected to earth potential through the EMC
filter capacitors of the drive. This may cause danger or damage the unit.
Note concerning units of frame size R5: When the capacitors of EMC filter +E202
Note concerning units of frame size R6: When the capacitors of EMC filter +E202
are disconnected, the EMC Directive requirements may not be fulfilled in first
environment, but are fulfilled in second environment. When the capacitors of EMC
Electrical installation
61
Diagram
Drive
INPUT
OUTPUT
PE
U1
V1 W1
UDC+ UDC- U2
V2 W2
1)
2)
3)
4)
(PE) PE
(PE)
5)
V1
W1
U1
installation:
Motor
Disconnecting device
(disconnecting means)
L1 L2 L3
1), 2)
Grounding of the motor cable shield at the motor end
cable is used
Conductive gaskets
b > 1/5 · a
power cables).
Note:
Electrical installation
62
Strip the conductor ends as follows to fit them inside the power cable connection
terminals.
mm in.
R5 16 0.63
R6 28 1.10
2. Remove the front cover by releasing the retaining clip with a screw driver and
4. Cut adequate holes into the rubber grommets and slide the grommets onto the
cables. Slide the cables through the holes of the bottom plate.
5. Strip off the outer sheathing of the cables under the 360 degrees grounding
clamps. Fasten the clamps onto the stripped parts of the cables.
6. Tighten the grounding clamps onto the twisted shields of the cables.
7. Connect the phase conductors of the mains cable to the U1, V1 and W1
terminals and the phase conductors of the motor cable to the U2, V2 and W2
terminals.
8. Cut holes to the clear plastic shroud for the conductors in frame size R5 and in
9. Press the clear plastic shroud onto the phase conductor terminals.
10. Secure the cables outside the unit mechanically. Connect the control cables as
described in section Connecting the control cables on page 67. Fasten the
covers, see Fastening the control cables and covers on page 70.
Electrical installation
63
9
9
U1
V1 W1
UDC+
UDC-
U2
V2 W2
PE
6
Electrical installation
64
PE
insulating tape or
shrink tubing.
terminal installation)
5
5
9
9
PE
6
95 mm
(3/0 AWG), a cable lug must
5
5
be used. A cable of wire size less than
95 mm
(3/0 AWG) connected to this
the drive.
Electrical installation
65
2. Remove the front cover by releasing the retaining clip with a screw driver and
8
8
3
3
2
4
4
4. Make the cable entry holes in the gland plate by breaking off the suitable knock-
5. Fasten the cable glands to the opened holes of the gland plate.
8. Connect the grounding conductors of the input and motor cables to the
grounding clamps.
9. Remove the clear plastic shroud as shown in section Power cable installation
10. Connect the phase conductors of the input cable to the U1, V1 and W1 terminals
and the phase conductors of the motor cable to the U2, V2 and W2 terminals.
See Wall installed units (European version) for cabling figures. In case of a cable
lug installation, use UL listed cable lugs and tools given below or corresponding
to meet UL requirements.
Electrical installation
66
After connecting the control cables, fasten the clear plastic shroud and front covers.
Warning sticker
There are warning stickers in different languages inside the packing box of the drive.
Attach a warning sticker in the language of your choice onto the plastic skeleton
The drive can be installed in a cabinet without the plastic front, top and connection
It is recommended:
to ground the cable shield 360 degrees at the cabinet entry. Grounding with the
360 degrees grounding clamps at the connection box back plate is then not
needed.
to lead the cable unstripped as close to the terminals as possible. Ground the
twisted shields of the power cables under the PE and grounding clamps.
Protect the RMIO board terminals X25 to X27 against contact when input voltage
exceeds 50 VAC.
Cover the power cable terminals with the clear plastic shroud as shown in section
Electrical installation
67
Connect the control cables as described below. Connect the conductors to the
appropriate detachable terminals of the RMIO board [refer to chapter Motor control
and I/O board (RMIO)]. Tighten the screws to secure the connection.
Terminals
Control panel
Optional module 2
Optional module 1
Control cable
grounding: see
Detachable connection terminals (pull up)
section 360
degrees
grounding
Electrical installation
68
Insulation
Double-shielded cable
Single-shielded cable
When the outer surface of the shield is covered with non-conductive material
Strip the cable carefully (do not cut the grounding wire and the shield)
Fasten the clamp to the grounding plate with a screw as close as possible to the
Single-shielded cables: Twist the grounding wires of the outer shield and connect
them through the shortest possible route to the nearest grounding hole with a cable
lug and a screw. Double-shielded cables: Connect each pair cable shield (twisted
grounding wires) with other pair cable shields of the same cable to the nearest
Do not connect shields of different cables to the same cable lug and grounding
screw.
Leave the other end of the shield unconnected or ground it indirectly via a few
nanofarads high-frequency capacitor (e.g. 3.3 nF / 630 V). The shield can also be
grounded directly at both ends if they are in the same ground line with no significant
Keep the signal wire pairs twisted as close to the terminals as possible. Twisting the
wire with its return wire reduces disturbances caused by inductive coupling.
Electrical installation
69
Module
As short as possible
Shield
shields here.
RTAC
from the motor shaft and the stator frame,
Shield
Electrical installation
70
When all control cables are connected, fasten them together with cable ties. Units
with a connection box: fasten the cables to the entry plate with cable ties. Units with
The optional module (such as fieldbus adapter, I/O extension module and the pulse
encoder interface) is inserted in the optional module slot of the RMIO board (see
Connecting the control cables) and fixed with two screws. See the appropriate
Note: Two RDCO modules are provided for the DDCS fibre optic link between the
RMIO boards of the line-side and motor-side converters. Channel CH0 of the
RDCO-03 module in the line-side converter and channel CH1 of the RDCO module
in the motor-side converter are used for the internal communication. In case multiple
Electrical installation
71
The optional Prevention of Unexpected Start function includes an AGPS board which
is connected to the drive and an external power supply. See also chapter Planning
WARNING! Dangerous voltages can be present on the AGPS board even when the
115...230 V supply is switched off. Follow the Safety instructions on the first pages of
this manual and the instruction in this chapter when working on the AGPS board.
