VERTICAL FORCES CAUSE VIBRATION IN A RECIPROCATING COMPRESSOR
Brian C. Howes, M.Sc., P.Eng.                          Valerie A. Zacharias, M.A.
ABSTRACT                                                  of the forces from all of the crossheads is zero.
                                                          Such an analysis can be misleading.
It is well known that forces that cause vibrations in     This paper describes the origin of these forces,
reciprocating compressors arise from a number of          discusses their practical implications, and presents
sources. These include unbalanced reciprocating           examples.
forces and moments, piping system pulsations, and
cylinder stretch. Reliable and efficient reciprocating    INTRODUCTION
compressor installations will result from including the
effects of all forces in the design calculations.         Recent field trouble-shooting experiences have
                                                          shown severe vertical vibration problems in certain
Evidence from field trouble-shooting indicates that       reciprocating compressor installations. The severity
force mechanisms operating in the vertical direction      of these vibration problems was made worse by the
in horizontal cylinder assemblies can cause               presence of mechanical resonance.
significant vibration. Therefore, a design that
ignores these potential sources of vibration              In the first case, lack of attention by the designers to
problems (as is common) may be inadequate.                the potential for large vertical shaking forces
                                                          between cylinders and pulsation dampener bottles
One such vertical force is caused by pressure             aggravated the problem.
pulsations acting on the suction and discharge
cylinder nozzle areas and bottles. While the nozzle       In the second case, vertical forces acting through
areas are generally equal, the differing pulsation        the crosshead guides appear to have contributed to
amplitudes and phases result in net vertical forces       high vibrations.
on the cylinder. This paper presents a proposal for
enhancing the API 618 guideline for pulsation             PRESSURE PULSATION GUIDELINES
control in reciprocating compressors. Currently, the
compressor side guideline is higher than the line         The shaded areas on each graph (Fig. 2 – 7)
side guideline and disregards frequency. The              indicate acceptable pulsations based on the
proposed guideline incorporates frequency and adds        American Petroleum Institute standard (API 618).
a limit based on vertical shaking forces that could be
generated in a cylinder.                                  Compressor Side
A second vertical force in a horizontal cylinder          The time domain curves show the compressor side
assembly arises because the connecting rod motion         pulsation limit (CPL), which shall be the lesser of
is not purely horizontal. The slider-crank mechanism
generates a time-varying force perpendicular to the          7% of average absolute line pressure, OR
motion of the piston through the crosshead guide.
Which varies with the crankshaft angle, the l/r              3R% of average absolute line pressure, where R
(connecting rod to crankshaft pin radius) ratio, the          is stage compression ratio.
gas forces, and the reciprocating inertia. These
vertical crosshead forces are sometimes contained         The purpose of the CPL is to avoid pressure-volume
by the foundation, but in some applications the           curve distortion. It does not address concerns about
stiffness under the crosshead guide is too low, and       vibration or compressor valve life.
high vibrations result. In many cases, a rigid body
analysis of these forces shows that the vector sum
Vibration, Dynamics & Noise                                                                  www.BETAMachinery.com
                                                                                                                           2
Lineside                                                                     high vibrations were observed on the
                                                                              concrete pedestal under the outboard
The frequency domain curves show the API lineside                             cylinder support.
design pulsation limit (DPL):
                                                                      Measurements
                           P                                          Excessive rod loads were ruled out as a cause of the
DPL = 3●                                                              breakage, because rod loads during the tests were
                    ID  f                                            within or at the manufacturer’s guidelines.
Where DPL = maximum allowable peak to peak level                      Pulsations were measured in the time domain at the
of pulsation at discrete frequencies,                                 suction and discharge valve caps (Fig. 2 & 3).
P = average absolute line pressure,
ID = inside pipe diameter (inches),                                   Suction side pulsations were within the compressor
f = pulsation frequency (Hertz).                                      side guideline (CPL), while discharge side pulsations
The purpose of the DPL is to avoid high unbalanced                    were about 120% of the guideline.
forces due to pressure pulsations.
CASE 1 – SINGLE STAGE FOUR THROW
COMPRESSOR
The Problem
Two four throw compressors had been experiencing
failures of pistons and rods over some years. On a
visit to the site in February, 1994, the following
problems were found:
      cylinder supports were loose or broken
         discharge bottle wedge supports were
          broken
         joints had fretted, shown by red dust (iron
          oxide) present at most of the joints in the                 Figure 2 Suction side overall pulsation was within
          cylinder supports                                                    guideline.
         anchor bolts and grout under the crosshead
          guide had broken
Figure 1 Rod and piston failures over many years                      Figure 3 Discharge side overall pulsation was
         made this unit uneconomic to run.                                     about 120% of guideline.
