Type COV Voltage Controlled Overcurrent Relay: ABB FL Descriptive Bulleti
Type COV Voltage Controlled Overcurrent Relay: ABB FL Descriptive Bulleti
Descriptive Bulleti n
Relay Division 41-165E
om
Coral Springs, FL
Allentown, PA Page 1
.c
Type COV
September, 1990 Device Number: 51/27
Supersedes DB 41-115, pages 1-8,
Voltage Controlled
dated February, 1988
Mailed to: E, 0, C/41-100A
Overcurrent Relay
ls
ua
an
tM
ar
lP
ca
tri
lec
.E
w
ww
Descriptive Bulletin
41-165E
om
Page 2
.c
App lica t ion in the air gap formed by the electromagnet Stationary Contact: Made of pure silver.
The COV relay provides back-up protection and the magnetic core. The electromagnet Will close 30 amperes at 250 volts dc. Has
for the generator and system from damage has two pairs of voltage coils. Each pair of sufficient wipe to assure positive contact. On
due to phase faults which are not cleared diametrically opposed coils is connected in double trip relays, adjustment of '!s.-inch
by primary relays and associated breakers. series. In addition, one pair is in series with contact follow or "wipe" is obtained by use
an adjustable resistor which provides the of a vernier adjusting screw on the stationary
It consists of a low-burden time-overcurrent necessary voltage drop-out adjustment, as contact plate.
ls
unit which is torque controlled by a high well as to shift the phase angle of one flux
speed cylinder-design voltage unit, and is with respect to the other in order to produce Moving Contact: Clamped to the insulated
applicable where it is desired to set the rotational torque of the cylinder. section of the induction disc shaft. Electrical
ua
overcurrent unit to operate on less than full connection is made through the spiral spring,
load current when the voltage decreases A spiral spring adjuster is located on the from the moving contact to the spring ad
below a predetermined value. underside of the supporting bridge and is juster frame, then to the relay terminal. Con
used to adjust the minimum setting of 80 volts. tacts will close 30 amperes at 250 volts dc.
Less than full load setting of the over-
current unit is required in vvercurrent pro Supporting Bridge: Houses the upper Damp in g Magnet: Made of high strength
an
tection of generators because the syn guide bearing of the moving element. Alnico. Controls operating time of the relay
chronous reactance of the machine limits
at low current values.
the fault current during sustained faults to Stationary Contact: Made of silver. Spring
about the same or less than rated load current. mounted within circular assembly to pro
Induction Disc: Spiral shaped to compen
vide adequate contact follow.
sate for spring wind-up throughout moving
Since the voltage and overcurrent units of
contact travel; provides accurate pickup at
tM
the COV relay are independently adjustable, Moving Contact: Also made of silver, and
any disc position.
the voltage controlled COV is preferable to attached to the molded hub of the moving
a voltage restrained type because of sim cylinder unit. The contact can be adjusted to
plified application and setting. The timing close over a range of 80 to 100 volts. It Spring Adjuster: Used to set the minimum
of a voltage restrained relay is affected by opens if the voltage is higher than the set trip current of the relay, and to provide in
bus voltage variation, making it difficult to value. Drop-out ratio is 98% of pickup, or between tap pickup adjustment when desired.
ar
coordinate with primary relays. higher.
(3) Indicating Contactor Switch (ICS)
Generator three-phase faults cannot be Adjustable Resistor: Provides adjustment of The dc Indicating Contactor Switch unit is a
detected by negative sequence current the voltage unit between 80 and 100 volts ac small clapper type device having a magnetic
relays. Hence, one type COV relay is recom (mounted on rear of relay chassis). armature to which leaf-spring mounted
lP
mended for generator back-up protection, in contacts are attached. The armature is at
conjunction with one type sao negative (2) Overcurrent Unit tracted to the core when the coil is energized
sequence current relay. If the sao is not Consists of an "E" shaped laminated core at or above pick-up value, causing the moving
used, three COV relays are required. which has a main tapped coil, and a shading contacts to bridge two stationary contacts,
coil on one of the outer legs to shift the flux completing the trip circuit. The ICS contacts
ca
out of phase.
Relay Type Time Curve This out-of-phase flux interacts with the
main coil flux to create a torque on the in
COV-6 Definite Minimum duction disc. Disc rotation is opposed by the
COV-7 Moderately Inverse
spiral spring which resets the contacts to
tri
COV-8 Inverse
COV-9 Very Inverse their normal position when applied current
COV-11 Extremely Inverse is below tap value setting.
Overcurrent Unit Tap Range (Amperes) Assures accurate and permanent alignment are connected in parallel with the main relay
0.5-2.5 2-6 4-12 of all components. contacts, and relieve them of carrying heavy
trip currents. The main relay contacts will
The relays may have either single or double Tap Blo ck : Indicates minimum current re close 30 amperes at 250 volts dc, and the ICS
circuit closing contacts for tripping either one quired to close relay contacts. contacts will safely carry this current long
or two circuit breakers. enough to trip a circuit breaker.