Make sure that the drive is disconnected from the mains (input power) and the
115...230 V source for the AGPS board is switched off during installation and
maintenance. If the drive is already connected to the mains, wait for 5 min after
See
section AGPS-11C in chapter Technical data for the technical data of the board.
Note: Maximum cable length between AGPS terminal block X2 and the drive
72
Ground the bottom plate of the enclosure or via terminal X1:1 of the AGPS board.
Connect the cable delivered with the kit between terminal block X2 of the AGPS
Connect a cable between connector X1 of the AGPS board (3) and the
115...230 V source.
X2
X1
115...230 V
3
73
Circuit diagram
Drive
115/230 VAC
3AFE00374994
74
Dimensional drawing
3AFE68293898
75
external control connections to the RMIO board for the ACS800 Standard
This chapter applies to ACS800 units which employ RMIO-01 board from revision J
Note for the ACS800-02 with enclosure extension and the ACS800-07
The connections for the RMIO board shown below apply also to optional terminal
block X2 available for the ACS800-02 and ACS800-07. The terminals of the RMIO
torque for screw terminals is 0.4 to 0.8 Nm (0.3 to 0.6 lbf ft). For disconnecting wires
from spring terminals, use a screw driver with a blade thickness of 0.6 mm
(0.024 in.) and width of 3.5 mm (0.138 in.), e.g. PHOENIX CONTACT SZF 1-
0,6X3,5.
Optional modules (Rxxx) may have identical terminal designations with the RMIO
board.
76
the application requires a fast start after connecting the input power supply
The RMIO board can be supplied from an external power source via terminal X23 or
X34 or via both X23 and X34. The internal power supply to terminal X34 can be left
WARNING! If the RMIO board is supplied from an external power source via
terminal X34, the loose end of the cable removed from the RMIO board terminal
must be secured mechanically to a location where it cannot come into contact with
electrical parts. If the screw terminal plug of the cable is removed, the wire ends
Parameter settings
77
External control cable connections to the RMIO board for the ACS800 Standard
Application Program (Factory Macro) are shown below. For external control
Firmware Manual.
X2* RMIO
X20 X20
RMIO
1 1 VREF- Reference voltage -10 VDC, 1 kohm < R
<
Tightening torque:
1 1 VREF+ Reference voltage 10 VDC, 1 kohm < RL <
0.2 to 0.4 Nm
2 2 AGND
10 kohm
in >
4 4 AI1-
200 kohm
6 6 AI2-
100 ohm
in =
8 8 AI3-
100 ohm
rpm
9 9 AO1+ Motor speed 0(4)...20 mA =
0...motor nom.
10 10 AO1-
speed, RL < 700 ohm
A
11 11 AO2+ Output current 0(4)...20 mA =
0...motor
12 12 AO2-
nom. current, R
L < 700 ohm
and ACS800-07
1 1 DI1 Stop/Start
1)
1)
4 2)
2)
0 = open, 1 = closed
3)
8 8 +24VD
3)
SPEEDS.
10 10 DGND2 Digital ground
11 4)
1 0 Constant speed 1
1 1 +24V Auxiliary voltage output and input, non-
5)
0 1 Constant speed 2
2 2 GND
isolated, 24 VDC 250 mA
1 1 Constant speed 3
X25 X25
4)
FUNC.
5)
3 3 RO1
X26 X26
2 2 RO2
3 3 RO2
X27 X27
Fault
2 2 RO3
3 3 RO3
78
External control cable connections to the RMIO board for the ACS800 Standard
Application Program (Factory Macro US version) are shown below. For external
control connections of other application macros and programs, see the appropriate
Firmware Manual.
X2* RMIO
RMIO
X20 X20
Tightening torque:
X21 X21
2 2 AGND
10 kohm
in >
4 4 AI1-
200 kohm
6 6 AI2-
100 ohm
in =
8 8 AI3-
100 ohm
rpm
9 9 AO1+ Motor speed 0(4)...20 mA =
0...motor nom.
10 10 AO1-
speed, RL < 700 ohm
A
11 11 AO2+ Output current 0(4)...20 mA =
0...motor
12 12 AO2-
nom. current, R
L < 700 ohm
X22 X22
1 1 DI1 Start ( )
2 2 DI2 Stop ( )
3 3 DI3 Forward/Reverse
and ACS800-U7
2)
1)
3)
2)
0 = open, 1 = closed
8 8 +24VD
3)
X23 X23
SPEEDS.
1 1 +24V Auxiliary voltage output and input, non-
5)
1 0 Constant speed 1
1 1 RO1 Relay output 1: ready
0 1 Constant speed 2
2 2 RO1
X26 X26
4)
FUNC.
5)
2 2 RO2
Fault
2 2 RO3
3 3 RO3
79
Analogue inputs
(0 mA / 4 mA ... 20 mA, R
in = 100 ohm) and one programmable differential voltage
Resolution 0.025 % (12 bit) for the -10 V ... +10 V input. 0.5 % (11 bit) for the 0 ... +10 V and 0 ...
20 mA inputs.
Inaccuracy ± 0.5 % (Full Scale Range) at 25 °C (77 °F). Temperature coefficient: ± 100 ppm/°C
(± 56 ppm/°F), max.