PAPER Vertical Forces Cause Vibration in a Reciprocating Compressor                                    www.BETAMachinery.com
                                                                                                                               3
                                                                      Figure 6 The orifice plate significantly reduced
Figure 4 As-found spectrum on the suction side                                 pulsation levels.
         shows high pulsation at 7X shaft speed.
                                                                      Modifications to the System
A spectrum of the as-found suction valve cap
pulsation is shown in Fig. 4, and of the discharge                    As-left readings (Fig. 6 & 7) were taken after orifice
valve cap pulsation in Fig.5.                                         plates were installed in both the suction and
                                                                      discharge nozzles. As shown in Fig. 7, the as-left
The DPL is included as a reference in each plot,                      pulsation at the seventh order on the discharge side
since there is currently no recognized pulsation limit                still exceeded the line side guideline by about 3X,
based on discrete frequencies for the compressor                      even though it was only about 20% of the as-found
side piping. In both cases, the DPL has been greatly                  reading.
exceeded at seven times crankshaft speed (7X).
                                                                      Three years later, the compressor is still working
                                                                      well.
Figure 5 As-found spectrum on the discharge side
         shows pulsation at 7X shaft speed is                         Figure 7 The orifice reduced pulsation at 7X to
         about 15 X DPL.                                                       about 20% of as-found; still three times
                                                                               DPL.
PAPER Vertical Forces Cause Vibration in a Reciprocating Compressor                                     www.BETAMachinery.com
                                                                                                                               4
                                                                      Figure 9 The maximum unbalanced force occurs
                                                                               when pipe length equals half wave length.
Figure 8 Vertical forces due to pulsation can                         Note that over the short length between the cylinder
         develop between the cylinder and the                         and the bottle, there is very little change in pressure
         bottle.                                                      amplitude at low frequencies (Fig. 9). The
                                                                      unbalanced force generated in short pipe runs by
Vertical Forces Between Bottle and Cylinder                           pressure pulsations at low orders of run speed (long
                                                                      wave lengths) will be much lower than at higher
Figure 8 shows a cross-section of the suction and                     orders, all other things being equal.
discharge bottles and cylinder on one side of the
machine. The standing wave pattern of the pressure                    Proposal for Additional API 618 Guideline
pulsation carries from the valves through the cylinder
gas passages and the cylinder nozzle into the bottle,                 That proposed guideline prevents design conflicts
on each side of the cylinder. There is no direct                      that arise between the CPL and the DPL in the piping
connection between the two standing waves,                            between the bottles and the cylinder.
because the suction and discharge valves are never
open at the same time.                                                In Beta’s experience, the DPL is too restrictive to be
                                                                      applied to the piping between the bottles and the
There is a difference between the amplitude and                       cylinders. It is generally acceptable to have low
phase of the pulsation at different points on the                     frequency (long wave length) cylinder side pressure
standing wave.                                                        pulsations that meet CPL but exceed DPL. If the
                                                                      DPL were applied, unnecessary and uneconomic
Varying pressure acting on an area produces a                         design changes would be required in many cases.
varying force. In the vertical direction, the areas of
concern are the projected areas of the inside                         Pressure pulsations by themselves do not shake the
diameters of the suction and discharge nozzles (Fig.                  compressor. It is the forces generated because of
8) on the bottle and the cylinder passages.                           pulsations that cause vibration problems. For this
                                                                      reason, we propose that compressor designs should
A computer model was used to predict pulsations,                      limit potential transverse (vertical in horizontal
and the model was verified with field measurements                    cylinders, horizontal in vertical cylinders) unbalanced
(Figs. 5 – 7). The worst vertical forces in the                       forces, not just pulsations. This force guideline is a
discharge nozzles were calculated to be about 7000                    compromise between ignoring the transverse forces
pounds peak to peak (pk – pk) and in the suction                      on the compressor side of the pulsation bottle and
nozzles about 1100 pounds pk – pk) and in the                         using the more restrictive (and likely uneconomic)
suction nozzles about 1100 pounds pk – pk, both at                    DPL guideline. It should be used with the CPL.
the seventh order. It is clear that these forces are
sufficient to cause the problems found.