Tap Screw: Two supplied. When changing
.E
taps, the spare is inserted into the new tap The target is reset external to the case by a
Vo l t a ge Unit Volts (Line-to-Line)
position prior to removing the already inserted push rod located at the bottom of the relay
one from the old position. This prevents case cover.
The contact is adjustable over a range of 80
open-circuiting of the associated current
to 100 volts. The contact will open if the
transformers. (4) ICS Taps
voltage is higher than the set value. The
Taps on the front of the relay provide con
dropout ratio of the unit is 98% or higher.
Magnetic Plugs: May be threaded into or nection of the Indicating Contactor Switch
out of the magnetic circuit to control satura for either 0.2 (left) or 2.0 (right) ampere dc
w
C o nstr uct io n tion and adjust calibration at high currents. minimum pick-up setting.
(1) Vol ta ge Unit Time Dial: Indicates initial position of the When the protective relay energizes a WL
Induction cylinder type. The moving element moving contact over a 2600 range. It is relay rated 125 or 250 volts dc, the 0.2
ww
consists of a spiral spring, a contact carrying indexed from position V. (minimum time) to ampere is recommended. The 2.0 ampere
arm, and an aluminum cylinder which rotates position 11 (maximum time). tap is used on 24 or 48 volt dc circuits ener
gizing a WL relay.
September, 1990
Descriptive Bulletin
41-165E
om
Page 3
.c
ls
ua
1 )-----f
an
tM
ar
lP
ca
tri
lec
.E
w
ww
September, 1990
Descriptive Bulletin
41-165E
om
Page 4
.c
Time-Overcurrent Unit Coordination Typical Tripping Characteri sticsCD
Type COV back-up relays should use the
100 I
same operating time characteristics as the
------------,---------------------------
primary protective relays on the adjacent I
system should be used to assure selective cu
E
coordination.
o
z
ls
A minimum coordinating time of 0.3 sec '0
ond, plus breaker operating time, is recom Cfl.
C
mended between the COV relay and the
QJ
relays with which coordination is to be
ua
OJ
effected. .s
'0
>
Overcurrent unit settings are defined either
by (a) time elial setting and current tap set
0 '--___;;;:;
ting or (b) tap setting and multiples of tap
o 50 100 150 200 250
vallie (;urrent applle(i- providing a specific
an
Current in % of Full Load (5 Amps)
()pm(itli1�l time.
CD 90 volt setting when shipped from factory.
Instantaneous Trip
fhe COV Illay be equipped with the liT unit. The liT provides high speed protection from Suggested Settings
!t provides hlS:jhspeed clearing of severe heavy fault currents. Also mounted on the (Normal Application)
faults It IS a pp li cabl e onl y if the fault contri test-jack pedestal, the Indicating Instantaneous
tM
tJutlon from the system to a fault at the ter Trip is similar in construction to the Indicating 1. Voltage Unit
·ninals of the m ac h ine !veatly exceeds the Contactor Switch, with the exception that Set for 90 volts drop-out (80 to 100 volts
(lachine slJhtransient contribution and ct's it is ac operated and is adjustable over a adjustable range).
,ne useel 011 lht� system Side rather than the range of 1 to 4 times minimum pickup. Vari
neutral side of the mdchine. able pickup is provided by core-screw ad 2. Overcurrent Range
justment on top of switch. When energized Set on 2.0 ampere tap (2-6 ampere range).
ar
Indicating Instantaneous Trip (liT) above pickup setting, liT contacts close to
complete the trip circuit and the target drops. 3. Time Dial
The liT unit is accurate within 10% of setting Set for selective time coordination with
and has a variable drop-out to pickup ratio relays on adjacent circuits
lP
c
tri
(f)
l>
lec
:yclcs AdJllstment: in Percent of 120 Volts in Continuous Flexitest Case Dimensions: DB 41-076
Volts Pickup Volt-AmperesCD Contactor Switches: DB 41-081
Other Protective Relays:
SO 80-100 98 7.2 132
�) O 80� 100 98 8.0 132 Application Selector Guide, TD 41-016
September, 1990
ABB Power T&D Company Inc.