Voltage +10 VDC, 0, -10 VDC ± 0.5 % (Full Scale Range) at 25 °C (77 °F). Temperature
Maximum load 10 mA
Maximum current 250 mA (shared between this output and optional modules installed on the RMIO)
Analogue outputs
Inaccuracy ± 1 % (Full Scale Range) at 25 °C (77 °F). Temperature coefficient: ± 200 ppm/°C
Digital inputs
With Standard Application Program six programmable digital inputs (common ground:
24 VDC, -15 % to +20 %) and a start interlock input. Group isolated, can be divided in
Thermistor input: 5 mA, < 1.5 kohm 1 (normal temperature), > 4 kohm 0
Internal supply for digital inputs (+24 VDC): short-circuit proof. An external 24 VDC
80
Relay outputs
Voltage 24 VDC ± 10 %
The terminals on the RMIO board as well as on the optional modules attachable to the board fulfil the Protective Extra
Low Voltage (PELV) requirements stated in EN 50178 provided that the external circuits connected to the terminals also
fulfil the requirements and the installation site is below 2000 m (6562 ft). Above 2000 m (6562 ft), see page 57.
81
X20
1 VREF-
2 AGND
X21
1 VREF+
2 AGND
3 AI1+
4 AI1-
Common mode
voltage between
5 AI2+
channels ±15 V
6 AI2-
7 AI3+
8 AI3-
9 AO1+
10 AO1-
11 AO2+
12 AO2-
X22
1 DI1
2 DI2
3 DI3
4 DI4
Jumper J1 settings:
9 DGND1
5 DI5
All digital inputs share a common
J1
6 DI6
ground. This is the default setting.
7 +24VD
8 +24VD
Grounds of input groups
11 DIIL
DI1
DI4 and DI5/DI6/DIIL
or
10 DGND2
voltage 50 V).
X23
1 +24 V
2 GND
X25
1 RO1
2 RO1
3 RO1
X26
1 RO2
2 RO2
3 RO2
X27
1 RO3
2 RO3
3 RO3
(Test voltage:
4 kV AC)
Ground
82
83
Installation checklist
Installation checklist
Check the mechanical and electrical installation of the drive before start-up. Go
WARNING! Only qualified electricians are allowed to commission the drive. Read
and follow the Safety instructions on the first pages of this manual. Ignoring the
Check...
MECHANICAL INSTALLATION
The ambient operating conditions are allowed. (See Mechanical installation, Technical data)
The unit is fixed properly on a vertical non-flammable wall. (See Mechanical installation.)
The motor and the driven equipment are ready for start. (See Planning the electrical
The +E202 and +E200 EMC filter capacitors are disconnected if the drive is connected to an
IT (ungrounded) system.
The capacitors are reformed if stored over one year (refer to ACS 600/800 Capacitor
The mains (input power) voltage matches the drive nominal input voltage.
The mains (input power) connections at U1, V1 and W1 and their tightening torques are OK.
Installation checklist
84
Check...
The motor connections at U2, V2 and W2 and their tightening torques are OK.
There are no tools, foreign objects or dust from drilling inside the drive.
Mains (input power) voltage cannot be applied to the output of the drive (with bypass
connection).
Installation checklist
85
This chapter describes the start-up procedure and use of the drive.
WARNING! Only qualified electricians are allowed to commission the drive. Read
and follow the Safety instructions on the first pages of this manual. Ignoring the
if the motor is started and stopped frequently. This prolongs the lifespan of the
charging contactor.
if the drive is connected to other drives via a common DC bus. Otherwise, the
For setting of parameter 16.15 I/O START MODE, change the control panel to
Note
In normal use, have the control panel control the RMIO board of the motor-side
converter (default, ID number 1). If the control panel is set to control the RMIO
board of the line-side converter (ID number 2), the drive does not stop by
Do not change the ID numbers of the converters from the default settings. If the
ID numbers of the line-side and motor side converters are set equal, the control
chopper and resistor are installed. The parameter index is valid for Standard
firmware manual. For parameter settings with a brake chopper and resistor, see
86
Control panel
The drive is equipped with a control panel (type CDP-312R). The CDP-312R is the
user interface of the line-side converter and the motor-side converter of the drive,
the parameter settings for the units application programs. More information on using
the panel can be found in the Firmware Manual delivered with the drive.
The control panel is wired to both the line-side converter and the motor-side
indicated by the converter name on the drive display; the suffix MR denotes motor-
side converter, LR denotes line-side converter. The control is switched between the
converters as follows:
ASXR7xxx
ID-NUMBER 1
2. Scroll to ID number 2.
IXXR7xxx
ID-NUMBER 2
ACT
ACS 800 0050_5LR
** FAULT **
DC OVERVOLT ( 3210)
WARNING! The drive does not stop by pressing the control panel Stop key in local
control mode.
87
DRIVE
IXXR7xxx
ID-NUMBER 2
2. Scroll to ID number 1.
ACXR7xxx
ID-NUMBER 1
1 L -> 0. 0 rpm I
ACT
FREQ 0. 00 Hz
CURRENT 0. 00 A
POWER 0. 00 %
88
89
This chapter contains listings of parameters specific to the ACS800-31 and ACS800-
U31.
This section describes the actual signals and parameters of the line-side converter
control program which are copied to the motor-side converter application program.
The user can view two actual signals (by default, measured line current and
intermediate circuit DC voltage) and change the values of the copied parameters
without changing the control panel between two control boards and programs. In
normal use, there is no need to set these or other parameters of the line-side
converter control program. For more information on the parameters, refer to IGBT
Term Definition
Actual signal Signal measured or calculated by the drive. Can be monitored by the
FbEq Fieldbus equivalent: The scaling between the value shown on the control
Actual signals
09 ACTUAL SIGNALS
Signals from the line converter.