PAPER Vertical Forces Cause Vibration in a Reciprocating Compressor                                     www.BETAMachinery.com
                                                                                                                            5
Unbalanced Force Guideline
                                                                      CASE 2 – SINGLE STAGE, SIX THROW
Unbalanced forces are calculated according to the                     COMPRESSORS
equation below, (where the pressures are vectors).
                                                                      The three units (Fig. 11) are large variable speed
Force = (area 1 x pressure 1) – (area 2 x pressure 2)                 horizontal compressors, mounted on skids bolted to
                                                                      3 ft. thick concrete foundation blocks. The
On the basis of empirical studies, the following                      foundation blocks are embedded into the sandy soil.
staged unbalanced force guidelines are proposed:                      No piles were used.
    Avoid coincidence between the vertical
     mechanical natural frequency of the cylinder
     bottle system and any peaks in the vertical
     unbalanced force spectra.
    Limit unbalanced forces in the cylinder nozzles at
     any discrete frequency as follows:
     1) the lesser of 500 lbs. Or 50 X nominal
     diameter (inches) maximum pk – pk on either the
     suction or the discharge side.
     2) if 1) is exceeded, the arithmetic sum of the
     suction and discharge forces should be less than
     1000 lbs. Or 100 X nominal diameter pk pk.
     3) If 2) is exceeded, the vector sum of suction                  Figure 11 Elevation view, with operating deflected
     and discharge forces should be less than 1000                              shapes (ODS) at resonance.
     lbs or 100 X nominal diameter pk – pk.
    If 3) is exceeded, the forces must be reduced.                   The Problem
To illustrate, one can calculate from the equation in                 The units are equipped with vibration sensors, which
Fig. 9 the allowable pulsations for a particular                      indicated excessive vibration. Supporting the exciter
system, as shown in Fig. 10. The CPL is too high to                   to the foundation had not helped.
control vibration; the DPL is too stringent.
                                                                      Measurements
                                                                      The highest vibration occurs near the top of the
                                                                      speed range at twice shaft speed in the vertical
                                                                      direction outboard on the exciter.
                                                                      The foundation exhibits a resonance near the top of
                                                                      the runspeed range. The modal damping of the
                                                                      foundation was estimated from vibration
                                                                      measurements to be about 3% of critical damping.
                                                                      The foundation vertical vibrations had node points
                                                                      located at the mid points of the motor and the
                                                                      compressor.
                                                                      Operating deflections (Fig. 11) showed that the
                                                                      exciter was amplifying the motion of the motor-
Figure 10 The proposed frequency-based
                                                                      compressor-foundation system due to geometry
          compressor side pulsation limit is a
                                                                      effects.
          compromise.
PAPER Vertical Forces Cause Vibration in a Reciprocating Compressor                                    www.BETAMachinery.com
                                                                                                                            6
Vibrations were not significantly different between
loaded and bypass conditions. Therefore, pulsations
were ruled out as a cause of the problem.
The shaft alignment of the unit was checked and
found to be acceptable. A small improvement in
alignment had no effect on vibration levels.
Modelling of the System
The motor-compressor-skid system had been
modelled in the design stage. The foundations had
been assumed to be rigid, an assumption which
proved to be incorrect.
A new finite element model of the system was                          Figure 12 Slider-crank mechanism generates
created following start-up, and after the problem had                           vertical force.
been identified. Using the model to test the effect of
changes showed that the skid-foundation resonance
is very hard to change without major modifications.
Modelling proved to be very valuable in the sense
that it indicated that doing a major change that made
intuitive sense would not have worked. The skid has
a weak shear connection to the concrete. It seemed
obvious that a continuous grout connection between
skid and concrete would stiffen the system, raise the
natural frequency, and solve the problem.
The model quickly showed that the stiffening effect of
the grout would be counteracted by moving the mass
of the motor and compressor farther away from the
neutral axis of motion. The rotational inertia of the
motor and compressor would be made more
influential on the mode, lowering the natural
                                                                      Figure 13 Substantial vertical forces are generated
frequency and counteracting the stiffening effect.
