POSITION CONTROL (PID) WITH MIN/MAX SELE (ARS) 69229S904A
This module is used in Turbine control system and can be plugged into a max PAC rack.
It is used preferably as position controller (PID) for electro-hydraulic drives. However the
existing structures and parameter ranges allow its application even in other closed loop
control circuits.
FEATURES
• Min/Max value selection
• PID controller
• Limiting Circuit
• Four channel current to voltage converter
• Isolated Voltage to Current converter
• Output current monitoring
• Power supply-potted blocks
BHEL/EDN/SAE Page 1 of 13 OM69229S904A/REV00
POSITION CONTROL (PID) WITH MIN/MAX SELE (ARS) 69229S904A
LED INDICATION
A GREEN LED at the bottom of the module front plate, is ON when the module is
healthy. A RED LED is ON when output current loop is open.
BUS ADDRESS
The module receives only +24V(Field Power supply) from the Bus ,other inputs and
outputs are hard wired through the front I/O connector. There is no bus communication
MODULE OPERATION
4 channel Current to voltage converter
Current to voltage converter converts 4-20mA current signal into a 0-10V voltage signal.
Channels 1, 2 & 3 are with isolation and 4 is without isolation. Converted voltage signals
are available at Jacks. I/O pins, I/O jacks and jumper selection for input current/voltage
are as shown below
Table 1
Channel Input pins Input Current Jumper selection Jumper selection O/p voltage
meas. Test Jacks for current for Voltage Test jack
Ch1 P3A-8 A9 w.r.t B9 S1-1&2 S1-2&3 A11(Vin1)
(Isolated) P3A-7 S5- close S5- open
Ch2 P3A-6 A8 w.r.t B8 S2-1&2 S2-2&3 B11 (Vin2)
(Isolated) P3A-5 S6- close S6- open
Ch3 P3A-3 A7 w.r.t B7 S3-1&2 S3-2&3 A12 (Vin3)
(Isolated) P3A-4 S7- close S7- open
LK4-open
S3-open A12(Vin3)
Internal S7- open
input LK4-close
S4-1&2 for±12V
S2-2&3 for 0V
Ch4 P3A-2 A6 w.r.t B6 S8 -close B12(Vin4)
P3A-1
BHEL/EDN/SAE Page 2 of 13 OM69229S904A/REV00
POSITION CONTROL (PID) WITH MIN/MAX SELE (ARS) 69229S904A
Min / Max value selection & limitation:
Three current to voltage converter outputs(Vin1, Vin2 & Vin3 ) are connected to a min/max
value selection circuit. A switch on the circuit board allows maximum value selection,
minimum value selection or limitation to be set in the maximum / minimum value selection
circuit and the output is available at test jack A4.
For maximum value selection switch SW1.1 & SW1.3 are closed and switch SW1.2 &
SW1.4 closed for minimum value selection. If the max/min value is to be selected from two
input parameters only, Vin1 must be one of the two channels used. The input and the two
switches for the channel not in use remains open.
Limit Range:
Limitation is selected by closing switches SW1.2 and SW1.3 or SW1.1 and SW1.4.The
value to be limited is connected to Vin1. At the first switch setting the upper limit value is
defined by the signal at i/p Vin2 and the lower limit value by the signal at Vin3. In the second
switch setting the effect of the limit values is reversed. If the upper limit value is smaller
than the lower limit value (overlap) the signal at Vin3 always assumes control.
Controller
The position controller consists of a PD-T1 and PI elements connected in series. The other
functions as mentioned below can be achieved by means of suitable circuit of inputs and
outputs or by means of parameter selection.
Other functions : P-, P - T1, PP - T1 - , PD - T1, PI or PDI - T1
PD - Element :
The transfer function can be expressed as follows :
F (P) = 1 + Kv . P . T1 / 1 + P. T1
Where as Kv = Derivative action gain
T1 = Time constant
Kv can be adjusted as follows.
* Range (Pre) selection with a switch SW2 on the printed board.
* Continuous setting with the Pot P19 on the front plate / panel.
BHEL/EDN/SAE Page 3 of 13 OM69229S904A/REV00
POSITION CONTROL (PID) WITH MIN/MAX SELE (ARS) 69229S904A
Depending on the setting of derivative action gain Kv , the PD - element shows the
following behavior :
For Kv = 0 : P- T1 - response
For Kv < 1 : PP - T1 - response
For Kv = 1 : P - response
For Kv > 1 : PD - T1 - response
The time constant T1 of the PD - element is adjustable with Pot P16 on the front panel.
The T1 range can be changed by changing the timing capacitor C90(47nF).
PI - Element
The transfer function can be expressed as follows :
FI (P) = Kp (1 + P. T2) / P. T2
Where as Kp = Proportional amplification factor
T2 = Time constant
Kp can be adjusted with Pot P17 and reset time of PI - element T2 with Pot P20 on the
front panel.