09.12 LCU ACT SIGNAL 1 Line converter signal selected by par. 95.08 LCU PAR1 SEL. 1=1 106
09.13 LCU ACT SIGNAL 2 Line converter signal selected by par. 95.09 LCU PAR2 SEL. 1=1 110
90
Parameters
95 HARDWARE SPECIF
Line converter references and actual signal selections.
95.06 LCU Q POW REF Reactive power reference for the line converter i.e. the value for
0
set to PERCENT.
P
P
Q
30
=
---
cos
=
------------------------
S
2
2
30 deg
P
+
Q
Par. 95.06
-10000 -3000
-1000
0
1000
3000
+10000
95.07 LCU DC REF (V) DC voltage reference for line converter i.e. the value for par. 23.01
0
DC VOLT REF.
95.08 LCU PAR1 SEL Selects the line-side converter address from which actual signal
106
95.09 LCU PAR2 SEL Selects the line-side converter address from which actual signal
110
91
The signals and parameters of the IGBT Supply Control Program which are specific
to the ACS800-31 and ACS800-U31 are described in the tables below. These
parameters of the IGBT Supply Control Program, refer to IGBT Supply Control
Term Definition
FbEq Fieldbus equivalent: the scaling between the value shown on the control
Parameters
16 SYSTEM CTR
Parameter lock, parameter back-up etc.
INPUTS
16.15 I/O START MODE Selects I/O control start mode when par. 98.01 COMMAND SEL is set
B DI2 EDGE
to I/O.
DI2 EDGE Starts the line converter by digital input DI2 rising edge. The line
0
DI2 LEVEL Starts the line converter by the level of digital input DI2. The line
1
converter starts to modulate and the charging resistors will be by-
passed when the line converter RMIO board is powered, its digital
Note: This selection changes the value of par. 98.01 COMMAND SEL
from the default setting MCW to I/O on the next RMIO board power-
up.
92
Automatic resets are possible only for certain fault types and when the
reset. Ensure that the use of this feature will not cause
danger.
31.01 NUMBER OF TRIALS Defines the number of automatic fault resets the drive performs within
I 0
31.02 TRIAL TIME Defines the time for the automatic fault reset function. See parameter
R 30 s
18000
31.03 DELAY TIME Defines the time that the drive will wait after a fault before attempting
R 0 s
31.04 OVERCURRENT Activates/deactivates the automatic reset for the line converter
B NO
overcurrent fault.
NO Inactive 0
31.05 OVERVOLTAGE Activates/deactivates the automatic reset for the intermediate link
B NO
overvoltage fault.
NO Inactive 0
31.06 UNDERVOLTAGE Activates/deactivates the automatic reset for the intermediate link
B NO
undervoltage fault.
NO Inactive 0
93
When the IGBT Supply Control Program is loaded into the ACS800-31 or ACS800-
U31, the following parameters are set to the default values given in the table below.
up.
94
95
Maintenance
Safety
WARNING! Read the Safety instructions on the first pages of this manual before
performing any maintenance on the equipment. Ignoring the safety instructions can
Maintenance intervals
and cleaning
the environment (every 6 to 12
months)
fan
Main cooling fan change Every six years See Main cooling fan.
Maintenance
96
Heatsink
The heatsink fins pick up dust from the cooling air. The drive runs into
environment (not dusty, not clean) the heatsink should be checked annually, in a
2. Blow clean compressed air (not humid) from bottom to top and simultaneously
use a vacuum cleaner at the air outlet to trap the dust. Note: If there is a risk of
the dust entering adjoining equipment, perform the cleaning in another room.
The cooling fan lifespan of the drive is about 50 000 operating hours. The actual
lifespan depends on the drive usage and ambient temperature. See the appropriate
ACS800 firmware manual for an actual signal which indicates the hours of usage of
the fan. For resetting the running time signal after a fan replacement, please contact
ABB.
Fan failure can be predicted by the increasing noise from fan bearings and the
gradual rise in the heatsink temperature in spite of heatsink cleaning. If the drive is
symptoms start appearing. Replacement fans are available from ABB. Do not use
Maintenance
97
1
1
5
4
Additional fan
Replacement (R5)
Remove the front cover. The fan is located on the right-hand side of the control panel
(R5). Lift the fan out and disconnect the cable. Install the new fan in reverse order.
Maintenance
98
Replacement (R6)
Remove the top cover by lifting it by the rear edge. To remove the fan, release the
retaining clips by pulling the back edge (1) of the fan upwards. Disconnect the cable
cover is removed
Rotation
direction
Capacitors
The drive intermediate circuit employs several electrolytic capacitors. Their lifespan
a mains fuse failure or a fault trip. Contact ABB if capacitor failure is suspected.
Replacements are available from ABB. Do not use other than ABB specified spare
parts.
Reforming
Reform (re-age) spare part capacitors once a year according to ACS 600/800
LEDs
Green The main +24 V power supply for the control panel and the
Maintenance
99
Fault tracing
This chapter describes the fault tracing of the line-side converter. For motor-side
converter fault tracing, see the appropriate application program firmware manual.
The control panel will display the warnings and faults of the unit (i.e. line-side
Information on warnings and faults concerning the line-side converter are contained
(English)].
The warnings and faults concerning the motor-side converter are dealt with in the
Flashing messages WARNING, ID:2 or FAULT, ID:2 on the control panel display
indicate a warning or fault state in the line-side converter when the panel is
FAULT, ID: 2
To display the warning or fault identification text, switch the control panel to view the
Conflicting ID numbers
If the ID numbers of the line-side and the motor-side converters are set equal, the
Disconnect the panel cable from the RMIO board of the motor-side converter.
Set the ID number of the line-side converter RMIO board to 2. For the setting
Firmware Manual.