II
Descriptive Bulletin
Relay Division
om
41-165E
Coral Springs, FL
1- Allentown, PA Page 5
.c
Type COV
December, 1990
Supersedes TO 41-020, Type COV on
Voltage Controlled
pages 13 and 14, dated November, 1987
Mailed to: E, 0, C/41-100A
Overcurrent Relay
ls
ua
Overcurrent, Voltage Controlled, Non-Directional, Single-Phase, (Device Number: 27/51)
Type Time Adjustable Contacts Indicating Current Range: Amps Ac Relay Data
Curve
--------
Voltage Contactor
Time Instantaneous Internal Style Case
Range Switch@
Unit Trip: liT Unit@) Schematic Number Size
COV-6<D Definite 80-100 Spst-cc 0.2/2.0 0.5-2.5 None 183A047 288B774A19 FT-21
volts ac amp dc 2-6 1878 495
4-12
an
1878 496
0.5-2.5 2-8 183A048 288B774A20
4-16 288B774A21
10-40 288B774A22
2-6 2-8 183A048 1878 497
4-16 1878 498
10-40 1878 499
tM
20-80 1878 500
4-12 4-16 183A048 1878 501
10-40 1878 502
20-80 1878 503
40-160 1878 504
COV-7<D Moderately 80-100 Spst-cc 0.2/2.0 0.5-2.5 None 183A047 288B773A19 FT-21
Inverse volts ac amp dc 2-6 1878 505
ar
4-12 1878 506
0.5-2.5 2-8 183A048 288B773A20
4-16 288B773A21
10-40 288B773A22--_.---- - -
® Denotes item available from stock. Rating of ICS unit used in specific types of relays is shown @) ITT: Indicating Instantaneous Trip rated per ranges shown
<D 50 Hertz relays and auxiliaries can be supplied at same in price tables. All other ratings must be negotiated. in price tables. Unit is nondirectionai, adjustable. and has
price. Order "Similar to Style Number .......... , except target actuated when coil is energized at or above pickup
50 Hertz". When ac current is necessary in a control trip circuit. the setting. Unit has a dropout ratio of 65% at minimum setting
.E
@ ICS: Indicating Contactor Switch (dc current operated) hav ICS unit can be replaced by an ACS unit. and 90% at maximum setting.
ing seal·in contacts and indicating target which are actuated
when the ICS coil is energized 'at or above pickup current The ACS unit may be supplied in place of an ICS unit at no
setting. Suitable for dc control voltages up to and including additional cost. Specify system voltage rating on order.
250 volts dc. Two current ranges available:
(1) 0.212.0 amps dc, with tapped coil.
(2) 1.0 amp dc, without taps.
w
ww
Descriptive Bulletin
om
41-165E
Page 6
.c
Overcurrent, Voltage Controlled, Non-Directional, Single-Phase, (Device Number: 27/51), Continued
Type Time Ad'ustable
l Contacts Indicating Current Range: Amps Ac Relay Data
Curve Contactor --"'-:- ----'. --- ----!-'-'- -- � ------ -= -
Vo tage =
T:-im
- e
-- n - n-
I sta ta -n-eu
- o- s .,--- -
Internal Style -Cas- e
Range Switch@
Unit Trip: liT Unit® Schematic Number Size
COV-9<D Very 80-100 Spst-cc 0.212.0 0.5-2.5 None 183A047 288B775A19 FT-21
Inverse volts ac amp dc 2-6 1876 245
ls
4-12 1876 246
0.5-2.5 2-8 183A048 288B775A20
4-16 288B775A21
10-40 288B775A22
ua
2-6 2-8 183A048 1878 523
4-16 1878 524
10-40 1878 525
20-80 1878 526
4-12 4-16 183A048 1878 527
10-40 1878 528
20-80 1878 529
40-160 1878 530
an
COV·11<D Extremely 80-100 Spst-cc 0.212.0 0.5-2.5 None 183A047 1956 083 FT·21
Inverse volts ac amp dc 2-6 1956 084
4-12 1956 085
0.5-2.5 2-8 183A048 1956 086
4-16 1956 087
10-40 1956 088
tM
2-6 2-8 183A048 1956 089
4-16 1956 090
10-40 1956 091
20-80 1956 092
4-12 4-16 183A048 1956 093
10-40 1956 094
20-80 1956 095
ar
40-160 1956 096
<D50 Hertz relays and auxiliaries can be supplied at same Rating of ICS unit used in specific types of relays is shown ® ITT: Indicating Instantaneous Trip rated per ranges shown
price. Order "Similar to Style Number ......... " except in price tables. All other ratings must be negotiated. in price tables. Unit is nondirectional. adjustable. and has
50 Hertz". target actuated when coil is energized at or above pickup
@ ICS: Indicating Contactor Switch (dc current operated) hav- When ac current is necessary in a control trip circuit, the setting. Unit has a dropout ratio of 65% at minimum setting
lP
ing seal-in contacts and indicating target which are actuated ICS un� can be replaced by an ACS unit. and 90% at maximum setting.
when the ICS coil is energized at or above pickup current
setting. Su�able for dc control voltages up to and including The ACS unit may be supplied in place of an ICS unit at no
250 volts dc. Two current ranges available: additional cost. Specify system voltage rating on order.
(1) 0.212.0 amps dc, with tapped coil.
( 2) 1.0 amp dc, without taps.
ca
tri
lec
.E
ASS Power T&D Company Inc. ASS Power T&D Company Inc.
Relay Division Relay Division
w
December, 1990