The ranges can be changed by changing the following components if required:
* Kp with resistor R83
* T2 with capacitors C111,C112 and C105
(effective value is the sum of capacitance values) as well as with resistor R109
Limiting
The output signal of PI - controller at Pin P3A-14 can be limited. The limiting values for
the output signal can be set with Pot P21 and P22.
The upper limiting is adjustable with Pot P21 (Socket A3) in the positive quadrants
between 0 and 12V.
The lower limiting in the negative quadrants between 0 and -12V with Pot P22
( Socket B3 ).
BHEL/EDN/SAE Page 4 of 13 OM69229S904A/REV00
POSITION CONTROL (PID) WITH MIN/MAX SELE (ARS) 69229S904A
V/I Converter with isolation ( 4 - 20mA ) and output current monitoring
Voltage to current converter converts the position voltage signal 0 to +10V into 4-20mA
with isolation. This can be connected to the load at pin P3A-13 & P3A-12 and also can be
measured at test jacks A10 and B10.
V/I output is monitored for loop break and Red LED on the front plate will glows when
there is a fault This signal is available at free contacts of the relay. O/P current monitoring
is optional and this can be done with jumper selection on connector S10. S10- 1&2 for
current monitoring and S10-2&3 for without monitoring.
Power Supply
The module taps and utilizes only field power supply available from the back plane pins
P1A-18 & P1A-19 (+24V) and P1A-21 & P1A-22 (GND). This power supply is protected
by resettable fuse, which do not require changing after fault occurs . When the fault is
removed and the fuse cools down, normal operation resumes. DC-DC converter blocks are
used to derive regulated +15V, -15V(without isolation) +15 & -15 (isolated) voltages
required for the internal circuits.
Surge Withstand
All field inputs and outputs are protected for surges .
ELECTRICAL SPECIFICATIONS
Current to voltage converter
Current input (Four channel)
Input and output pins , output measurement test jacks and switch settings are as per table 1
Rated current range : 4 – 20mA
Voltage output
Range : 0 to +10V(conversion accuracy 0.05%)
Max: 12V
Max /Min value selection and limiting circuit
BHEL/EDN/SAE Page 5 of 13 OM69229S904A/REV00
POSITION CONTROL (PID) WITH MIN/MAX SELE (ARS) 69229S904A
MAX value selection : Switches SW1.1 & SW1.3 closed
MIN value selection : Switches SW1.2 & SW1.4 closed
Limiting circuit
SW1.2 & SW1.3 closed SW1.1 & SW1.4 closed
Upper limit value at pin Vin2(ch2) Upper limit value at Vin3(ch3)
Lower limit value at pin Vin3(ch3) Lower limit value at Vin2(ch2)
Analog inputs
P3A-8 (Ch1) Vin1- ± 10V
P3A-6 (Ch2) Vin1- ± 10V Voltage inputs
P3A-3 (Ch3) Vin1- ± 10V
Analog output
At test jack A4 : ±10V
Zero point deviation ( max): ± 26 mV
CONTROLLER - PD
Analog inputs
1. Input from min/max section : 0 to ±10V
Jack A4 (Vin4 - Actual value )
Input delay at A4: 0.1 mS
2. Pin P3A-10 compensating input(jack B1)
3. Socket B4 optimizing input
Transfer function
F1 ( P ) = 1 + Kv. P. T1 / 1 + P.T1
Setting function
Pot P16 (on front plate) for time constants T1
Setting range : 0.45 to 4.7 ms
Setting function T1
Standard mounting
BHEL/EDN/SAE Page 6 of 13 OM69229S904A/REV00
POSITION CONTROL (PID) WITH MIN/MAX SELE (ARS) 69229S904A
MTL Film capacitor C90: 47 nF
T1 Max. = 100 K . C90
Max. value of the capacitor C90: 4.7 uF / 63V - 10uF / 25V
* Derivative action gain Kv
* Switch SW2.1 to SW2.4 on the printed board for range selection.
* Pot P19 (on front plate) on the printed board for continuous setting.
Setting function Kv
Standard mounting
Resistor R89 : 1.3K
Thus for Closed switch SW2.4 and pot position maximum it gives rise to the following :
Kv Max. = 30.8
For different value of R89 the following expression is applicable :
Kv Max. = 40 ( K ohm ) / R89 ( K ohm )
If all switches of SW2 are open, then Kv = 0 and the PD - element shows only P - T1 -
behavior ( delay ).
CONTROLLER - PI
Analog inputs
1.Min/Max selection output, Test socket A4
2.Socket A5 optimizing input
Rated voltage range : ±10V ( Linear transfer Max. - ±11V )
Input resistance : 40 Kohm
BHEL/EDN/SAE Page 7 of 13 OM69229S904A/REV00
POSITION CONTROL (PID) WITH MIN/MAX SELE (ARS) 69229S904A
Analog outputs
Pin P3A-14 output of PI - element
Socket A2 output of the PI – element
Socket A1 output of the PD - element limited to ± 11.9V
Rated voltage range : ± 10V ( Linear transfer range ±11V.