Connect the disconnected cable to the RMIO board of the motor-side converter
Fault tracing
100
Fault tracing
101
Technical data
This chapter contains the technical specifications of the drive, e.g. the ratings, sizes
and technical requirements, provisions for fulfilling the requirements for CE and
Technical data
102
IEC data
Ratings
The IEC ratings for the ACS800-31 with 50 Hz and 60 Hz supplies are given below.
overload
ratings
use
use
size
dissipation
cont.max
I
max
P
cont.max
I
2N
P
N
I
2hd
P
hd
A
A
kW
A
kW
A
kW 3
m
/h W
Three-phase supply voltage 380 V, 400 V, 415 V, 440 V, 460 V, 480 V or 500 V
Technical data
103
Symbols
Nominal ratings
Icont.max
continuous rms output current. No overload capability at 40°C.
max
maximum output current. Available for 10 s at start, otherwise as long as allowed by drive
temperature.
Typical ratings:
No-overload use
Pcont.max
typical motor power. The power ratings apply to most IEC 34 motors at the nominal voltage,
2N
continuous rms current. 10% overload is allowed for one minute every 5 minutes.
P
N
typical motor power. The power ratings apply to most IEC 34 motors at the nominal voltage,
I2hd
continuous rms current. 50% overload is allowed for one minute every 5 minutes.
P
hd
typical motor power. The power ratings apply to most IEC 34 motors at the nominal voltage,
Sizing
The current ratings are the same regardless of the supply voltage within one voltage range. To achieve
the rated motor power given in the table, the rated current of the drive must be higher than or equal to
Note 1: The maximum allowed momentary motor shaft power is limited to approximately 1.3 · P
cont.max.
If the limit is exceeded, motor torque and current are automatically restricted. The function protects the
Note 2: The ratings apply at an ambient temperature of 40°C (104°F). At lower temperatures the
max).
Note 3: Use the DriveSize PC tool for a more accurate dimensioning if the ambient temperature is
Derating
The load capacity (current and power) decreases if the installation site altitude exceeds 1000 metres
Temperature derating
In the temperature range +40°C (+104°F) to +50°C (+122°F) the rated output current is decreased 1%
for every additional 1°C (1.8°F). The output current is calculated by multiplying the current given in the
Example If the ambient temperature is 50°C (+122°F), the derating factor is 100% - 1 %
· 10°C =
In altitudes from 1000 to 4000 m (3300 to 13123 ft) above sea level, the derating is 1% for every 100 m
(328 ft). For a more accurate derating, use the DriveSize PC tool.
Technical data
104
Fuses for short-circuit protection of the mains cable are listed below. The fuses also
protect the adjoining equipment of the drive in case of a short-circuit. Check that the
operating time of the fuse is below 0.1 seconds. The operating time depends on
the supply network impedance and the cross-sectional area and length of the supply
cable. See also Planning the electrical installation: Thermal overload and short-
Note 1: In multicable installations, install only one fuse per phase (not one fuse per conductor).
Note 3: Fuses from other manufacturers can be used if they meet the ratings.
current
A A
2
Three-phase supply voltage 380 V, 400 V, 415 V, 440 V, 460 V, 480 V or 500 V
* maximum total I
t value for 550 V
Technical data
105
Cable types
The table below gives copper and aluminium cable types for different load currents.
Cable sizing is based on max. 9 cables laid on a cable ladder side by side, ambient
temperature 30°C, PVC insulation, surface temperature 70°C (EN 60204-1 and
IEC 60364-5-2/2001). For other conditions, size the cables according to local safety
regulations, appropriate input voltage and the load current of the drive.
copper shield
copper shield
Max. load
Cable type
Max. load
Cable type
current
current
A
2
mm
A
2
mm
34 3x6 61 3x25
47 3x10 75 3x35
62 3x16 91 3x50
186 3x95
215 3x120
249 3x150
284 3x185
Cable entries
Mains, DC link and motor cable terminal sizes (per phase), accepted cable
Frame size U1, V1, W1, U2, V2, W2, UDC+,UDC- Earthing PE
IP21
torque
torque
2
2
mm
mm Nm mm
Nm
R5 6 70 35 10 6 70 15
mm mm mm kg dB
Technical data
106
NEMA data
Ratings
The NEMA ratings for the ACS800-U31 and ACS800-31 with 60 Hz supplies are
given below. The symbols are described below the table. For sizing, derating and
max
Normal use
ACS800-U31 size
I
Heavy-duty use Frame
Air flow Heat
ACS800-31 size
size
dissipation
2N
P
N
I
2hd
P
hd
A
A
HP
A
HP 3
ft
/min BTU/Hr
allowed with motor power < 125 HP and a reactive power reference of 0
**
Symbols
Nominal ratings
max
maximum output current. Available for 10 s at start, otherwise as long as allowed by drive
temperature.
2N
continuous rms current. 10% overload is typically allowed for one minute every 5 minutes.
PN
typical motor power. The power ratings apply to most 4-pole NEMA rated motors (230 V,
2hd
continuous rms current. 50% overload is typically allowed for one minute every 5 minutes.
P
hd
typical motor power. The power ratings apply to most 4-pole NEMA rated motors (230 V,
Note 1: The ratings apply at an ambient temperature of 40°C (104°F). At lower temperatures the
Technical data
107
The ratings of UL listed fuses for branch circuit protection are listed below. The fuses
also prevent damage to the adjoining equipment of the drive in case of a short-circuit
inside the drive. Check that the operating time of the fuse is below 0.1 seconds.
The operating time depends on the supply network impedance and the cross-
sectional area and length of the supply cable. The fuses must be of the non-time
delay type. See also Planning the electrical installation: Thermal overload and
short-circuit protection.
Note 1: In multicable installations, install only one fuse per phase (not one fuse per conductor).
Note 3: Fuses from other manufacturers can be used if they meet the ratings.