                                                                      by the motion of the crosshead
Analysis
                                                                      torsional mode about the centreline of the crankshaft
It was unclear what force could be present in the
                                                                      with a node in the middle of the compressor, the
system at 2X shaft speed that could cause such
                                                                      couple shown in Fig. 14 would have caused high
vibrations, even with the foundation resonance since
                                                                      vibration.
it was reasonably well damped.
                                                                      Upon reflection, it was realized that the offset
Figure 12 illustrates the source of vertical force at the
                                                                      between cylinders (Fig. 15) causes the forces in the
crosshead. Figure 13 shows the vertical force versus
                                                                      opposed pairs (e.g. throws 1 & 2 or 5 & 6) to produce
crank angle for this compressor at the cylinder 1
                                                                      another couple, this one about an axis parallel to
crosshead. These vertical forces were considered
                                                                      piston motion. If the foundation behaved as a rigid
and initially rejected as a source of the problem,
                                                                      body, the three couples from the three pairs of
since they are all equal in magnitude and vectorially
                                                                      throws would cancel.
cancel due to the phasing of the 6-throw crankshaft
(120 degrees between throws).
                                                                      In this case, the out-of-phase motion of the
                                                                      foundation at twice crankshaft speed allows the
Figure 14 shows how the crosshead forces can
                                                                      couples to excite the mode.
cause the compressor to rock. Had there been a
PAPER Vertical Forces Cause Vibration in a Reciprocating Compressor                                    www.BETAMachinery.com
                                                                                                                                          7
                                                                      SUMMARY
                                                                      Vertical forces in compressor cylinder-to-bottle
                                                                      nozzles need to be considered in the design stage.
                                                                      Since there is no suitable design guideline currently
                                                                      available for these forces, one is proposed.
                                                                      Slider crank mechanisms produce forces transverse
                                                                      to the crosshead guide or cylinder. These forces
                                                                      should be considered in the design of reciprocating
                                                                      machinery systems.
                                                                      FURTHER WORK
Figure 14 Crosshead forces produce a couple
          about the centreline of the crankshaft.                     Consideration should be given to enhancing the DPL
                                                                      guideline to include unbalanced forces, or even to
                                                                      replacing the DPL guideline with an unbalanced
                                                                      force guideline. In many instances, the DPL by itself
                                                                      is too strict or too lenient, depending on how the
                                                                      pulsations couple with the pipe lengths.
                                                                      REFERENCES
                                                                      Reciprocating Compressors for General Refinery
                                                                      Services. API Standard 618. Third Edition.
                                                                      American Petroleum Institute, Washington, 1986.
                                                                      Reciprocating Compressors for Petroleum, Chemical,
                                                                      & Gas Industry Services. API Standard 618. Fourth
                                                                      Edition. American Petroleum Institute, Washington,
Figure 15 Side view of compressor – offset                            1995.
cylinders generate moments.
                                                                      Reports 1440, 1453, 1510, 5167, Beta Machinery
                                                                      Analysis Ltd. Various dates.
Modification
                                                                      THE AUTHORS
The amplitude of the vibrations was reduced by 30%
                                                                      The two authors are employed by Beta Machinery Analysis Ltd.
by stiffening the connection of the motor end bells to                Brian Howes obtained his M.Sc. in Mechanical Engineering in
the skid, using jacking bolts. This modification did                  1972. His experience includes trouble-shooting on a wide variety
not change the frequency of the peak response. It                     of high end equipment, research and development in pulsation
appears that no complete solution is possible except                  and vibration of piping systems, and analysis of mechanical and
                                                                      structural systems so as to ensure acceptable static strength and
by changing the foundation natural frequency.                         dynamic response. He is Beta’s Chief Engineer.
Conclusions – Case 2                                                  Valerie Zacharias obtained her M.A. in Communications in 1978,
                                                                      and did a postgraduate year in Computer Science in 1979. Her
                                                                      experience includes acoustical modelling of reciprocating
The forces and moments in a reciprocating                             compressors, and ten years in the predictive maintenance
compressor do not necessarily cancel. In particular,                  business, primarily in customer service, training, and
when the unit is not mounted on a rigid body, modal                   communications. Mrs. Zacharias handles Customer Service.
excitation may result. Care must be taken when
designing compressor foundations to avoid natural
frequencies at one and two times crankshaft speed.
It is also clear that vertical forces at crossheads
should be considered when trouble-shooting
vibration problems in the field.
PAPER Vertical Forces Cause Vibration in a Reciprocating Compressor                                            www.BETAMachinery.com