0% found this document useful (0 votes)
337 views5 pages

WP-004 ICCP Inspection

The document provides procedures for inspecting an impressed current cathodic protection system at a gas transportation facility in Indonesia. It outlines responsibilities, equipment, and a 5-step procedure to test the transformer rectifier, junction boxes, and pipe-to-soil potentials at test points. Measurements will be taken of voltages, currents, and potentials which will be evaluated against criteria to check performance and ensure adequate corrosion protection.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
337 views5 pages

WP-004 ICCP Inspection

The document provides procedures for inspecting an impressed current cathodic protection system at a gas transportation facility in Indonesia. It outlines responsibilities, equipment, and a 5-step procedure to test the transformer rectifier, junction boxes, and pipe-to-soil potentials at test points. Measurements will be taken of voltages, currents, and potentials which will be evaluated against criteria to check performance and ensure adequate corrosion protection.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
You are on page 1/ 5

PT.

TRANSPORTASI GAS INDONESIA


(1SVC-028315)
DOCUMENT NO:

TGI-FIMS-WP-004-A4

PT BONNE INDOTEKNIK

PAGE 1 OF 5

FACILITY INTEGRITY MANAGEMENT SYSTEM

IMPRESSED CURRENT CATHODIC PROTECTION INSPECTION PROCEDURE

Approved

Approved With Comment

Resubmit For Approval

Reviewed (Not For Approval)

Reviewed With Comment


NOTES:
APPROVAL OF THIS DOCUMENT WILL NOT RELIEVE
CONTRACTOR FROM ITS OBLIGATION TO COMPLETE
ALL THE WORK IN ACCORDANCE WITH THE TERMS AND
CONDITIONS OF THE CONTRACT

TGI-ENG TGI-PA TGI-PM

Etc.

1
B

A 19 AUG 2013 ISSUED FOR REVIEW AN AM DT

Prepared Reviewed Approved


Rev. Date Description
PT BONNE INDOTEKNIK

TABLE OF CONTENT

Page

1. Introduction 3

2. Reference 3

3. Equipment 3

4. Responsibilities 3

5. Procedure. 4
5.1 Cathodic Protection Criteria 4
5.2 Transformer Rectifier (TR) 4
5.3 Junction Box 5
5.4 Test Point 5

2
1. Introduction

The purpose of this inspection is to determine the performance of Impressed


Current Cathodic Protection (ICCP) at PT. TGI Jabung Station facility.

2. Reference
Ref 1 ISO 15589-1 Petroleum and natural gas industries –
CathodicProetction of pipeline transportation systems
– Part 1: On-land pipelines.
Ref 1 NACE TM-0497 Measurement Techniques Related to Criteria of
Cathodic Protection on Underground and Submerged
Piping System
Ref 1 NACE SP-0207 Performing Close-Interval Potential Survey and DC
Surface Potential Gradient Surveys on Buried or
Submerged Metallic Pipelines
Ref 1 NACE SP-0502 Pipeline External Corrosion Direct Assessment
Methodology.
Ref 1 NACE, RP 0286 Electrical isolation of cathodically protected pipelines.
Ref 1 John MORGAN Cathodic Protection
Ref 1 NACE Corrosion Engineer’s Reference Book, Third Edition
Ref 1 NACE Course CP-2 Cathodic Protection Technician Course Manual.
Ref 1 A.W. Peabody Control of Pipeline Corrosion (Houston, TX: NACE,
1967).
3. Equipment
 Multimeter (1 m VDC to 40 VDC)
 Clamp Amperemeter
 Copper-Copper Sulfate reference electrode
 High-voltage resistance meter
 Current interrupter
 Test Wire
 Hand Tools

4. Responsibilities

4.1 Corrosion Engineer


 Set-up the program of ICCP test
 Review the result
4.2 Corrosion Technician
 Arrange site works based on program set by Corrosion Engineer
 Ensure the instrument is valid for operation
 Compile data potential measurement and prepare report to
Corrosion Engineer
 Prepare the equipment
 Perform ICCP test

3
5. Procedure.
5.1 Cathodic Protection Criteria

NACE Standard Practice SP-0169-2007, address criteria for cathodic protection of


underground pipelines. Applicable excerpts from these criteria, which will be
used during inspection of cathodic protection system, are as follows:

 A negative (cathodic ) potential of at least 850 mV with the cathodic


protection applied. This potential is measured with respect to a saturated
copper/ copper sulfate reference electrode contacting the electrolyte.
Voltage drops other than those across the structure-to electrolyte
boundary must be considered for valid interpretation of this voltage
measurement.
 A negative polarized potential of at least 850 mV relative to a saturated
copper/ copper sulfate reference electrode.
 A minimum of 100 mV of cathodic protection polarization between the
structure surface and stable reference electrode contacting the
electrolyte. The formation or decay of polarization can be measured to
satisfy this criterion.
To avoid detrimental effects on the applied coating by cathodicdisbonding or
hydrogen induced stress cracking on steel, the potential shall not exceed a too
negative potential. This overprotection potential may vary from –1.2 V/Cu-CuSO 4 for
a low carbon steel pipe in an aerated soil to –1.0 V/Cu-CuSO 4 for an high strength
steel pipe.
These values of potential have to be measured as close as possible from the “true”
values, correcting the error due to the ohmic drop in the soil.

5.2 Transformer Rectifier (TR)

 Ensure that the transformer rectifier is secured to the bracket mounting and
the enclosure is properly grounded.
 Verify that the polarity of the DC circuit is correct, positive terminal to the
anode and negative terminal to the structure.
 Verify that proper AC power rating is supplied to the transformer rectifier.
 Check that the AC input and DC output terminal is mechanically strong and
electrically conductive.
 Adjust the DC output setting to its minimum output.
 Ensure that the AC circuit breaker is in off position.
 Record the serial no. and model of the transformer rectifier.
 Perform a comprehensive check to the input voltage and record the
measurement result
 Perform a comprehensive check to all connection, jumper, and fuses
prior energizing the power to this unit
 Ensure all components are held tight to the panel

4
 Cover the main fuse at input power at MCCB/Switch/ Breaker
 Energize the transformer rectifier following the procedure as
mentioned in manual book
 Record the DC current and DC voltage resulted

5.3 Junction Box

 Ensure that all cable connections are mechanically strong and electrically
conductive.
 Ensure that all cables are tagged properly.
 Ensure that the boxes are properly grounded.
 After Transformer Rectifier is re-energized, check the DC current
output in each Junction Box
 Record the DC current output on anode ground bed using DC clamp
meter or from measuring shunt inside Positive Junction Box
 Record the DC current output on negative cable using DC clamp meter
or from shunt inside Negative Junction Box

5.4 Test Point


 Ensure that all cable connections are mechanically strong and electrically
conductive.
 Measured and record the native potential at each test point when
transformer rectifier in off position, prior to re-energizing the cathodic
protection system.
 Check pipe-to-soil potential at all Test Point and other accessible location
after cathodic protection system is re-energized

You might also like