ACS800-U31 type
Input
Fuse
ACS800-31 type
current
Three-phase supply voltage 380 V, 400 V, 415 V, 440 V, 460 V, 480 V or 500 V
Technical data
108
Cable types
Cable sizing is based on NEC Table 310-16 for copper wires, 75°C (167°F) wire insulation at 40°C
(104°F) ambient temperature. Not more than three current-carrying conductors in raceway or cable or
earth (directly buried). For other conditions, dimension the cables according to local safety regulations,
Max. load
Cable type
current
A
AWG/kcmil
31 10
44 8
57 6
75 4
88 3
101 2
114 1
132 1/0
154 2/0
176 3/0
202 4/0
Cable Entries
Input, DC link and motor cable (per phase) terminal sizes, accepted cable diameters
Frame size U1, V1, W1, U2, V2, W2, UDC+, UDC- Grounding PE
(UL type 1)
torque
torque
Technical data
109
Voltage (U
Prospective short-circuit
Maximum allowed prospective short-circuit current in the supply is 65 kA in a second
UL 508C)
US and Canada: The drive is suitable for use on a circuit capable of delivering not more
than 65 kA rms symmetrical amperes at the drive nominal voltage when protected by T
class fuses.
(cos phi1 )
Harmonic distortion Harmonics are below the limits defined in IEEE519 for all Isc/IL. Each individual harmonic
sc/I
Rsc
THD voltage (%) THD current (%)
20 4 4
100 0.8 5
50
I
⎛ --------------------
n
THD
= ∑
⎝ I
1 contmax
THD = Total Harmonic Distortion (THD). The voltage THD depends on the short-circuit
I
th
n = n
harmonic component
sc = R
sce = I
sc/I
Technical data
110
Motor connection
Voltage (U
2) 0 to U
1 , 3-phase symmetrical, U
Nmains
fwp =
· f
Nmotor
U
Nmotor
U
Nmotor: rated motor voltage; f
Nmotor: rated motor frequency
Maximum recommended
300 m (984 ft). Additional restriction for units with EMC filtering (type code selections
Efficiency
Cooling
Degrees of protection
IP20 (UL type open) and IP21 (UL type 1). IPXXD from above.
Without front cover, the unit must be protected against contact according to IP2x [see
chapter Electrical installation: Cabinet installed units (IP 00, UL type open)].
AGPS-11C
Technical data
111
Ambient conditions
Environmental limits for the drive are given below. The drive is to be used in a heated,
Operation
Storage
Transportation
Derating]
Derating.
corrosive gases.
Contamination levels
No conductive dust allowed.
2, IEC 60721-3-1)
Chemical gases: Class 3C2
Chemical gases: Class 1C2
Chemical gases: Class 2C2
(5 to 13.2 Hz),
(5 to 13.2 Hz),
(2 to 9 Hz),
2
2
2
2
2
2
max. 7 m/s
(23 ft/s
)
max. 7 m/s
(23 ft/s
)
max. 15 m/s
(49 ft/s
)
2
2
2
2
11 ms
11 ms
Technical data
112
Materials
Drive enclosure PC/ABS 2.5 mm, colour NCS 1502-Y (RAL 90021 / PMS 420 C)
hot-dip zinc coated steel sheet 1.5 to 2 mm, thickness of coating 100 micrometres
Disposal The drive contains raw materials that should be recycled to preserve energy and natural
resources. The package materials are environmentally compatible and recyclable. All
metal parts can be recycled. The plastic parts can either be recycled or burned under
controlled circumstances, according to local regulations. Most recyclable parts are marked
If recycling is not feasible, all parts excluding electrolytic capacitors and printed circuit
boards can be landfilled. The DC capacitors (C1-1 to C1-x) contain electrolyte and the
printed circuit boards contain lead, both of which are classified as hazardous waste within
the EU. They must be removed and handled according to local regulations.
For further information on environmental aspects and more detailed recycling instructions,
Applicable standards
The drive complies with the following standards. The compliance with the European Low
EN 60204-1 (1997) Safety of machinery. Electrical equipment of machines. Part 1: General requirements.
Provisions for compliance: The final assembler of the machine is responsible for installing
- an emergency-stop device
EN 60529: 1991
Degrees of protection provided by enclosures (IP code)
(IEC 60529)
IEC 60664-1 (1992) Insulation coordination for equipment within low-voltage systems. Part 1: Principles,
EN 61800-3 (2004) Adjustable speed electrical power drive systems. Part 3: EMC requirements and specific
test methods
NEMA 250 (2003) Enclosures for Electrical Equipment (1000 Volts Maximum)
Technical data
113
CE marking
A CE mark is attached to the drive to verify that the unit follows the provisions of the European Low
Voltage and EMC Directives (Directive 73/23/EEC, as amended by 93/68/EEC and Directive 89/336/
Definitions
operate without problems within an electromagnetic environment. Likewise, the equipment must not
disturb or interfere with any other product or system within its locality.
First environment includes establishments connected to a low-voltage network which supplies buildings
Second environment includes establishments connected to a network not supplying domestic premises.
Drive of category C2: drive of rated voltage less than 1000 V and intended to be installed and
commissioned only by a professional when used in the first environment. Note: A professional is a
person or organisation having necessary skills in installing and/or commissioning power drive systems,
Drive of category C3: drive of rated voltage less than 1000 V and intended for use in the second
Drive of category C4: drive of rated voltage equal to or above 1000 V, or rated current equal to or above
The EMC Directive defines the requirements for immunity and emissions of electrical equipment used
within the European Union. The EMC product standard [EN 61800-3 (2004)] covers requirements
The drive complies with the standard with the following provisions:
2. The motor and control cables are selected as specified in the Hardware Manual.
3. The drive is installed according to the instructions given in the Hardware Manual.
WARNING! The drive may cause radio interference if used in a residential or domestic environment.