For Rl >10K )
Short circuit resistance against Gnd (M) : Continuously
Capacitance load : < 10nF
Transfer function
Socket A1
(O/p of PD)
F1 F2 P3A-14
(O/p of PI)
F(A1) = F1(P) = KP . 1/ 1+PT3
F(P3A-14) = F1(P) . F2(P)
F(P3A-14) = KP . 1 / 1+PT3 . 1+PT2 / PT2
Setting functions Kp
Pot P17 (on front plate) for proportional amplification Kp
Setting range 0.45 to 5.5
Standard mounting
Resistor R83 - 18 K
For different value of R83, the following equation is applicable :
BHEL/EDN/SAE Page 8 of 13 OM69229S904A/REV00
POSITION CONTROL (PID) WITH MIN/MAX SELE (ARS) 69229S904A
Kp Min. = R83 (K) / 40 (K)
Pot P20 (on front plate) for resetting time constant T2 of the PI - element.
Setting range : 0.38 to 4.12 S
Setting function T2
Standard mounting
Capacitor C105, C111 & C112 : 3.3uF
Resistance R109 : 2.2 M ohm
For different values of capacitors, the following equation is applicable :
T2 Max. = 0.39 . R109 ( C105 + C111+C112 + 0.1 )
Max. value for C105,C111 & C112: Each 6.8 uF / 63V
Capacitor (C95+C104) & (C105,C111 & C112) for time constant ( of time delay ) T3
Standard mounting
Capacitor C95+C104 : 4.7uF
For standard mounting ( without C95+C104 ), T3 is negligible.
For different values of capacitors C95+C104, the following equation holds good :
T3 = Kp . 40 (Kohm) . C95+C104 (uF)
Pot P18 (on FP, multiturn) for setting
Socket B5
Setting range : -10V to + 10V.
BHEL/EDN/SAE Page 9 of 13 OM69229S904A/REV00
POSITION CONTROL (PID) WITH MIN/MAX SELE (ARS) 69229S904A
For standard mounting
Resistance R21 and R22: 1 Kohm
Limiting circuit (PID O/P)
Pot P21 multi turn for upper limiting
Socket A3
Setting range : 0 to 12.5V
Pot P22( multi turn ) for lower limiting.
Socket B3
Setting range : 0 to -12.5V
Voltage to current converter
Analog input voltage
(Jumper on link S9 to be mounted)
0 to +10V (output of PID controller)
Output Current
Pin P3A-13 w.r.t P3A-12 : 4 to 20mA ± 50uA
corresponds to 0 to +10V at P3A-14
Load resistance ( Max ) : 500 R
BHEL/EDN/SAE Page 10 of 13 OM69229S904A/REV00
POSITION CONTROL (PID) WITH MIN/MAX SELE (ARS) 69229S904A
Output Current Monitor
Switch S10 – Link on pins 1 & 2 – No monitoring
Link on pins 2 & 3 – output current monitoring for loop open
Fault indication through relay contacts in case of loop open
Relay Contact outputs : Pin P3A-15 (+ve) & P3A-16(-ve)
Alarm (Front Plate) : L1 - Red (fault)
- Green (Healthy)
POWER SUPPLY VOLTAGE
Operating voltage (field PS) : +24V (Nominal )
Range : +20 to +28 (P1A-18 & P1A-19)
Zero reference voltage : 0 V (P1A-21 & P1A-22)
No load current consumption : 300mA
Power dissipation : app. 7.2W
MECHANICAL SPECIFICATIONS
a. Module Size : 254 X 298.5 X 42 mm
b. Edge connector : 22 pin, EB83-L22SGFW
c. Weight : 700gms
ENVIRONMENTAL SPECIFICATIONS
a. Operating temperature range : 0 to 70°C.
b. Storage temperature range : 0 to + 85°C
c. Humidity : 95%RH
d. Vibration : 0.5g with sinusoidal exitation in X,Y,Z
axes with 15 to 500
BHEL/EDN/SAE Page 11 of 13 OM69229S904A/REV00
POSITION CONTROL (PID) WITH MIN/MAX SELE (ARS) 69229S904A
PIN CONFIGURATION
PIN NO. FUNCTIONAL RANGE
DESCRIPTION
P1A-18 & P1A-19 Power supply +20 to +28V
P1A-21 & P1A-22 Gnd. 0V
P3A-8 w.r.t P3A-7(Ch1) Current input + 4mA to +20mA
(actual i/p-PD)
P3A-6 w.r.t P3A-5(Ch2) Current input + 4mA to +20mA
(actual i/p-PD)
P3A-3 w.r.t P3A-4(Ch3) Current input + 4mA to +20mA
(actual i/p-PD)
P3A-2 w.r.t P3A-1(Ch4) Current input + 4mA to +20mA
(ref. i/p-PD)
P3A-10 Compensating I/P-PD ±10V
P3A-14 PID O/P ±10V
P3A-13 w.r.t P3A-12 Current O/P (PID) +4mA to +20mA
P3A-15(+) , P3A-16 Fault o/p thro’ 0.5A, 48V Max
relay Contacts
BHEL/EDN/SAE Page 12 of 13 OM69229S904A/REV00