”Weatherproof“ for outdoor installation
KF 0404 B
1.5-4 mm², Cu 3~
terminal with 2 clamping units per pole
5-pole per pole 8 x 1,5 mm² r / f, 6 x 2,5 mm² r / f, 4 x 4 mm² r / f, 2 x 6 mm² r / f
cable entries via knockouts, order ASS separately (see cable entry systems LES)
"weatherproof" resistant to weather influences (UV due to solar radiation, protected against rainwater, temperature resistant,
impact resistant, etc.)
saltwater-proof
"offshore applications"
lid fasteners sealable without accessories
retaining strap and external brackets for wall fixing included
colour: black, RAL 9011
rated insulation voltage Ui = 690 V a.c./d.c.
rated current: 32 A
material PC-GFS (polycarbonate)
degree of protection IP 66 / IP 67 / IP 69
IP 67, temporary submersion
IP 69, water pressure max. 100 bar, water temperature max. 80
°C, distance ≥ 0.15 m
width 104 mm
height 104 mm
depth 70 mm
weight 0,17 kg
tightening torque for terminal 0.7 Nm
in accordance with IEC 60670-22
in accordance with DNV GL - Certificate No: TAE00000EE
Russian Maritime Register of Shipping, technical documentation is
approved by the letter No. 250-A-1180-108795
Drawings
Dimension drawing
Page 1 of 3
Gustav Hensel GmbH & Co. KG * Gustav-Hensel-Str. 6 * 57368 Lennestadt * Germany * Telefon: +49 (0)2723/609-0 * Fax: +49 (0)2723/60052 * Date: March 27. 2020
”Weatherproof“ for outdoor installation
KF 0404 B
1.5-4 mm², Cu 3~
Detail mass
Box walls
Operating and ambient conditions
Application area Suitable for for outdoor installation (harsh environment and/or
outdoor).
To reduce the formation and accumulation of condensed water see
technical information.
Resistant to occasional cleaning procedures (direct jet) Resistance to occasional cleaning procedures (direct jet) with high-
pressure cleaner without cleaning additives, water pressure: max
100 bar, water temperature: max 80 °C, distance ≥ 0.15 m, in
accordance with DIN EN 60529:2014-09 (IEC 60529:2013) = IP 69.
Only with cable entries HENSEL AKM or ASS.
Ambient temperature Average value over 24 hours + 55 °C
Maximum value + 70 °C
Minimum value - 25 °C
Relative humidity 50% at 40° C
short-time
100% at 25° C
Fire protection in the event of internal faults Demands placed on electrical devices from standards and laws
Minimum requirements
Page 2 of 3
Gustav Hensel GmbH & Co. KG * Gustav-Hensel-Str. 6 * 57368 Lennestadt * Germany * Telefon: +49 (0)2723/609-0 * Fax: +49 (0)2723/60052 * Date: March 27. 2020
”Weatherproof“ for outdoor installation
KF 0404 B
1.5-4 mm², Cu 3~
- Glow wire test in accordance with IEC 60695-2-11:
- 650°C for boxes and cable glands
- 850°C for parts of insulating material necessary to retain current
carrying parts in position
Burning behaviour Glow wire test IEC 60695-2-11: 960 °C
UL Subject 94: V-0
flame-retardant
self-extinguishing
Degree of protection against mechanical load IK09 (10 Joule)
Toxic behaviour halogen-free
silicone-free
"halogen-free" in accordance with the examination of the cables
and insulated wires - corrosiveness of fumes - as per IEC 60754-2
Note: For material properties see technical data.
Page 3 of 3
Gustav Hensel GmbH & Co. KG * Gustav-Hensel-Str. 6 * 57368 Lennestadt * Germany * Telefon: +49 (0)2723/609-0 * Fax: +49 (0)2723/60052 * Date: March 27. 2020