The user is required to take measures to prevent interference, in addition to the requirements for CE
Note: It is not allowed to install a drive equipped with EMC filter +E202 on IT (unearthed) systems. The
supply network becomes connected to earth potential through the EMC filter capacitors which may
Technical data
114
The drive complies with the standard with the following provisions:
1. The drive is equipped with EMC filter +E200. See also page 60.
2. The motor and control cables are selected as specified in the Hardware Manual.
3. The drive is installed according to the instructions given in the Hardware Manual.
WARNING! A drive of category C3 is not intended to be used on a low-voltage public network which
supplies domestic premises. Radio frequency interference is expected if the drive is used on such a
network.
If the provisions under Second environment (drive of category C3) cannot be met, e.g. the drive cannot
be equipped with EMC filter +E200 when installed to an IT (unearthed) network, the requirements of the
some cases, the inherent suppression in transformers and cables is sufficient. If in doubt, a supply
transformer with static screening between the primary and secondary windings can be used.
Supply transformer
Neighbouring network
Static screen
Point of measurement
Low voltage
Low voltage
Equipment
Drive
(victim)
Equipment
Equipment
2. An EMC plan for preventing disturbances is drawn up for the installation. A template is available
3. The motor and control cables are selected as specified in the Hardware Manual.
4. The drive is installed according to the instructions given in the Hardware Manual.
WARNING! A drive of category C4 is not intended to be used on a low-voltage public network which
supplies domestic premises. Radio frequency interference is expected if the drive is used on such a
network.
Machinery Directive
The drive complies with the European Union Machinery Directive (98/37/EC) requirements for an
Technical data
115
C-tick marking
C-tick marking is required in Australia and New Zealand. A C-tick mark is attached to each drive in
order to verify compliance with the relevant standard (IEC 61800-3 (2004) Adjustable speed electrical
power drive systems. Part 3: EMC requirements and specific test methods), mandated by the Trans-
Definitions
operate without problems within an electromagnetic environment. Likewise, the equipment must not
disturb or interfere with any other product or system within its locality.
The Trans-Tasman Electromagnetic Compatibility Scheme (EMCS) was introduced by the Australian
Communication Authority (ACA) and the Radio Spectrum Management Group (RSM) of the New
Zealand Ministry of Economic Development (NZMED) in November 2001. The aim of the scheme is to
protect the radiofrequency spectrum by introducing technical limits for emission from electrical/
electronic products.
First environment includes establishments connected to a low-voltage network which supplies buildings
Second environment includes establishments connected to a network not supplying domestic premises.
Drive of category C2: drive of rated voltage less than 1000 V and intended to be installed and
commissioned only by a professional when used in the first environment. Note: A professional is a
person or organisation having necessary skills in installing and/or commissioning power drive systems,
Drive of category C3: drive of rated voltage less than 1000 V and intended for use in the second
Drive of category C4: drive of rated voltage equal to or above 1000 V, or rated current equal to or above
The drive complies with the limits of IEC 61800-3 with the following provisions:
2. The drive is installed according to the instructions given in the Hardware Manual.
3. The motor and control cables used are selected as specified in the Hardware Manual.
Note: The drive must not be equipped with EMC filter +E202 when installed to IT (unearthed) systems.
The mains becomes connected to earth potential through the EMC filter capacitors. In IT systems this
Technical data
116
The drive complies with the standard with the following provisions:
1. The drive is equipped with EMC filter +E200. See also page 60.
2. The motor and control cables are selected as specified in the Hardware Manual.
3. The drive is installed according to the instructions given in the Hardware Manual.
WARNING! A drive of category C3 is not intended to be used on a low-voltage public network which
supplies domestic premises. Radio frequency interference is expected if the drive is used on such a
network.
If the provisions under Second environment (drive of category C3) cannot be met, e.g. the drive cannot
be equipped with EMC filter +E200 when installed to an IT (unearthed) network, the requirements of the
some cases, the inherent suppression in transformers and cables is sufficient. If in doubt, a supply
transformer with static screening between the primary and secondary windings can be used.
Supply transformer
Neighbouring network
Static screen
Point of measurement
Low voltage
Low voltage
Equipment
Drive
(victim)
Equipment
Equipment
2. An EMC plan for preventing disturbances is drawn up for the installation. A template is available
3. The motor and control cables are selected as specified in the Hardware Manual.
4. The drive is installed according to the instructions given in the Hardware Manual.
WARNING! A drive of category C4 is not intended to be used on a low-voltage public network which
supplies domestic premises. Radio frequency interference is expected if the drive is used on such a
network.
Technical data
117
UL/CSA markings
The ACS800-U31 and ACS800-31 are C-UL US listed. CSA marking is pending.
UL
The drive is suitable for use on a circuit capable of delivering not more than 65 kA rms symmetrical
amperes at the drive nominal voltage (600 V maximum for 690 V units) when protected by T class
fuses.
The drive provides overload protection in accordance with the National Electrical Code (US). See
ACS800 Firmware Manual for setting. Default setting is off, must be activated at start-up.
The drives are to be used in a heated indoor controlled environment. See section Ambient conditions
The manufacturer warrants the equipment supplied against defects in design, materials and
workmanship for a period of twelve (12) months after installation or twenty-four (24) months from date
of manufacturing, whichever first occurs. The local ABB office or distributor may grant a warranty period
different to the above and refer to local terms of liability as defined in the supply contract.
any costs resulting from a failure if the installation, commissioning, repair, alternation, or ambient
conditions of the drive do not fulfil the requirements specified in the documentation delivered with
In no event shall the manufacturer, its suppliers or subcontractors be liable for special, indirect,
This is the sole and exclusive warranty given by the manufacturer with respect to the equipment and is
in lieu of and excludes all other warranties, express or implied, arising by operation of law or otherwise,
including, but not limited to, any implied warranties of merchantability or fitness for a particular purpose.
If you have any questions concerning your ABB drive, please contact the local distributor or ABB office.
The technical data, information and specifications are valid at the time of printing. The manufacturer
Technical data
118
Technical data
119
Dimensional drawings
Dimensional drawings
120
US gland/conduit plate
Dimensional drawings
gland plate.
Frame size R5 (IP21, UL type open, UL type 1)
68406200 A
US gland/conduit
plate
Diameters of knock-
UL type 1 when
US gland plate.
Frame size R6 (IP21, UL type open, UL type 1)
68405726 A
Dimensional drawings
121
122
Dimensional drawings
123
Resistor braking
This chapter describes how to select, protect and wire external brake choppers and
resistors for the drive. The chapter also contains installation instructions and the
technical data.
[3AFY58920541 (English)].
WARNING! Never use a brake resistor with a resistance below the value specified
for the particular drive / brake chopper / resistor combination. The drive and the
chopper are not able to handle the overcurrent caused by the low resistance.
Resistor braking
124
The nominal ratings for dimensioning the brake resistors for the ACS800-31 and
ACS800-31
Chopper
Brake resistor Cable Pbrmax
Degree of protection
ACS800-U31
type
Type R E
R
Rcont
No. of
P
Chopper Resistor
type
elements
2
ohm kJ kW mm
kW
Three-phase supply voltage 380 V, 400 V, 415 V, 440 V, 460 V, 480 V or 500 V
00184674 E
R Resistance value for the listed resistor assembly. Note: This is also the minimum allowed resistance for the brake resistor.
R
Short energy pulse that the resistor assembly withstands every 400 seconds. This energy will heat the resistor element from 40 °C
Rcont
Continuous power (heat) dissipation of the resistor when placed correctly. Energy E
P
R dissipates in 400 seconds.
brmax
Maximum braking power of the drive equipped with the standard chopper and resistor. The drive and the chopper will withstand this
braking power for one minute every ten minutes. Note: The braking energy transmitted to the resistor during any period
All braking choppers and resistors must be installed outside the converter module. Note: The SACE and SAFUR resistors are not UL
listed.
Resistor braking
125
The installation instructions for the chopper and resistor are given in NBRA-6xx
choppers and resistors must be installed outside the drive module in a place where
WARNING! The materials near the brake resistor must be non-flammable. The
surface temperature of the resistor is high. Air flowing from the resistor is hundreds
Use the cable type used for drive input cabling (refer to chapter Technical data) to
ensure the input fuses will also protect the resistor cable. Alternatively, two-
conductor shielded cable with the same cross-sectional area can be used. The
Protection
It is highly recommended to equip the drive with a main contactor for safety reasons.
Wire the contactor so that it opens in case the resistor overheats. This is essential
for safety since the drive will not otherwise be able to interrupt the main supply if the
L1 L2 L3
OFF
Fuses
2
1
3
5
13
3
ON
2
4
6
14
4
ACS800
U1 V1 W1
Θ
Thermal switch (standard
in ABB resistors)
K1
Resistor braking
126
Frame size R6: Check the setting of parameter 21.09. If stop by coasting is
For the use of the brake resistor overload protection (parameters 27.02...27.05),
WARNING! If the drive is equipped with a brake chopper but the chopper is not
enabled by parameter setting, the brake resistor must be disconnected because the
WARNING! Parameter 95.07 LCU DC REF (V) must be set to the minimum value
(default) with brake resistors. Otherwise energy from the supply network can flow to
the brake resistor causing overheating of the resistor and damage to the equipment.
For settings of other application programs, see the appropriate firmware manual.
Resistor braking
127
This chapter describes how to connect an external +24 V power supply for the RMIO
boards of the motor-side and line-side converters via terminal X34. For current
consumption of the RMIO board, see chapter Motor control and I/O board (RMIO).
Note: For the motor-side converter RMIO board, external power is easier to supply
via terminal X23, see chapter Motor control and I/O board (RMIO).
Parameter settings
External +24 V power supply for the RMIO boards via terminal X34
128
1. Break off the tab covering the +24 VDC power input connector with pliers.
3. Disconnect the wires from the connector (keep the connector for later use).
7. Connect the wires of the +24 V external power supply to the disconnected
connector:
X34
4
4
External +24 V power supply for the RMIO boards via terminal X34
129
RMIO board
1
2
3
X34
+
-
7
8
1
2
Connection of a two-way
connector
RMIO board
1
2
3
X34
+
-
1
2
3
Connection of a three-way
connector
External +24 V power supply for the RMIO boards via terminal X34
130
Frame size R5
The location of terminal X34 in the line-side converter is shown below. Connect the
Terminal X34
Frame size R6
1. Remove the top cover by releasing the retaining clip with a screw driver and
and disconnecting the fibre optic cables. Disconnect other optional modules if
present.
4. Disconnect the additional fan cable (detachable terminal) and release the strain
relief.
External +24 V power supply for the RMIO boards via terminal X34
131
10. Connect the external +24 V supply to the board as described in steps 2 to 5, 7
11. Reconnect all disconnected cables and fasten the covers in reverse order.
6
2
5 5 5
7
7
External +24 V power supply for the RMIO boards via terminal X34
132
External +24 V power supply for the RMIO boards via terminal X34
3AFE68599954 Rev A EN
EFFECTIVE: 14.10.2005
ABB Oy
ABB Inc.
AC Drives
Automation Technologies
FI-00381 HELSINKI
16250 West Glendale Drive
FINLAND
New Berlin, WI 53151
Telephone +358 10 22 11
USA
Internet http://www.abb.com
800-HELP-365